Regency H27 User Manual

0 (0)

H27 Direct Vent Gas Fireplace

Owners &

Installation Manual

www.hampton-fire.com

MODELS: H27-NG Natural Gas H27-LP Propane

WARNING:

If the information in these instructions are not followed exactly, a fire or explosion may result causing property damage, personal injury or loss of life.

FOR YOUR SAFETY

Do not store or use gasoline or other flammable vapours and liquids in the vicinity of this or any other appliance.

Installation and service must be performed by a qualified installer, service agency or the gas supplier.

FOR YOUR SAFETY

What to do if you smell gas:

Do not try to light any appliance

Do not touch any electrical switch: do not use any phone in your building.

Immediately call your gas supplier from a neighbour's phone. Follow the gas supplier's instructions.

If you cannot reach your gas supplier, call the fire department.

This appliance may only be installed in an aftermarket permanently located, manufactured (USA only) or mobile home,wherenotprohibitedby local codes.

This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases, unless a certified kit is used.

Tested by:

Installer: Please complete the details on the back cover and leave this manual with the homeowner.

Homeowner: Please keep these instructions for future reference.

918-812

FPI FIREPLACE PRODUCTS INTERNATIONAL LTD. 6988 Venture St., Delta, BC Canada, V4G 1H4

04/12/11

HAMPTON®

Direct Vent Freestanding Gas Stove

To the New Owner:

Congratulations!

You are the owner of a state-of-the-art Hampton® Gas Stove by REGENCY FIREPLACE PRODUCTS. The H27 is a hand crafted appliance and has been designed to provide you with all the warmth and charm of a wood fireplace at the flick of a switch. The model H27 has been approved by Warnock Hersey for both safety and efficiency. As it also bears our own mark, it promises to provide you with economy, comfort and security for many trouble free years to follow. Please take a moment now to acquaint yourself with these instructions and the many features of your Hampton® Stove.

2

Hampton® H27 Direct Vent Freestanding Gas Stove

 

TABLE OF CONTENTS

SAFETY LABEL

 

Copy of Safety Label .....................................................

4

REQUIREMENTS

 

MA Code - CO Detector.................................................

6

INSTALLATION

 

Important Message ......................................................

8

Specifications ................................................................

8

Information for Mobile / Manufactured Homes

 

After First Sale...............................................................

8

General Safety Information............................................

9

Installation Checklist......................................................

9

Clearances To Combustibles.........................................

9

Locating Your Gas Stove.............................................

10

Manufactured Mobile Home Additional Requirements 10

Combustion and Ventilation Air....................................

10

Optional Fan Installation..............................................

10

Venting Introduction.....................................................

12

Installation Precautions ...............................................

12

Vent Restrictor Position ...............................................

12

Rotating 45o Elbow ......................................................

12

Exterior Vent Terminal Locations .................................

13

4” x 6-5/8” Rigid Pipe Cross Reference Chart.............

14

Rigid Pipe Venting Systems ........................................

16

Venting Arrangements .................................................

17

Vertical Termination with Co-linear Flex System .........

20

DV Stove Horizontal Vent Kit.......................................

21

Residential and Manufactured Homes / Mobile Home 23

Minimum horizontal termination Installations...............

23

Dura-Vent Termination Kit............................................

24

Horizontal terminations................................................

25

Vertical ........................................................................

26

Terminations ................................................................

26

Converting Class-A Metal Chimney or ........................

28

Masonry Chimney to Direct Vent System...................

28

Cathedral Ceilings .......................................................

29

High Elevation .............................................................

29

Gas Connection...........................................................

29

Aeration Adjustment ....................................................

30

Gas Pipe .....................................................................

30

Pressure Testing..........................................................

30

Conversion from NG to LP ..........................................

31

Log Set Installation......................................................

34

Optional side shelves installation ................................

36

Wall Thermostat ..........................................................

36

Remote Control ..........................................................

36

Final Check..................................................................

37

Wiring Diagrams..........................................................

37

OPERATING INSTRUCTIONS

 

Operating Instructions .................................................

39

Lighting Procedure ......................................................

39

Shutdown Procedure...................................................

39

First Fire ......................................................................

39

Automatic Convection

 

Fan Operation..............................................................

39

Copy of the Lighting Plate Instructions .......................

40

Normal Operating Sounds of Gas Appliances.............

41

MAINTENANCE

 

Maintenance Instructions.............................................

41

Fan Maintenance.........................................................

42

Log Replacement ........................................................

42

Glass Replacement .....................................................

42

Removing Valve...........................................................

43

Installing Valve Assembly ............................................

43

PARTS LIST

 

Main assembly.............................................................

44

Burner & Log Assembly...............................................

46

WARRANTY

 

Warranty ......................................................................

47

3

Hampton® H27 Direct Vent Freestanding Gas Stove

SAFETY LABEL

This is a copy of the label that accompanies each Direct Vent Freestanding Gas Stove.

We have printed a copy of the contents here for your review.

NOTE: Hampton® units are constantly being improved. Check the label on the unit and if there is a difference, the label on the unit is the correct one.

COPY OF SAFETY LABEL

DUPLICATE SERIAL NO. 351

Listed: VENTED GAS FIREPLACE HEATER

 

DO NOT REMOVE THIS LABEL /

Certified for/Certifiée pour:

NE PAS ENLEVER CETTE ÉTIQUETTE

CANADA and U.S.A.

