RBI Futera Fusion FTF-PVCVO-2 Installation Instructions Manual

Page 1
FTF-PVCVO-2
Condensing Finned Copper Gas Boilers (CB) & Water Heaters (CW)
82-0340
Optional PVC VentSystem
Installation instructions Supplement
Also read and follow:
 is manual is intended only for use by a quali ed heating installer/technician. Read and follow this manual, all supplements and related
instructional information provided with the boiler. Install, start and service the boiler only in the sequence and methods given in these instructions. Failure to do so can result in severe personal injury, death or substantial property damage.
Do not use the boiler during construction. Construction dust and particulate, particularly drywall dust, will cause contamination of
the burner, resulting in possible severe personal injury, death or substantial property damage.  e boiler can only be operated with a dust­free air supply. Follow the instruction manual procedures to duct air to the boiler air intake. If the boiler has been contaminated by operation with contaminated air, follow the instruction manual guidelines to clean, repair or replace the boiler if necessary.
A x these instr uctions near to the boiler. Instruct the building owner to retain the instructions for future use by a quali ed service technician,
and to follow all guidelines in the User’s Information Manual.
03/13 Copyright 2008 Mestek, Inc.
Page 2
tional PVC vent system installation instructions su
ppl
O
ement
 ese instructions are speci c to using schedule 40 PVC pipe as the vent system for the RBI Fusion.  e instructions contained in the Fusion Installation and Operation Manual, including all applicable Combustion Air & Ventilation and Venting instructions must be followed.
Venting of the Futera Fusion with PVC material
requires the factory supplied PVC adapter kit.  e vent system must conform to local codes and/or the latest edition of the National Fuel Gas Code ANSI Z223.1/ NFPA 54. Failure to properly vent this product can result in CO poisoning causing severe personal injury or death!
The return water temperature entering the Futera
Fusion using the PVC venting option must not exceed 155°F. Higher return water temperatures will result in a reduction of the  ring rate.
The PVC vent adapter, Figures 1 and 2, comes fitted with a flue temperature sensor and flue temperature high limit switch. This system provides redundant over-temperature protection for the PVC vent system.  e  ue temperature sensor continuously monitors the temperature of the  ue gas exiting the Fusion. If the return water temperature exceeds 155°F the HeatNet Control, via the flue temperature sensor, will recognize the resultant increase in flue temperature and reduce the  ring rate of the Fusion. Should the sensor fail, the manual reset high limit switch will trip and shut down the Fusion before the  ue temperature can exceed a safe limit.
Figure 1 PVC Vent Horizontal Adaptor
2
Page 3
tional PVC vent system installation instructions supplement
O
Figure 2 PVC Vent Vertical Adaptor
PVC VENT ADAPTOR INSTALLATION
Improper installation of the PVC vent adaptor can
cause pooling of corrosive condensate and result in premature failure of the vent adaptor voiding the manufacturer’s warranty!
Remove the right rear jacket panel to gain access to the Fusion’s economizer cabinet. With the PVC vent adaptor positioned at the rear of the unit carefully insert the manual reset high limit through the  ue pipe opening in the rear cabinet panel. Mount the high limit to the economizer bracket as shown in Figure 3.
Do not kink or damage the high limit capillary tube or the
limit may be ruined voiding the manufacturer’s warranty!
Place the small end of the vent adaptor through the vent pipe opening in the rear cabinet panel. Position the vent adaptor so the high limit switch capillary is at the top of the adaptor, Figures 1 and 2.
3
Page 4
tional PVC vent system installation instructions su
ppl
O
ement
Figure 3 PVC Vent Adaptor Installation
Carefully push the vent adaptor into the vent collar until it bo oms against the stop bead on the adaptor and tighten the ring clamp to secure the vent adaptor to the Fusion vent collar, Figures 1 and 2.
PVC VENT ADAPTOR WIRING
Failure to properly connect the  ue temperature sensor
and  ue temperature high limit switch will prevent the Fusion from operating.
Locate the wire harness inside the economizer cabinet. Connect the two wires with the 1/4 in. quick connects to the  ue temperature high limit switch. Connect the two wires with the 3/16 quick con­nects to the  ue temperature sensor.
PVC VENT SYSTEM INSTALLATION
Never insulate or encapsulate the PVC vent system or
overheating and failure of the vent system may occur.  e PVC vent system must be exposed to ambient air and readily visible for inspection. Failure to properly vent this product can result in CO poisoning causing severe personal injury or death! Exception: Per NFPA=54 Secion 12.6.8: The remaining space surrounding a chimney liner, gas vent, special gas vent or plastic piping installed within a masonry chimney shall not be used to vent another appliance.
 e PVC vent adapter has been engineered to directly accept PVC vent pipe.  e internal gasket in the vent adaptor will form a gas and water tight seal. No glues or sealants are required at this connection. Slide the required horizontal length of PVC pipe into the vent adaptor and tighten the ring clamp to secure it in place.  e vent system must be sized per Table 1.
Table 1 Vent System Size
Model Size
500-1500
1750-2000 10 254
2500-3000 8 203
3500-4000 10 254
 e maximum equivalent length for a positive pressure vent system is 60  , 18.3 m. Each 90° elbow and the vent terminal are equal to 10 linear  , 3.0 linear m of pipe.
To maximize the performance of the vent system, locate 90° elbows as far from the Fusion and one another as possible.
When horizontal vent runs exceed 5  , 1.5 m they must be supported at 3  , 0.98 m pitched intervals with overhead hangers. The vent system must be down, toward the vent terminal, 1/4 in/ , 21 mm/m.
If the vent system contains vertical sections horizontal vent runs between the Fusion and the vertical section must be pitched back, toward the economizer, 1/4 in/ , 21 mm/m, to prevent condensate from pooling in the vent.
