RBI HW 630, HW 420, HW 530, HW 735, HW 840 Installation & Operation Manual

...
Page 1
CIOM-6
42-9134 Rev. 4
SERIES 8800 & 8900 FINNED COPPER
GAS BOILERS (MODEL HB) &
WATER HEATERS (MODEL HW)
INSTALLATION & OPERATION MANUAL
DESIGNED AND TESTED ACCORDING TO A.S.M.E. BOILER AND PRESSURE VESSEL CODE, SECTION IV FOR A MAXIMUM ALLOWABLE WORKING PRESSURE OF 160 PSI,
WARNING: If the information in this manual is not followed exactly, a fire or explosion may result causing property damage, personal injury or loss of life.
Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.
WHAT TO DO IF YOU SMELL GAS:
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any phone in your building.
• Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the fire department.
Installation and service must be performed by a qualified installer, service agency or the gas supplier.
WARNING: Failure to properly vent this unit can cause excessive amounts of carbon monoxide resulting in severe personal injury or death!
1103 kPa
WATER.
INSTALLER, THESE INSTRUCTIONS TO BE AFFIXED ADJACENT TO THE HEATER.
CONSUMER, RETAIN THESE INSTRUCTIONS FOR FUTURE REFERENCE PURPOSES.
260 North Elm Street 7555 Tranmere Drive Westfield, MA 01085 Phone: (413) 568-9571 Phone: (905) 670-5888 Fax: (413) 568-9613 Fax: (905) 670-5782
Mississauga, Ontario L5S 1L4 Canada
Page 2
SERIES 8800 & 8900 INSTALLATION AND OPERATING INSTRUCTIONSPage 2
AVERTISSMENT. Assurez-vous de bien suivre les instructions données dans cette notice pour réduire au minimum le risque d’incendie ou d’explosion ou pour éviter tout dommoge matériel, toute blessure ou la mort
Ne pas entreposer ni utiliser d’essence ou ni d’autres vapeurs ou liquides inflammables à proximité de cet appareil ou de tout autre appareil.
QUE FAIRE SI VOUS SENTEZ UNE ODEUR DE GAZ:
• Ne pas tenter d’allumer d’appareil.
• Ne touchez à aucun interrupteur; ne pas vous servir des téléphones se trouvant dans le bâtiment.
• Appelez immédiatement votre fournisseur de gas depuis un voisin. Suivez les intructions du fournisseur.
• Si vous ne purvez rejoindre le fournisseur, appelez le service des incendies.
L’installation et l’entretien doivent être assurés par un installateur ou un service d’entretien qualifié ou par le fournisseur de gaz.
CONTENTS
Before You Start .................................................page 2
Ratings & Capacities ..........................................page 3
Boiler/Water Heater Location .............................page 3
Combustion Air & Ventilation ..............................page 4
Chimney & Vent Pipe Connections ....................page 8
Common Vent Systems ......................................page 9
General Piping Requirements ..........................page 10
Heating System Piping .....................................page 10
Domestic Water Supply Piping ......................... page 15
Gas Supply Piping............................................ page 20
Electrical Wiring ...............................................page 21
General Operation............................................ page 21
Operating Instructions ......................................page 22
Checking & Adjustments ..................................page 23
Control Description ..........................................page 25
Maintenance..................................................... page 26
Trouble-Shooting ..............................................page 28
Repair Parts, 8900 ...........................................page 30
Repair Parts, 8800 ...........................................page 39
BEFORE YOU START
This manual covers the application, installation, operation and maintenance of a Series 8800 and 8900 finned copper heating boiler/water heater/pool heater.
To obtain the safe, dependable, efficient operation and long life for which this heating boiler/water heater was designed, these instructions must be read, understood and followed.
The Series 8800 and 8900 finned copper heating boiler/ water heaters have been design certified by CSA for use with natural and propane gas under the latest revision of ANSI-Z21.10.3/CSA 4.3, Gas Water Heaters, ANSI­Z21.13/CSA 4.9, Gas-Fired Low Pressure Steam and Hot Water Boilers and CAN1-3.1, Industrial and Commercial Gas Fired Packaged Boilers. Each unit has been constructed and hydrostatically tested for a maximum working pressure of 160 psi, Section IV of the A.S.M.E. Boiler and Pressure Vessel Code.
All aspects of the boiler/water heater installation must conform to the requirements of the authority having jurisdiction, or, in the absence of such requirements, to the National Fuel Gas Code, ANSI Z223.1/NFPA 54-latest revision. Where required by the authority having jurisdiction, the installation must conform to the Standard for Controls and Safety Devices for Automatically Fired Boilers, ANSI/ASME CSD-1.
In Canada, the installation must be in accordance with the requirements of CAN/CGA B149.1 or .2, Installation Code for Gas Burning Appliances and Equipment.
If installed in the Commonwealth of Massachusetts, you MUST FOLLOW the additional instructions contained in RBI's instruction sheet MACODE-3. If you do not have a copy, call your RBI distributor or contact the RBI Customer Service Department.
The owner should maintain a record of all service work performed with the date and a description of the work done. Include the name of the service organization for future reference.
1103 kPa
in accordance with
Page 3
SERIES 8800 & 8900 INSTALLATION AND OPERATING INSTRUCTIONS Page 3
Direct all questions to your RBI distributor or contact the RBI Customer Service Department, 260 North Elm Street, Westfield, MA 01085 for U.S. or 7555 Tranmere Drive, Mississauga ONT L5S 1L4 for Canada. Always include the model and serial numbers from the rating plate of the boiler/ water heater in question.
RATINGS & CAPACITIES
Before undertaking the installation of the Series 8800 and 8900 boiler/water heater check the rating plate to ensure that the unit has been sized properly for the job. The “Net I=B=R Ratings” specify the equivalent amount of direct cast iron radiation that the unit can supply under normal conditions. Also ensure that the unit has been set up for the type of gas available at the installation site. Other important considerations are the availability of an adequate electrical supply, fresh air for combustion and a suitable chimney or vent system.
BOILER/WATER HEATER LOCATION
1. Locate the boiler/water heater in an area that provides good access to the unit. Servicing may require the removal of jacket panels. minimum clearances between adjacent construction and the boiler/water heater as listed in Table 1 or 1A.
NOTE: Service clearances are not mandatory, but are recommended to ensure ease of service should it be required.
Table 1 (8800)
Clearance to Service
Combustibles Clearance
in
To p 24 Back 24 Left Side 24 Right Side 24 Front 48 Flue 6
Table 1A (8900)
Clearance to Service
Combustibles Clearance
in
To p 24 Back 18 Left Side 18 Right Side 18 Front 48 Flue 6
mm 610 610 610 610
1220
152
mm 610 457 457 457
1220
152
Allow the
in 18 18 24 24 48
6
in 18 18 18 18 36
6
mm 457 457 610 610
1220
152
mm 457 457 457 457 914 152
2. An optimum site will be level, central to the piping system, close to a chimney and have adequate fresh air for combustion. Ensure that the boiler/water heater is level from front to back and from side to side. Use metal shims to level the boiler/water heater. Electrical and electronic components must also be protected from exposure to water during operation and maintenance. DO NOT install this boiler/water heater in a location that would subject any of the gas ignition components to direct contact with water or excessive moisture during operation or servicing.
3. Ensure that the floor is structurally sound and will support the weight of the boiler/water heater.
NOTE: Never install a Series 8800 or 8900 boiler/ water heater on a concrete floor that contains wires, cables, water pipes or hoses. This boiler/water heater is designed for noncombustible floors only! Never install this boiler/water heater on combustible materials or carpeting even if a non-combustible foundation material is placed over them!
4. Locate the boiler/water heater in an area that will prevent water damage to adjacent construction should a leak occur or during routine maintenance. If such a location doesn’t exist, a suitable drain pan that’s adequately drained must be installed under the unit. The combustion air to the unit.
5.
DO NOT place this boiler/water heater in a location that would restrict the introduction of combustion air into the unit or subject it to a negative pressure, see “GENERAL VENTING GUIDELINES”.
6. NEVER place this boiler/water heater in a location that would subject it to temperatures at or near freezing.
WARNING: Never store combustible materials, gasoline or any product containing flammable vapors or liquids in the vicinity of the boiler/water heater. Failure to comply with this warning can result in an explosion or fire causing extensive property damage, severe personal injury or death!
pan must not restrict the flow of
Page 4
SERIES 8800 & 8900 INSTALLATION AND OPERATING INSTRUCTIONSPage 4
COMBUSTION AIR & VENTILATION
WARNING: This boiler/water heater must be supplied with combustion air in accordance with Section 5.3, Air for Combustion & Ventilation, of the latest revision of the National Fuel Gas Code, ANSI Z223.1/ NFPA 54 and all applicable local building codes. Canadian installations must comply with CAN/ CGA B149.1 or .2 Installation Code for Gas Burning Appliances and Equipment, or applicable provisions of the local building codes. Failure to provide adequate combustion air for this boiler/water heater can result in excessive levels of carbon monoxide which can result in severe personal injury or death!
To operate properly and safely this boiler/water heater requires a continuous supply of air for combustion. NEVER store objects on or around the boiler/water heater!
CAUTION: Combustion air contaminated with fluorocarbons or other halogenated compounds such as cleaning solvents and refrigerants will result in the formation of acids in the combustion chamber. These acids will cause premature failure of the boiler/water heater voiding the warranty!
CAUTION: If the boiler/water heater is operated while the building is under construction it MUST be protected from wood, concrete, sheet rock and other types of dust. Failure to properly protect the unit from construction dust will damage the unit voiding the warranty!
All Air From Inside The Building
If the boiler/water heater is to be located in a confined space minimum clearances listed in Table 1 or 1A must be maintained between the boiler/water heater and any combustible construction. When installed in a confined space, Figures 1, 2, 3, 4 and 5, two permanent openings communicating with an additional room(s) are required. The combined volume of these spaces must have sufficient volume to meet the criteria for an unconfined space. The total air requirements of all gas utilization equipment, fireplaces, wood stoves or any type of exhaust fan must be considered when making this determination. Each opening must have a minimum free area of 1 in2/1000 Btu/hr, total input rating of confined area. Each opening must be no less than
100 in2,
be within 12 in,
76 mm
opening must be within 12 in, than 3 in,
All Air From Outside The Building
When installed in a confined space two permanent openings communicating directly with, or by ducts to, the outdoors or spaces that freely communicate with the outdoors must be present. The upper opening must be within 12 in,
76 mm
opening must be within 12 in, than 3 in,
Where directly communicating with the outdoors or communicating with the outdoors through vertical ducts, each opening shall have a minimum free area of 1 in2/4000 Btu/hr, rating of all of the equipment in the enclosure.
64,516 mm
from, the top of the enclosure. The bottom
76 mm
from, the top of the enclosure. The bottom
76 mm
ALL
305 mm
from, the bottom of the enclosure.
305 mm
from, the bottom of the enclosure.
2200 mm2/kW
gas utilization equipment in the
2
in size. The upper opening must
of, but not less than 3 in,
305 mm
of, but not less than 3 in,
305 mm
550 mm2/kW
based on the
of, but not less
of, but not less
of the total input
Page 5
SERIES 8800 & 8900 INSTALLATION AND OPERATING INSTRUCTIONS Page 5
Where communicating with the outdoors through horizontal ducts, each opening shall have a minimum free area of 1 in2/2000 Btu/hr,
1100 mm2/kW
of the total input rating of all of the equipment in the enclosure. When ducts are used, they must have the same cross­sectional area as the free area of the opening to which they connect.
Canadian installations must comply with CSA B149.1 when
air supply
outdoors for assisted, or power draft-assisted be a permanent
is provided by natural air flow from the
natural draft
air supply
, partial fan-assisted, fan-
burners
, there shall
opening(s) having a cross-
sectional area of not less than 1 in2 per 7,000 Btuh
(310 mm2 per kW)
plus 1 in2 per 14,000 Btuh
up to and including 1 million Btuh,
(155 mm2 per kW)
in excess
of 1 million Btuh.
When calculating the free area necessary to meet the make-up air requirements of the enclosure, consideration must be given to the blockage effects of louvers, grills and screens. Screens must have a minimum mesh size of 1/4 in,
6.4 mm
. If the free area through a louver or grill is not known, ducts should be sized per Table 2.
Table 2 - Make-up Air Louver Sizing
Required Cross Sectional Area
Input 1/4 in
6.4 mm
75% Free Area 25% Free Area
(MBH) Wire Screen Metal Louvers Wooden Louvers
2
in
420 105 530 133 630 158 735 184 840 210 950 238 1050 263 1160 290 1260 315 1370 343 1470 368 1580 395 1685 421 1790 448 1900 475 2000 500 2400 600 2800 700 3200 800 3600 900 4000 1000
cm
677
858 1019 1187 1355 1535 1697 1871 2032 2213 2374 2548 2716 2890 3065 3226 3871 4516 5161 5806 6452
2
2
in
140 177 210 245 280 317 350 387 420 457 490 527 562 597 633 667 800 933
1067 1200 1333
cm
903 1142 1355 1581 1806 2032 2258 2497 2710 2948 3161 3400 3626 3852 4084 4303 5161 6019 6884 7742 8600
2
2
in
420 530 630 735 840 950
1050 1160 1260 1370 1470 1580
10,194
1685
10,871
1790
11,548
1900
12,258
2000
12,903
2400
15,483
2800
18,064
3200
20,645
3600
23,226
4000
25,806
cm
2710 3419 4064 4742 5419 6129 6774 7484 8129 8839 9484
2
Figure 1 - Vertical Venting Using A Metal Chimney And Inside Air (8900/8800 Series)
2 FT .6 m
10 FT 3.4 m
3 FT 1 m
3 FT 1 m
5 FT 1.52 m
RIOM-40
Page 6
SERIES 8800 & 8900 INSTALLATION AND OPERATING INSTRUCTIONSPage 6
Figure 2 - Vertical Venting Using A Masonary Chimney And Inside Air (8900/8800 Series)
10 FT 3.1 m
3 FT 1 m
3 FT 1 m
5 FT 1.52 m
Figure 3 - Dual Flue Outlets And Inside Air (8900/8800 Series)
2 FT .6 m
10 FT 3.4 m
3 FT 1 m
10 FT 3.4 m
5 FT 1.5 m
RIOM-41
RIOM-42
Page 7
SERIES 8800 & 8900 INSTALLATION AND OPERATING INSTRUCTIONS Page 7
Figure 4 - Common Vents and Inside Air (8900/8800 Series)
10FT 3.1 m
3FT 1m
5FT 1.52m
3FT 1m
Figure 4A - Common Vents and Inside Air (8800/8900 Series) Dual Flue
10 FT
3.1 m
3 FT
1 m
RIOM-43
3 FT
1 m
5 FT
1.52 m
Figure 5 - Horizontal Venting And Inside Air (8900/8800 Series)
BUILDING OVERHANG
4FT 1.2 M MAX.