 

351

WN# 16378

 

 

 

Tested to: Gas-Fired Appliances For Use At High

 

Serial No./ No de serie

Altitudes CGA 2-17-M91,Vented Gas Fireplace Heaters ANSI Z21.88a-2007/CSA 2.33a-2007

MAY BE INSTALLED IN MANUFACTURED (MOBILE) HOMES AFTER FIRST SALE

FACTORY EQUIPPED FOR NATURAL GAS Model:H27-NG ÉQUIPÉ A L'UISINE POUR GAZ NATURAL

Model/Modele:H27

NG-

Minimum supply pressure

5" WC/C.E. (1.25 kPa)

Pression d'allimentation minimum

Manifold pressure High

3.8" WC/C.E. (0.94 kPa)

Pression à la tubulure d'échappement élevée

Manifold pressure Low

1.1" WC/C.E. (0.27 kPa)

Pression à la tubulure d'échappement basse

Maximum Input

25,000 Btu/h (7.32 Kw/h)

Débit Calorifique maximum

Minimum Input

12,500 Btu/h (3.66 Kw/h)

Débit Calorifique minimum

Orifice size

#42 DMS

(2.37mm)

Dimensions de l'orifice

Altitude

0-4500 ft/pi

(0-1372m)

L'altitude

FACTORY EQUIPPED FOR PROPANE GAS Model:H27-LP ÉQUIPÉ A L'UISINE POUR GAZ PROPANE

Model/Modele:H27

LP-

Minimum supply pressure

12" WC/C.E. (3.00 kPa)

Pression d'allimentation minimum

Manifold pressure High

11" WC/C.E.

(2.74 kPa)

Pression à la tubulure d'échappement élevée

Manifold pressure Low

2.9" WC/C.E.

(0.72 kPa)

Pression à la tubulure d'échappement basse

Maximum Input

23,000 Btu/h (6.74 Kw/h)

Débit Calorifique maximum

Minimum Input

11,500 Btu/h (3.37 Kw/h)

Débit Calorifique minimum

Orifice size

#54 DMS

(1.4mm)

Dimensions de l'orifice

Altitude

0-4500 ft/pi

(0-1372m)

L'altitude

Minimum Clearances to Combustibles/Degagement Minimum De Materiaux Combustibles

Minimum ceiling height from top of unit:24"/610mm Minimum plafond hauteur en haut de

l'appareil: 24"/610mm

A

6"/150mm

C 2" / 50mm

B

3"/75mm

E 2"/50mm

Minimum clearance of Vent Terminal to Outside Corner & Inside Corner: with AstroCap 6"/150mm

with Dura-Vent Cap 12"/300mm

Left Side Wall

Left Side Wall See Manual for details

A

A

E

B

C

 

Horizontal

Vertical

 

Pipe

Pipe

 

 

 

E

A

 

 

Right Side Wall

Right Side Wall

 

VENTED GAS FIREPLACE HEATER: This appliance must be installed in accordance with local codes, if any; if none, follow:the national Fuel Gas Code, ANSI Z223.1, or Natural Gas and Propane Installation Code, CSA B149.1.Electrical Supply (115 V, 1.13A, 60 Hz). This vented gas fireplace heater is not for use with filters. Not for use with solid fuels.

FOYER AU GAZ À ÈVACUATION: Installer l`appareil selon les codes ou reglements locaux, ou, en l`absence de tels règlements, selon les codes d’installation ANSI Z223.1, National Fuel Gas Code ou CSA-B149.1 en vigueur. Alimentation électrique. Ne doit pas être utilisé avec un combustible solide.

FPI Fireplace Products International Ltd. Delta, BC, Canada

 

Made in Canada/Fabrique au Canada

918-813

 

For the State of Massachusetts, installation and repair must be done by a plumber or gasfitter licensed in the

Commonwealth of Massachusetts.

For the State of Massachusetts, flexible connectors shall not exceed 36 inches in length.

For the State of Massachusetts, the appliances individual manual shut-off must be a t-handle type valve.

The State of Massachusetts requires the installation of a carbon monoxide alarm in accordance with NFPA 720 and a CO alarm with battery back up in the same room where the gas appliance is installed.

4

Hampton® H27 Direct Vent Freestanding Gas Stove

 

REQUIREMENTS

MA Code - CO Detector

(for the State of Massachusetts only)

5.08: Modifications to NFPA-54, Chapter 10

(2) Revise 10.8.3 by adding the following additional requirements:

(a) For all side wall horizontally vented gas fueled equipment installed in every dwelling, building or structure used in whole or in part for residential purposes, including those owned or operated by the Commonwealth and where the side wall exhaust vent termination is less than seven (7) feet above finished grade in the area of the venting, including but not limited to decks and porches, the following requirements shall be satisfied:

1. INSTALLATION OF CARBON MONOXIDE DETECTORS. At the time of installation of the side wall horizontal vented gas fueled equipment, the installing plumber or gasfitter shall observe that a hard wired carbon monoxide detector with an alarm and battery back-up is installed on the floor level where the gas equipment is to be installed. In addition, the installing plumber or gasfitter shall observe that a battery operated or hard wired carbon monoxide detector with an alarm is installed on each additional level of the dwelling, building or structure served by the side wall horizontal vented gas fueled equipment. It shall be the responsibility of the property owner to secure the services of qualified licensed professionals for the installation of hard wired carbon monoxide detectors

a.In the event that the side wall horizontally vented gas fueled equipment is installed in a crawl space or an attic, the hard wired carbon monoxide detector with alarm and battery back-up may be installed on the next adjacent floor level.

b.In the event that the requirements of this subdivision can not be met at the time of completion of installation, the owner shall have a period of thirty (30) days to comply with the above requirements; provided, however, that during said thirty (30) day period, a battery operated carbon monoxide detector with an alarm shall be installed.

2.APPROVED CARBON MONOXIDE DETECTORS. Each carbon monoxide detector as required in accordance with the above provisions shall comply with NFPA 720 and be ANSI/UL 2034 listed and IAS certified.

3.SIGNAGE. A metal or plastic identification plate shall be permanently mounted to the exterior of the building at a minimum height of eight

(8) feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment. The sign shall read, in print size no less than one-half (1/2) inch in size, "GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL

OBSTRUCTIONS".

4. INSPECTION. The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installation unless, upon inspection, the inspector observes carbon monoxide detectors and signage installed in accordance with the provisions of 248 CMR 5.08(2)(a)1 through 4.

