Size:
2.29 Mb
Download

English

 

PRO-ESeries User's Manual

 

1.

Introduction

2

2.

Controls and Indicators

5

3.

Installation

7

4.

Operation

9

5.

Troubleshooting

12

6.

Replacing the Battery

13

7.

Obtaining Service

16

8.

Specifications

17

9.

Configurable Parameters & Settings

18

10.

Limited Product Warranty

19

11.

Declaration of Conformity

21

© Copyright Para Systems, Inc., 2003

1

English

Thank you for purchasing a MINUTEMAN power protection product. It has been designed and manufactured to provide many years of trouble free service.

IMPORTANT SAFETY INSTRUCTIONS

SAVE THESE INSTRUCTIONS !

Please read this manual before installing your PRO-ESeries UPS, models PRO500E, PRO700E, PRO1100E, PRO1500E, PRO500iE, PRO700iE, PRO1100iE, PRO1500iE, as it provides important information that should be followed during installation and maintenance of the UPS and batteries allowing you to correctly set up your system for the maximum safety and performance. Included is information on customer support and factory service if it is required. If you experience a problem with the UPS please refer to the Troubleshooting guide in this manual to correct the problem or collect enough information so that the MINUTEMAN Technical Support Department can rapidly assist you.

This symbol indicates "ATTENTION"

This symbol indicates "Risk of Electrical Shock"

This symbol indicates "Alternating Current Supply Phase" This symbol indicates "Alternating Current Supply"

This symbol indicates "Direct Current Supply"

This symbol indicates "Equipment Grounding Conductor"

CAUTION! To reduce the risk of electrical shock with the installation of this UPS equipment and the connected equipment, the user must ensure that the combined sum of the AC leakage current does not exceed 3.5mA.

2

CAUTION! Connect the UPS to a two pole, three wire groundingAC wall outlet. The receptacle must be connected to the appropriatebranch protection (circuit breaker or fuse). Connection to any othertype of receptacle may result in a shock hazard and violate local electrical codes.

CAUTION! To reduce the risk of electrical shock in conditions where

the load equipment grounding cannot be verified, disconnect the UPS

from the AC wall outlet before installing a computer interface cable.

Reconnect the power cord only after all signaling connections are made.

English

WARNING: Risk of Electrical Shock. Hazardous live parts inside these power supplies are energized from the battery even when the AC input is disconnected.

To de-energizethe outputs of the UPS:

1.If the UPS is on press and release the On/Off/Test button.

2.Disconnect the UPS from the AC wall outlet.

3.To de-energizethe UPS completely, disconnect the battery.

This Uninterruptible Power Supply (UPS) contains potentially hazardous voltages. DO NOT attempt to disassemble the UPS. This UPS contains no user serviceable parts. Repairs and battery replacement must be performed by

AUTHORIZED SERVICE PERSONNEL ONLY.

NOTICE: This equipment has been tested and found to comply with

the limits for a Class B computing device in accordance with the speci-fications in Subpart J of Part 15 of FCC Rules and the Class B limits for radio noise emissions from digital apparatus set out in the Radio Interference of

the Canadian Department of Communications. These limits are designed to provide reasonable protection against such interference in a residential installation. This equipment generates and uses radio frequency and if not installed and used properly, that is, in strict accordance with the manufacturer's instructions, this equipment may cause interference to radio and television reception. If this equipment does cause interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:

!Re-orientthe receiving antenna.

!Relocate the computer with respect to the receiver.

!Move the computer away from the receiver.

!Plug the computer into a different outlet so that the computer and receiver are on different branch circuits.

!Shielded communications interface cables must be used with this product.

WARNING: Changes or modifications to this unit not expressly approved by the party responsible for compliance could void the user's authority to operate the equipment.

3

English

Receiving Inspection

After removing your MINUTEMAN UPS from its carton, it should be inspected for damage that may have occurred in shipping. Immediately notify the carrier and place of purchase if any damage is found. Warranty claims for damage caused by the carrier will not be honored. The packing materials that your UPS was shipped in are carefully designed to minimize any shipping damage. In the unlikely case that the UPS needs to be returned to MINUTEMAN, please use the original packing material. Since MINUTEMAN is not responsible for shipping damage incurred when the system is returned, the original packing material is inexpensive insurance. PLEASE SAVE THE PACKING MATERIALS!

