Raypak WH1-0401 Installation Manual

0 (0)

INSTALLATION & OPERATING

INSTRUCTIONS

Raytherm®

Hot Water

Supply

Heaters

Models 0133–4001

Type WH

® LLC

WARNING: Improper installation, adjustment, alteration, service or maintenance can

cause property damage, personal injury or loss of life. Refer to this manual.

Installation and service must be performed by a qualified installer, service agency or

the gas supplier.

 

 

 

FOR YOUR SAFETY: Do not store or use gasoline or other flammable vapors and

liquids or other combustible materials in the vicinity of this or any other appliance. To

do so may result in an explosion or fire.

 

 

WHAT TO DO IF YOU SMELL GAS:

 

 

• Do not try to light any appliance.

 

 

• Do not touch any electrical switch; do not use any phone in your building.

• Immediately call your gas supplier from a neighbor's phone. Follow the gas

supplier's instructions.

 

 

• If you cannot reach your gas supplier, call the fire department.

 

Installation and service must be performed by a qualified installer, service agency or

the gas supplier.

 

 

 

This manual should be maintained in legible condition and kept adjacent to the heater or in a safe place for future

reference.

 

 

 

CATALOG NO. 3000.52Q

Effective: 09-01-15

Replaces: 04-20-12

P/N 241075 Rev. 18

Rev. 16 reflects the following:

Changes to: ASME Mark on page 1, warnings on page 4, warning on page 27

Additions: Warnings on page 7, warning on page 13, warnings on page 14, warning on page 19, caution on page 20, warning on page 30, warning on page 48

2

 

 

CONTENTS

 

WARNINGS

 

4

Burner Adjustment

34

Pay Attention to These Terms

 

4

Visual Inspection

34

GENERAL SAFETY

 

5

Electrical

34

Time/Temperature Relationships in Scalds 6

High Gas Pressure Switch

34

RECEIVING EQUIPMENT

 

6

Burner Tray Removal

34

Model Identification

 

6

Gas Valve Removal

34

General Specifications

 

7

Main Burner And Orifice Removal

35

All Models (Approved)

 

7

Pilot Removal

35

Hot Water Supply Heaters

 

7

Combustion Fan Removal

35

INSTALLATION

 

7

TROUBLESHOOTING

36

Installation Codes

 

7

Electrical

36

Installation Base

 

7

Mechanical

37

Clearances

 

8

WIRING DIAGRAMS

38

Specifications and Dimensions

 

9

Wiring Diagram—W2/WH2 133

38

Outdoor Water Heaters

 

12

Wiring Diagram—WH1 0181/0261

39

Combustion Air (Indoor Units Only) Air for

 

Wiring Diagram—WH1 0331/0401

40

Combustion and Ventilation

 

12

Wiring Diagram—WH1 0514–0724

41

Venting

 

13

Wiring Diagram—WH1 0824–1826

42

Vent Piping

 

17

Wiring Diagram—WH1 2100–2500

43

Vent Damper Installation

 

18

Wiring Diagram—WH1 3001–4001

44

Plumbing

 

20

Troubleshooting—Pumps

45

Flow Rates

 

22

SERVICE AND MAINTENANCE

 

Piping—Domestic Hot Water Supply

 

 

PROCEDURES

45

Heaters

 

23

Tube Cleaning

45

Piping Diagram—Type WH - Unitemp 80

 

 

Burner Tray Removal

46

System

 

24

Gas Valve Removal

46

Controls—General

 

25

Gas Valve Adjustment - Robertshaw

 

Limit Controls

 

26

(Invensys) 7000 Series 2-Stage Gas Valve

Electrical Connections

 

27

with Solenoid Valve

46

Location of Controls

 

28

Main Burner and Orifice Removal

47

START-UP PROCEDURES

30

Pilot Removal and Cleaning

47

Before Start-Up

 

30

High Limit or Tankstat Removal

47

General

 

30

Heat Exchanger Removal

47

Initial Start-Up - Pump and Motor

 

30

Heat Exchanger Re-Assembly

47

Intermittent Pilot System Checkout

 

 

Combustion Chamber Removal

48

Procedure (S8600)

 

32

Control Well Replacement

48

INSPECTION PROCEDURES

32

Tube Replacement

48

Burners

 

32

Cleaning Flue Gas Passageways

49

Controls

 

32

REPLACEMENT PARTS

49

Inspection Procedures

 

33

WARRANTY

50

ADDENDA: LOW NOx HEATERS

 

 

 

 

Models 0181 to 0401

33

 

 

Operation

 

33

 

 

Start-Up Procedures

 

 

 

 

(S8610B Ignition Module)

 

33

 

 

3

DANGER:
WARNING:
CAUTION:
NOTE:

WARNINGS—Pay Attention to These Terms

Indicates the presence of immediate hazards which will cause severe personal injury, death or substantial property damage if ignored.