(b) EXEMPTIONS: The following equipment is exempt from 248 CMR 5.08(2)(a)1 through 4:

1.The equipment listed in Chapter 10 entitled "Equipment Not Required To Be Vented" in the most current edition of NFPA 54 as adopted by the Board; and

2.Product Approved side wall horizontally vented gas fueled equipment installed in a room or structure separate from the dwelling, building or structure used in whole or in part for residential purposes.

(c) MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM PROVIDED. When the manufacturer of Product Approved side wall horizontally vented gas equipment provides a venting system design or venting system components with the equipment, the instructions provided by the manufacturer for installation of the equipment and the venting system shall include:

1.Detailed instructions for the installation of the venting system design or the venting system components; and

2.A complete parts list for the venting system design or venting system.

(d) MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM NOT PROVIDED. When the manufacturer of a Product Approved side wall horizontally vented gas fueled equipment does not provide the parts for venting the flue gases, but identifies "special venting systems", the following requirements shall be satisfied by the manufacturer:

1.The referenced "special venting system" instructions shall be included with the appliance or equipment installation instructions; and

2.The "special venting systems" shall be Product Approved by the Board, and the instructions for that system shall include a parts list and detailed installation instructions.

(e) A copy of all installation instructions for all Product Approved side wall horizontally vented gas fueled equipment, all venting instructions, all parts lists for venting instructions, and/or all venting design instructions shall remain with the appliance or equipment at the completion of the installation.

5

Hampton® H27 Direct Vent Freestanding Gas Stove

DIMENSIONS

** Shown with optional side shelves.

6

Hampton® H27 Direct Vent Freestanding Gas Stove

 

BEFORE YOU START

Safe installation and operation of this appliance requires common sense, however, we are required by the Canadian Safety Standards andANSI Standards to make you aware of the following:

INSTALLATION

YOUNG CHILDREN SHOULD BE CARE-

FULLY SUPERVISED WHEN THEY ARE

IN THE SAME AREA AS THE APPLI-

ANCE. TODDLERS,YOUNG CHILDREN

AND OTHERS MAY BE SUSCEPTIBLE

TO ACCIDENTAL CONTACT BURNS. A

PHYSICAL BARRIERS IS RECOMMEND-

ED IF THERE ARE AT RISK INDIVIDUAL

INTHE HOUSE. TO RESTRICT ACCESS

TO A FIREPLACE OR STOVE, INSTALL

AN ADJUSTABLE SAFETY GATE TO

KEEP TODDLERS, YOUNG CHILDREN

AND OTHER AT RISK INDIVIDUALS OUT

OF THE ROOM AND AWAY FROM HOT

SURFACES.

INSTALLATION AND REPAIR SHOULD BE DONE BY AN AUTHORIZED SERVICE PERSON. THE APPLIANCE SHOULD BE INSPECTED BEFORE USE AND AT LEAST ANNUALLY BY A PROFESSIONAL SERVICE PERSON. MORE FREQUENT CLEANING MAY BE REQUIRED DUE TO EXCESSIVE LINT FROM CARPETING, BEDDING MATERIAL,ETC.IT IS IMPERATIVETHAT CONTROLCOMPARTMENTS,BURNERS AND CIRCULATING AIR PASSAGEWAYS OF THE APPLIANCE BE KEPT CLEAN.

DUE TO HIGH TEMPERATURES, THE APPLIANCE SHOULD BE LOCATED OUT OF TRAFFIC AND AWAY FROM FURNITURE AND DRAPERIES.

WARNING: FAILURE TO INSTALL THIS APPLIANCE CORRECTLY WILL VOID YOUR WARRANTY AND MAY CAUSE A SERIOUS HOUSE FIRE.

CHILDREN AND ADULTS SHOULD BE ALERTED TO THE HAZARDS OF HIGH SURFACE TEMPERATURES, ESPECIALLY THE FIREPLACE GLASS, AND SHOULD STAY AWAYTO AVOID BURNS OR CLOTHING IGNITION.

CLOTHING OR OTHER FLAMMABLE MATERIAL SHOULD NOT BE PLACED ON OR NEAR THE APPLIANCE.

7

Hampton® H27 Direct Vent Freestanding Gas Stove

INSTALLATION

IMPORTANT MESSAGE

SAVE THESE

INSTRUCTIONS

The Direct Vent Freestanding Gas Stove must be installed in accordance with these instructions.

Carefully read all the instructions in this manual first.

Consult the building authority having jurisdiction to determine the need for a permit prior to starting the installation.

Note: Failure to follow the instructions could cause a malfunction of the heater which could result in death, serious bodily injury, and/or property damage. Failure to follow these instructions may also void your fire insurance and/or warranty.

Note: These instructions take precedence over Simpson Dura-Vent instructions.

SPECIFICATIONS

Fuels: H27-NG is approved for use with natural gas.

H27-LPis approved for use with liquefied petroleum gases (propane).

Electrical: 120V A.C. system.

Optional Circulation Fan:

Variable speed, 125/75.

Log Sets: Ceramic fibre, 4 per set.

Vent System: Coaxial (6-5/8" outer / 4" inner liner) rigid flue and termination cap.

INFORMATION FOR

MOBILE /

MANUFACTURED HOMES AFTER FIRST SALE

This Hampton® product has been tested and listed by ITS Testing Services as a Direct Vent Wall Furnace to the following standards:

CGA-2.17-M91, and ANSI Z21.88a-2007/CSA 2.33a-2007.

This Direct Vent SystemAppliance must be installed in accordance with the manufacturer's installation instructions and the Manufactured Home Construction and Safety Standard, Title 24 CFR, Part 3280, or the current Standard of Fire Safety Criteria for Manufactured Home Installations, Sites, and Communities ANSI/NFPA 501A, and with CAN/ CSA Z240-MH Mobile Home Standard in Canada.