Para Systems Life Support Policy

As a general policy, Para Systems Inc. (Para Systems) does not recommend the use of any of its products in life support applications where failure or malfunction of the Para Systems product can be reasonably expected to cause failure of the life support device or to significantly affect its safety or effectiveness. Para Systems does not recommend the use of any of its products in direct patient care. Para Systems will not knowingly sell its products for use in such applications unless it receives in writing assurances satisfactory to Para Systems that (a) the risks of injury or damage have been minimized, (b) the customer assumes all such risks, and (c) the liability of Para Systems Inc. is adequately protected under the circumstances.

Examples of devices considered to be life support devices are neonatal oxygen analyzers, nerve stimulators (whether used for anesthesia, pain relief, or other purposes), auto transfusion devices, blood pumps, defibrillators, arrhythmia detectors and alarms, pacemakers, hemodialysis systems, peritoneal dialysis systems, neonatal ventilator incubators, ventilators for both adults and infants, anesthesia ventilators, and infusion pumps as well as any other devices designated as “critical” by the United States FDA.

Hospital grade wiring devices and leakage current may be ordered as options on many PARA SYSTEMS UPS systems. PARA SYSTEMS does not claim that units with this modification are certified or listed as Hospital Grade by PARA SYSTEMS or any other organization. Therefore, these units do not meet the requirements for use in direct patient care.

4

English

On-Line/On-Battery/Boost/BuckLED

Fault LED

Overload LED

Weak/Bad Battery LED

On/Off/Test Button

Press and release the ON/OFF/Test Button after 1 beep to turn the UPS ON or OFF (see section 4).

On-Line

On-Battery

Buck Boost

The On-Line/On-Battery/Boostand Buck (green) LED illuminates in a steady state when the UPS is on and supplying AC power to the load. The LED blinks and the audible alarm sounds, when supplying battery power to the load. The LED blinks and no audible alarm when the UPS is in either the boost or the buck mode.

The Fault (red) LED illuminates when the UPS has detected an internal fault. (see section 5)

The Overload (yellow) LED illuminates when the loads connected to the UPS exceeds the UPS power rating. (see section 5)

The Weak/Bad Battery (red) LED illuminates when the UPS has detected that the batteries are Weak/Bad. Battery replacement might be required. (see section 5)

5

English

REAR PANEL

1

10

 

2

120V Models

 

 

 

 

 

 

 

 

 

 

 

4

3

 

 

 

 

 

9

 

 

 

 

 

 

 

 

 

 

 

5

 

 

 

 

 

 

 

 

8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6 7

1.The Information/Rating Label.

2.The Battery Backup and Surge output power receptacles are NEMA 5-15Rtype (IEC 320 C13 sockets for 230V models).

3.The USB Communications Interface Port is for UPS monitoring and control.

4.The RS232 Communications Interface Port is for UPS monitoring and control.

5.The Dipswitches are for setting the Inverter output voltage.

6.The input power cord has a NEMA 5-15PPlug (IEC 320 C14 socket for 230V models).

7.The input circuit breaker will trip in the event the load exceeds the UPS’s power rating.

8.The RJ11/RJ45 modular connectors are used for 10 Base-TNetwork/Fax/ Modem protection.

WARNING: The 230V models are NETWORK PROTECTION ONLY.

9.The Surge ONLY output power receptacles are NEMA 5-15Rtype (IEC 320 C13 sockets for 230V models).

NOTE: The Surge ONLY output power receptacles are only on the following models: PRO500E, PRO700E, PRO500iE, PRO700iE.

10.The Site Wiring Fault (SWF) LED illuminates when the UPS detects an improperly wired AC wall outlet (120V models only).

 

 

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

230V Models

2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3

 

 

 

 

 

 

 

 

 

9

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5

 

4

 

 

 

 

 

 

 

 

 

 

 

 

 

8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6

 

6

7

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

English

INSTALLATION PLACEMENT

The PRO-Eseries is intended to be install in a temperature controlled environment that is free of conductive contaminants. Select a location which will provide good air circulation for the UPS at all times. Avoid locations near heating devices, water or excessive humidity, or where the UPS is exposed to direct sunlight. Route power cords so they cannot be walked on or damaged.