Indicates the presence of hazards or unsafe practices which could cause severe personal injury, death or substantial property damage if ignored. Indicates the presence of hazards or unsafe practices which could cause minor personal injury or product or property damage if ignored.

Indicates special instructions on installation, operation, or maintenance which are important but not related to personal injury hazards.

DANGER: Failure to install the draft hood and properly vent the water heater to the outdoors as outlined in the Venting section of this manual can result in unsafe operation of the water heater. To avoid the risk of fire, explosion, or asphyxiation from carbon monoxide, never operate this water heater unless it is properly vented and has an adequate air supply for proper operation. Be sure to inspect the vent system for proper installation at initial start-up; and at least annually thereafter. Refer to the Maintenance section of this manual for more information regarding vent system inspections.

DANGER: Make sure the gas on which the heater will operate is the same type as that specified on the heater rating plate.

DANGER: When servicing or replacing components that are in direct contact with the water, be certain that:

• There is no pressure in the heater. (Pull the release on the relief valve. Do not depend on the pressure gauge reading).

• The heater water is not hot.

• The electrical power is off.

WARNING: Risk of electrical shock. More than one disconnect switch may be required to de-energize the equipment before servicing.

WARNING: All venting types must be of the same material or product throughout the entire exhaust installation to ensure proper securing and sealing.

WARNING: Should overheating occur or the gas supply valve fail to shut, do not turn off or disconnect the electrical supply to the heater. Instead, shut off the gas supply at a location external to the heater.

WARNING: Both propane and natural gas have an odorant added to help detection. Some people may not physically be able to smell or recognize this odorant. If unsure or unfamiliar about the smell associated with propane or natural gas, ask the gas supplier. Other conditions, such as "Odorant Fade", which causes the odorant to "fade", or diminish in intensity can also hide or camouflage a gas leak.

WARNING: UL recognized fuel gas detectors are recommended in all enclosed propane and natural gas applications wherein there is a potential for an explosive mixture of fuel gas to accumulate and their installation should be in accordance with the detector manufacturer's recommendations and/or local laws, rules, regulations, or customs.

WARNING: Do not use this heater if any part has been under water. Immediately call a qualified service technician to inspect the heater and to replace any part of the control system and any gas control which has been under water.

WARNING: Altering any Raypak pressure vessel by installing replacement heat exchangers, tube bundle headers, or any ASME parts not manufactured and/or approved by Raypak will instantly void the ASME and/or CSA ratings of the vessel and any Raypak warranty on the vessel. Altering the ASME and/or CSA ratings of the vessel also violates national, state, and local approval codes.

WARNING: Propane appliances should not be installed below-grade (for example, in a basement) if such installation is prohibited by federal, state and/or local laws, rules, regulations or customs.

4

WARNING - CALIFORNIA PROPOSITION 65: This product contains chemicals known to the State of California to cause cancer, birth defects or other reproductive harm.

! DANGER

Vapors from flammable liquids will explode and catch fire causing death or severe burns.

Do not use or store flammable products such as gasoline solvents or adhesives in the same room or area near the water heater.

Keep flammable products:

1.Far away from heater,

2.In approved containers,

3.Tightly closed and

4.Out of children's reach.

Water heater has a main burner and pilot flame.

The pilot flame:

1.Is on all the time or intermittently (IID).

2.Will ignite flammable vapors.

Vapors:

1.Cannot be seen,

2.Are heavier than air,

3.Go a long way on the floor,

4.Can be carried from other rooms to the pilot flame by air currents.

Installation:

Do not install water heater where flammable products will be stored or used unless the main burner and pilot flames are at least 18" above the floor. This will reduce, but not eliminate, the

risk of vapors being ignited by the main burner or pilot flame.

GENERALRead and follow water heaterSAFETYwarnings and instructions.

To meet commercial hot water needs, this heater is equipped with a manual reset temperature limit that does not exceed 200°F. However, water temperatures over 125°F can cause instant severe burns or death from scalds. This is the preferred temperature setting when supplying general purpose hot water.

Safety and energy conservation are factors to be considered when setting the water temperature on the thermostat. The most energy-efficient operation will result when the temperature setting is the lowest that satisfies the needs consistent with the application.

Maximum water temperatures occur just after burner has shut-off. To determine the water temperature being delivered, turn on the hot water only, place a thermometer in the stream, and read the thermometer.

Water temperature over 125°F can cause instant severe burns or death from scalds.