This appliance installation must comply with the manufacturer's installation instructions and local codes, if any. In the absence of local codes follow the current National Fuel Gas Code, ANSI

Z223.1 and the current National Electrical Code

ANSI/NFPA 70 in the U.S.A., and the current

CAN/CGA B149 Gas Installation Code and the current Canadian Electrical Code CSA C22.1 in Canada.

This Hampton® Mobile/Manufactured Home Listed appliance comes factory equippedwithameanstosecuretheunit.

This Hampton® Mobile/Manufactured Home listed appliance comes equipped with a dedicated #8 ground lug to which an 18 gauge copper wire from the steel chassis ground must be attached.

Thisappliancemayonlybeinstalledin an aftermarket permanently located, manufactured (USA only) or mobile home, where not prohibited by local codes.

This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases, unless a certified kit is used.

1)Provide adequate clearances for servicing, proper operation and around the air openings into the combustion chamber.

2)The appliance must be installed on a flat, solid, continuoussurface(e.g.wood,metal,concrete).

This may be the floor, or it can be raised up on a platform to enhance its visual impact. The appliance may be installed on carpeting, tile, wood flooring or other combustible material, because the appliance's base extends the full width and depth of the appliance. The Direct Vent Freestanding Gas Stove can be installed in a wide variety of ways and will fit nearly any room layout. It may be installed in a recessed position, framed out into the room, or across a corner.

3)The Direct Vent Freestanding Gas Stove is approved for alcove installations, which meet the clearances listed on in the "Clearance to

Combustibles" section. This unit is approved for manufactured home installations, see the "Manufactured Mobile Home Additional

Requirements" section and "Venting Arrangements" section for the required vent arrangements. If installed into a manufactured home the unit must be bolted down to the floor.

4)This appliance is Listed for bedroom installations when used with a Listed Millivolt Thermostat. Some areas may have further requirements, check local codes before installation.

5)This appliance is Listed forAlcove installations, maintain minimum Alcove clearances as follows, minimum width of 34-3/4" (882mm), a maximum depth of 36" (914mm), and minimum ceiling height of 51" (1295mm) from floor to ceiling.

6)Werecommendthatyouplanyourinstallationon paperusingexactmeasurementsforclearances andfloorprotectionbeforeactuallyinstallingthis appliance. Have a qualified building inspector review your plans before installation.

8

Hampton® H27 Direct Vent Freestanding Gas Stove

 

GENERAL SAFETY

INFORMATION

1)The appliance installation must conform with local Canadian Electrical Code.

2)The appliance when installed, must be electrically grounded in accordance with local codes, or in the absence of local codes with the current

National Electrical Code,ANSI/NFPA70 or CSA C22.1 Canadian Electrical Code.

3)The appliance should be inspected for shipping damage before use and serviced annually by a professional service person. More frequent cleaning may be required due to excessive lint from carpeting, bedding material, etc. It is imperative that control compartments, and circulating air passageways of the appliance be kept clean and free from excessive lint from carpeting.

4)See general construction and assembly instructions. The appliance and vent should be enclosed when installed in or passing through a living area, where children may come in contact with it.

5)This appliance must be connected to the speci-

fied vent and termination cap to the outside of

the building envelope. Never vent to another room or inside a building. Make sure that the vent is fitted as per the instructions starting inthe"ExteriorVentTerminalLocations"section.

6)Inspect the venting system annually for blockage and any signs of deterioration.

7)Venting terminals shall not be recessed into a wall or siding.

8)Any safety glass removed for servicing must be replaced prior to operating the appliance.

9)To prevent injury, do not allow anyone who is unfamiliarwiththeoperationtousethefireplace.

Emissions from burning wood or gas could contain chemicals known to the State of

California to cause cancer, birth defects or other reproductive harm.

INSTALLATION

CHECKLIST

1)Locate your appliance. Refer to the following sections:

a.Clearances to Combustibles

b.Locating Your Gas Stove

c.For venting requirements, see "Venting

Introduction" to "Rigid Pipe Venting

Systems" sections.

2)Install Optional Fan. Refer to the "Optional Fan

Installation" section.

3)Set vent restrictor. Refer to the

"Vent Restrictor Position" section.

4)Install venting:

a.Check all venting requirements. See

"Vent Restrictor Position" to Rigid Pipe Venting Systems" sections

b.Vertical Termination with Co-linear Flex

System

c.DV Stove Horizontal Vent Kit

d.Minimum Horizontal Termination

e.Dura-Vent Termination Kit

5)Make gas connections. Refer to the "Gas Connection" section.

Test the pilot. Must be as per diagram in the "Maintenance Instruction" section.

If converting to Propane, make changes prior. Refer to the "Conversion from Natural Gas to Propane" section.

6)Test Gas Pressure. Refer to the "Pressure

Testing" section.

7)Install standard and optional features. Refer to the following sections where applicable:

a.Log Set Installation

b.Decorative Door Grill

c.Wall Thermostat

d.Remote Control

8)Final check. Refer to the "Final Check" section.

Before leaving this unit with the customer, the installer must ensure that the appliance is firing correctly and operation fully explained to customer.

This includes:

1)Clocking the appliance to ensure the correct

firing rate (rate noted on label) after burning appliance for 15 minutes.

2)If required, adjusting the primary air to ensure that the flame does not carbon. First allow the unit to burn for 15-20 min. to stabilize.

CAUTION: Any alteration to the product that causessootingorcarboningthatresultsindamageisnottheresponsibilityofthemanufacturer.

INSTALLATION

CLEARANCES TO

COMBUSTIBLES

The clearances listed are MINIMUM distances. Measure the clearance to both the appliance and the chimney connector. The farthest distance is correct if the two clearances do not coincide.

For example, if the appliance is set as indicated in one of the figures but the connector is too close, move the stove until the correct clearance to the connector is obtained.