Operating Temperature (Maximum): 0 to 40 degrees C (+32 to 104 degrees F) Operating Elevation: 0 to 3,000m (0 to 10,000 ft)

Operating and Storage Relative Humidity: 95%, non-condensingStorage Temperature:-15to +45 degrees C (+5 to +113 degrees F) Storage Elevation: 0 to 15,000m (0 to +50,000 ft)

INSTALLATION

Be sure to read the installation placement and all the cautions before installing the UPS. Place the UPS in the final desired location and complete the rest of the installation procedure. USE CAUTION: The UPS is heavy. Use the appropriate number of personnel when installing the UPS.

CONNECTING YOUR EQUIPMENT

Plug the equipment into the output receptacles on the rear panel of the UPS. Do not use extension cords, adapter plugs, power strips or surge strips on the output of the UPS. Ensure that you do not exceed the maximum output rating of the UPS (refer to the UPS's back panel or the Electrical Specifications in this manual).

CAUTION! DO NOT connect a laser printer to the output receptacles on the UPS, unless the UPS is rated 2000VA or greater. A laser printer

draws significantly more power when printing than at idle and may overload the UPS.

7

English

WARNING! DO NOT plug Power Strips or Surge Protection Devices into the ”Battery Backup” Receptacles on the UPS. Plugging Power

Strips or Surge Protection Devices into the “Battery Backup”

Receptacles may cause internal damage to the UPS, the Power Strip, or the Surge Protection Device.

CONNECTING THE UPS TO AN AC SOURCE

Plug the UPS into a two pole, three wire, grounded receptacle only. Do not use extension cords, adapter plugs, power strips or surge strips.

CHECKING THE SITE WIRING FAULT

After plugging in the UPS, check the Site Wiring Fault (SWF) LED on the rear panel of the UPS. If the SWF LED is illuminated, the UPS is plugged into an improperly wired AC outlet.

CAUTION! If the UPS indicates a Site Wiring Fault (SWF), have a Qualified Electrician correct the problem.

CHARGING THE BATTERY

The PRO-ESeries UPS will charge the internal batteries whenever the UPS is connected to an AC source. It is recommended that the UPS's batteries be charged for a minimum of 4 hours before use. The UPS may be used immediately, however, the “ON Battery” runtime may be less than normally expected.

NOTE: If the UPS is going to be out of service or stored for a prolonged period of time, the batteries must be recharged for at leasttwenty-fourhours every ninety days.

COMMUNICATIONS PORT CONNECTION (OPTIONAL)

MINUTEMAN Power Monitoring Software and interface cables kits can be used with the PRO-ESeries UPS. Use only MINUTEMAN or MINUTEMAN approved interface cables with these UPSs. Connect the interface cable (Serial or USB) to the appropriate communications port on the rear panel of the UPS. Connect the other end of the cable to the device that will be monitoring/controlling the UPS.

NOTE: Connecting to the Communications Port is optional. The UPS works properly without a connection.

NETWORK/FAX/MODEM PROTECTION CONNECTION (OPTIONAL) Connect a 10 Base-T network, Fax or Modem line to the RJ11/45 protection sockets on the rear panel of the UPS. This connection will require another length of telephone or network cable. The cable coming from the telephone service or networked system is connected to the port marked “IN”. The equipment to be protected is connected to the port marked "OUT".

NOTE: Connecting to the Network/Fax/Modem protection socket connection is optional. The UPS works properly without a connection.

WARNING: The RJ45 protection sockets for the 230V models areNETWORK PROTECTION ONLY. Connecting a Fax/Modem/Phone line is

PROHIBITED.

8

English

TURNING THE UNIT ON/OFF

ON / OFF / Test Button

Press and release the ON/OFF/Test Button after one beep to turn the UPS ON and supply power to the load. The load is immediately powered while the UPS runs a two-secondself test. Press and release the ON/OFF/Test Button after one beep to turn the UPS OFF. The UPS will continue to charge the batteries whenever it is plugged into an AC outlet and there is AC present.