PITCH PIPE DOWN TOWARDS TERMINAL CAP 1/4 IN. PER FOOT 20 MM/M OF RUN TO
3FT .9 m
1.5 FT 0.5m MINIMUM DIST ANCE FROM
EXHAUST TO MAXIMUM SNOW LINE.
ALLOW FOR CONDENSATE DRAINAGE
3FT 1 m
5FT 1.52 m
RIOM-44
RIOM-45
Page 8
SERIES 8800 & 8900 INSTALLATION AND OPERATING INSTRUCTIONSPage 8
CHIMNEY & VENT PIPE CONNECTIONS
WARNING: The vent installation must be in accordance with Part 7, Venting of Equipment, of the National Fuel Gas Code, ANSI Z223.1/NFPA 54-latest revision or applicable provisions of the local building codes. Canadian installations must comply with CAN/CGA B149.1 or .2 Installation Code. Improper venting can result in excessive levels of carbon monoxide which can result in severe personal injury or death!
Chimney Inspection & Sizing
A thorough inspection of the masonry chimney must be performed to ensure that the chimney is clean, properly constructed, lined and sized. Exterior masonry chimneys should not be used unless properly lined to prevent condensation and draft problems. Table 3A and 3B lists the equivalent breeching and flue sizes required for the boiler/water heater.
Table 3A - Equivalent Breeching & Chimney Size
Model Size Model Size
Size in 420 10 530 10 630 12 735 14 840 14 950 14 1050 16 1160 16 1260 16 1370 18 1470 18
Note: These sizes are based on a 20 ft,
mm 254 254 305 356 356 356 406 406 406 457 457
Size in 1580 18 1685 18 1790 20 1900 20 2000 22 2400 24 2800 26 3200 28 3600 30 4000 30
6.1m
chimney height.
mm 457 457 508 508 559 610 660 711 762 762
When more than one appliance is connected to the same chimney flue, the flue must be large enough to safely vent the combined output of all the appliances.
WARNING: If an appliance using any type of a mechanical draft system operating under positive pressure is connected to a chimney flue, never connect any other appliances to this flue. Doing so can result in the accumulation of carbon monoxide which can cause severe personal injury or death!
Vent Connections
Always use a type B or single wall galvanized metal vent pipe the same diameter as the draft diverter flue collar. Use the shortest, straightest vent system possible for the installation. If horizontal runs exceed 6 ft, must be supported at 6 ft,
1.8 m
intervals with overhead
1.8 m
they
hangers. The vent system should be sloped up toward the chimney at a minimum rate of 1/4 in/ft,
20 mm/m
and terminate flush with the inside of the chimney flue. Fasten each connection with at least 3 corrosion resistant sheet metal screws.
WARNING: Never modify or alter any part of the boiler’s draft diverter. This includes the removal or alteration of any baffles. Never install a vent pipe of a diameter different than that of the boiler draft hood flue collar. Failure to comply with this warning can result in severe personal injury or death.
Always provide a minimum clearance of 6 in,
152 mm
between type C vent pipe and any combustible materials. Type B1 vent may be used, clearance between it and any combustible material must be as listed.
Table 3B - Equivalent Breeching & Chimney Size Dual Flue
Model Size Model Size
Size in 840 10 950 10 1050 12 1160 12 1260 12 1370 14 1470 14 1580 14 1685 14
Note: Minimum vertical rise off top dual flue units: 3 ft, 840-3200), 5 ft,
mm 254 254 305 305 305 355 355 355 355
1.5 m
(sizes 3600-4000).
Size in 1790 16 1900 16 2000 14 2400 16 2800 18 3200 20 3600 22 4000 22
1 m
mm 406 406 356 406 457 508 559 559
(sizes
WARNING: Failure to maintain minimum clearances between vent connectors and any combustible material can result in a fire causing extensive property damage, severe personal injury or death!
To determine the appropriate power venter for the boiler/ water heater, see Table 4, Power Venter Sizes. Follow the power venter manufacturer’s installation instructions.
Table 4 - Power Venter Sizes
8900 Power Venter Max. Pipe Length
Model Size FT
420-530 HS-2 100
630 HS-3 100
735-1160 HS-4 100
1260-1900 HS-5 100
m 31 31 31 31
Models 2000-4000 - Consult Tjernlund
Page 9
SERIES 8800 & 8900 INSTALLATION AND OPERATING INSTRUCTIONS Page 9
COMMON VENT SYSTEMS
If an existing boiler/water heater is removed from a common venting system, the common venting system may then be too large for the proper venting of the remaining appliances connected to it. At the time of removal of an existing boiler/water heater, the following steps shall be followed with each appliance remaining connected to the common venting system placed in operation, while the other appliances remaining connected to the common venting system are not in operation.
Au moment du retrait d’une chaudière existante, les mesures suivantes doivent être prises pour chaque appareil toujours raccordé au système d’évacuation commun et qui fonctionne alors que d’autres appareils toujours raccordés au système d’évacuation ne fonction­nent pas: système d’évacuation
a) Seal any unused openings in the common venting
system.
Sceller toutes les ouvertures non utilisées du sys­tème d’évacuation.
b) Visually inspect the venting system for proper size
and horizontal pitch and determine there is no blockage or restriction, leakage, corrosion and other deficiencies which could cause an unsafe condition.
Inspecter de façon visuelle le système d’évacu-ation pour déterminer la grosser et l’inclinaison horizontale qui conviennent et s’assurer que le système est exempt d’obstruction, d’étranglement de fruite, de corrosion et autres défaillances qui pourraient présenter des risques.
c) Insofar as is practical, close all building doors and
windows and all doors between the space in which the appliances remaining connected to the common venting system are located and other spaces of the building. Turn on clothes dryers and any appliance not connected to the common venting system. Turn on any exhaust fans, such as range hoods and bathroom exhaust, so they will operate at maximum speed. Do not operate a summer exhaust fan for a boiler installation. Close fireplace dampers.
Dans la mesure du possible, fermer toutes les portes et les fenêtres du bâtiment et toutes les portes entre l’espace où les appareils toujours raccordés du système d’évacuation sont installés et les autres espaces du bâtiment. Mettre en marche les sécheuses, tous les appareils non raccordés au système d’évacuation commun et tous les ventilateurs d’extraction comme les hottes de cuisinère et les ventilateurs des salles de bain. S’assurer que ces ventilateurs fonctionnent à la
vitesse maximale. Ne pas faire fonctionner les ventilateurs d’été. Fermer les registres des cheminées.
d) Place in operation the appliance being inspected.
Follow the lighting instructions. Adjust thermostat so appliance will operate continuously.
Mettre l’appareil inspecté en marche. Suivre les instructions d’allumage. Régler le thermostat de façon que l’appareil fonctionne de façon continue.
e) Test for spillage at the draft hood relief opening after
5 minutes of main burner operation. Use the flame of a match or candle, or smoke from a cigarette, cigar or pipe.
Faire fonctionner le brûleur principal pendant 5 min ensuite, déterminer si le coupe-tirage déborde à l'ouverture de décharge. Utiliser la flamme d'une allunette ou d'une chandelle ou la fumée d'une cigarette, d'un cigare ou d'une pipe.
f) After it has been determined that each appliance
remaining connected to the common venting system properly vents when tested as outlined above, return doors, windows, exhaust fans, fireplace dampers and any other gas-burning appliance to their previous condition of use.
Une fois qu’il a été d éterminé, selon la métode indiquée ci-dessus, que chaque appareil raccordé au système d’évacuation est mis à l’air libre de façor adéquate. Remettre les portes et les fenêtres, les ventilateurs, les registres de cheminées et les appareils au gaz à leur position originale.
g) Any improper operation of the common venting
system should be corrected so the installation conforms with the National Fuel Gas Code, ANSI Z223.1/NFPA 54. When resizing any portion of the common venting system, the common venting system should be resized to approach the minimum size as determined using the appropriate tables in Part 11 in the National Fuel Gas Code, ANSI Z223.1/NFPA 54 and or CAN/CGA-B149 Installation Codes.
Tout mauvais fonctionnement du systéme d'évacu­tion commun devrait étré corrigé de façor que l'installation soit conforme au National Fue Gas Code, ANSI Z223.1/NFPA 54 et (ou) aux codes d'installation CSA-B149. Si la grosseur d'une section du système d'évacuation doit étré modifiée, le système devrait étré modifié pour respecter les valeurs minimales des tableaux pertinents de l'appendice F du National Fuel Gas Code, ANSI Z223.1/NFPA 54 et (ou) des codes d'installation CSA-B149.
Page 10
SERIES 8800 & 8900 INSTALLATION AND OPERATING INSTRUCTIONSPage 10
GENERAL PIPING REQUIREMENTS
CAUTION: Improper piping of this boiler/water heater will void the manufacturer’s warranty and can cause boiler failure resulting in flooding and extensive property damage! Excessive water hardness causing lime build-up in the copper heat exchanger tubes is
NOT
covered under the manufacturer’s warranty. Excessive pitting and erosion of the internal surface of the copper heat exchanger tubes is under the manufacturer’s warranty if the result of high water flow rates, see Table 6A and 6B. Return water temperatures below 110°F, 43°C will result in heat exchanger damage from excessive condensation voiding the manufacturer’s warranty, see Primary/Secondary Piping Figure 7.
NOTE: Shut off valves and unions should be installed at the inlet and outlet connections of the boiler/hot water heater to provide for isolation of the unit should servicing be necessary.
Relief Valve
Pipe the discharge of the pressure relief valve to prevent scalding in the event of a discharge, see Figure 6. The discharge piping must be sized the same as the pressure relief valve outlet and installed to allow complete drainage of both the relief valve and the discharge piping.
Figure 6
1" (25mm) CLEARANCE MUST BE MAINTAINED BETWEEN HOT WATER PIPING AND COMBUSTIBLE CONSTRUCTION.
NOT
covered
CAUTION: Failure to properly install the flow switch may result in damage to the boiler/water heater heat exchanger voiding the warranty!
HEATING SYSTEM PIPING
General Piping Requirements
All heating system piping must be installed by a qualified technician in accordance with the latest revision of the ANSI/ASME Boiler and Pressure Vessel Code, Section IV, and ANSI/ASME CSD-1, Standard for Controls and Safety Devices for Automatically Fired Boilers. All applicable local codes and ordinances must also be followed. A minimum clearance of 1 in, maintained between heating system pipes and all combustible construction. All heating system piping must be supported by suitable hangers not the boiler.
The thermal expansion of the system must be considered when supporting the system. A minimum system pressure of 12 psig, maintained.
Heating Boiler Piping Connections
The supply and return connections should be sized to suit the system, see Table 5.
Table 5 - Supply & Return Pipe Sizing
Model Supply Return 8900 21/2" NPT 21/2" NPT 8800 3" Victaulic 3" Victaulic *Models 420-950 may have 21/2" x 2" reducing fitting installed.
25 mm
82.7 kPa
must be
must be
DISCHARGE PIPE SIZE TO EQUAL VALVE OUTLET.
OUTLET
INLET
RIOM-46
DO NOT RESTRICT FLOW.
DISCHARGE SO AS TO AVOID EXPOSURE OF PERSONS TO HOT LIQUID OR VAPOR AND ALLOW COMPLETE DRAINAGE 0F RELIEF VALVE AND PIPING
.
WARNING: Never install any type of valve between the boiler/water heater and the relief valve or an explosion causing extensive property damage, severe personal injury or death may occur!
Flow Switch
The flow switch supplied with the boiler/water heater must be wired to the terminal strip in the junction box to prevent the boiler from firing unless there’s adequate water flow through the unit. The flow switch must be installed in the supply piping adjacent to the boiler outlet connection.
Pump Requirements
This low mass boiler requires a continuous minimum water flow for proper operation. The system pump must be sized to overcome the head loss of the boiler and the heating system in order to achieve the required temperature rise. Table 6A and 6B provides the heat exchanger pressure drop and temperature rise figures. The temperature rise across the boiler must never exceed 35°F,
19.4°C
. The pump delay turns the pump on each time the burners fire and runs the pump for up to 10 minutes after the call for heat is satisfied.
CAUTION: A temperature rise outside of the range listed in Table 6A and 6B indicates that the flow rate through the heat exchanger is incorrect which will damage the heat exchanger voiding the warranty!
The maximum allowable flow rate through an 8900 boiler with copper heat exchanger is 92 GPM,
5.8 L/s
and 185 GPM,
11.7 L/s
on single pass.
The maximum allowable flow rate through an 8800 boiler with copper heat exchanger is 185 GPM,
11.7 L/s
and 370 GPM,
23.3 L/s
on single pass.