This appliance may be installed only with the clearances as shown in the situations pictured.

Do not combine clearances from one type of installation with another in order to achieve closer clearances.

This unit can be installed on a solid combustible surface like a wood floor. This unit can also be installed directly on carpeting or vinyl.

Use the minimum clearances shown in the diagrams below:

H27-NG & H27-LP Clearances

A Left Side Wall to Unit*

6"

/ 150 mm

B Back Wall to Unit

3"

/ 75 mm

C Vertical Vent Pipe to Back Wall

 

 

2" / 50 mm

E Unit Corner to Wall

2"

/50 mm

Unit Top to Alcove Ceiling 24"

/ 610 mm

Minimum ceiling height is 24" /610 mm from top of unit.

9

Hampton® H27 Direct Vent Freestanding Gas Stove

INSTALLATION

LOCATING YOUR

GAS STOVE

When selecting a location for your stove, ensure that the clearances listed above are met as well as ensuring that there is adequate accessibility for servicing and proper operation.

OPTIONAL FAN

INSTALLATION

Fan Kit Contains:

Qty. Description

1 Fan Assembly c/w green wire attached

1Thermodisc

1power cord

22-1/4" x 20 hex nut

1Fan Speed Control

1)a) Remove the rear access panel on the back of the stove by removing the 2 screws under the rear panel.

A)Cross Corner

B)Room Divider

C)Island

D)Flat on Wall

E)Flat on Wall Corner

F)Flush with Wall/Alcove

For Vent Termination requirements, see "Exterior Vent Terminal Locations" section.

screw

screw

b) Lift off the 2 bolts at the top.

Take care not to cut wires when lowering the panel.

MANUFACTURED

MOBILE HOME

ADDITIONAL

REQUIREMENTS

1)Ensure that structural members are not cut or weakened during installation.

2)Ensure proper grounding using the #8 ground lug provided.

3)Appliance must be anchored to the floor with the supplied anchoring methods.

COMBUSTION AND VENTILATION AIR

The combustion air from this appliance is drawn from outside the building through the outer flue.

Extra provision for combustion air inside the room is not required.

Bolts

Lift Rear Panel off the 2 top bolts

2) Disconnect the red and grey wires.

3)Remove the Top Control Panel Assembly by removing the three screws.

Top Control Panel Assembly

4)Remove the nylon hole plug from the control panel.

5)Install the fan speed controller onto the control panel and secure with nut and washer. Connect the red and black wires from the wire harness to speed controller.

NOTE: Speed control wires must be in the down position when control panel is in place.

Fan Speed

Controller

6) Push black knob onto speed control.

7)Re-attach control panel with 3 screws, reversing step 3.

10

Hampton® H27 Direct Vent Freestanding Gas Stove

 

Regency H27 User Manual

INSTALLATION

8)Place the blower close to the base of the unit and feed the long red and black wires through the opening of the base of the unit and the short red and black wires through the small hole at the base of the unit.

9)Slide Thermodisc into the bracket on the left side of the rear firebox.

12)Before re-attaching the rear access panel, the valve wires and the fan wires need to be connected.

Re-connect the red and grey valve wires.

Connect the fan wires.

Thermodisc

Thermodisc

Braket

 

11)Mount the blower assembly in position under the base of the stove and secure with the 2 supplied bolts (2-1/4" #20 hex head)

13)Slide the Rear Access Panel back into position and secure with 2 screws.

WARNING: Electrical Grounding Instructions

This appliance is equipped with a three pronged (grounding) plug for your protection against shock hazard and should be plugged directly into a properly grounded three-prong receptacle. Do not cut or remove the grounding prong from this plug.

11

Hampton® H27 Direct Vent Freestanding Gas Stove

INSTALLATION

VENTING

INTRODUCTION

The Horizontal Termination Kit and other approved venting systems as per table on next page, in combination with the Direct Vent Freestanding

Gas Stoves, H27-NG, and H27-LP, have been tested and listed as direct vent heater systems by

Warnock Hersey.

These units use the "balanced flue" technology

Co-Axial system. The inner liner vents products of combustion to the outside while the outer pipe draws outside combustion air into the combustion chamber thereby eliminating the need to use heated room air for combustion and losing warm room air up the chimney.

Note: These flue pipes must not be connected to any other appliance.

The gas appliance and vent system must be vented directly to the outside of the building, and never be attached to a chimney serving a separate solid fuel or gas burning appliance. Each direct vent gas appliance must use it's own separate vent system. Common vent systems are prohibited.

IMPORTANT

Read all instructions carefully before starting the installation. Failure to follow these instructions may create a fire or other safety hazard, and will void the warranty. Be sure to check the venting and clearance to combustible requirements. Consult your local building codes before beginning installation.

The location of the termination cap must conform to the requirements in the "Exterior Vent Terminal Locations" section.

INSTALLATION

PRECAUTIONS

These venting systems are engineered products that have been designed and tested for use with the

H27-NG, and H27-LP. The warranty will be voided and serious fire, health or other safety hazards may result from any of the following actions:

1)Installation of any damaged Direct Vent component

2)Unauthorized modification of the Direct Vent

System

3)Installation of any component part not manufactured by approved venting systems as per table on next page or FPI Fireplace Products

International Ltd.

4)Installation other than as instructed by approved venting systems as per table on next page and FPI Fireplace Products International Ltd.

Warning: Always maintain required clearances (air spaces) to nearby combustibles to prevent a fire hazard. Do not fill air spaces with insulation.

Be sure to check the vent termination clearance requirements from decks, windows, soffits, gas regulators, air supply inlets and public walkways as specified in the "Exterior Vent Terminal Locations" section and in your local building codes.

The gas appliance and vent system must be vented directly to the outside of the building, and never be attached to a chimney serving a separate solid fuel or gas-burning appliance.

Each direct vent gas appliance must use it's own separate vent system. Common vent systems are prohibited.