SELF TEST

The self test feature is useful to verify the correct operation of the UPS and the condition of the batteries. With the UPS in the normal On-Linemode, press and hold the ON/OFF/Test Button for approximately 4 seconds (four beeps), then release the button. The UPS will perform aten-secondself test. During the self test, the UPS will switch to battery power and theOn-LineLED will blink and the audible alarm will sound. The length of the test that is automatically performed every two weeks is longer than thestart-upor user invoked test. This test will run for approximatelyfifteen-secondsto measure the battery’s capability to provide an acceptable amount of runtime. If the UPS fails a self test, one of the LEDs will remain illuminated indicating the type of problem.

Note: The UPS will automatically perform a self test onstart-upand every two weeks.

DIP SWITCH SETTINGS

The DIP Switch setting may be changed by the user to set the desired Inverter (on battery) output voltage. The DIP Switch must be set to the desired Inverter output voltage and then the UPS must be turned OFF and restarted to reconfigure the microprocessor and save the changes. The Inverter (on battery) output voltage setting for the 120V models can be either 120VAC (default) or 127VAC. Changing the Inverter output voltage to 127VAC, will also change the Buck setpoint from 130VAC (default) to 136VAC. The Inverter (on battery) output voltage setting for the 230V models can be either 230VAC (default) or 208VAC. Changing the Inverter output voltage to 208VAC, will also change the Boost1 setpoint from 206VAC (default) to 198VAC.

Inverter output voltage Switch 1 2 120V (230V)

127V (208V)

9

English

ALARMS

ON BATTERY

When the UPS is operating on the batteries, the On-BatteryLED will blink and the audible alarm will sound once every10-seconds.The alarm will stop once the UPS returns to theOn-Lineoperation.

LOW BATTERY WARNING

The UPS will sound two beeps every five-secondswhen the battery reserve runs low. This condition will continue until AC returns or the UPS shuts down from battery exhaustion.

WEAK/BAD BATTERY

The UPS automatically tests the battery’s condition and will illuminate the Weak/ Bad Battery LED and sound the alarm. This alarm will be repeated until the batteries pass a self test. If the battery is bad or disconnected, the Weak/Bad Battery LED will illuminate and the alarm will beep three times every five-min-utes until the battery is reconnected or replaced. If the battery is weak, the Weak/Bad Battery LED will illuminate and the alarm will beep one time everyten-minutesuntil the battery is recharged or replaced. It is recommended that the UPS be allowed to charge overnight before performing a battery test to confirm a Weak/Bad Battery condition.

NOTE: If the UPS has a Weak/Bad Battery Alarm after reconnecting of replacing the batteries, the user must initiate a self test to clear the Weak/Bad Battery Alarm. To initiate a self test see section 4 "SELF TEST".

OVERLOAD

When the amount of load attached to the UPS exceeds its power rating, the Overload LED will illuminate and the UPS will sound a constant alarm. This alarm will remain on until the excess load is removed or the UPS’s self protection circuit shuts the UPS down.

UPS FAULT

When the UPS detects a hardware fault, the Fault LED will illuminate and the UPS will sound a constant alarm. The fault condition, in some instances, may be reset by turning the UPS OFF and then ON. (see section 5 Troubleshooting)

FAN LOCK

AC Mode: If the fan becomes locked, the alarm will beep one time every twoseconds until the fan is unlocked.

Battery Mode: If the fan becomes locked, the alarm will beep one time every two-secondsforthirty-seconds,then the output will turn off, the alarm will sound continuously and the Fault LED will illuminate. The UPS must be turned off and the fan unlocked to clear the Fan lock Alarm.

10

COMMUNICATIONS PORTS (RS232 and USB)

The RS232 communication port is a standard DB9 female with both RS232 and simulated contact closure capability. The PRO-Eseries UPS will poll the port and activate the port for RS232 or contact closure in accordance with the type of cable it finds connected to the port. To change the port configuration requires the unit be turned off and restarted with the desired cable connected. The pinout for the port is depicted per the chart below.