Children, disabled, and elderly are at highest risk of being scalded.

See instruction manual before setting temperature at water heater.

Feel water before bathing or showering.

Temperature limiting valves are available, see manual.

The following chart details the relationship of water temperature and time with regard to scald injury and may be used as a guide in determining the safest water temperature for your applications.

Temperature

Time to Produce Serious Burn

120°F

More than 5 minutes

125°F

1-1/2 to 2 minutes

130°F

About 30 seconds

135°F

About 10 seconds

140°F

Less than 5 seconds

145°F

Less than 3 seconds

150°F

About 1-1/2 seconds

155°F

About 1 second

Table courtesy of Shriners Burn Institute.

Table A: Time to Produce Serious Burn

5

Time/Temperature Relationships in Scalds

The temperature of the water in the storage tank heater can be regulated by setting the temperature dial on front of the tankstat. To comply with safety regulations, the tankstat was set at its lowest setting before shipment from the factory.

Fig. 1 illustrates a mechanical tankstat. To adjust the water temperature, insert a small straight screwdriver into slotted screw in hole in front of tankstat and turn wheel to desired setting. Thermostat is adjustable up to 190°F.

Fig. 1: Tankstat Adjustment

DANGER: There is a Hot Water SCALD Potential if the tankstat is set too high.

CAUTION: Hotter water increases the risk of SCALDING!

NOTE: When this heater is supplying general purpose hot water requirements for use by individuals, a thermostatically controlled mixing valve for reducing point of use water temperature is recommended to reduce the risk of scald injury. Contact a licensed plumber or the local plumbing authority for further information.

RECEIVING EQUIPMENT

WARNING: Pump motors should NOT be supported by any type of stand or support from above due to possible misalignment of pump and motor which might occur.

On receipt of the equipment, visually check for external damage to the carton or the shipping crate. If the carton or shipping crate is damaged, make a note on the Bill of Lading and report the damage to the Carrier immediately. Remove the heater from the carton or the shipping crate.

Do NOT use the shipping crate base as an installation base. On occasion, items are shipped loose. Be sure that you receive the number of packages indicated on the Bill of Lading.

When ordering parts, you must specify Model and Serial Number of the heater. When ordering under warranty conditions, you must also specify date of installation.

Raypak recommends that this manual be reviewed thoroughly before installing your Raypak heater. If there are any questions which this manual does not answer, please contact the factory or your local Raypak representative.

Claims for shortages and damages must be filed with carrier by consignee. Permission to return goods must be factory-authorized and are subject to a stocking charge.

Purchased parts are subject to replacement only under the manufacturer's warranty. Debits for defective replacement parts will not be accepted and will be replaced in kind only per our standard warranties.

Model Identification

The model identification number and the heater serial number are found on the heater data plate. The model number will have the form WH1-0514A or similar depending on the heater model. (WH = Hot Water Supply System, 1 = on/off firing, 0514 = size of heater).

Rated inputs are suitable for up to 2000 feet elevation. For elevations above 2000 feet, reduce input 4% for each 1000 feet above sea level.

6

General Specifications

The Raypak water heaters are design certified and tested under the latest requirements of the American National Standard, ANSI Z21.10.3/CSA 4.3. Each heater has been constructed and pressure tested in accordance with the requirements of Section IV of the American Society of Mechanical Engineers Code, and factory fire tested. Materials are CSA-certified for lowlead content (<.25%).

All Models (Approved)

All models are National Board approved. Temperature and pressure gauge is standard. Intermittent ignition device is standard on models 0514 and up.

Model 0133 has 4-pass heat exchanger, 1 tube per pass.

Models 0181-0401 have 2-pass heat exchangers, 5 tubes first pass, 4 tubes second pass.

Models 0514-1826 have 2-pass heat exchangers, 5 tubes first pass, 4 tubes second pass.

Models 2100-4001 have 2-pass heat exchangers, 9 tubes per pass.

Models 0926-4001 have optional single pass with cast iron headers only.

Hot Water Supply Heaters

All Raypak hot water supply heaters are ASME rated and design certified as hot water heaters, with 125 PSI pressure relief valves.

TYPE WH1 with ON/OFF CONTROLS Models 0133-4001

To be used with storage tank systems. Available with integrally mounted pump, factory mounted and wired for models 0133-1826. Models 0181, 0261, 0331 and 0401 are Low NOx Hot Water Heaters.

TYPE WH2 with MODULATING CONTROLS

Models 0133-4001

Hot water supply heater with 110°-170°F gas modulation. Available with integrally mounted pump, factory mounted and wired for models 0133-1826. To be used with storage tank systems.