SAFETY PRECAUTIONS FOR

THE INSTALLER

1)Wear gloves and safety glasses for protection.

2)Exercise extreme caution when using ladders or on roof tops.

3)Be aware of electrical wiring locations in walls and ceilings.

VENT RESTRICTOR

POSITION

To set the Vent restriction as indicated in the diagrams in "Venting Arrangements" section, simply loosen the screws and push the vent restrictor plate to the correct position. Tighten the screws.

1) Remove all 4 screws that secure the elbow to the unit using a 1/4" magnetic nut driver.

Remove all 4 screws and washers

ROTATING 45O ELBOW

2)Rotate the elbow 180o

3)Secure the elbow by securing

it with the 4 screws.

12

Hampton® H27 Direct Vent Freestanding Gas Stove

 

INSTALLATION

EXTERIOR VENT TERMINAL LOCATIONS

 

 

Minimum Clearance Requirements

Canada1

USA2

 

 

 

 

 

 

A

Clearance above grade, veranda, porch, deck, or balcony

12"(30cm)

12"(30cm)

 

 

 

 

 

 

B

Clearance to window or door that may be opened

12"(30cm)

9" (23cm)

 

 

 

 

 

 

C

Clearance to permanently closed window

*

*

 

 

 

 

 

 

D

Vertical clearance to ventilated soffi t located above the terminal within a horizontal distance of 2 feet (61cm)

22"(56cm)

22"(56cm)

 

 

from the center line of the terminal (check with the local code)

 

 

 

 

 

 

 

 

E

Clearance to unventilated soffi t

12"(30cm)

12"(30cm)

 

 

 

 

 

 

F

Clearance to outside corner: with AstroCap and Vent Riser Termination Caps

6"(15cm)

6"(15cm)

 

 

 

 

 

 

 

Clearance to outside corner: with all other approved Termination Caps.

12"(30cm)

12"(30cm)

 

 

 

 

 

 

G

Clearance to inside corner: with AstroCap and Vent Riser Termination Caps

6"(15cm)

6"(15cm)

 

 

 

 

 

 

 

Clearance to inside corner: with all other approved Termination Caps

12"(30cm)

12"(30cm)

 

 

 

 

 

 

H

Clearance to each side of center line extended above meter/regulator assembly

36"(90cm)a

*

 

 

 

 

 

 

J

Clearance to service regulator vent outlet

36"(90cm)

*

 

 

 

 

 

 

K

Clearance to non-mechanical air supply inlet to building or the combustion air inlet to any other appliance

12"(30cm)

9" (23cm)

 

 

 

 

 

 

L

Clearance to a mechanical air supply inlet

72"(1.8m)

36"(90cm)b

 

 

#3' (91cm) above if within 10' (3m) horizontally.

 

 

 

 

 

 

 

 

M

Clearance above paved sidewalk or a paved driveway located on public property

84"(2.1m)

*

 

N

Clearance under veranda, porch, deck, or balcony

12"(30cm)

*

1

In accordance with current CSA B149.1, Natural Gas and Propane Installation Code

 

 

2

In accordance with the current ANSI Z223.1/NFPA 54, National Fuel Gas Code

 

 

A vent shall not terminate directly above a sidewalk or paved driveway which is located between two single family dwellings and serves both dwellings.

‡ Permitted only if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the fl oor * Clearance in accordance with local installation codes and the requirements of the gas supplier

a 3 feet (91cm) within a height of 15 feet (4.5m) above the meter / regulator assembly b 3 feet (91cm) above - if within 10 feet (3m) horizontally

13

Hampton® H27 Direct Vent Freestanding Gas Stove

INSTALLATION

4” X 6-5/8” RIGID PIPE CROSS REFERENCE CHART

Components from different Manufacturers may not be mixed. Not All Rigid Pipe components are available directly from FPI.

Description

Simpson

Selkirk

American Metal

Metal-Fab™

Security

ICC Excel

 

Direct Vent Pro®

Direct Temp™

Products®

Sure Seal

SecureVent®

Direct

 

 

 

Amerivent Direct

 

 

 

 

 

 

 

 

 

 

6” Pipe Length-Galvanized

46DVA-06

4DT-6

N/A

4D6

SV4L6

TC-4DL6

 

 

 

 

 

 

 

6” Pipe Length-Black

46DVA-06B

4DT-6B

N/A

4D6B

SV4LB6

TC-4DL6B

 

 

 

 

 

 

 

7” Pipe Length-Galvanized

N/A

N/A

4D7

N/A

N/A

N/A

 

 

 

 

 

 

 

7” Pipe Length-Black

N/A

N/A

4D7B

N/A

N/A

N/A

 

 

 

 

 

 

 

9” Pipe Length-Galvanized

46DVA-09

4DT-9

N/A

N/A

N/A

N/A

 

 

 

 

 

 

 

9” Pipe Length-Black

46DVA-09B

4DT-9B

N/A

N/A

N/A

N/A

 

 

 

 

 

 

 

12” Pipe Length-Galvanized

46DVA-12

4DT-12

4D12

4D12

SV4L12

TC-4DL1

 

 

 

 

 

 

 

12” Pipe Length-Black

46DVA-12B

4DT-12B

4D12B

4D12B

SV4LB12

TC-4DL1B

 

 

 

 

 

 

 

18” Pipe Length-Galvanized

46DVA-18

4DT-18

4D18

4D18

SV4LA

TC-4DL18

 

 

 

 

 

 

 

18” Pipe Length-Black

46DVA-18B

4DT-18B

4D18B

4D18B

SV4LA

TC-4DL18B

 

 

 

 

 

 

 

24” Pipe Length-Galvanized

46DVA-24

4DT-24

4D24

4D24

SV4L24

TC-4DL2

 

 

 

 

 

 

 

24” Pipe Length-Black

46DVA-24B

4DT-24B

4D24B

4D24B

SV4LB24

TC-4DL2B

 