Page 11
SERIES 8800 & 8900 INSTALLATION AND OPERATING INSTRUCTIONS Page 11
Table 6A - Temperature Rise Table — 2 Pass Headers
20°F
Press
Flow
Model
420 530 630 735 840 950 1050 1160 1260 1370 1470 1580 1685 1790 1900 2000 2400 2800 3200 3600 4000
*Flow exceeds recommended maximum use a greater temperature rise or consult manufacturer. Cupro-nickel heat exchanger should be considered.
GPM Ft
34.0
42.9
51.0
59.5
68.0
77.0
85.1
94.0*
164.0
196.8*
Rate
— — — — — — —
— — — —
Drop
0.4
0.7
1.1
1.6
2.4
3.3
4.4
5.8 — — — — — — —
4.1
6.8 — — — —
11.1°C
Press
Flow
Drop
Rate
L/s kPa
1.1
2.1
2.0
2.7
3.2
3.2
4.8
3.8
7.0
4.3
9.8
4.9
12.9
5.4
17.0
5.9 — — — — — — —
12.0
10.3
20.0
12.4 — — — —
— — — — — — —
— — — —
25°F
Flow Rate
GPM Ft
34.3
40.8
47.6
54.4
61.6
68.0
75.2
81.6
88.8
95.3* — — — —
131.2
157.4
183.7 — — —
Press Drop
0.4
0.7
1.1
1.6
2.2
2.9
3.8
4.8
6.1
7.4 — — — —
2.7
4.5
6.9 — — —
13.9°C
Press
Flow
Drop
Rate
L/s kPa
1.3
2.2
2.1
2.6
3.2
3.0
4.6
3.4
6.5
3.9
8.6
4.3
11.2
4.7
14.2
5.2
17.9
5.6
21.8
6.0 —
8.0
8.3
13.2
9.9
20.3
11.6 —
30°F
Flow
Rate
GPM Ft
— —
34.0
39.7
45.4
51.3
56.7
62.6
68.0
74.0
79.4
85.3
91.0
96.7* —
109.3
131.2
153.1
174.9
196.8* —
Press
Drop
— —
0.5
0.8
1.1
1.6
2.1
2.7
3.4
4.3
5.3
6.5
7.7
9.2 —
1.9
3.2
4.9
7.2
10.0 —
16.7°C
Press
Flow
Drop
Rate
L/s kPa
— —
2.1
1.5
2.5
2.3
2.9
3.3
3.2
4.6
3.6
6.1
4.0
8.0
4.3
10.1
4.7
12.8
5.0
15.6
5.4
19.0
5.7
22.8
6.1
27.0
6.9
5.7
8.3
9.4
9.7
14.5
11.0
21.1
12.4
29.3
— —
35°F
Flow Rate
GPM Ft
— — —
34.0
38.9
44.0
48.6
53.7
58.3
63.4
68.0
73.1
78.0
82.9
87.9
93.7
112.5
131.2
149.9
168.7
187.4*
Press
Drop
— — —
0.6
0.8
1.2
1.6
2.0
2.6
3.3
4.0
4.8
5.8
6.9
8.1
1.4
2.4
3.7
5.4
7.5
10.1
19.4°C
Press
Flow
Drop
Rate
L/s kPa
— — —
2.1
1.7
2.5
2.5
2.8
3.5
3.1
4.6
3.4
6.0
3.7
7.6
4.0
9.6
4.3
11.7
4.6
14.3
4.9
17.1
5.2
20.3
5.5
23.9
5.9
4.3
7.1
7.1
8.3
10.9
9.5
15.8
10.6
22.0
11.8
29.6
— — —
Table 6B - Temperature Rise Table — Single Pass Headers
25°F
Press
Flow
Drop
Rate GPM Ft
— — — — —
61.6
68.0
75.2
81.6
88.8
95.3
102.4
109.2
116.0
123.1
131.2
157.4
183.7
209.9
236.2
262.4
— — — — —
0.3
0.4
0.5
0.7
0.8
1.0
1.3
1.5
1.8
2.1
0.4
0.6
1.0
1.4
1.9
2.6
Model
420 530 630 735 840 950 1050 1160 1260 1370 1470 1580 1685 1790 1900 2000 2400 2800 3200 3600 4000
20°F
Press
Flow
GPM Ft
68.0
77.0
85.1
94.0
102.1
111.0
119.1
128.0
136.5
145.0
153.9
164.0
196.8
229.6
262.4
295.2
328.0
Rate
— — — —
Drop
— — — —
0.3
0.5
0.6
0.8
1.0
1.3
1.6
1.9
2.3
2.7
3.2
0.6
0.9
1.4
2.1
2.9
3.9
11.1°C
Press
Flow
Drop
Rate
L/s kPa
— — — —
1.0
4.3
1.4
4.9
1.8
5.4
2.4
5.9
3.0
6.4
3.7
7.0
4.6
7.5
5.6
8.1
6.7
8.6
7.9
9.1
9.3
9.7
1.7
10.3
2.8
12.4
4.3
14.5
6.2
16.6
8.6
18.6
11.6
20.7
— — — —
13.9°C
Press
Flow
Drop
Rate
L/s kPa
3.9
4.3
4.7
5.2
5.6
6.0
6.5
6.9
7.3
7.8
8.3
9.9
11.6
13.2
14.9
16.6
0.9
1.2
1.6
2.0
2.5
3.0
3.7
4.4
5.2
6.2
1.1
1.8
2.8
4.1
5.7
7.7
30°F
Press
Flow
Drop
Rate
GPM Ft
— — — — — — —
62.6
68.0
74.0
79.4
85.3
91.0
96.7
102.6 —
131.2
153.1
174.9
196.8
218.7
— — — — — — —
0.4
0.5
0.6
0.7
0.9
1.1
1.3
1.5 —
0.4
0.7
1.0
1.4
1.9
16.7°C
Press
Flow
Drop
Rate
L/s kPa
— — — — — — —
4.0
4.3
4.7
5.0
5.4
5.7
6.1
6.5
1.1
1.4
1.8
2.2
2.6
3.2
3.7
4.4
8.3
9.7
11.0
12.4
13.8
1.3
2.0
2.9
4.1
5.5
— — — — — — —
35°F
Press
Flow Rate
GPM Ft
— — — — — — — — —
63.4
68.0
73.1
78.0
82.9
87.9 — —
131.2
149.9
168.7
187.4
Drop
— — — — — — — — —
0.5
0.6
0.7
0.8
1.0
1.1 — —
0.5
0.7
1.0
1.4
19.4°C
Press
Flow
Drop
Rate
L/s kPa
— — — — — — — — —
4.0
4.3
4.6
4.9
5.2
5.5 — —
8.3
9.5
10.6
11.8
— — — — — — — — —
1.3
1.6
2.0
2.4
2.8
3.3 — —
1.5
2.2
3.1
4.1
Page 12
SERIES 8800 & 8900 INSTALLATION AND OPERATING INSTRUCTIONSPage 12
Low Water Cutoff
If a boiler is installed above any radiation elements it must be fitted with a low water cutoff device.
Refer to the wiring diagram supplied with the boiler/ water heater for proper wiring connections.
Expansion Tank
An expansion tank or other means to control thermal expansion must be installed in the heating system. An expansion tank must be installed close to the boiler on the suction side of the pump.
Primary/Secondary Piping
Boilers connected to heating systems using zone valves, zone pumps, or systems that have excessive flow rates or return water temperatures less than 110°F,
43°C
must be isolated from these systems to protect the
boiler.
Variable Water Flows
Figure 7 shows a typical primary/secondary piping system. A dedicated pump is used to maintain a constant water flow through the boiler. This secondary pump is sized to overcome the head loss of the boiler and secondary piping system while supplying the flow rate required to maintain the desired temperature rise across the boiler. The primary pump is sized to provide the required flow to the heating system. The secondary piping connections to the primary system piping must not be more than 12 in,
305 mm
apart to ensure zero
pressure drop in the primary system, see Figure 7.
Low Return Water Temperatures
To prevent the problems associated with condensation of the products of combustion due to low return water temperatures a primary/secondary piping system with a bypass and bypass valve must be installed, see Figure 8. The bypass and bypass valve must be sized the same as the secondary piping. A balancing valve must also be installed in the supply side of the secondary piping downstream of the bypass. The balancing valve should be adjusted to divert some of the heated discharge water into the return water until the required inlet water temperature is achieved. The primary and secondary pumps should be sized to provide the required flow through each system. The secondary piping connections to the primary system piping must not be more than 12 in,
305 mm
apart to ensure zero pressure drop in the primary system, see Figure 8.
Multiple Boiler Systems
Systems using multiple boilers can also be installed using a primary/secondary manifold system, Figure 9.
Piping For Use With Cooling Units
The boiler, when used in connection with a refrigeration system, must be installed so the chilled medium is piped in parallel with the boiler. Appropriate valves must be used to prevent the chilled water from entering the boiler.
When a boiler is connected to a heating coil that may be exposed to refrigerated air from an air handling device, the piping system must be equipped with flow­control valves or some other automatic means of preventing gravity circulation of the boiler water during the cooling cycle.
Page 13
SERIES 8800 & 8900 INSTALLATION AND OPERATING INSTRUCTIONS Page 13
Figure 7 - Typical Primary/Secondary Piping System
(See Notes)
1
Circuit Setter
Pump
Valve
Check Valve
Backflow-Prevention
Device
Figure 8 - Low Temperature Piping
See Notes and Adjustment Procedures
1
H-1 Rev 2
H-3 Rev 2
Pressure
Relief Valve
Thermometer
Aquastat
Epansion
Tank
Union
Automatic
Air Vent
Pressure Reducing
Valve
NOTES:
1.Boilercircuitpipingmustbesizedlargeenoughtohandle maximumflowthroughunit.
2.Boilerpumpsizedtoboilerdesignflowrequirements.
3.Allboilersfurnishedwithfactorymountedoutletwater temperaturegauge.
4.Boilerpumppurgingrequired.Useterminalssupplied.
Notice:Thesedrawingsshowsuggestedpipingconfigurationandvalving. Checkwithlocalcodesandordinancesforspecificrequirements.
Adjustment Procedure To Maintain Inlet Temperature
Above Dew Point
T1-Temp-Min=110° For Atmospheric
T1-Temp-Min=125° Sealed Combustion
1. Turn heater on and open valves A & B.
2. After steady-state operation, if T1 is less than Temp-Min slowly close valve B until T1 climbs to desired operating temperature above Temp-Min.
3. If T1 is greater than desired operating temperature, slowly close valve A to adjust to lower desired temperature above Temp-Min.
4. Check after system operating temperature has stabilized. Make final adjustments.
5. Follow same adjustment procedure for sealed combustion.
Page 14
SERIES 8800 & 8900 INSTALLATION AND OPERATING INSTRUCTIONSPage 14
Figure 9 - Multiple Boiler Piping
(See Notes)
5
Circuit Setter
1
NOTES:
1. Boiler circuit piping must be sized large enough to handle maximum flow through unit.
2. Boiler pump sized to boiler design flow requirements.
3. All boilers furnished with factory mounted outlet water temperature gauge.
4. Boiler pump purging required. Use terminals supplied.
5. Secondary loop pipe diameter must be sized large enough to handle maximum flow through all units.
Notice: These drawings show suggested piping configuration and valving. Check with local codes and ordinances for specific requirements.
H-15 Rev 2
Pump
Valve
Check Valve
Backflow-Prevention
Device
Pressure
Relief Valve
Thermometer
Aquastat
Epansion
Tank
Union
Automatic
Air Vent
Pressure Reducing
Valve
Page 15
SERIES 8800 & 8900 INSTALLATION AND OPERATING INSTRUCTIONS Page 15
DOMESTIC WATER SUPPLY PIPING
CAUTION: Proper controls must be used to prevent water supplied for domestic use from exceeding 130°F, higher water temperatures are required for appliances such as a dishwasher, a mixing valve or some other tempering means must be installed. Households with small children may require water temperatures less than 120°F, must be complied with!
General Piping Requirements
Ensure that the water heater is equipped with bronze headers. Piping and components connected to the water heater must be suitable for use with potable water. The water heater must not be connected to any heating system piping or components previously used with a non-potable water heating appliance. Toxic chemicals, such as those used for boiler treatment, are not to be introduced into any potable water used for space heating. If a hot water storage tank is used in the system it must be equipped with a temperature and pressure relief valve that complies with ANSI Z21.22 or CAN-4.4 and CAN-4.6.
NOTE: The storage tank must be located as close to the water heater as possible to prevent excessive head loss which will reduce flow.
Water Chemistry
The required temperature rise across the water heater is based on water having a hardness between 8 and 18 grains per gallon with a level of dissolved solids not exceeding 350 ppm. Water having a hardness less than 8 grains can cause excessive corrosion of the heat exchanger. Water that has a hardness greater than 18 grains per gallon and/or a level of dissolved solids exceeding 350 ppm will require a recalculation of the pump size and temperature rise.
54
°C or a scald injury will occur! When
49
°C. Local codes
CAUTION: through a water heater with copper heat exchanger on an 8900 is 92 GPM, on single pass. The cupro-nickel heat exchanger allows for 100 GPM, single pass.
The maximum allowable flow rate through a water heater with copper heat exchanger on an 8800 is 185 GPM,
11.7 L/s
The cupro-nickel heat exchanger allows for 200 GPM,
12.6 L/s
Tables 6A and 6B.
RBI water heaters are designed to run scale free. Due to the extreme variables of water conditions world wide it is necessary to consider pH values and water hardness in relationship to scaling. It is crucial to consider these two variables when making heat exchanger and pump selections. If local water conditions are extreme, follow the guidelines in the Heat Exchanger Selection Table (Table 7A) and the Pumping Performance Table (Table 7B). Scale free operation can be achieved by using water with a hardness between 8 and 18 and by maintaining the pH between 5 and 9. Follow the conditions listed under NORMAL in the table. In some areas of the country additional precautions must be observed due to unusual characteristics of the local water supply. Call the nearest RBI representative for details.