7

TYPE WH3 with 2-STAGE

CONTROLS

Models 0181-4001

Hot water supply heater with low-high fire for 2-stage control. Available with integrally mounted pump, factory mounted and wired for models 0181-1826. To be used with storage tank systems.

INSTALLATION

Installation Codes

Installation must be in accordance with local codes, or, in the absence of local codes, with the latest editions of the National Fuel Gas Code, ANSI Z223.1/NFPA 54, and the National Electrical Code, ANSI/NFPA 70. In Canada installations must conform with the current CAN/CSA B149 and the Canadian Electrical Code Part 1 CSA C22.2 No.1. Where required by the authority having jurisdiction, the installation must conform to American Society of Mechanical Engineers Safety Code for Controls and Safety Devices for Automatically Fired Heaters, CSD-1.

WARNING: This product must be installed by a licensed plumber or gas fitter when installed within the Commonweatlh of Massachusetts.

Installation Base

The heater should be mounted on a level, non-com- bustible surface. Heater must not be installed on carpeting. The heater can be installed on a combustible surface only when the appropriate listed floor shield base is provided. An optional listed floor shield base is available for factory installation with the heater on all indoor models. Do NOT use the shipping base crate as an installation base.

NOTE: The heater should be located in an area where water leakage will not result in damage to the area adjacent to the appliance or to the structure. When such locations cannot be avoided, it is recommended that a suitable drain pan, adequately drained, be installed under the appliance. The pan must not restrict air flow.

WARNING: The heater shall not be located in an area where water sprinklers, or other devices, may cause water to spray through the cabinet louvers and into the heater. This could cause internal rusting or damage electrical components, and void the warranty.

Heater

Floor Base

Model

Part

Number

Number

0133

001749

0182/0181

058313

0260/0261

058314

0330/0331

058315

0400/0401

058316

0514

056199

0624

056200

0724

056201

0824

056202

0926*

054597

1083*

054598

1178*

054599

1287*

054600

1414*

054601

1571*

058378

1758*

058379

0962

059233

1125

059234

1223

059235

1336

059236

1468

059237

1631

059238

1826

059239

*Models with factory installed floor shield as standard.

BOLD TYPE indicates Low NOx models.

Table B: Combustible Floorshield Ordering Information

Fig. 2: Alternate Method for Providing a NonCombustible Base

Clearances

Installation Clearances

(All Dimensions are in Inches)

 

 

 

Heater Size

 

 

 

 

0133

0181 to

 

0514 to

 

0926 to

2100 to

Location

 

0401

 

0824

 

1826

4001

 

Floor

 

 

See Note 1

 

 

 

Front

 

 

See Note 2

 

 

 

Back

12

12

 

12

 

24

24

 

Right

6

12

 

6

 

24

24

 

Left

12

12

 

18

 

24

24

 

*Vent

6

6

 

6

 

6

6

 

Indoor Top

42

39

 

36

 

24

24

 

Outdoor Top

 

Unobstructed

 

NA

Note 1: Combustible floor shield is required when heater is to be installed on a combustible surface. (See ordering info.)

Note 2: Servicing Clearances: Provide at least 24" (Models 0133-

1826), 48" (Models 2100-4001) in front of unit for removal & servicing of the Controls & Burner Tray. Provide at least 18" on side opposite water connections for deliming of Heat Exchanger Tubes. *Vent includes factory supplied drafthoods and does not include field supplied vent systems above the drafthood. On Models 2100-4001 drafthood is built into heater.

Table C: Clearances From Combustible Surfaces

 

 

 

 

Heater Size

 

 

 

0133

0181 to

 

0514 to

0926 to

2100 to

Description

Location

 

0401

 

0824

1826

4001

a. 3-1/2 in. thick masonry walls

Back

9

9

 

9

16

16

without ventilated air space.

Right

5

9

 

5

16

16

 

Left

9

9

 

12

16

16

 

Vent

5

5

 

5

5

5

 

Indoor Top

43

39

 

36

24

24

 

Outdoor Top

 

 

Unobstructed

NA

b. 1/2 in. insulation board

Back

6

6

 

6

12

12

over 1 in. glass fiber or

Right

3

6

 

3

12

12

mineral wool batts.

Left

6

6

 

9

12

12

 

Vent

3

3

 

3

3

3

 

Indoor Top

30

30

 

24

16

16

 

Outdoor Top

 

 

Unobstructed

NA

c. 0.024 sheet metal over 1 in.

Back

4

4

 

4

8

8

glass fiber or mineral wool

Right

3

4

 

3

8

8

batts reinforced with wire

Left

4

4

 

6

8

8

on rear face with ventilated

Vent

3

3

 

3

3

3

air space.