Pin 1: EPO Emergency Power Off (pull and hold this pin low to turn off the UPS, release this pin from low to turn to restart the UPS)

Pin 2: /TXD

Pin 3: /RXD and receive ups shutdown command Pin 4: Simulated contact closure AC fail, NO Pin 5: Ground

Pin 6: Simulated contact closure low battery warning, NO Pin 7: Simulated contact closure AC fail, NC

Pin 8: AC fail signal (high to low signal) Pin 9: Not Used

NOTE: See the SentryII CD for the Power Monitoring Software installation. See the USB Driver CD for the USB installation.

English

11

English

 

 

 

 

 

 

 

 

 

 

 

Symptom

Possible Cause

What To Do

 

 

UPS will not turn on

On/Off/Test button not

Press and release the On/Off/

 

 

 

pushed

Test button to start UPS

 

 

UPS operates in

Input AC circuit breaker is

Reset circuit breaker by

 

 

battery mode only,

tripped

pressing the plunger back in.

 

 

even though there is

 

If the AC circuit breaker trips

 

 

normal AC present

 

after UPS starts up, reduce

 

 

 

 

the load on the UPS

 

 

Fault LED is

UPS has detected an

Call for service

 

 

illuminated

internal fault

 

 

 

Site Wiring Fault

Incorrect service wiring

Have a Qualified Electrician

 

 

LED is illuminated

 

correct the service wiring

 

 

The On-line/On-

The UPS is being

Disconnect the computer

 

 

Battery LED is

controlled via its

cable from the UPS and press

 

 

illuminated, but

communications port

the On button. If UPS works

 

 

there is no output

 

normally, the software has

 

 

 

 

control of the UPS

 

 

UPS does not

The batteries may be weak

Charge the batteries for 8

 

 

provide expected

or at the end of useful

hours and retest. If the runtime

 

 

runtime

service life

is still less than expected, the

 

 

 

 

batteries may need to be

 

 

 

 

replaced, even though the

 

 

 

 

Weak/Bad Battery LED is not

 

 

 

 

illuminated

 

 

Weak/Bad Battery

Weak/bad batteries or bad

Check battery connections,

 

 

LED is illuminated

connections at the battery

charge the batteries for 8

 

 

 

 

hours, replace the batteries

 

 

 

 

 

 

 

UPS occasionally

Normal operation

The UPS is performing its

 

 

emits a beep

 

intended function

 

 

Overload LED is

The load has exceeded the

Check the specifications (see

 

 

illuminated and a

UPS's capacity

section 8). Remove part of the

 

 

constant alarm

 

load

 

 

The On-LineLED is

The UPS is in either the

The UPS is performing its

 

 

blinking and the au-

Boost mode or the Buck

intended function

 

 

dible alarm is silent

mode

 

12

English

REPLACING THE BATTERY

(AUTHORIZED SERVICE PERSONNEL ONLY)

The PRO-ESeries UPS has an easy to replacehot-swappablebatteries. Please read all of theWARNINGS andCAUTIONS before attempting to service the batteries.

NOTE: If there is a power interruption while replacing thehot-swappablebatteries, with the UPS on, the load will not be backed up.

WARNING! This Uninterruptible Power Supply contains potentially hazardous voltages. Do not attempt to disassemble the UPS beyond battery replacement procedures below. This UPS contains nouser serviceable parts. Repairs and Battery replacement must be performed byAUTHORIZED SERVICE PERSONNEL ONLY.

CAUTION: Do not open or mutilate batteries. Released electrolyte is harmful to the skin and eyes and may be toxic.

CAUTION: Do not dispose of batteries in a fire. The batteries may explode. The batteries in this UPS are recyclable. Dispose of the batteries

properly. The batteries contain lead and pose a hazard to the environment and human health if not disposed of properly. Refer to local codes for proper disposal requirements or return the

battery to MINUTEMAN.

CAUTION: Although battery system voltages are only 12VDC, 24VDC, and 36VDC the battery system can still present a risk of electrical shock. The current capability of a battery is sufficient to burn wire

or tools very rapidly, producing molten metal. Observe these precautions when replacing the batteries:

1.Remove watches, rings, or other metal objects.