To properly size the pump a grain hardness and pH test must be taken at the installation site before the order is placed. Proper pump sizing will improve heater performance and help ensure heater longevity.
Expansion Tank
An expansion tank or other means to control thermal expansion must be installed in the water heating system if back flow prevention devices are installed.
The maximum allowable flow rate
5.8 L/s
and is 185 GPM,
6.3 L/s
and 370 GPM,
and 400 GPM,
and 200 GPM,
23.3 L/s
25.2 L/s
on single pass. See
on single pass.
11.7 L/s
12.6 L/s
on
A cupro-nickel heat exchanger may also be required. The manufacturer should be consulted when these water conditions are encountered. See Table 7A.
Page 16
SERIES 8800 & 8900 INSTALLATION AND OPERATING INSTRUCTIONSPage 16
Pump Requirements
This low-mass water heater requires a continuous mini­mum water flow for proper operation. The factory recommended circulating pump has been sized to overcome the head loss of the water heater plus a 30 foot piping loop under normal water conditions. Table 7B provides the heat exchanger pressure drop chart and temperature rise table. The temperature rise across
the water heater must never exceed 35°F,
19.4°C
.
Cold Water Supply
The cold water supply must be piped to the water heater’s outlet piping between the water heater and the hot water storage tank. This will prevent untempered water from entering the water heater, see the temperature rise control section below. A typical water heating system is shown in Figure 10 and 11.
Temperature Rise Control
Water returned to the water heater inlet must not be less than 110°F, 43°C or excessive condensation of the products of combustion will damage the water heater voiding the warranty. The method outlined below can be employed to prevent this condition from occurring. A balancing valve should be installed on the outlet side of the water heater for purposes of adjusting the flow rate through the heat exchanger. Thermometers are
installed on both the inlet and outlet of the water heater for determining the temperature rise through the unit.
The proper velocity through the water heater must be maintained in accordance with Table 7B for efficient operation and long life. If the temperature rise through the water heater is lower than recommended the water velocity is too high. Premature erosion of the heat exchanger will occur. Conversely, if the temperature rise is higher than recommended in Table 7B the flow rate is too low. Scaling and softening of the heat exchanger will occur.
Thermostatic Mixing Valve - Water Above 140°F, 60°C
Water can be stored at temperatures above 140°F, 60° provided that a thermo-statically controlled mixing valve is used to temper the hot water to an acceptable temperature before it’s supplied for domestic use.
The mixing valve MUST be set to prevent a scald injury from occurring, see the caution against scalding.
Storage of water for domestic use above 140°F, 60° will provide an increased quantity of tempered water and help prevent growth of water born bacteria.
C
C
Table 7A - 8800 and 8900 Heat Exchanger Selection Graph
Page 17
SERIES 8800 & 8900 INSTALLATION AND OPERATING INSTRUCTIONS Page 17
Table 7B - 8900 Pumping Performance Requirement Table
Page 18
SERIES 8800 & 8900 INSTALLATION AND OPERATING INSTRUCTIONSPage 18
Table 7B - 8800 Pumping Performance Requirement Table
Page 19
SERIES 8800 & 8900 INSTALLATION AND OPERATING INSTRUCTIONS Page 19
Figure 10 - Typical Water Heating Piping (HW Models Only)
(See Notes)
Pump
3
8
2
1
4
7
D-1 Rev 5
RBI stock storage tanks do not
incorporate this tapping: See Note 1.
Attention:
Figure 11 - Multiple Water Heating Piping (HW Models Only)
(See Notes)
4
3
6
8
Valve
Globe Valve
Angle Valve
Bufferfly Valve
Balance Valve
Ball Valve
Motorized Valve
Solenoid
Operated Valve
Self-Operated
Valve
Pressure
Reducing Valve
Check Valve
4
Pressure
Relief Valve
1
7
2
NOTES:
1. Optional cold water make up and recirculation line location.
2. When using intermittent pump and pump delay, locate remote aquastat well in lower 1/3 of tank. Install aquastat with heat sensing compound.
3. Thermal expansion tank may be required, check local codes.
4. When using optional factory mounted pump, max pipe length 30’ total, 6-90° elbows, full pipe size.
5. CAUTION: MEASURE WATER HARDNESS AND pH AT JOB SITE.
The pH and water hardness must be measured before selecting heat exchanger and pump. Consult the Heat Exchanger Graph and Pumping Performance Table before making selection.
6. Common piping must be sized for maximum combined heater flow.
7. Hot water tanks should be equipped with a combination temperature & pressure relief valve.
8. MA Code requires an 1/8” hole in check valve to compensate for thermal expansion.
Notice: These drawings show suggested piping configuration and valving.
Check with local codes and ordinances for specific requirements.
Flow Switch
Thermometer
7
2
6
D-4 Rev 5
Aquastat Union
Pressure Switch
Gas Pressure
Regulator
Attention:
RBI stock storage tanks do not
incorporate this tapping: See Note 1.
Automatic
Air Vent
Temperature &
Pressure
Relief Valve
Vacuum
Relief Valve
Drain Valve
(Typ.)
Page 20
SERIES 8800 & 8900 INSTALLATION AND OPERATING INSTRUCTIONSPage 20
GAS SUPPLY PIPING
WARNING: Check the boiler/water heater rating plate to make sure that the boiler/water heater is for the type of gas that will be used. If it isn’t, do not connect the boiler/water heater to the gas supply. Gas supply piping must be in accordance with the National Fuel Code, ANSI Z223.1-latest revision or applicable provisions of the local building codes. Canadian installations must comply with CAN/CGA B149.1 or .2 Installation Code. Failure to comply with this warning can result in extensive property damage, severe personal injury or death!
The Series 8800 and 8900 come from the factory ready to be piped to the gas supply. If for any reason the boiler/water heater is not for the type of gas available at the installation site, call the nearest RBI representative to resolve the problem.
NOTE: A minimum gas supply presssure of 6 in,
152 mm
and maximum 14 in, propane, must be available at the safety shutoff valve inlet with the unit(s) operating.
W.C. natural or 11 in,
356 mm
279 mm
W.C. propane
W.C. natural or
A ground joint union should be installed between the boiler gas controls and the supply piping. Each of these items are needed to ensure long life and ease of servicing. Always use a pipe sealant that is suitable for use with LP gas.
Table 9 - Equivalent Pipe Length Chart
Nominal Iron Pipe Size, (in)
1" 1 1/4" 1 1/2"
2" 2 1/2"
3"
4"
Notes: 1. For flow through branch.
2. For flow at full open.
Type of pipe fitting
90°
Elbow
Te e
Equivalent of pipe length (ft)
5.2
2.6
6.9
3.5
8.0
4.0
10.3
5.2
12.3
6.2
15.3
7.7
15.3
7.7
Gate
1
Valve
0.6
0.8
0.9
1.2
1.4
1.8
1.8
Gas
Cock
1.5
1.9
2.3
3.0
3.7
4.5
4.5
2
2
CAUTION: Always use a square jawed wrench on the gas valve body when making gas connections to it. Never over-tighten the piping entering the gas valve body or gas valve failure may result!
Figure 12 - Gas Supply Piping
Table 8 should be used to ensure that the gas supply piping is sized properly. If more than one appliance is supplied by the same supply pipe, the piping must be sized based on the maximum possible demand. Do not neglect the pressure drop due to pipe fittings. Table 8 should be used in conjunction with Table 9 to ensure that the gas supply piping has the capacity to meet the demand.
Figure 12 depicts the proper way to connect the boiler/ water heater to the gas supply piping. The manual shut­off valve MUST be installed in the supply piping. It should be installed 5 ft,
1.5 m
above the floor where required by local codes. Provide a sediment trap at the bottom of the vertical section of the gas supply pipe upstream of the gas controls.
Table 8 - Gas Pipe Capacity
Maximum pipe capacity in ft3/hr based on 0.60 specific gravity gas at a pressure of 0.5 psig or less and a 0.3" W.C. pressure drop.
Nominal Iron Pipe Size, (in)
1" 1 1/4" 1 1/2"
2" 2 1/2"
3"
4"
Note: Multiply the gas volume by 0.62 for propane flow capacity in ft3/hr.
Multiply the propane flow capacity by 2500 Btu/ft3 to determine the propane Btu/hr capacity for a given pipe size and length.
10
520 1050 1600 3050 4800 8500 17,500
20
350 730 1100 2100 3300 5900 12,000
Pipe length in feet
30
40
50
Maximum gas volume of pipe, (ft3/hr)
285
245
500 760 1450 2300 4100 8300
215
440 670 1270 2000 3600 7400
590 890 1650 2700 4700 9700
60
195
400 610 1150 1850 3250 6800
80
170
350 530 990 1600 2800 5800
100
150 305 460 870 1400 2500 5100
150
120 250 380 710 1130 2000 4100
RIOM-47
When applicable, provisions for vent, bleed and gas relief lines must be made in accordance with the latest revision of ANSI Z223.1/NFPA 54.
Safe lighting and other performance criteria were met with the gas manifold and control assembly provided on the boiler. All gas connections MUST be leak tested before putting the boiler into operation.
WARNING: Never use an open flame to test for gas leaks. Always use an approved leak detection method. Failure to comply with this warning can cause extensive property damage, severe personal injury or death!
Page 21
SERIES 8800 & 8900 INSTALLATION AND OPERATING INSTRUCTIONS Page 21
Whenever the gas supply piping is pressure tested the boiler/water heater gas controls must be protected. If the test pressure is equal to, or less than 1/2 psig,
3.5 kPa
manual shut off valve, see Figure 12. If the test pressure is greater than, or equal to 1/2 psig, the boiler/water heater and its individual shut-off valve.
isolate the boiler/water heater by closing it’s
3.5 kPa
, disconnect
ELECTRICAL WIRING
Electrical Power Connections
CAUTION: Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation! Verify proper operation after servicing!
ATTENTION. Au moment de l’entretien des commandes, étiquetez tous les fils avant de les débrancher. Des erreurs de câblage peuvent entraîner un fonctionnement inadéquat et dangereux. S’assurer que l’appareil fonctionne adéquatement une fois l’entretirn terminé.
The electrical connections to this boiler/water heater must be made in accordance with all applicable local codes and the latest revision of the National Electrical Code, ANSI /NFPA-70. Installation should also conform with CSA C22.1 Canadian Electrical Code Part I if installed in Canada.
GENERAL OPERATION
WARNING: Before proceeding read and fully understand the instructions contained in this manual. Do not attempt to operate this boiler/ water heater if it has not been installed in accordance with the guidelines set forth in this manual. Failure to comply with this warning can result in extensive property damage, severe personal injury or death!
Should overheating occur or the gas supply fail to shut off, turn off the manual gas control valve to the appliance. Do not interrupt water flow through the boiler/ water heater.
En cas de surchauffe ou si l’alimentation en gaz ne s’arrête pas, fermez manuellement le robinet d’arrêt de l’admission de gaz.
Hydronic Heating Boilers
Open the make-up water valve and slowly fill the boiler and all of the radiation with water. Ensure that all bleed and drain valves are closed.
Adjust the make-up water pressure regulator so a minimum 12 psig, maintained at the highest point in the system piping. If a make-up water pump is used adjust it to maintain a minimum 12 psig,
82.7kPa
82.7 kPa
system pressure is
system pressure.
Install a separate 120 volt 15 amp circuit for the boiler/ water heater. A shut-off switch should be located at the boiler/water heater. The boiler/water heater must be grounded in accordance with the authority having jurisdiction, or if none, the latest revision of the National Electrical Code, ANSI/NFPA-70.
Line voltage field wiring of any controls or other devices must conform to the temperature limitation of type T wire at 95°F, 35°C above room temperature. Use copper conductors with a minimum size of #14 awg.
Refer to the wiring diagram supplied with the boiler/ water heater for proper wiring connections.
Open the system bleed and drain valves, one at a time, to purge the air trapped in the heating system piping.
With the boiler off, run the system pump for at least 30 minutes and bleed the system piping using the bleed valves. If strainers are used in the system piping, the make-up water valve should be closed and the strainers checked and cleaned.
The system expansion tank should be checked to ensure that the correct water level in the tank is maintained. The tank should be less than half full of water with the system full and adjusted to the correct operating pressure.
Start the boiler as described in the “OPERATING INSTRUCTIONS” section. Run the boiler for at least an hour. The system pump(s) and all radiation units must be operated during this time. Ensure that the make-up water valve is open.
Page 22
SERIES 8800 & 8900 INSTALLATION AND OPERATING INSTRUCTIONSPage 22
Shut the boiler off and open the bleed valves to purge the air trapped in the heating system piping. Close the make-up water valve and check and clean the strainers and make-up water pressure reducing valve.
Open the make-up water valve and adjust the system pressure if necessary. The system should be checked and bled after three days of operation.
OPERATING INSTRUCTIONS
FOR YOUR SAFETY READ BEFORE OPERATING
POUR VOTRE SÉCURITÉ LISEZ AVANT DE METTRE EN MARCHE
A. This appliance is equipped with an ignition device
which automatically lights the pilot. Do the pilot by hand.
Cet appareil est muni d’un dispositif d’allumage qui allume automatiquement la veilleuse. Ne tentez pas d’allumer la veilleuse manuellement.
B. BEFORE OPERATING smell all around the
appliance area for gas. Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor.
DANGER: Propane gas may not always be detected by smell. Propane gas is heavier than air and can collect in low areas.
Propane gas can ignite or explode if an ignition source is present and result in death, serious injury and property damage!
FOR YOUR SAFETY
•Have only qualified licensed professionals install, service and maintain this appliance and your gas system in accordance with all applicable codes.
•Install a nationally listed combustible gas detector(s) in your home.