Indoor Top

24

24

 

18

12

12

 

Outdoor Top

 

 

Unobstructed

NA

d. 3-1/2 in. thick masonry wall

Back

6

6

 

6

8

8

with ventilated air space.

Right

6

6

 

6

8

8

 

Left

6

6

 

6

8

8

 

Vent

6

6

 

6

6

6

 

Indoor Top

42

39

 

36

24

24

 

Outdoor Top

NA

 

Unobstructed

NA

e. 0.024 sheet metal with

Back

4

4

 

4

8

8

ventilated air space.

Right

2

4

 

2

8

8

 

Left

4

4

 

6

8

8

 

Vent

2

2

 

2

2

2

 

Indoor Top

24

24

 

18

12

12

 

Outdoor Top

 

 

Unobstructed

NA

f. 1/2 in. thick insulation

Back

4

4

 

4

8

8

board with ventilated

Right

3

4

 

3

8

8

air space.

Left

4

4

 

6

8

8

 

Vent

3

3

 

3

3

3

 

Indoor Top

24

24

 

18

12

12

 

Outdoor Top

NA

 

Unobstructed

NA

g. 0.024 sheet metal with

Back

4

4

 

4

8

8

ventilated air space over

Right

3

4

 

3

8

8

0.024 sheet metal with

Left

4

4

 

6

8

8

ventilated air space.

Vent

3

3

 

3

3

3

 

Indoor Top

24

24

 

18

12

12

 

Outdoor Top

 

 

Unobstructed

NA

h. 1 in. glass fiber or mineral

Back

4

4

 

4

8

8

wool batts sandwiched

Right

3

4

 

3

8

8

between two sheets 0.024

Left

4

4

 

6

8

8

sheet metal with ventilated

Vent

3

3

 

3

3

3

air space.

Indoor Top

24

24

 

18

12

12

 

Outdoor Top

NA

 

Unobstructed

NA

Table D: Clearances to Protected Surfaces

8

NOTE: The heater shall be installed in a space large in comparison to the size of the heater. Large space is defined as having a volume at least sixteen (16) times the total volume of the heater.

Specifications and Dimensions

 

 

 

 

Indoor

Outdoor

 

 

 

 

Model

 

Recovery

Recovery

Number

Input MBH

GPH*

GPH*

WH-0133

136.0

135

132

* Recovery based on manufacturer’s rating.

NOTE:

Ratings are shown for elevations up to 2,000 feet. For elevations over 2,000 feet, reduce ratings 4% for each 1,000 feet above sea level.

MODELS 0182-0400 and 0181-0401

 

 

 

 

 

 

 

 

 

 

 

Indoor

 

 

Dimensions (in inches)

 

 

 

 

 

 

Width

Height

 

Flue

 

Input

 

Recovery

 

J

Diameter

Model Number

MBH

 

GPH*

 

A

C

K

WH-0182/0181

181.0

 

180

 

18-1/4

62-5/8

12-1/16

6

WH-0206/0261

264.0

 

262

 

22-3/8

62-7/8

11-1/8

7

WH-0330/0331

334.0

 

332

 

25-3/4

63-3/4

10-3/4

8

WH-0400/0401

399.0

 

397

 

29-1/4

65-3/8

12-1/2

9

 

 

 

 

 

 

 

 

* Recovery based on manufacturer’s rating.

 

 

 

 

 

 

 

 

 

 

 

9

 

NOTE:

Ratings are shown for elevations up to 2,000 feet. For elevations over 2,000 feet, reduce ratings 4% for each 1,000 feet above sea level.

Bold type indicates Low NOx models.

MODELS 0514-0824

29-1/2

 

 

 

 

 

K

 

 

 

 

14-3/4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DRAFT HOOD

 

 

WATER

 

 

 

 

 

 

 

 

2

 

 

 

 

 

 

 

 

2-3/4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

44-1/8

 

 

57

 

 

 

 

 

GAS

 

 

 

 

 

 

 

1 NPT

 

 

 

 

 

OUT

IN

 

 

 

33

 

 

 

 

 

 

 

 

 

 

 

 

 

 

28-1/4

 

 

 

 

 

 

 

 

 

 

 

 

 

17

 

 

 

 

 

6

 

3-3/4

 

 

 

11-1/8

 

 

 

 

 

Indoor/Outdoor

 

 

Dimensions (in inches)

 

 

 

 

 

Width

Flue

 

 

Model

Input

Recovery

 

Diameter

L

Number

MBH

GPH*

 

 

A

K

 

WH-0514

511.5

508

 

32-3/4

10

 

25-3/8

WH-0624

627.0

623

 

37-1/2

12

 

29-1/2

WH-0724

726.0

722

 

41-5/8

12

 

34-1/4

WH-0824

825.0

820

 

45-3/4

14

 

38-1/2

* Recovery based on manufacturer’s rating.

