Rockwell Automation CEP7 User Manual

0 (0)
Rockwell Automation CEP7 User Manual

CEP7 E3 Electronic Overload Relay

Short Circuit Ratings

WARNING To prevent electrical shock, disconnect from power source before installing or servicing.

WARNING Select the motor branch circuit protection that complies with the national Electrical Code and any other governing regional and local codes.

The E3 overload relay is suitable for use on circuits capable of delivering not more that the RMS symmetrical amperes listed in the following tables:

Short Circuit Ratings

Table 1 Standard Fault Short Circuit Ratings per UL508 and CSA 22.2 No.14

MCS-E3 Cat. No.

Max. available fault

Max. voltage (V)

 

current (A)

 

 

 

 

CEP7-C_-23-X

5,000

 

CEP7-C_-43-X

5,000

 

CEP7-C_-85-X

10,000

 

CEP7-C_-180-X

10,000

600

CEP7-C_-420-X

18,000

 

CEP7-C_-860-X

42,000

 

CEP7-C_-CT-5000

5,000

 

Table 2 High Fault Short Circuit Ratings per UL 508 and CSA 22.2 no. 14 With CA6 and CA7 Contactors

CEP7 Cat. No.

 

Contactor Cat. No.

Max. Starter FLC (A)

Max available fault

Max. voltage (V)

Max Class J or

 

 

 

 

current (A)

 

CC fuse (A)

 

-23-XX

CA7-09

9

 

 

20

 

-23-XX

CA7-12

12

 

 

20

 

-23-XX

CA7-16

16

 

 

30

 

-23-XX

CA7-23

23

 

 

30

 

-43-XX

CA7-30

30

 

 

50

 

-43-XX

CA7-37

37

 

 

50

 

-43-XX

CA7-43

43

 

 

70

 

-85-XX

CA7-60

60

 

 

80

 

-85-XX

CA7-72

72

 

 

100

 

-85-XX

CA7-85

85

 

 

150

CEP7-C1

-180-140, CT-5000

CA6-D95

95

100,000

600

200

CEP7-C2

-180-140, CT-5000

CA6-D110

110

 

 

200

CEP7-C3

-180-140, CT-5000

CA6-D140

140

 

 

250

CEP7-C5

-180-210, CT-5000

CA6-D180

180

 

 

300

 

-420-210, CT-5000

CA6-D210

210

 

 

400

 

-420-210, CT-5000

CA6-D250

250

 

 

400

 

-420-210, CT-5000

CA6-D300

300

 

 

500

 

-420-302, CT-5000

CA6-D210

210

 

 

400

 

-420-302, CT-5000

CA6-D250

250

 

 

400

 

-420-302, CT-5000

CA6-D300

300

 

 

500

 

-420-420, CT-5000

CA6-D300

300

 

 

500

 

-420-420, CT-5000

CA6-D420

420

 

 

600

PN-17758

DIR 10000010792 (Version 03)

Printed in U.S.A.