•If you suspect a leak:
1. Have everyone leave the building immediately.
2. Do not attempt to light any appliance.
3. Do not touch any electrical or electronic switches in the building.
4. Do not use any phone in the building.
5. Call your gas supplier from a phone outside of the building.
6. If you cannot reach your gas supplier call the fire department.
AVANT DE FAIRE FONCTIONNER, reniflez tout autour de l’appareil pour déceler une odeur de gaz. Reniflez près du plancher, car certains gaz sont plus lourds que l’air et peuvent s’accumuler au niveau du sol.
not
try to light
QUE FAIRE SI VOUS SENTEZ UNE ODEUR DE GAZ:
• Ne pas tenter d’allumer d’appareil.
• Ne touchez à aucun interrupteur; ne pas vous servir des téléphones se trouvant dans le bâtiment.
• Appelez immédiatement votre fournisseur de gaz depuis un voisin. Suives les instructions du fournisseur.
• Si vous ne pouvez rejoindre le fournisseur, appelez le service de incendies.
C. Do not use this appliance if any part has been under
water. Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control that has been under water.
N’utilisez pas cet appareil s’il a été plongé dans l’eau, même partiellement. Faites inspecter l’appareil par un tecnicien qualifié et remplacez toute partie du système de contrôle et toute commande qui ont été plongés dans l’eau.
CAUTION: To prevent being burned, stand clear of the boiler during ignition and do not touch any hot metal parts!
OPERATING INSTRUCTIONS
1.
STOP!
Read the safety information above. If, at any time, the appliance will not operate properly, follow the instructions “TO TURN OFF GAS TO APPLIANCE.”
2. Set the operating control or thermostat to off or its lowest setting.
3. Turn off all electric power to the appliance.
4. This appliance is equipped with an ignition device which automatically lights the pilot. Do the pilot by hand.
5. Close the manual main and pilot gas shut-off valves.
6. Wait five (5) minutes to clear out any gas. Then smell for gas, including near the floor. If you smell gas,
STOP!
above. If you don’t smell gas go to next step.
7. Connect a manometer having a minimum capacity of 20 in, gas valve. Make sure that the gas supply piping has been purged of air and that all gas joints up to the gas valve have been thoroughly checked for leaks.
8. Open the manual pilot valve.
9. Turn on all electric power to the boiler.
10. Set the operating control or thermostat to the desired setting.
11. The pilot(s) should automatically light. Do not try to light the pilot(s) by hand!
12. With the pilot(s) lit, open the main gas shut-off valve.
13. The burners should light with proper boiler operation.
14. The pilot and manifold pressures should match those listed in Table 10. To adjust the manifold gas pressure see the instructions in the section.
Follow “B” in the safety information
508 mm
W.C. to the outlet pressure port of the
Gas Pressure Adjustment
“CHECKING AND ADJUSTMENTS”
not
try to light
Page 23
SERIES 8800 & 8900 INSTALLATION AND OPERATING INSTRUCTIONS Page 23
Required Gas Pressure
Provide gas supply pressure at inlet to boiler gas train as follows:
LP Nat Minimum (in W.C.) 11 6 Maximum (in W.C.) 14 14
Measure pressure when the boiler is firing at full rate. Low gas pressure could indicate undersized gas line or insufficient gas supply.
"Static and operating gas pressure required at the gas valve inlet is between 6" W.C. and 14" W.C. for natural gas and 11" W.C. and 14" W.C. for propane. If the gas pressure is above this limit, a lock-up style regulator suitable for dead end service such as an Equimeter or Fisher must be installed to prevent increase (creep) of gas pressure when the units are not operating. This pressure regulator (supplied by others) may be installed at the service entrance to each unit or a "master" regulator sized to handle multiple units may be utilized. Consult local gas utility or regulator manufacturer for recommendations to meet specific job site requirements."
Table 10 - Pilot & Manifold Settings
inches W.C.
Natural 3.5 (± .2) Propane 10 (± .2)
mm W.C.
89 (± 5)
254 (± 5)
Instructions De Mise En Marche
1. ARRÊTEZ! Lisez les instructions de sécurité sur la portion supérieure de cette étiquette.
2. Réglez le thermostat à la température la plus basse.
3. Coupez l’alimentation électrique de l’appareil.
4. Cet appareil est muni d’un dispositif d’allumage qui allume automatiquement la veilleuse. Ne tentez pas d’allumer la veilleuse manuellement.
5.
Fermer la vanne manuelle d’arrêt d’alimintation de gaz.
6. Attendre cinq (5) minutes pour laisser échapper tout le gaz. Reniflez tout autour de l’appareil, y compris près du plancher, pour déceler une odeur de gaz. Si vous sentez une odeur de gaz, ARRÊTEZ! Passez à l’étape B des instructions de sécurité sur la portion supérieure de cette étiquette. S’il n’y a pas d’odeur de gaz, passez à l’étape suivante.
7.
Ouver la vanne manuelle d’arrêt d’alimintation de gaz.
8. Mettez l’appareil sous tension.
9. Réglez le thermostat à la température désirée.
10. Si l’appareil ne se met pas en marche, suivez les instructions intitulées «Comment couper l’admission de gaz de l’appareil» et appelez un technicien qualifié ou le fournisseur de gaz.
To Turn Off Gas To Appliance
1. Set the operating control or thermostat to its lowest setting.
2. Turn off all electric power to the appliance if service is to be performed.
3. Close the manual main and pilot gas shut-off valves.
COUPER L’ADMISSION DE GAZ DE L’APAREIL
1. Réglez le thermostat à la température la plus basse.
2. Coupez l’alimentation électrique de l’appareil s’il faut procéder à l’entretien.
3.
Fermer la vanne manuelle d’arrêt d’alimintation de gaz.
CHECKING & ADJUSTMENTS
1. With the burners in operation, close the manual shutoff valve in the gas supply line. As soon as the main burner flames go out, open the manual shutoff valve. A normal ignition sequence should take place. If the burners fail to light, the system will make one more ignition attempt. If the burners have not lit after the last ignition try, the gas valve will close and the system will go into lock out on CSD-1 units or continuous retry. DO NOT attempt to reset the system until the ignition system has been inspected and the problem resolved. The pilot and manifold pressures should match those listed in Table 10.
2. With the burners in operation, interrupt the power to the control circuit by lowering the operating control or thermostat. The main burners should go out. Reset the operating control or thermostat, a normal ignition sequence should follow.
3. To test the ignition safety shutoff device, close the manual shutoff valve in the gas supply line. Within 5 seconds of main burner flame extinction, the main gas valve solenoid should close with an audible noise.
4. A sparking noise should be heard while the ignition module tries to relight the pilot. After 15 seconds the module should lockout and the trial for ignition end. After 5 minutes a second trial for ignition should occur. Open the manual shutoff valve in the gas supply line and reset the ignition control system. A normal ignition sequence should take place.
Page 24
SERIES 8800 & 8900 INSTALLATION AND OPERATING INSTRUCTIONSPage 24
Pilot Adjustment
The pilot burner flame should envelope 3/8" to 1/2" of the flame sensing probe, Figure 13. To adjust the pilot the following steps must be taken:
1. Remove the pilot gas pressure regulator cap.
2. Turn the pressure regulator adjustment screw clock­wise to increase the flame and counterclockwise to decrease it.
3. Replace the pressure regulator adjustment screw cap.
Figure 13 - Pilot Flame Adjustment
SCREWS
BRASS FERULE
1/4" TUBING
Gas Pressure Adjustment
CAUTION: The maximum inlet gas pressure listed on the rating plate must not be exceeded or damage to the boiler/water heater may occur voiding the warranty!
The minimum supply pressure listed on the rating plate is for input adjustment.
NATURAL GAS: Optimum results are obtained when the boiler/water heater is operated with the manifold pressure(s) set per Table 10. The manifold pressure should not vary outside this range. The gas valve pressure regulator has been preset at the factory. If adjustment is necessary the following steps must be followed:
1. Attach a 20 in,
508 mm
W.C. manometer to the tap
on the manifold.
2. Remove the regulator adjustment screw cap from the gas regulator. On systems that do not use a separate gas regulator, remove the adjustment screw cap from the gas valve body on the valve closest to the gas supply piping.
3. Rotate the regulator adjustment screw clockwise to increase the manifold pressure, counterclockwise to decrease it.
4. Replace the regulator adjustment screw cap and manifold pressure tap plug.
PROPANE GAS: Optimum results are obtained when the boiler/water heater is operated with the manifold pressure(s) set per Table 10. If the manifold pressure is off by more than 5% adjust it according to steps 1 through 4 above.
Input Rate, Natural Gas
Gas appliances are rated based on sea level operation with no adjustment required at elevations up to 2000 ft.,
610 m
. At elevations above 2000 ft,
610 m
input ratings
should be reduced by 4% for each additional 1000 ft,
305 m
.
Check the input rate as follows:
1. Turn off all other gas appliances that use the same gas meter as the boiler/water heater.
2. Call your gas supplier and ask for the heating value of the gas.
3. Start the boiler/water heater and let it run for 15 minutes.
4. Using the gas meter and a stopwatch, clock the time that it takes to burn 10 ft3,
0.28m3
of gas and divide
this time by 10.
5. Insert the heating value and the time, in seconds, into the formula below.
6. Input = (heating value, Btu/hr)(3600)/(time, seconds)
7. If the computed rate deviates by more than 5% from the rated input value of the unit adjust the manifold pressure accordingly. DO NOT adjust the manifold pressure by more than 5%. If a proper rate cannot be maintained without adjusting the manifold pressure beyond the 5% limit, the main burner orifices must be replaced. If the input rate is too low, go to the next larger size of main burner orifices. If the input rate is too high, go to the next smaller size.
CAUTION: Never increase the input to the boiler/ water heater above that for which it is rated. Doing so can cause premature failure of the unit!
CAUTION: Never force the regulator adjustment screw beyond the stop limits or damage to the regulator will occur!
Page 25
SERIES 8800 & 8900 INSTALLATION AND OPERATING INSTRUCTIONS Page 25
CONTROL DESCRIPTION
Boiler Thermostat
If a thermostat is to be used to control the boiler always follow the instructions included with the thermostat. Proper location of the thermostat will ensure efficient trouble-free operation of the boiler. Mount the thermostat to an inside wall at a height approximately five feet above the floor.
Avoid placing the thermostat in areas that will not provide an accurate measurement of the room temperature. Locating the thermostat behind a door, in an alcove, close to a source of thermal radiation or in a drafty area will cause poor or sporadic heating.
For a thermostat that employs an adjustable heat anticipator, adjust the anticipator to match the current measured in the thermostat circuit. An increased anticipator setting may be necessary if the unit cycles frequently. If the room temperature over-shoots the thermostat setting, reduce the anticipator setting.
Operating Control
The preferred control setting for potable hot water is 130°F, 54°C. The operating control should be set to the lowest setting that will satisfy the consumer's needs.
High Limit (Aquastat)
The high limit is located in the top control area of the boiler/water heater. A remote capillary bulb is run to a well on the outlet side of the supply header. The high limit can be reset by depressing the black rubber plug in the front top jacket panel.
The water heater high limit should be set a minimum of 20°F, 11°C higher than the operating control. Refer to the HOT WATER SUPPLY section for the proper supply water temperature.
Flow Switch
A flow switch is provided in the water outlet piping to prevent the boiler/water heater from firing without adequate water flow through the heat exchanger.
Low Water Cutoff
If the boiler is to be installed above radiation or if required by other codes or regulations, install a low water cutoff in appropriate piping. Wire the switch and any external controls in series to the "Interlock" contacts in the junction box (see the attached Connection Diagrams for details). Ensure that the low water cutoff device(s) will function properly.
WARNING: Setting the thermostat or operation control too high can result in scalding resulting in severe personal injury!
Page 26
SERIES 8800 & 8900 INSTALLATION AND OPERATING INSTRUCTIONSPage 26
MAINTENANCE
WARNING: Disconnect electrical power and close the manual gas shut off valve before performing maintenance or severe personal injury may result!
WARNING: Improper installation, adjustment, alteration, service or maintenance can cause property damage, personal injury, exposure to hazardous materials or loss of life. Installation and service must be performed by a qualified installer, service agency or the gas supplier who must read and follow the supplied instructions before installing, servicing or removing this boiler. This boiler contains crystalline silica materials that have been identified as carcinogenic or possibly carcinogenic to humans when inhaled.
AVERTISSMENT: Une instqallation, un réglage, une réparation ou un entretien non comforme aux normes peut entraîner des dommages matériels, des blessures,exposition à des matiéres dangereuses ou la mort. L’installation et l’entretien doivent être effectués par un installateur ou un service d’entretien qualifié ou le foumisseur de gaz qui doivent avoir lu les instructions foumies avant de faire l’installation, l’entretien ou l’enlèvement de la chaudière et les respecter, Cette chaudière contient des matériaux qui ont été identifiés comme étant cancérogènes ou pouvant l’être.
CAUTION: Servicing, inspection and adjustment must be done by a trained technician in accordance with all applicable local and national codes. Improper servicing or adjustment can damage the boiler /water heater!
The boiler/water heater should be cleaned and inspected once a year and before each heating season. Make sure that the burner and ignition components are free from dust, soot, dirt, corrosion or other deposits that would impair the boiler/water heater’s performance. Refer to page 30 (8900) or page 39 (8800) for component identification.
Combustion Chamber Inspection
1. Remove the left or right lower jacket end panel, item 5 or 24 (8900) or item 5 or 24 (8800).
2. Remove the upper end refractory brackets and carefully remove the end refractory panel.
3. Inspect the combustion chamber, heat exchanger and burner tray components for sign of corrosion and/or deterioration.
4. Clean or replace components as required.
CAUTION: Improper burner servicing can result in premature burner failure voiding the warranty.