 

 

 

A

19-1/2

A/2

L

STACKLESS TOP

INDOOR

 

ELECT

OUTDOOR

CONN

 

PUMP (OPTIONAL)

PUMP COVER (OPTIONAL)

14-1/2

10

COMBUSTIBLE

2-1/4

FLOOR SHIELD (OPTIONAL) 5

NOTE:

Ratings are shown for elevations up to 2,000 feet. For elevations over 2,000 feet, reduce ratings 4% for each 1,000 feet above sea level.

MODELS 0962-1826

 

 

 

 

32-1/2

 

 

 

 

 

A

 

 

 

 

K

 

 

 

 

A/2

 

 

 

 

 

 

 

 

 

 

L

 

 

 

11-1/4

 

 

 

 

 

 

 

 

WATER

 

 

 

 

 

 

 

 

 

 

2-1/2

 

 

 

 

 

 

 

 

 

 

23-5/8

 

 

 

 

 

 

 

 

 

B

 

 

 

 

 

 

 

 

 

 

 

C

 

IN

G

 

 

 

 

 

 

 

 

OUT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

27-3/4

 

 

GAS

 

 

 

 

 

 

 

 

 

 

14

 

 

 

 

 

 

 

2-1/2

 

5-1/8

 

 

COMBUSTIBLE FLOOR SHIELD

 

 

 

 

1-1/8

 

(OPTIONAL)

 

 

 

 

 

11-1/8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6

 

 

 

 

 

 

 

 

 

 

 

 

Dimensions (in inches)

 

 

 

 

 

 

 

Overall

Jacket

Gas

 

Flue

 

 

Model

Input

Recovery

Width

Height

Height

Conn.

Diameter

 

A

B

C

G

 

K

 

L

Number

MBH

GPH*

 

 

WH-0962

961.7

956

52-3/8

68-3/4

33-1/2

1

 

14

 

28

WH-1125

1124.7

1118

59-1/4

74-1/2

33-1/2

1

 

16

 

32

WH-1223

1222.5

1215

63-5/8

74-1/2

33-1/2

1-1/4

 

16

 

32

WH-1336

1336.6

1328

68-5/8

76-1/2

33-1/2

1-1/4

 

18

 

36

WH-1468

1467.0

1458

74-7/8

76-1/2

33-1/2

1-1/4

 

18

 

36

WH-1631

1630.0

1620

82-1/8

79-1/2

36-1/2

1-1/4

 

18

 

36

WH-1826

1825.6

1814

89-3/8

81-1/2

36-1/2

1-1/4

 

20

 

40

* Recovery based on manufacturer’s rating.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10

 

 

19-1/2

INDOOR

DRAFT

HOOD

PUMP (OPTIONAL)

 

14-1/2

11-3/4

ELECT

CONN

 

 

(J-BOX)

5

NOTE:

Ratings are shown for elevations up to 2,000 feet. For elevations over 2,000 feet, reduce ratings 4% for each 1,000 feet above sea level.

MODELS 0926-1758

 

 

32-1/2

 

 

 

 

H

 

 

 

 

 

 

 

 

 

 

 

46-3/4

 

 

OUT

IN

 

G

 

 

 

 

 

 

 

 

27-3/4

 

 

 

GAS

 

 

 

 

 

14

 

 

 

 

 

 

5-1/8

1-1/8

 

 

 

11-1/8

 

 

 

6

 

 

 

 

 

 

 

 

 

 

 

 

 

Dimensions (in inches)

 

 

 

Width

 

Gas

Water

Model

Input

Recovery

 

Conn.

Conns.

A

 

G

H

Number

MBH

GPH*

 

WH-0926

926.0

920

52-3/8

 

1

2-1/2

WH-1083

1083.0

1076

59-1/4

 

1

2-1/2

WH-1178

1178.0

1171

63-5/8

 

1-1/4

2-1/2

WH-1287

1287.0

1279

68-5/8

 

1-1/4

2-1/2

WH-1414

1413.0

1404

74-7/8

 

1-1/4

2-1/2

WH-1571

1570.0

1560

82-1/8

 

1-1/4

2-1/2

WH-1758

1758.0

1747

89-3/8

 

1-1/4

2-1/2

* Recovery based on manufacturer’s rating.

