CEP7 E3 Electronic Overload Relay
Short Circuit Ratings
WARNING To prevent electrical shock, disconnect from power source before installing or servicing.
WARNING Select the motor branch circuit protection that complies with the national Electrical Code and any other governing regional and local codes.
The E3 overload relay is suitable for use on circuits capable of delivering not more that the RMS symmetrical amperes listed in the following tables:
Short Circuit Ratings
Table 1 Standard Fault Short Circuit Ratings per UL508 and CSA 22.2 No.14
MCS-E3 Cat. No. |
Max. available fault |
Max. voltage (V) |
|
current (A) |
|
|
|
|
CEP7-C_-23-X |
5,000 |
|
CEP7-C_-43-X |
5,000 |
|
CEP7-C_-85-X |
10,000 |
|
CEP7-C_-180-X |
10,000 |
600 |
CEP7-C_-420-X |
18,000 |
|
CEP7-C_-860-X |
42,000 |
|
CEP7-C_-CT-5000 |
5,000 |
|
Table 2 High Fault Short Circuit Ratings per UL 508 and CSA 22.2 no. 14 With CA6 and CA7 Contactors
CEP7 Cat. No. |
|
Contactor Cat. No. |
Max. Starter FLC (A) |
Max available fault |
Max. voltage (V) |
Max Class J or |
|
|
|
|
current (A) |
|
CC fuse (A) |
|
-23-XX |
CA7-09 |
9 |
|
|
20 |
|
-23-XX |
CA7-12 |
12 |
|
|
20 |
|
-23-XX |
CA7-16 |
16 |
|
|
30 |
|
-23-XX |
CA7-23 |
23 |
|
|
30 |
|
-43-XX |
CA7-30 |
30 |
|
|
50 |
|
-43-XX |
CA7-37 |
37 |
|
|
50 |
|
-43-XX |
CA7-43 |
43 |
|
|
70 |
|
-85-XX |
CA7-60 |
60 |
|
|
80 |
|
-85-XX |
CA7-72 |
72 |
|
|
100 |
|
-85-XX |
CA7-85 |
85 |
|
|
150 |
CEP7-C1 |
-180-140, CT-5000 |
CA6-D95 |
95 |
100,000 |
600 |
200 |
CEP7-C2 |
-180-140, CT-5000 |
CA6-D110 |
110 |
|
|
200 |
CEP7-C3 |
-180-140, CT-5000 |
CA6-D140 |
140 |
|
|
250 |
CEP7-C5 |
-180-210, CT-5000 |
CA6-D180 |
180 |
|
|
300 |
|
-420-210, CT-5000 |
CA6-D210 |
210 |
|
|
400 |
|
-420-210, CT-5000 |
CA6-D250 |
250 |
|
|
400 |
|
-420-210, CT-5000 |
CA6-D300 |
300 |
|
|
500 |
|
-420-302, CT-5000 |
CA6-D210 |
210 |
|
|
400 |
|
-420-302, CT-5000 |
CA6-D250 |
250 |
|
|
400 |
|
-420-302, CT-5000 |
CA6-D300 |
300 |
|
|
500 |
|
-420-420, CT-5000 |
CA6-D300 |
300 |
|
|
500 |
|
-420-420, CT-5000 |
CA6-D420 |
420 |
|
|
600 |
PN-17758
DIR 10000010792 (Version 03)
Printed in U.S.A.