2.Use hand tools with insulated handles.

3.Wear protective eye gear (goggles), rubber gloves and boots.

4.Do not lay tools or other metal parts on top of batteries.

5.Disconnect the charging source prior to connecting or disconnecting the battery terminals.

6.Determine if the battery is inadvertently grounded. If the battery is, remove the source of the grounding. Contact with any part of a grounded battery can result in an electrical shock.

The likehood of such shock will be reduced, if such grounds are removed during installation and maintenance.

13

CAUTION: Replace batteries with the same number and type as originally installed in the UPS. These batteries have pressure operated vents. These UPSs contain sealednon-spillablelead acid batteries.

English

 

 

 

 

 

 

 

PRO-E

PRO500E

PRO700E

PRO1100E

PRO1500E

 

Model #

PRO500iE

PRO700iE

PRO1100iE

PRO1500iE

 

 

 

 

 

 

 

 

 

Battery

1-12V9Ah

2-12V7Ah

3-12V7Ah

3-12V9Ah

 

 

Model #

 

 

 

 

 

 

 

 

Panasonic

LC-R129

LC-R127

LC-R127

LC-R129

 

 

Part #

 

 

 

 

 

 

 

 

Yuasa Part #

REW45-12

NP 7-12

NP 7-12

REW45-12

 

 

 

 

 

 

 

BATTERY REPLACEMENT PROCEDURE

PLEASE READ THE CAUTIONS AND WARNINGS BEFORE ATTEMPTING TO REPLACE THE BATTERIES

Hot-swappablebatteries mean that the batteries can be replaced without powering down the whole UPS system.

NOTE: If there is a power interruption while replacing thehot-swappablebatteries, with the UPS on, the load will not be backed up. Tohot-swapthe batteries start with step number 6.

1.Turn off the equipment that is plugged into the output receptacles of the UPS.

2.Press and release the On/Off/Test button on the front panel to turn the UPS OFF.

3.Unplug the UPS's AC power cord from the AC wall outlet.

4.Unplug the equipment from the output receptacles of the UPS.

5.Unplug the computer interface cable from the rear panel of the UPS.

6.Remove the retaining screws from the bottom of the front panel of the UPS.

7.Grasp the bottom of the front panel and gently pull the front panel off the UPS.

8.Lay the front panel on top of the UPS.

14

English

9.Disconnect the positive (red) wire from the battery positve terminal.

10.Disconnect the battery negative (black) wire from the battery negative terminal.

NOTE: Use CAUTION, do not touch the battery positive wire to the battery negative wire.

11.Remove the battery bracket retaining screw and slide the battery bracket upwards.

12.Using the pull tab, pull the batteries out completely. DO NOT pull the batteries out by pulling the battery jumper wires.

13.Remove the battery jumper wires.

14.Verify proper polarity. Re-installthe battery jumper wires on the new batteries.

15.Slide the new batteries into the battery compartment.

16.Re-installthe battery bracket and the battery bracket retaining screw.

17.Verify proper polarity. Reconnect the battery negative (black) wire to the battery negative terminal.

18.Verify proper polarity. Reconnect the battery positive (red) wire to the battery positive terminal. Some sparking may occur, this is normal.

19.Re-installthe front panel of the UPS.

20.Re-installthe retaining screws for the front panel of the UPS.

21.Dispose of the old batteries properly at an appropriate recycling facility or return them to the supplier in the packing material for the new batteries.

22.The UPS is now ready for the normal start-upoperation.

NOTE: If the UPS has a Weak/Bad Battery Alarm after replacing the batteries, the user must initiate a self test to clear the Weak/Bad Battery Alarm. To initiate a self test see section 4 "SELF TEST".

15

English

IF THE UPS REQUIRES SERVICE

1.Use the TROUBLESHOOTING section to eliminate obvious causes. 2.Verify there are no circuit breakers tripped. A tripped circuit breaker is the

most common problem.

3.Call your dealer for assistance. If you cannot reach your dealer, or if they cannot resolve the problem call or fax MINUTEMAN Technical Support at the following numbers; Voice phone (972) 446-7363,FAX line (972)446-9011or visit our Web site at www.minutemanups.com the "Discussion Board". Please have the following information available BEFORE calling the Technical Support Department.