 

 

MODELS 2100-4000

A

19-1/2

 

PUMP COVER (OPTIONAL)

PUMP (OPTIONAL)

14-1/2

ELECT 11-3/4 CONN

(J-BOX)

COMBUSTIBLE FLOOR SHIELD

 

(OPTIONAL)

5

 

NOTE:

Ratings are shown for elevations up to 2,000 feet. For elevations over 2,000 feet, reduce ratings 4% for each 1,000 feet above sea level.

 

 

 

 

 

 

 

 

 

 

 

 

 

Dimensions (in inches)

 

 

 

 

 

 

Overall

Gas

Water

 

Flue

Model

Input

Recovery

Width

Height

Conn.

Conns.

 

Diameter

A

B

G

H

 

K

Number

MBH

GPH*

 

WH-2100

2100.0

2087

61

68-1/4

**

3

 

24

WH-2500

2499.0

2484

70

68-1/4

**

3

 

26

WH-3001

3000.0

2982

81-1/4

68-1/4

2

3

 

28

WH-3500

3500.0

3479

92-1/2

68-1/4

2

3

 

30

WH-4001

4000.0

3976

103-3/4

68-1/4

2

3

 

32

 

 

 

 

 

 

 

 

 

* Recovery based on manufacturer’s rating.

 

 

 

 

** 1-1/2” or 2” contingent on code requirements

 

 

 

 

 

 

 

 

 

 

 

11

MODEL,

NOTE:

Ratings are shown for elevations up to 2,000 feet. For elevations over 2,000 feet, reduce ratings 4% for each 1,000 feet above sea level.

Outdoor Water Heaters

These heaters are design certified for outdoor installation. Heaters must not be installed under an overhang of less than three (3) feet from the top on the heater. Three (3) sides must be open in the area under the overhang. Roof water drainage must be diverted away from the heaters installed under overhangs with the use of gutters.

The point from where the flue products exit the heater must be a minimum of four (4) feet below, four (4) feet horizontally from or one (1) foot above any door, window or gravity inlet to a building. The top surface of the heater shall be at least three (3) feet above any forced air inlet, or intake ducts located within ten (10) feet horizontally.

CAUTION: Combustion air must not be contaminated by corrosive chemical fumes which can damage the heater. Measures must be taken to prevent the entry of corrosive chemical fumes to the combustion and ventilation air supply. Such chemicals include, but are not limited to, chlorinated and/or fluorinated hydrocarbons such as found in refrigerants, aerosol propellants, dry-cleaning fluids, degreasers, and paint removers. Other harmful elements may come from bleaches, air fresheners, or mastics. Vapors from these types of products can form corrosive acid compounds when burned in a gas flame. The resulting acidic condensate can damage or substantially reduce the life of the heater. It may become necessary to provide outside air directly to the heater in order to avoid this problem.

a. All Air From Inside The Building:

Each opening shall have a minimum net free square inches as noted:

Fig. 3: Outdoor Clearances from Openings

High Wind Conditions (Outdoor

Units Only)

In areas where high winds are frequent, it may be necessary to locate the heater a minimum of 3' from high vertical walls, or install a wind break so the heater is not in direct wind current.

Combustion Air (Indoor Units Only) Air for Combustion and Ventilation

The heater must have both combustion and ventilation air. Minimum requirements for net free air supply openings are 12 inches from ceiling for ventilation and 12 inches from the floor for combustion air as outlined in ANSI Z223.1, and any local codes that may have jurisdiction.

 

Square

 

Square

 

Model

Inches

Model

Inches

 

0133

136

1223

1223

 

0182/0181

181

1336

1337

 

0260/0261

264

1468

1467

 

0330/0331

334

1631

1630

 

0400/0401

399

1826

1826

 

0514

512

2100

2100

 

0624

627

2500

2499

 

0724

726

3001

3000

 

0824

825

3500

3500

 

0962

962

4001

4000

 

1125

1125

 

 

 

BOLD TYPE indicates Low NOx models.

Table E: All Air From Inside The Building

b. All Air From Outdoors:

When air is supplied directly from outside of building, each opening shall have a minimum net free square inches as noted:

 

Square

 

Square

 

Model

Inches

Model

Inches

 

0133

34

1223

306

 

0182/0181

46

1336

335

 

0260/0261

66

1468

367

 

0330/0331

84

1631

408

 

0400/0401

100

1826

457

 

0514

128

2100

525

 

0624

157

2500

625

 

0724

182

3001

750

 

0824

207

3500

875

 

0962

241

4001

1000

 

1125

282

 

 

 

BOLD TYPE indicates Low NOx models.