 

 

 

 

 

 

36” Pipe Length-Galvanized

46DVA-36

4DT-36

4D36

4D36

SV4L36

TC-4DL3

 

 

 

 

 

 

 

36” Pipe Length-Black

46DVA-36B

4DT-36B

4D36B

4D36B

SV4LB36

TC-4DL3B

 

 

 

 

 

 

 

48” Pipe Length-Galvanized

46DVA-48

4DT-48

4D48

4D48

SV4L48

TC-4DL4

 

 

 

 

 

 

 

48” Pipe Length-Black

46DVA-48B

4DT-48B

4D48B

4D48B

SV4LB48

TC-4DL4B

 

 

 

 

 

 

 

60” Pipe Length-Galvanized

46DVA-60

4DT-60

N/A

N/A

N/A

N/A

 

 

 

 

 

 

 

60” Pipe Length-Black

46DVA-60B

4DT-60B

N/A

N/A

N/A

N/A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Adjustable Length 3”-10”-Galvanized

N/A

N/A

N/A

4DAL

N/A

TC-4DLT

 

 

 

 

 

 

 

Adjustable Length 3”-10”-Black

N/A

N/A

N/A

4DALB

N/A

TC-4DLTB

 

 

 

 

 

 

 

Adjustable Length 7”-Galvanized

N/A

N/A

4D7A

N/A

N/A

N/A

 

 

 

 

 

 

 

Adjustable Length 7”-Black

N/A

N/A

4D7AB

N/A

N/A

N/A

 

 

 

 

 

 

 

Extension Pipe 8-1/2”-Galvanized

46DVA-08A

N/A

N/A

N/A

N/A

N/A

 

 

 

 

 

 

 

Extension Pipe 8-1/2”-Black

46DVA-08AB

N/A

N/A

N/A

N/A

N/A

 

 

 

 

 

 

 

Adjustable Length 12”-Galvanized

N/A

N/A

4D12A

N/A

SV4LA12

N/A

 

 

 

 

 

 

 

Adjustable Length 12”-Black

N/A

N/A

4D12A

N/A

SV4LBA12

N/A

 

 

 

 

 

 

 

Extension Pipe 16”-Galvanized

46DVA-16A

N/A

N/A

N/A

N/A

N/A

 

 

 

 

 

 

 

Extension Pipe 16”-Black

46DVA-16AB

N/A

N/A

N/A

N/A

N/A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

45º Elbow-Galvanized

46DVA-E45

4DT-EL45

4D45L

N/A

N/A

TE-4DE45

 

 

 

 

 

 

 

45º Elbow-Black

46DVA-E45B

4DT-EL45B

4DT-EL45B

N/A

N/A

TE-4DE45B

 

 

 

 

 

 

 

45º Elbow Swivel-Galvanized

See 46DVA-E45

N/A

N/A

4D45L

SV4E45

N/A

 

 

 

 

 

 

 

45º Elbow Swivel-Black

See 46DVA-E45B

N/A

N/A

4D45LB

SV4EB45

N/A

 

 

 

 

 

 

 

90º Elbow-Galvanized

46DVA-E90

4DT-EL90S

4DT-EL90S

N/A

N/A

TE-4DE90

 

 

 

 

 

 

 

90º Elbow-Black

46DVA-E90B

4DT-EL90SB

4DT-EL90SB

N/A

SV4EBR90-1

TE-4DE90B

 

 

 

 

 

 

 

90º Elbow, Swivel-Galvanized

See 46DVA-E90

N/A

N/A

4D90L

SV4E90-1

N/A

 

 

 

 

 

 

 

90º Elbow, Swivel-Black

See 46DVA-E90B

N/A

N/A

4D90LB

SV4EB90-1

N/A

 

 

 

 

 

 

 

90º Starter Elbow, Swivel-Galvanized

N/A

N/A

N/A

4D90A

N/A

N/A

 

 

 

 

 

 

 

Adaptor*

N/A

N/A

N/A

4D90L

N/A

N/A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Ceiling Support

N/A

4DT-CS

4DFSP

4DSP

SV4SD

TE-4DE45

 

 

 

 

 

 

 

Cathedral Support Box

46DVA-CS

4DT-CSS

4DRSB

4DRS

SV4CSB

TE-4DE45B

 

 

 

 

 

 

 

Wall Support/Band

46DVA-WS

4DT-WS/B

4DWS

4DWS

SV4BM

N/A

 

 

 

 

 

 

 

Offset Support

46DVA-ES (N/A - FPI)

4DT-OS

N/A

N/A

SV4SU

N/A

 

 

 

 

 

 

 

Wall Thimble-Black

46DVA-WT

4DT-WT

4DWT

4DWT

SV4RSM

TE-4DE90

 

 

 

 

 

 

 

Wall Thimble Support/Ceiling Support

46DVA-DC

N/A

N/A

N/A

SV4PF

TE-4DE90B

 

 

 

 

 

 

 

Firestop Spacer

46DVA-FS

4DT-FS

4DFSP

4DFS

SV4BF

N/A

 

 

 

 

 

 

 

Trim Plate-Black

N/A

4DT-TP

4DFPB

4DCP

SV4LA

N/A

 

 

 

 

 

 

 

14

Hampton® H27 Direct Vent Freestanding Gas Stove

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

INSTALLATION

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Description

 

Simpson

 

 

Selkirk

 

 

American Metal

Metal-Fab™

 

Security

ICC Excel

 

 

 

 

 

 

 

Direct Vent Pro®

 

Direct Temp™

 

 

 

Products®

Sure Seal

SecureVent®

Direct

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Amerivent Direct

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Attic Insulation Shield 12”

 

46DVA-IS N/A@ FPI

N/A

 

 

 

 

 

4DAIS12

N/A

SV4RSA

N/A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Attic Insulation Shield - Cold Climates 36”

 

N/A

N/A

 

 

 

 

 

4DAIS12

N/A

N/A

TM-4AS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Basic Horizontal Termination Kit (A)

 

Disc.