A.Your name and address.

B.Where and when the unit was purchased.

C.All of the model information on the rear panel of your UPS.

D.Any information on the failure, including LEDs that may be illuminated.

E.A description of the protected equipment, including model numbers if possible.

F.A technician will ask you for the above information and, if possible, help solve your problem over the phone. In the event that the unit requires factory service, the technician will issue you a Return Material Authorization Number (RMA #).

G.If the UPS is under warranty, the repairs will be done at no charge. If not, there will be a charge for repair.

4.Pack the UPS in its original packaging. If the original packaging is no longer available, ask the Technical Support Technician about obtaining a new set. It is important to pack the UPS properly in order to avoid damage in transit.

Never use Styrofoam beads for a packing material.

A. Include a letter with your name, address, day time phone number, RMA number, a copy of your original sales receipt, and a brief description of the problem.

5.Mark the RMA # on the outside of all packages. The factory cannot accept any package without the RMA # marked on the outside.

6.Return the UPS by insured, prepaid carrier to:

Para Systems Inc.

MINUTEMAN UPS

1455 LeMay Drive

Carrollton, TX 75007

ATTN: RMA # _______

16

English

MODEL NUMBER

PRO500E

PRO700E

PRO1100E

PRO1500E

(230V Models)

(PRO500iE)

(PRO700iE)

(PRO1100iE)

(PRO1500iE)

Acceptable Input voltage

 

0 - 165VAC

(0 - 290VAC)

 

Input voltage (AC Mode)

 

75 - 145VAC (150 - 280VAC)

 

Output voltage (AC Mode)

120VAC: 105-130VAC

(230VAC: 206-250VAC)

Nominal input frequency

 

50 or 60 Hz, autosensing

 

Input protection

 

Resettable circuit breaker

 

Frequency limits (AC Mode)

 

50 or 60 Hz, +/-6Hz

 

Transfer time

 

2-6mS typical

 

Maximum load

500VA

700VA

1100VA

1500VA

 

350W

490W

770W

1050W

On-batteryoutput voltage

Default 120V (230V) / User

selectable at 120/127V, (208/230V)

On-batteryfrequency

50/60 Hz, +/-.5Hz, unless synchronized to utility

On-batterywaveshape

 

Simulated Sine Wave

 

Protection

Over current, short circuit protected and latching shutdown

Surge energy rating (one time,

 

500 J (440 J)

 

10/1000 uS waveform)

 

 

 

 

 

Surge current capability

 

6500 Amps total

 

(one time, 8/20 uS waveform)

 

 

Surge response time

0 ns (instantaneous) normal mode; <5 ns common mode

Surge voltage let-through(as

 

<5%

 

a percentage of an applied

 

 

ANSI C62.41 Cat. A +/-6kV)

 

 

 

 

 

Noise filter

Normal and common mode EMI/RFI suppression

Battery type: Sealed, non-

1-12V9Ah

2-12V7Ah

3-12V7Ah

3-12V9Ah

spillable, maintenance free,

lead-acid

 

 

 

 

 

Typical battery life

3-5years, depending on discharge cycles and ambient temp

Typical recharge time

 

8 hours from total discharge

 

10 Base-Tsurge protection let-

 

 

 

 

 

through (as a percentage of

 

<5%

 

an applied +/-6kV 1.2/50 us,

 

 

500 a 8/20 uS test)

 

 

 

 

 

Telephone line surge protec-

 

 

 

 

 

tion let-through(as a percent-

 

<1%

 

age of an applied +/-6kV 1.2/

 

 

 

 

 

 

 

50 us, 500a 8/20 uS test)

 

 

 

 

 

Runtime: Half Load

15-Minutes

17-Minutes

 

16-Minutes

14-Minutes

Runtime: Full Load

4-Minutes

5-Minutes

 

5-Minutes

4.5-Minutes

Electromagnetic immunity

IEC 801-2level IV,801-4level IV, 801-5level III

Audible noise at 1 m (3 ft.)