Pipe Diameter
In mm
8 203
4
Page 5
tional PVC vent system installation instructions supplement
O
PVC VENT PIPE PREPARATION & ASSEMBLY
Only schedule 40 PVC pipe sized per Table 1 is to be used.
 e use of heavier wall pipe may prevent the Fusion from operating properly!
1. Cut pipe ends squarely and remove all burrs, ridges and foreign ma er using the appropriate tools and materials.
Failure to remove burrs or ridges will result in the
cement in the fitting socket being scraped from the socket surface producing a dry joint which will have a high probability of failure.
2. Before applying any cement dry  t pipe and   ings together to ensure that the parts  t properly.
3. Disassemble dry   ed parts and clean the pipe and   ing surfaces to be joined with a PVC cleaner. Surfaces to be joined must be free of dirt, moisture, oil and other foreign ma er.
All primers, cleaners and cements must meet all local
codes. Before using primers, cleaners and cements, stir or shake well, making sure the contents are liquid. Do not use if found to be lumpy or in a jelly-like state. Do not add solvents or thinners to reclaim thickened or lumpy material. Primers and cement should be NSF and/or UPC listed. Failure to use proper materials when venting this product can result in CO poisoning causing severe personal injury or death
All primers, cleaners and cements must meet all local codes. Before using primers, cleaners and cements, stir or shake well, making sure the contents are liquid. Do not use if found to be lumpy or in a jelly-like state. Do not add solvents or thinners to reclaim thickened or lumpy material. Primers and cement should be NSF and/or UPC listed. Failure to use proper materials when venting this product can result in CO poisoning causing severe personal injury or death
Primers, cleaners and cements are extremely  ammable and harmful or fatal if swallowed. Always store primers, cleaners and cements in a cool, dry, well ventilated place. Do not store them near heat, sparks or  ames. Keep containers closed when not in use. Wear impervious clothing while handling. Do not smoke, eat or drink while handling primers, cleaners and cements. Wash thoroughly after handling and before eating. Wear eye protection when handling. The harmful vapors can be absorbed through the skin and may irritate eyes and skin. If inhaled, get fresh air and seek medical a ention if ill feelings persist. In case of eye and/or skin contact, immediately  ush with plenty of water for 15 minutes and seek medical attention if irritation persists. If swallowed, drink water, do not induce vomiting and call a physician or poison control center immediately. Failure to read and observe all safety information printed on primer, cleaner and cement containers can result in severe personal injury or death!
Cleaners and primers are intended for different
functions and should not be considered inter­changeable. Verify with vent material manufacturer for speci c requirements.
4. Apply a coat of primer to the pipe and   ing surfaces that will be joined.
5. Apply a thin coat of cement to the   ing surface that will be joined making sure not over apply the cement which can cause puddling inside the   ing.
6. Apply a liberal coat of cement to the pipe surface that will be joined making sure to completely coat the area so it is free of voids.
7. QUICKLY assemble the parts while the cement is  uid! If the cement dries before the parts are assembled, re-coat the surfaces with cement then assemble them.
8. Push the end of the pipe completely into the   ing socket so it bo oms out and rotate the   ing or pipe at least 1/4 turn to achieve proper cement spread. Make sure the parts are in the correct orientation before the cement cures.  e cement bonds by melting the PVC so once the joint is made it cannot be disassembled.
9. Hold the pipe and   ing for 30 seconds to allow the joint to su ciently cure then carefully clean o any excess cement with a cloth.
10. Follow the PVC cement manufacturer’s instructions to allow the connections su cient time to cure before pu ing any stress on the joint.
5
Page 6
tional PVC vent system installation instructions su
ppl
O
ement
PVC VENT TERMINALS
When vented horizontally the vent and air intake systems may be terminated using standard PVC   ings with 1/4 in stainless steel bird-screen inserts as shown below.  e minimum distance from the wall must be maintained as shown in the Figures below.
Figure 4 Horizontal PVC TEE Terminal
8'' Min
1/4'' SS Bird Screen
In Openings
Figure 5 Horizontal PVC 45° Elbow Terminal
Figure 6 Horizontal PVC 90° Elbow Terminal
1/4'' SS Bird Screen
In Opening
10'' Min
Figure 7 Horizontal PVC Coupling Terminal
8'' Min
1/4'' SS Bird Screen
In Openings
1/4'' SS Bird Screen
In Opening
10'' Min
6
Page 7
tional PVC vent system installation instructions supplement
O
Figure 8 Vertical PVC Terminal
1/4'' SS Bird Screen In Opening
 e input of the unit must be set per Table 2 or nuisance shutdowns may occur under strong wind conditions.
Table 1 Turn Down vs Combustion Air Source
Terminal Type Combustion Air Turn Down Ratio
Tee
45° Elbow
90° Elbow
Coupling
Indoor 3:1
Outdoor 4:1
Indoor n/a
Outdoor 3:1
Indoor 3:1
Outdoor 4:1
Indoor 3:1
Outdoor 4:1
When vented vertically the vent and air intake systems should be terminated using standard 45° and 90° PVC Elbow   ings with a 1/4 in stainless steel bird-screen insert as shown below.
 e rest of the applicable Combustion Air & Ventilation and Venting instructions contained in the INSTALLATION & OPE TION MANUAL MUST BE FOLLOWED.
7
Page 8
260 North Elm Street 7555 Tranmere Drive West eld, MA 01085 Mississauga, Ontario L5S 1L4 Canada Phone: (413) 568-9571 Phone: (905) 670-5888 Fax: (413) 568-9613 Fax: (905) 670-5782
www.rbiwaterheaters.com
Copyright 2008 Mestek, Inc.
Loading...