Burner Drawer & Burner Removal
1. Close the manual shutoff valves in the gas supply lines and turn off electrical power to the boiler/water heater.
2. Disconnect the gas train from the gas supply piping at the ground joint union, Figure 12.
3. Remove the flame roll-out shield, 8900 only.
4. Remove the two bolts that attach the burner drawer to the base frame.
5. Disconnect the pilot tubing from the solenoid valve and the ignition lead from the ignition control.
6. Pull the burner drawer out until the burners are fully exposed.
7. Inspect each burner for damage or signs of deterioration. Use a brush or compressed air to remove any debris from the burner ports.
8. DO NOT install damaged or badly corroded burners, replace them.
9. Install the burners making sure that they are properly seated in the burner drawer.
10. Replace the burner drawer and flame roll out shield, 8900 only, following the removal steps in reverse order.
Heat Exchanger Inspection & Cleaning
1. Close the shut off valves in the inlet and outlet piping. Relieve the system pressure from the boiler by carefully lifting the relief valve or opening the drain valve.
2. Disconnect the boiler/water heater from the system piping.
3. Remove the left and right headers and mounting studs.
4. Remove the left & right upper and left & right lower jacket end panels, items 5 & 24 (8900) or items 5 & 24 (8800).
5. Remove the left & right front corner trim panels,
8900.
6. Remove the flue collector front panel.
7. Remove the upper front refractory channel assembly and front refractory panels.
8. Slide the heat exchanger out and thoroughly inspect it.
9. The outside surfaces of the copper tubes should be free of any soot deposits. A slight black smudge is normal with some types of gases. Black soot indicates poor combustion. Green deposits indicate condensation due to low return water temperatures. In either case the heat exchanger must be cleaned thoroughly with water and the problem resolved before the boiler/water heater is returned to service.
10. Replace the cleaned heat exchanger and other components in the reverse order of their removal.
Page 27
SERIES 8800 & 8900 INSTALLATION AND OPERATING INSTRUCTIONS Page 27
Heat Exchanger Replacement
1. Sagging or distorted heat exchanger tubes are an indication of low water flow through the system.
2. A damaged heat exchanger must be replaced and the condition that caused the damage resolved before the boiler/water heater is returned to service.
Vent System
Thoroughly inspect the vent system for any signs of blockage, corrosion or leakage. Immediately replace any unsound vent system piping.
Controls
Use the “GENERAL OPERATION” and “CHECKING AND ADJUSTMENTS” sections of this manual for reference.
1. Check the thermostat or operating controls for proper operation.
2. A float type low water cutoff device must be flushed out per the manufacturers’ instructions. The probe on a probe low water cut off must be removed, cleaned and inspected at least once a year. Ensure that the low water cutoff operate properly. If not, replace them.
3. The flow switch contacts must be open when water flow is not present.
4. The relief valve should not weep or discharge water at normal system pressure. If it does contact a qualified service technician to have it inspected. NEVER try to clean or repair the relief valve! If the valve fails to operate properly, have it replaced!
5. The aquastat high limit controls the maximum water temperature in the boiler and should be 20°F,
11°C
above set point temperature. If the water temperature reaches the set temperature before the demand for heat has been met, the aquastat high limit should shut the boiler off. The water temperature should never exceed the maximum set point of 240°F,
116 °C
. The aquastat high limit cannot be repaired. If it fails to function properly, replace it.
6. Visually check the pilot and main burner flames to ensure proper operation, see Figures 13 & 14.
WARNING: A yellow, floating flame indicates a lack of combustion air. A lifting flame indicates too much combustion air. Do not operate the boiler/water heater until the problem is solved or severe personal injury or death may occur!
Figure 14 - Main Burner Flames
NORMAL
(HARD FLAME)
LIFTING
(TOO MUCH AIR)
YELLOW TIPPING
(MARGINAL)
YELLOW FLAME
(TOO LITTLE AIR)
RIOM-49
Page 28
SERIES 8800 & 8900 INSTALLATION AND OPERATING INSTRUCTIONSPage 28
TROUBLE-SHOOTING FLOW CHART FOR HONEYWELL OR UTC IGNITION MODULE (24V CONTROL SYSTEM)
Proper line voltage
L1 to L2 on heater
terminal strip
24V on secondary
terminals of heater
transformer
24V across 24V and 24V
(GND) terminals of
ignition module
On application of 24V,
control produces audible
spark at pilot
Pilot
Ignites
Adjust the pilot gas
pressure using the
pilot regulator. Pilot
ignition problems
can be caused by
high or low pilot
pressure.
Pilot ignites
Check for tripped breaker or open safety
/ limit switch in supply voltage circuit.
Check for broken or loose
connection to transformer, if none
replace transformer.
Check for open limit in this 24V circuit operating control, high limit, flow switch, LWCO, high / low gas pressure switches,
remote operating controls, etc.
Check for loose or broken ignition lead. Check for shorted pilot electrode.
If pilot and ignition lead test good replace module.
During pilot ignition period (audible spark present) check
for 24V between PV and MV/PV terminals of module.
24V at pilot gas
valve leads
A tripped manual reset
high limit may
indicate insufficient
water flow.
Check for loose or
broken wire between
pilot valve and
PV-MV/PV terminals.
Replace module.
Main Flame
Ignites
Manifold pressure in proper
range (3.5”-4.2” N.G.,
10”-11” L.P.). If no pressure on
manifold, during main flame trial for ignition period, check for pressure at tappings of each
main valve. Replace valve
that shows no pressure at
downstream tapping while
powered with pressure at
upstream tapping.
With pilot lit: 24V
between the MV and
MV/PV terminals of
the module
24V at terminals of
all valves in main
gas train
Pilot valve opens.
Confirm that gas is
present at pilot valve
inlet.
Insure pilot line and
pilot orifice are clear
and that the pilot is
undamaged. The pilot
ignites.
Check for loose or
broken wire between
MV-MV/PV terminals.
Replace pilot solenoid
valve.
Replace the pilot
assembly.
Replace module.
main valves and
Page 29
SERIES 8800 & 8900 INSTALLATION AND OPERATING INSTRUCTIONS Page 29
Trouble-Shooting
PROBLEM POSSIBLE CAUSES CORRECTIVE ACTION
Boiler Pounds or Knocks Low or no water flow Ensure that pump is operating
properly - look for voltage through flow switch.
Ensure that all system valves are open.
Ensure that all air has been bled from the system.
Ensure that maximum temperature rise of 35°F, 19°C has not been exceeded.
Low or no system pressure Ensure that water makeup valve is
open and functioning.
Heat exchanger blocked Remove return header and inspect
the heat exchanger tubes.
Relief Valve Leaks System pressure too high Ensure relief valve is properly sized
for the system - never exceed 160 psi.
Expansion tank is waterlogged Ensure expansion tank is properly
sized for the system.
Expansion tank is isolated Ensure valve between expansion
tank and system is open.
Sooting of Heat Exchanger Return water temperature to low Adjust balancing valves for a
minimum return water temperature of 110°F,
Inadequate combustion air Ensure that the make up air supply
is adequate per NFPA 54/ANSI Z223.
Ensure that the vent system is sized properly, is not blocked or restricted and that there is adequate draft
present in the breeching. Rated input has been exceeded Ensure that the input rate is correct. Incorrect fuel type Ensure that the fuel type supplied
matches the rating plate.
43 °C.
Page 30
SERIES 8800 & 8900 INSTALLATION AND OPERATING INSTRUCTIONSPage 30
PARTS LIST (MODELS 420-1900)
36
33
Page 31
SERIES 8800 & 8900 INSTALLATION AND OPERATING INSTRUCTIONS Page 31
SERVICE AND REPLACEMENT PARTS LIST (MODELS 420-1900)
8900 8900 Model Size with Item Quantities Below
Ref # Name of Part
1 Jacket Lower Front Panel 03-0077 1
2 Jacket Lower Rear Panel 03-0061 1
3, 4, LH Upper Rear Corner Post 03-0107 111111111111111
25, 26 RH Upper Rear Corner Post 03-0108 111111111111111
LH Upper Front Corner Post 03-0109 111111111111111 RH Upper Front Corner Post 03-0110 111111111111111 LH Lower Rear Corner Post 03-0111 111111111111111 RH Lower Rear Corner Post 03-0112 111111111111111 LH Lower Front Corner Post 03-0113 111111111111111 RH Lower Front Corner Post 03-0114 111111111111111
5, 24 Jacket End Panels (Upper/Lower) 72-0016 111111111111111
6 Inlet/Outlet Header, Cast Iron
Inlet/Outlet Header, Bronze Inlet/Outlet Header, Cast Iron (Mod) Inlet/Outlet Header, Bronze (Mod)
7 Return Header, Cast Iron
Return Header, Bronze
8 O Ring, Inlet/Outlet & Return Headers 06-0001 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 NS Stud, Inlet/Outlet & Return Headers 57-0225 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 NS Nut, Inlet/Outlet & Return Headers 57-0491 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12
Part # 420 530 630 735 840 950 1050 1160 1260 1370 1470 1580 1685 1790 1900
03-0078 1 03-0079 1 03-0080 1 03-0081 1 03-0082 1 03-0083 1 03-0084 1 03-0085 1 03-0086 1 03-0087 1 03-0088 1 03-0089 1 03-0090 1 03-0091 1
03-0062 1 03-0063 1 03-0064 1 03-0065 1 03-0066 1 03-0067 1 03-0068 1 03-0069 1 03-0070 1 03-0071 1 03-0072 1 03-0073 1 03-0074 1 03-0075 1
01-0001S
01-0003S 01-0001M 01-0003M
01-0002S
01-0004S
111111111111111 111111111111111 111111111111111 111111111111111 111111111111111 111111111111111
Page 32
SERIES 8800 & 8900 INSTALLATION AND OPERATING INSTRUCTIONSPage 32
8900 8900 Model Size with Item Quantities Below
Ref # Name of Part
12 Base Frame Assembly 70-0192 1
NS Heat Shield 70-0482 1
13, 13a Burner Tube 10-0277 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35
Burner Tube w/Bracket 70-0635 1 11111111111111
NS Burner Spacers 70-0363 1
14 Union, 1" 53-0054 1 11111
Union, 1 1/4" 53-0055 1111111 Union, 1 1/2" 53-0056 1 1
15 Firing Valve, 3/4" 11-0461 1* 1* 1* 1*
Firing Valve, 1" 11-0456 1 1 1 1 2* 2* 2* 2* 2* 2* 2* 2* 2* 2* 2* Firing Valve, 1 1/4" 11-0457 1111111 Firing Valve, 1 1/2" 11-0458 1 1
NS Main Gas Valve, V88A, 1" 11-0156 1 11111
Main Gas Valve, V88A, 1 1/4" 11-0157 1111111 Main Gas Valve, V88A, 1 1/2" 11-0158 1 1
16 Main Gas Valve, V8944B, 1" 11-0171 1 1 1 1 2* 2* 2* 2* 2* 2* 2* 2* 2* 2* 2*
Main Gas Valve, V8944B, 1 1/4" 11-0172 1111111 Main Gas Valve, V8944B, 1 1/2" 11-0173 1 1
*4 Stage Only
Part # 420 530 630 735 840 950 1050 1160 1260 1370 1470 1580 1685 1790 1900
70-0193 1 70-0194 1 70-0195 1 70-0196 1 70-0197 1 70-0198 1 70-0199 1 70-0200 1 70-0201 1 70-0202 1 70-0203 1 70-0204 1 70-0205 1 70-0206 1
70-0483 1 70-0484 1 70-0485 1 70-0486 1 70-0487 1 70-0488 1 70-0489 1 70-0490 1 70-0491 1 70-0492 1 70-0493 1 70-0494 1 70-0495 1 70-0496 1
70-0364 1 70-0365 1 70-0366 1 70-0367 1 70-0368 1 70-0369 1 70-0370 1 70-0371 1 70-0372 1 70-0373 1 70-0374 1 70-0375 1 70-0376 1 70-0377 1
Page 33
SERIES 8800 & 8900 INSTALLATION AND OPERATING INSTRUCTIONS Page 33
8900 8900 Model Size with Item Quantities Below
Ref # Name of Part
NS Valve Body, V5055B, 1" (Mod) 11-0251 1 11111