 

<45 dBA

 

Size - Net

7.56 x 12.56 x 6.38"

8.03 x 16.18 x 6.38"

H X D X W

192 x 319 x 162 mm

204 x 411 x 162 mm

Size - Shipping

13 x 18.9 x 11.4"

13 x 22.8 x 12.6"

H X D X W

330 x 480 x 290 mm

330 x 580 x 320 mm

Weight - Net (Shipping)

20.3 (23)lb

27.33 (30)lb

39.24 (43)lb

42.33 (47)lb

9.2 (10.4)Kg

12.4 (13.6)Kg

17.8 (19.5)Kg

19.2 (20.9)Kg

 

Safety and approvals

UL1778, cUL (CSA

22.1), TUV; 230V models

EMC Verification

 

FCC Class B, CE certified

 

17

English

(These items may require optional software or hardware)

Function

Factory

User Choices

Description

 

Default

 

 

UPS ID

PRO-E

Up to 64

Use this function to uniquely

 

 

characters

identify the UPS in your network

 

 

to define

configuration

 

 

the UPS

 

Battery

Date of

Date of battery

Enter the current date when

install

manufacture

replacement -

replacing batteries

date

 

month/day/year

 

 

 

XX/XX/XXXX

 

Battery

1826

Up to 5

At first battery replacement, reset

life in

 

characters

to reflect actual number of days

days

 

 

experience in your environment or

 

 

 

 

 

 

leave factory default

Enable/

Enabled

Enable

When enabled, the UPS will

Disable

 

or

automatically restart from a low

auto

 

Disable

battery shutdown when normal AC

restart

 

 

returns

Set

Enabled

Enabled, at

Enabled - the UPS will emit a

audible

 

low battery,

short beep when in the battery

alarm

 

disabled

mode. At Low Battery the UPS

state

 

 

will emit two beeps from low

 

 

 

battery warning until shutdown.

 

 

 

Disabled - Use only when software

 

 

 

is controlling the UPS or to

 

 

 

silence the alarm

Shut-

UPS output

UPS output

UPS Output - When the UPS is

down

 

or UPS

told to shut down, it turns off the

Type

 

 

UPS output only. UPS - Turns off

 

 

 

the UPS which requires the UPS

 

 

 

to be turned on manually

Set

120VAC

120, 127VAC

Changes output voltage during

inverter

(230VAC)

(230, 208VAC)

battery mode operations

output

 

 

 

voltage

 

 

 

 

 

 

 

Enable/

Disabled

Enable

Enabled - the UPS will be

Disable

 

or

completely powered OFF and

EPO

 

Disable

remain OFF until EPO is disabled

18

English

Para Systems Inc. (Para Systems) warrants this equipment, when properly applied and operated within specified conditions, against faulty materials or workmanship for a period of three years from the date of purchase. For equipment sites within the United States and Canada, this warranty covers repair or replacement of defective equipment at the discretion of Para Systems. Repair will be from the nearest authorized service center. Replacement parts and warranty labor will be borne by Para Systems. For equipment located outside of the United States and Canada, Para Systems only covers faulty parts. Para Systems products repaired or replaced pursuant to this warranty shall be warranted for the unexpired portion of the warranty applying to the original product. This warranty applies only to the original purchaser who must have properly registered the product within 10 days of purchase.

The warranty shall be void if (a) the equipment is damaged by the customer, is improperly used, is subjected to an adverse operating environment, or is operated outside the limits of its electrical specifications; (b) the equipment is repaired or modified by anyone other than Para Systems or Para Systems-ap-proved personnel; or (c) has been used in a manner contrary to the product’s User's Manual or other written instructions.

Any technical advice furnished before or after delivery in regard to use or application of Para Systems’s equipment is furnished without charge and on the basis that it represents Para Systems’s best judgment under the circumstances, but it is used at the recipient’s sole risk.

EXCEPT AS PROVIDED HEREIN, PARA SYSTEMS MAKES NO WARRANTIES, EXPRESSED OR IMPLIED, INCLUDING WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE. Some states do not permit limitation of implied warranties; therefore, the aforesaid limitation(s) may not apply to the purchaser.

19