Table F: All Air From Outdoors

12

NOTE: If louvers, grills or screens are used on the openings, obtain the net free area from their supplier or manufacturer. If the design free area of a louver is not known nor available, it shall be assumed that wood louvers will have 20-25 percent free area and metal louvers will have 60-75 percent free area as specified in the National Fuel Gas Code.

Venting

WARNING: Examine the venting system at least

once a year. Check all joints and vent pipe

connections for tightness, corrosion or deterioration.

Outdoor Installations

Model 0133

1.Remove the front (4) screws.

2.Line up outdoor top vent opening over heater vent opening.

3.Lower outdoor top onto unit lining up slots in the outdoor top with screws holes in jacket top.

4.Reinstall (5) screws to secure jacket top and outdoor top to unit.

Fig. 4: Outdoor Top Installation

Models 0181-0401 and 0182-0400

OUTDOOR

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

8-3/8"

FLOOR BASE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fig. 5: Outdoor Top Installation

Vent Terminal (Outdoor) Stackless Top

Installation

1.Insert tabs into keyhole (4 places).

2.Snap tabs into keyholes so as not to pull out.

Pagoda Top (Shipped Loose with Heater)

Fig. 6: Outdoor Top Installation

13

Models 0514-0824

1.Lower outdoor "Stackless" top onto unit. Position top so it is centered on unit from side-to-side and front-to-rear.

Fig. 7: Outdoor Top Installation

2.Tighten the (4) screws (Shown below) until they come in contact with the unit jacket top, then evenly tighten all (4) screws to secure to unit.

Fig. 8: Outdoor Top Installation

Models 0926-1758

Heaters are shipped with outdoor vent terminal factory installed.

Models 2100-4001

These units are not certified for outdoor installation.

Indoor Installations

WARNING: Do not use the “one permanent opening” method if the equipment room is under negative pressure conditions or the equipment is common vented with other gas-fired appliances.

WARNING: These heaters must not be connected into any portion of mechanical draft systems operating under positive pressure. To do so may cause the flue products to be discharged into the living space causing serious health injury.

Model 0133

Refer to Fig. 9 on the following page.

1.Shut-off main electrical power switch to heater.

2.Turn heater manual ON/OFF switch, located in upper control panel, to the "OFF" position.

3.Shut-off gas supply and water supply to the heater.

4.Mount drafthood on heater and attach with the 8 sheet metal screws provided. Drafthood should be positioned with the vent sensor located on the front left side as shown.

5.Remove plastic plug from left side of heater jacket and install the plastic grommet provided.

6.Route flue sensor wire harness through the grommet installed in Step 5.

7.Remove door and locate wire from roll out sensor to High Limit with the male/female connector.

8.Disconnect male/female connector and attach to the 2 wires from drafthood vent sensor harness.

14

Raypak WH1-0401 Installation  Manual

Fig. 9: Indoor Top Installation

15

Models 0181-0401 and 0182-0400

Vent Terminal/Indoor Stack

Installation

1.Remove the louvered jacket top by removing four

(4) #10 flathead screws.

2.If originally installed, remove "Pagoda" top from the louvered jacket top.

3.Place the inner stack adapter panel over the flue collector inside the heater. Make sure the flanged side of the flue opening is up.

4.Turn the stack (drafthood) upside down and set it down bottom side up.

5.Turn the jacket top panel (removed in step 1) upside down and place it over the stack.

6.Attach the three (3) mounting brackets to the stack using the screws provided and the holes that are pre-drilled in the stack. Make sure the brackets are positioned with the flange near the top side of the stack (see Fig. 10). Caution must be taken not to over tighten and strip the screw threads.

7.Turn the assembled stack and jacket top, right side up. The jacket top will be trapped between the brackets and the top of the stack. Place the stack over the inner adapter panel flanged hole and lower the louvered jacket top panel back into its original position. Reinstall the four (4) green #10 flathead screws removed in step 1 above.

Models 0514-0824

Locate and assemble as shown below. Secure with screws supplied in envelope in carton.

Fig. 11: Indoor Top Installation

Models 0962-1826

Locate and assemble as shown below. Secure with screws supplied in envelope in carton.

SCREW HOLE LOCATION

3-1/4"

DRAFTHOOD

JACKET TOP PANEL

(part of the heater)

#10 SHEET METAL SCREW (3) MOUNTING BRACKET (3)

INNER STACK ADAPTER PANEL FLUE COLLECTOR

(part of heater)

COMBUSTIBLE FLOOR SHIELD

(optional for indoor) 2-1/2"

Fig. 10: Indoor Top Installation

Fig. 12: Indoor Top Installation

Models 2100-4001

These models have built-in drafthoods. For proper operation, the drafthood outlet must be connected to the venting system.