Valve Body, V5055B, 1 1/4" (Mod) 11-0252 1111111 Valve Body, V5055B, 1 1/2" (Mod) 11-0253 1 1 Valve Actuator, V9055A, (Mod) 11-0303 1 11111111111111
NS Main Gas Valve, V48A, 1", 120V 11-0151 1 11111
Main Gas Valve, V48A, 1 1/4", 120V 11-0152 1111111 Main Gas Valve, V48A, 1 1/2", 120V 11-0153 1 1 Main Gas Valve, V4944B, 1", 120V 11-0166 1 11111 Main Gas Valve, V4944B, 1 1/4", 120V 11-0167 1111111 Main Gas Valve, V4944B, 1 1/2", 120V 11-0168 1 1
17 "A" Valve, 1" 11-0465 1 11111
"A" Valve, 1 1/4" 11-0466 1111111
"A" Valve, 1 1/2" 11-0467 1 1 NS Bracket Refractory Upper End 03-0306 2 22222222222222 NS Bracket Refractory Lower End 03-0307 2 22222222222222
18 End Refractory Panel, Left & Right 05-0001 2 22222222222222 19 Center Refractory Panel 05-0002 2
20 Corner Refractory Panel 05-0005 4
18, 19, 20
Tile Kit
NS Bracket Refractory Front/Rear 03-0308 2 23334455566677
Part # 420 530 630 735 840 950 1050 1160 1260 1370 1470 1580 1685 1790 1900
05-0003 2 05-0004 2222444666
05-0006 4 05-0007 4 05-0008 4 05-0009 4 05-0010 4 05-0011 4 05-0012 4 05-0013 4 05-0014 4 05-0015 4 05-0016 4
05-0017 4 70-0226K 70-0227K 70-0228K 70-0229K 70-0230K 70-0231K 70-0232K 70-0233K 70-0234K 70-0235K 70-0236K 70-0237K 70-0238K 70-0239K 70-0240K
Page 34
SERIES 8800 & 8900 INSTALLATION AND OPERATING INSTRUCTIONSPage 34
8900 8900 Model Size with Item Quantities Below
Ref # Name of Part
NS Upper Front Refractory Channel 70-0177 1
NS Upper Rear Refractory Channel 70-0162 1
21 Draft Diverter Top Panel Assembly 70-0030 1
21a
Draft Diverter Top Panel Assembly (Dual Flue)
Part # 420 530 630 735 840 950 1050 1160 1260 1370 1470 1580 1685 1790 1900
70-0178 1
70-0179 1
70-0180 1
70-0181 1
70-0182 1
70-0183 1
70-0184 1
70-0185 1
70-0186 1
70-0187 1
70-0188 1
70-0189 1
70-0190 1
70-0191 1
70-0163 1
70-0164 1
70-0165 1
70-0166 1
70-0167 1
70-0168 1
70-0169 1
70-0170 1
70-0171 1
70-0172 1
70-0173 1
70-0174 1
70-0175 1
70-0176 1
70-0031 1
70-0032 1
70-0033 1
70-0034 1
70-0035 1
70-0036 1
70-0037 1
70-0038 1
70-0039 1
70-0040 1
70-0041 1
70-0042 1
70-0043 1
70-0044 1
70-0045 1
70-0046 1
70-0047 1
70-0048 1
70-0049 1
70-0050 1
70-0051 1
70-0052 1
70-0053 1
70-0054 1
70-0055 1
Page 35
SERIES 8800 & 8900 INSTALLATION AND OPERATING INSTRUCTIONS Page 35
8900 8900 Model Size with Item Quantities Below
Ref # Name of Part
22 Jacket Upper Front Panel 03-0043 1
27 Jacket Top Panel 03-0001 1
27a Jacket Top Panel (Dual Flue) 03-0016 1
28 Jacket Upper Rear Panel 03-0027 1
29 Burner Drawer Side Rail Assy, Left & Right 70-0362 2 22222222222222
Part # 420 530 630 735 840 950 1050 1160 1260 1370 1470 1580 1685 1790 1900
03-0044 1
03-0045 1
03-0046 1
03-0047 1
03-0048 1
03-0049 1
03-0050 1
03-0051 1
03-0052 1
03-0053 1
03-0054 1
03-0055 1
03-0056 1
03-0057 1
03-0002 1
03-0003 1
03-0004 1
03-0005 1
03-0006 1
03-0007 1
03-0008 1
03-0009 1
03-0010 1
03-0011 1
03-0012 1
03-0013 1
03-0014 1
03-0015 1
03-0017 1
03-0018 1
03-0019 1
03-0020 1
03-0021 1
03-0022 1
03-0023 1
03-0024 1
03-0025 1
03-0026 1
03-0028 1
03-0029 1
03-0030 1
03-0031 1
03-0032 1
03-0033 1
03-0034 1
03-0035 1
03-0036 1
03-0037 1
03-0038 1
03-0039 1
03-0040 1
03-0041 1
Page 36
SERIES 8800 & 8900 INSTALLATION AND OPERATING INSTRUCTIONSPage 36
8900 8900 Model Size with Item Quantities Below
Ref # Name of Part
NS Heat Exchanger Assembly (Copper) 70-0072 1
NS Heat Exchanger Assembly (Cupronickel) 70-0087 1
NS Heat Exchanger Assembly (Copper) 70-0102 1
NS Heat Exchanger Assembly (Cupronickel) 70-0117 1
Part # 420 530 630 735 840 950 1050 1160 1260 1370 1470 1580 1685 1790 1900
70-0073 1
70-0074 1
70-0075 1
70-0076 1
70-0077 1
70-0078 1
70-0079 1
70-0080 1
70-0081 1
70-0082 1
70-0083 1
70-0084 1
70-0085 1
70-0086 1
70-0088 1
70-0089 1
70-0090 1
70-0091 1
70-0092 1
70-0093 1
70-0094 1
70-0095 1
70-0096 1
70-0097 1
70-0098 1
70-0099 1
70-0100 1
70-0101 1
70-0103 1
70-0104 1
70-0105 1
70-0106 1
70-0107 1
70-0108 1
70-0109 1
70-0110 1
70-0111 1
70-0112 1
70-0113 1
70-0114 1
70-0115 1
70-0116 1
70-0118 1
70-0119 1
70-0120 1
70-0121 1
70-0122 1
70-0123 1
70-0124 1
70-0125 1
70-0126 1
70-0127 1
70-0128 1
70-0129 1
70-0130 1
70-0131 1
Page 37
SERIES 8800 & 8900 INSTALLATION AND OPERATING INSTRUCTIONS Page 37
8900 8900 Model Size with Item Quantities Below
Ref # Name of Part
30 Tube Bundle (Copper) 70-0132 1
30 Tube Bundle (Cupronickel) 70-0147 1
31 Main Gas Pressure Regulator, RV61, 1" 11-0501 1 11111
Main Gas Pressure Regulator, RV81, 1 1/4" 11-0042 1111111 Main Gas Pressure Regulator, RV81, 1 1/2" 11-0503 1 1
32 Ignitor, PSE-NA29 70-9013 1 11111111111111
Ignitor, PSE-NA185 70-9014 1 11111111111111 Ignitor, PSE-NA29, LP 70-0631 1 11111111111111 Ignitor, PSE-NA185, LP 70-0632 1 11111111111111
33 Solenoid Valve w/Regulator, NG, 24V 11-0373 1 11111111111111
Solenoid Valve w/Regulator, LP, 24V 11-0375 1 11111111111111 Solenoid Valve w/Regulator, NG, 120V 11-0372 1 11111111111111 Solenoid Valve w/Regulator, LP, 120V 11-0374 1 11111111111111
NS Pilot Valve, H91WG, 24V (prior to 0905) 11-0017 1 11111111111111
Pilot Valve, V4046C, 120V (prior to 0905) 11-0016 1 11111111111111
NS Pilot Regulator, RV12LT (prior to 0905) 11-0041 1 11111111111111
35 Manual Pilot "B" Valve 11-0031 1 11111111111111 36 Ignition Module, S8610M 16-0054 1 11111111111111
Ignition Module, UTC 1003 (CSD-1 Only) 16-0058 1 11111111111111
Alarm Board, (CSD-1) 16-0023 1 11111111111111 NS BTC 4 Stage 14-0307 1 11111111111111 NS Ignition Module, RM7890A 16-0001 1 11111111111111 NS Keyboard Display Module, S7800A 16-0010 1 11111111111111 NS Amplifier, R7847A 16-0005 1 11111111111111 NS UV Amplifier, R7849A 16-0006 1 11111111111111 NS Spark Generator, Q652B 16-0008 1 11111111111111 NS Ignition Cable Assembly 120V 16-0201 1 11111111111111
37 Transformer, 40VA 15-0002 1 11111111111111 NS Rocker Switch 48-0001 1 11111111111111 NS Relay, 24V AC 15-0113 1 11111111111111 NS Fan Manager, ST82B 15-0101 1 11111111111111 NS Pump Contactor 1PH 15-0118 1 11111111111111
Pump Contactor 3PH 15-0111 1 11111111111111
Part # 420 530 630 735 840 950 1050 1160 1260 1370 1470 1580 1685 1790 1900
70-0133 1 70-0134 1 70-0135 1 70-0136 1 70-0137 1 70-0138 1 70-0139 1 70-0140 1 70-0141 1 70-0142 1 70-0143 1 70-0144 1 70-0145 1 70-0146 1
70-0148 1 70-0149 1 70-0150 1 70-0151 1 70-0152 1 70-0153 1 70-0154 1 70-0155 1 70-0156 1 70-0157 1 70-0158 1 70-0159 1 70-0160 1 70-0161 1
Page 38
SERIES 8800 & 8900 INSTALLATION AND OPERATING INSTRUCTIONSPage 38
8900 8900 Model Size with Item Quantities Below
Ref # Name of Part
NS Low Gas Pressure Switch (Manual Reset) 11-0410 1 11111111111111 NS High Gas Pressure Switch (Manual Reset) 11-0411 1 11111111111111 NS Terminal Block 2P 48-0151 1 11111111111111 NS Terminal Block 6P 48-0157 1 11111111111111
38 High Limit, L4008E, (HB) 14-0112 1 11111111111111
High Limit, L4008E, (HW) 14-0105 1 11111111111111 39 High Limit Well, 3/8 x 3 3/16 13-0105 1 11111111111111 40 Operator, L4008A,(HB), On/Off 14-0102 1 11111111111111
Operator, L6008A, (HW) 14-0106 1 11111111111111
Operator, L6008G, (2 stage) 14-0107 1 11111111111111
Operator, T991E, (HB) 14-0108 1 11111111111111
Operator, T991E, (HW) 14-0110 1 11111111111111
Operator, T6031A, (pool heaters) 14-0003 1 11111111111111 41 Orifice, #29, NG 10-0016 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36
Orifice, #30 (2,000' - 3,999'), NG 10-0017 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36
Orifice, #31 (4,000' - 5,999'), NG 10-0018 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36
Orifice, #32 (6,000' - 7,999'), NG 10-0019 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36
Orifice, #47, LP 10-0009 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36
Orifice, #49 (2,000' - 3,999'), LP 10-0010 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36
Orifice, #51 (4,000' - 5,999'), LP 10-0099 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36
Orifice, #52 (6,000' - 7,999'), LP 10-0100 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36
NS Pressure Relief Valve 50# 30-0360 1 1111111
Pressure Relief Valve 50# 30-0374 11111
Pressure Relief Valve 50# 30-0379 1 1
NS Pressure Relief Valve 125# 30-0364 1 11111111111111 NS Tridicator 13-0308 1 11111111111111 NS Thermometer 13-0302 1 11111111111111
42 Thermometer Well, 3/8 x 2 5/8 13-0103 1 11111111111111
NS Thermometer w/well 13-0320 1 11111111111111 NS Flow Switch 14-0203 1 11111111111111
Flow Switch (Potter) 14-0201 1 11111111111111
NS Rating Plate 82-0054 1 11111111111111 NS Paint 66-0013 1 11111111111111 NS Induced Draft Kit, HS2
Induced Draft Kit, HS3
Induced Draft Kit, HS4
Induced Draft Kit, HS5
NS Vent Termination Hood 6" 09-0112 1 1
Vent Termination Hood 8" 09-0113 111111
Vent Termination Hood 10" 09-0115 1111111
Part # 420 530 630 735 840 950 1050 1160 1260 1370 1470 1580 1685 1790 1900
12-0010EK 12-0001FK 12-0001GK 12-0002DK
11
11111
1111111
Page 39
SERIES 8800 & 8900 INSTALLATION AND OPERATING INSTRUCTIONS Page 39
PARTS LIST (MODELS 2000-4000)
21
19
18
22
25
7
36
33
42
39
3086
Page 40
SERIES 8800 & 8900 INSTALLATION AND OPERATING INSTRUCTIONSPage 40
SERVICE AND REPLACEMENT PARTS LIST (MODELS 2000-4000)
8800 8800 Model Size with Item Quantities Below
Ref # Name Of Part Part # 2000 2400 2800 3200 3600 4000
1 Jacket Lower Front Panel 03-1077 1
2 Jacket Lower Rear Panel 03-1071 1
3, 4, LH Upper Rear Corner Post 03-1084 111111
25, 26 RH Upper Rear Corner Post 03-1085 111111
LH Upper Front Corner Post 03-1086 111111
RH Upper Front Corner Post 03-1087 111111
LH Lower Rear Corner Post 03-1088 111111
RH Lower Rear Corner Post 03-1089 111111
LH Upper Rear Corner Post 03-1090 111111
RH Upper Rear Corner Post 03-1091 111111
5, 24 Jacket End Panels (Upper/Lower) 72-0051 111111
6 Inlet/Outlet Header, Bronze
NS Inlet/Outlet Header, Bronze (Mod)
7 Return Header, Bronze
NS Return Header, Bronze (Mod)
8 O Ring, Inlet/Outlet & Return Headers 06-0001 32 32 32 32 32 32 NS Stud, Inlet/Outlet & Return Headers 57-0226 24 24 24 24 24 24 NS Nut, Inlet/Outlet & Return Headers 57-0492 24 24 24 24 24 24 NS Heat Exchanger "V" Baffle 03-1147 15
12 Base Frame Assembly 70-1708 1
NS Heat Shield 70-1733 2
13, 13a Burner Tube, Aluminized Steel 10-0256 19 23 27 30 34 38
Burner Tube, Aluminized w/ Bracket 70-1851 111222 Burner Tube, Stainless Steel 10-0258 19 23 27 30 34 38 Burner Tube, Stainless w/ Bracket 70-1852 111222
14 Union, 1 1/2" 53-0056 1
Union, 2" 53-0057 1 1 1 Union, 2 1/2" 53-0058 1 1
15 Firing Valve, 1 1/4" 11-0457 2* 2
Firing Valve, 1 1/2" 11-0458 1 2* 2* 2 2 Firing Valve, 2" 11-0459 1 1 Firing Valve, 2 1/2" (FM Only) 11-0460 1 1
16 Main Gas Valve, V8944B, 1 1/4" 11-0172 2* 2
Main Gas Valve, V8944B, 1 1/2" 11-0173 1 2* 2* 2 2 Main Gas Valve, V8944B, 2" 11-0174 1 1
NS Main Gas Valve, V4944B, 1 1/2", 120V 11-0168 1
Main Gas Valve, V4944B, 2", 120V 11-0169 1 1
*4 Stage Only
03-1078 1 03-1079 1 03-1080 1 03-1081 1 03-1082 1
03-1072 1 03-1073 1 03-1074 1 03-1075 1 03-1076 1
01-0012S
01-0012M
01-0013S
01-0013M
03-1148 30 03-1149 30 03-1150 30 03-1151 30 03-1152 30
70-1709 1 70-1710 1 70-1711 1 70-1712 1 70-1713 1
70-1734 2 70-1735 2 70-1736 1 1 70-1737 1 1 70-1738 1 1
111111 111111 111111 111111
Page 41
SERIES 8800 & 8900 INSTALLATION AND OPERATING INSTRUCTIONS Page 41
8800 8800 Model Size with Item Quantities Below
Ref # Name Of Part Part # 2000 2400 2800 3200 3600 4000