4DT-HKA

 

 

 

 

 

4DHTK2

4DHTKA

SV-SHK

N/A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Horizontal Termination Kit (B)

 

46DVA-KHA

4DT-HKB

 

 

 

 

 

4DHTK1

4DHTKB

SV-HK

N/A

 

 

 

 

 

 

 

(Changed Components)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Vertical Termination Kit

 

Disc.

4DT-VKC

 

 

 

 

 

4DHTK

4DHTK

SV-FK

N/A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

High Wind Vertical Cap

 

46DVA-VCH

N/A

 

 

 

 

 

N/A

N/A

N/A

TM-4VT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

High Wind Horizontal Cap

 

46DVA-HC

N/A

 

 

 

 

 

N/A

N/A

N/A

TM-4DHT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Horizontal Square Termination Cap

 

See 46DVA-HC

4DT-HHC

 

 

 

 

 

4DHC

4DHT

SV4CHC-1

TM-4HT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Vertical Termination Cap

 

46DVA-VC

4DT-HVC

 

 

 

 

 

4DVC

4DVT

SV4CGV-1

TM-4VT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Storm Collar

 

 

 

 

46DVA-08A

4DT-SC

 

 

 

 

 

4DSC

4DSC

SV4FC

TM-SC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Adjustable Flashing 0/12-6/12

 

46DVA-F6

4DT-ST14

 

 

 

 

 

4D12S

4DST14

SV4STC14

TF-4FA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Adjustable Flashing 6/12-12/12

 

46DVA-FLA

4DT-ST36

 

 

 

 

 

4D36S

4DST36

SV4STC36

TF-4FB

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Vinyl Siding Standoff

 

46DVA-VSS

4DT-VS

 

 

 

 

 

N/A

4DVS

SV4VS

TM-VSS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Vinyl Siding Shield Plate

 

N/A

4DT-VSP

 

 

 

 

 

N/A

N/A

SV4VS

N/A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Snorkel Termination 14”

 

46DVA-SNKL

N/A

 

 

 

 

 

N/A

N/A

N/A

TM-4ST14

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Snorkel Termination 36”

 

N/A

N/A

 

 

 

 

 

N/A

N/A

N/A

TM-4ST36

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Restrictor Disk

 

 

 

 

N/A

N/A

 

 

 

 

 

N/A

N/A

N/A

TM-4DS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Extended Vertical Termination Cap

 

N/A

N/A

 

 

 

 

 

N/A

N/A

N/A

N/A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Chimney Conversion Kit A (USA only)

 

46DVA-KCA

N/A

 

 

 

 

 

N/A

N/A

N/A

TM-4CA6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Chimney Conversion Kit B (USA only)

 

46DVA-KCB

N/A

 

 

 

 

 

N/A

N/A

N/A

TM-4CA7

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Chimney Conversion Kit C (USA only)

 

46DVA-KCC

N/A

 

 

 

 

 

N/A

N/A

N/A

TM-4CA8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Chimney Conversion Kit Masonry

 

46DVA-KMC

N/A

 

 

 

 

 

N/A

N/A

N/A

N/A

 

 

(USA only)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Wall Firestop

 

 

 

 

46DVA-WFS

N/A

 

 

 

 

 

N/A

N/A

N/A

TM-4TR

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Colinear Flex Connectors

 

46DVA-ADF

N/A

 

 

 

 

 

N/A

N/A

N/A

N/A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FPI

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

946-506/P

 

 

Vent Guard (Optional) for AstroCap

 

 

 

 

946-205

 

 

 

 

 

 

 

Vinyl Siding Shield for Riser Vent Terminal

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

510-994

 

 

Rigid Pipe Adaptor (Must use with all rigid piping)

 

946-208/P

Vent Guard (Optional) for Riser Vent Terminal

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

640-530/P

 

 

Riser Vent Terminal

 

 

 

 

 

 

946-523/P

AstroCap Horizontal Cap

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

946-605

 

 

Starter Collar Increaser 4” x 6-5/8” to 5” x 8”

946-206

 

 

 

 

 

 

 

Vinyl Siding Standoff for AstroCap

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Note: When using Metal-Fab Sure Seal Rigid Piping - please note that the Adaptor (4DDA) must be used in conjunction with FPI Rigid Pipe Adaptor (510-994).

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Offset Pipe Selection: Use this table to determine offset pipe lengths.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Pipe Length

 

 

4” x 6-5/8” Venting

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

For specifi c instructions on venting components - visit the

 

 

(L)

 

 

Run (X)

 

Rise (Y)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

manufacturers website listed below.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0” (0mm)

 

4-7/8” (124mm)

 

13-7/8” (340mm)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Simpson Direct Vent Pro: www.duravent.com

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6” (152mm)

 

 

8” (203mm)

 

16-1/2” (419mm)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Selkirk Direct-Temp: www.selkirkcorp.com

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

9” (229mm)

 

10-1/8” (257mm)

 

18-5/8” (473mm)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

American Metal Products: www.americanmetalproducts.com

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

12” (305mm)

 

12-1/4” (311mm)

 

20-3/4” (527mm)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Metal-Fab Sure Seal: www.mtlfab.com

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

24” (610mm)

 

20-5/8” (524mm)

 

29-1/8” (740mm)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Security Secure Vent: www.securitychimneys.com

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

36” (914mm)

 

 

29” (737mm)

 

37-1/2” (953mm)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Industrial Chimney Company: www.icc-rsf.com

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

48” (1219mm)

 

37-7/16” (951mm)

 

45-15/16” (1167mm)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Note: Horizontal runs of vent must be level, or have a 1/4” rise for every 1 foot of run towards the termination.

Never allow the vent to run downward - this could cause high temperatures and may present a possible fi re hazard.

15