NS Main Gas Valve, V88A, 1 1/2" 11-0158 1
Main Gas Valve, V88A, 2" 11-0159 12222
NS Main Gas Valve, V48A, 1 1/2", 120V 11-0153 1
Main Gas Valve, V48A, 2", 120V 11-0154 1 2 1 Main Gas Valve, V48A, 2 1/2", 120V 11-0155 1 1
NS Valve Body, V5055A, 1 1/2" 11-0261 1
Valve Body, V5055A, 2" 11-0262 1 2 2 Valve Body, V5055A, 2 1/2" 11-0263 2 2
NS Valve Body, V5055B, 1 1/2", (Mod) 11-0253 1
Valve Body, V5055B, 2", (Mod) 11-0254 1 1 1 Valve Body, V5055B, 2 1/2", (Mod) 11-0255 1 1
NS Valve Actuator, V4055A 11-0308 111111
Valve Actuator, V4055D 11-0311 111111 Valve Actuator, V4062A, (2 Stage) 11-0304 111111 Valve Actuator, V9055A, (Mod) 11-0303 111111 N.O.V.V., V4295S, 3/4" 11-0361 111111
17 "A" Valve, 1 1/2" 11-0467 1
"A" Valve, 2" 11-0454 11111
"A" Valve, 2 1/2" (FM Only) 11-0455 1 1 18 End Refractory Panel, Left & Right 05-0050 222222 19 Center Refractory Panel 853413 4468810 20 Corner Refractory Panel 05-0052 4
18, 19, 20
22, 28 Jacket Upper Front & Rear Panel 03-1064 2
Tile Kit
NS Bracket Refractory Front/Rear 03-0308 334455 NS Upper Front/Rear Refractory Support 03-1155 2
NS Upper Right/Left Refractory Support 03-1161 222222
21 Draft Diverter Top Panel Assembly 70-1666 1
21a Draft Diverter Top Panel Assembly (Dual Flue) 70-1672 1
27 Jacket Top Panel 03-1051 1
05-0053 4 05-0054 4 05-0055 4 05-0056 4
05-0057 4 70-1739K 70-1740K 70-1741K 70-1742K 70-1743K 70-1744K
03-1156 2
03-1157 2
03-1158 2
03-1159 2
03-1160 2
70-1667 1
70-1668 1
70-1669 1
70-1670 1
70-1671 1
70-1673 1
70-1674 1
70-1675 1
70-1676 1
70-1677 1
03-1065 2
03-1066 2
03-1067 2
03-1068 2
03-1069 2
03-1052 1
03-1053 1
03-1054 1
03-1055 1
03-1056 1
Page 42
SERIES 8800 & 8900 INSTALLATION AND OPERATING INSTRUCTIONSPage 42
8800 8800 Model Size with Item Quantities Below
Ref # Name Of Part Part # 2000 2400 2800 3200 3600 4000
27a Jacket Top Panel (Dual Flue) 03-1057 1
03-1058 1
03-1059 1
03-1060 1
03-1061 1
03-1062 1
NS Jacket Top Channel, Left & Right 03-1063 222222
29 Burner Drawer Side Rail Assy, Left 70-1793 111111
Burner Drawer Side Rail Assy, Right 70-1794 111111
NS Tube Bundle (Copper) 70-1696 1
70-1697 1
70-1698 1
70-1699 1
70-1700 1
70-1701 1
Tube Bundle (Cupronickel) 70-1702 1
70-1703 1
70-1704 1
70-1705 1
70-1706 1
70-1707 1
30 Heat Exchanger (Copper) 70-1684 1
70-1685 1
70-1686 1
70-1687 1
70-1688 1
70-1689 1
Heat Exchanger (Cupronickel) 70-1690 1
70-1691 1
70-1692 1
70-1693 1
70-1694 1
70-1695 1
NS 3" Gruvlok Coupling 53-0100 222222
3" x 4" Gruvlok Nipple 53-0300 222222 3" x 4" Gruvlok Nipple, Brass 53-0600 222222
31 Main Gas Pressure Regulator, RV81, 1 1/2" 11-0503 1
Main Gas Pressure Regulator, RV91, 2" 11-0504 1 1 1 Main Gas Pressure Regulator, RV111, 2 1/2" 11-0505 1 1
32 Ignitor, PSE-NA29, NG, 24V 70-9013 111111
Ignitor, PSE-NA185, NG, 120V 70-9014 111111 Ignitor, PSE-NA29, LP, 24V 70-0631 111111 Ignitor, PSE-NA185, LP, 120V 70-0632 111111
33 Solenoid Valve w/Regulator, NG, 24V 11-0373 111111
Solenoid Valve w/Regulator, LP, 24V 11-0375 111111 Solenoid Valve w/Regulator, NG, 120V 11-0372 111111 Solenoid Valve w/Regulator, LP, 120V 11-0374 111111
NS Pilot Valve, 24V (prior to 0905) 11-0017 111111
Pilot Valve, 120V (prior to 0905) 11-0016 111111
NS Pilot Regulator, RV12LT (prior to 0905) 11-0041 111111
35 Manual Pilot "B" Valve 11-0031 111111 NS Spark Generator, Q652B 16-0008 111111 NS Ignition Cable Assembly 16-0201 111111
36 Ignition Module, S8610M 16-0054 111111
Ignition Module, UTC 1003 (CSD-1 Only) 16-0058 111111 NS Alarm Board (CSD-1) 16-0023 111111 NS Ignition Module, RM7890A 16-0001 111111 NS Keyboard Display Module, S7800A 16-0010 111111 NS Amplifier, R7847A 16-0005 111111 NS UV Amplifier, R7849A 16-0006 111111
37 Transformer, 40 VA 15-0002 111111 NS Rocker Switch 48-0001 111111 NS Relay, 24V AC 15-0113 111111 NS Relay, 120V AC 15-0114 111111
Page 43
SERIES 8800 & 8900 INSTALLATION AND OPERATING INSTRUCTIONS Page 43
8800 8800 Model Size with Item Quantities Below
Ref # Name Of Part Part # 2000 2400 2800 3200 3600 4000
NS Pump Contactor 1PH 15-0118 111111
Pump Contactor 3PH 15-0111 111111 NS Low Gas Pressure Switch (Manual Reset) 11-0410 111111 NS High Gas Pressure Switch (Manual Reset) 11-0411 111111 NS Terminal Block 2P 48-0151 111111 NS Terminal Block 4P 48-0152 111111 NS Terminal Block 8P 48-0154 111111
38 High Limit, L4008E, (HB) 14-0112 111111
High Limit, L4008E, (HW) 14-0105 111111
39 High Limit Well, 3/8 x 13/16 13-0105 111111 40 Operator, L4008A, (HB), On/Off 14-0102 111111
Operator, L6008A, (HW), On/Off 14-0106 111111
Operator, L6008G, 2 stage 14-0107 111111
Operator, T991E, (HB), Mod 14-0108 111111
Operator, T991E, (HW) Mod 14-0110 111111
Operator, T6031A (pool heater) 14-0003 111111
41 Orifice, #17, NG 10-0014 20 24 28 32 36 40
Orifice, #19 (2,000' - 3,999'), NG 10-0007 20 24 28 32 36 40
Orifice, #22 (4,000' - 5,999'), NG 10-0095 20 24 28 32 36 40
Orifice, #25 (6,000 - 7,999'), NG 10-0097 20 24 28 32 36 40
Orifice, #34, LP 10-0021 20 24 28 32 36 40
Orifice, #37 (2,000' - 3,999'), LP 10-0024 20 24 28 32 36 40
Orifice, #39 (4,000' - 5,999'), LP 10-0026 20 24 28 32 36 40
Orifice, #41 (6,000' - 7,999'), LP 10-0028 20 24 28 32 36 40 NS Pressure Relief Valve 50# 30-0369 1 1
Pressure Relief Valve 50# 30-0382 1 1 1
Pressure Relief Valve 50# 13-0026 1
Pressure Relief Valve 125# 30-0364 1
Pressure Relief Valve 125# 13-0009 1 1 1
Pressure Relief Valve 125# 13-0003 1
Pressure Relief Valve 125# 13-0053 1 NS Tridicator 13-0305 111111 NS Thermometer (HB) 13-0302 111111
Thermometer (HW) 13-0302 222222
42 Thermometer Well, 3/8 x 2 5/8 13-0103 111111 NS Flow Switch 14-0203 111111 NS Flow Switch (Potter) 14-0201 111111 NS Rating Plate 82-0054 111111 NS Paint 66-0013 111111
Page 44
SERIES 8800 & 8900 INSTALLATION AND OPERATING INSTRUCTIONSPage 44
MACODE-3
NOTICE!
Commonwealth of Massachusetts
Installation Requirements
(a) For all side wall horizontally vented gas fueled equipment installed in every dwelling, building
or structure used in whole or in part for residential purposes, including those owned or operated by the commonwealth and where the side wall exhaust vent termination is less than seven (7) feet above finished grade, in the area of the venting, including but not limited to decks and porches, the following requirements shall be satisfied:
1. INSTALLATION OF CARBON MONOXIDE DETECTORS. At the time of installation of the side wall horizontal vented gas fueled equipment, the installing plumber or gasfitter shall observe that a hard wired carbon monoxide detector with an alarm and battery back-up is installed on the floor level where the gas equipment is to be installed. In addition, the installing plumber or gasfitter shall observe that a battery operated or hard wired carbon monoxide detector with an alarm is installed on each additional level of the dwelling, building or structure served by the side wall horizontal vented gas fueled equipment. It shall be the responsibility of the property owner to secure the services of qualified licensed professionals for the installation of hard wired carbon monoxide detectors.
a. In the event that the side wall horizontally vented gas fueled equipment is installed in a crawl
space or an attic, the hard wired carbon monoxide detector with alarm and battery back-up may be installed on the next adjacent floor level.
b. In the event that the requirements of this subdivision can not be met at the time of completion
of installation, the owner shall have a period of thirty (30) days to comply with the above requirements; provided, however, that during said thirty (30) day period, a battery operated carbon monoxide detector with an alarm shall be installed.
2. APPROVED CARBON MONOXIDE DETECTORS. Each carbon monoxide detector as required in accordance with the above provisions shall comply with NFPA 720 and be ANSI/UL 2034 listed and IAS certified.
3. SIGNAGE. A metal or plastic identification plate shall be permanently mounted to the exterior of the building at a minimum height of eight (8) feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment. The sign shall read, in print size no less than one-half (1/2) inch in size, “GAS VENT DIRECTLY BELOW. KEEP
CLEAR OF ALL OBSTRUCTIONS”.
4. INSPECTION. The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installation unless, upon inspection, the inspector observes carbon monoxide detectors and signage installed in accordance with the provisions of 248 CMR
5.08(2)(a)1 through 4.
WARNING: Improper venting can result in excessive levels of carbon monoxide which can cause severe personal injury or death!
Page 45
SERIES 8800 & 8900 INSTALLATION AND OPERATING INSTRUCTIONS Page 45
MACODE-3
NOTICE!
Commonwealth of Massachusetts
Installation Requirements
In the Commonwealth of Massachusetts, the installation must be performed by a licensed plumber or gas fitter.
(b) Exemptions
The following equipment is exempt from 248 CMR 5.08(2)(a) 1 through 4:
1. The equipment listed in Chapter 10 entitled “Equipment Not Required To Be Vented” in the most
current edition of NFPA 54 as adopted by the Board; and
2. Product Approved side wall horizontally vented gas fueled equipment installed in a room or
structure separate from the dwelling, building or structure used in whole or in part for residential purposes.
(c) MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM PROVIDED.
When the manufacturer of Product Approved side wall horizontally vented gas equipment provides a venting system design or venting system components with the equipment, the instructions provided by the manufacturer for installation of the equipment and the venting system shall include:
1. Detailed instructions for the installation of the venting system design or the venting system
components; and
2. A complete parts list for the venting system design or venting system.
(d) MANUFACTURER REQUIREMENTS – GAS EQUIPMENT VENTING SYSTEM NOT PROVIDED.
When the manufacturer of a Product Approved side wall horizontally vented gas fueled equipment does not provide the parts for venting the flue gases, but identifies “special venting systems”, the following requirements shall be satisfied by the manufacturer:
1. The referenced “special venting system” instructions shall be included with the appliance or
equipment installation instructions; and
2. The “special venting systems” shall be Product Approved by the Board, and the instructions for that
system shall include a parts list and detailed installation instructions.
(e) A copy of all installation instructions for all Product Approved side wall horizon-tally vented
gas fueled equipment, all venting instructions, all parts lists for venting instructions, and/or all venting design instructions shall remain with the appliance or equipment at the completion of the installation.
WARNING: Improper venting can result in excessive levels of carbon monoxide which can cause severe personal injury or death!
Page 46
SERIES 8800 & 8900 INSTALLATION AND OPERATING INSTRUCTIONSPage 46
Page 47
SERIES 8800 & 8900 INSTALLATION AND OPERATING INSTRUCTIONS Page 47
Page 48
260 North Elm Street 7555 Tranmere Drive Westfield, MA 01085 Phone: (413) 568-9571 Phone: (905) 670-5888 Fax: (413) 568-9613 Fax: (905) 670-5782
Mississauga, Ontario L5S 1L4 Canada
Loading...