Rackmount Solutions 1200VA, 3000VA, 1000VA, 2200VA, 1500VA, 600VA User Manual

Size:
719.94 Kb
Download

U P S

Uninterruptible Power System

Line-InteractiveRack-MountNetwork UPS

600VA/ 1000VA/ 1200VA 1500VA/ 2200VA/ 3000VA

USER‘S MANUAL

TABLE OF CONTENTS

I N T R O D U C T I O N … … … … … … … … … … … … … … … … … … … … … … … … … … . . i

1.IMPORTANT SAFETY INSTRUCTIONS………………………………………...……………..………1

2.PRESENTATION………………...………….……………………,.………………………..…………2

3.INSTALLATION………………………………………………………………………...……………6

4.OPERATION………………………………………………………………………...………………9

5.SOFTWARE AND COMPUTER INTERFACE………………………………..…………………………10

6.BATTERY CABINET…………………………………………………………………………………11

APPENDIX A. TROUBLESHOOTING……………………………………………………………………11

APPENDIX B. SPECIFICATIONS……………………………………………………….………………12

INTRODUCTION

Please read and save this manual!

Thank you for selecting this uninterruptible power system (UPS). It provides you with a perfect protection for connected equipment. The manual is a guide to install and use the UPS. It includes important safety instructions for operation and correct installation of the UPS. If you should have any problems with the UPS, please refer to this manual before calling customer service.

Please save or recycle the packaging materials!

The UPS‘s shipping materials are designed with great care to provide protection within delivery. These materials are invaluable if you ever have to return the UPS for service. Damage happened during transit is not covered under the warranty.

Intelligent microprocessor control

The UPS is a microprocessor-controlledunit. This means that it operates with the newest technology, high performance and powerful function.

The UPS is an intelligent protector and provides pure, reliable AC power to the critical loads - protecting them from utility power blackout, swells, sags and interference.

Furthermore, in order to save the battery energy, UPS can automatically turn it off under backup mode if none of the connected loads is operating.

Advanced battery management

The visual and audible indications of the UPS present the battery’s status. Self-testfunction let UPS detect a weak battery before it is put into service. The UPS normally perform aself-testat power up condition.

i

1. IMPORTANTSAFETYINSTRUCTIONS

SAVE THESE INSTRUCTIONS - This Manual Contains Important Instructions that should be Followed during Installation and Maintenance of the UPS and Batteries.

Intend for Installation in a Controlled Environment.

Servicing of batteries should be performed or supervised by personnel knowledgeable of batteries and the required precautions. Keep unauthorized personnel away from batteries.

When Replacing Battery, Replace With the Same Number and Type

CAUTION - Do Not Dispose of Battery or Batteries in a Fire, The Battery May Explode.

CAUTION - Do Not Open or Mutilate the Battery or Batteries, Released Electrolyte is Harmful to the Skin and Eyes. It May be Toxic.

CAUTION - A Battery can present a Risk of Electrical Shock and High Short Circuit Current. The Following Precautions Should be Observed When Working on Batteries:

Remove watches, rings or other metal objects. Use tools with insulated handles.

Wear rubber gloves and boots.

Do not lay tools or metal parts on top of batteries.

Disconnect charging source prior to connecting or disconnecting battery terminals.

1

2. PRESENTATION

Front Panel (600VA/ 1000VA), 1U size

Front Panel (1200VA/ 1500VA), 2U size

Front Panel (2200VA/ 3000VA), 3U size

2

Back Panel (600VA/ 1000VA), 1U size

Back Panel (1200VA/ 1500VA), 2U SIZE

(1500VA/110V NO BYPASS OUTPUT)

3

Back Panel (2200VA), 3U SIZE

Back Panel (3000VA), 3U SIZE

4

2.1 “Power On” Indicator

Power On indicator illuminates when utility power’s condition is normal.

2.2 BACKUPindicator

The indicator illuminates when the power is supplied from the batteries.

2.3 “Battery FaultIndicator

This illuminates indicating weak battery. Recharge the battery for at least four hours. If after recharging this still illuminates, replace the battery by following the instructions in the manual.(You can plug out then check battery)

2.4 Power Switch

Can be used as the master on/off switch of your equipment by leaving your equipment connected to UPS and switched on.

2.5 UPS Outlets

Provide instantaneous back-uppower protection to your equipment. Supply temporary uninterrupted operation for your equipment during power failure.

2.6 Bypass Power Sag Outlets

Provides bypass power sag protection to your equipment. Prevent power problems traveling through your system via unprotected peripherals.

2.7 Circuit Breaker Protection

Serves as an overload and fault protection. This is a critical component of the advanced UPS

2.8 “Phone Jack” Communications Ports

Telecom transfer ports provide users to extend the applications.

Caution: To reduce the risk of fire, use only No. 26AWG or larger telecommunication line cord.

2.9 communication function

Provide RS-232interface and UPSMON software to support NOVELL, UNIX, DOS, WINDOWS and other operating systems.

5

3. INSTALLATION

Inspect the UPS upon receipt. The packaging is recyclable; keep it for reuse or disposed of properly.

3.1 Recharge the battery

UPS may be used by anyone immediately upon receipt. The battery is fully charged before shipped from the factory. However, user is recommended to recharge the battery at least eight hours before using UPS. Energy loss may occur during shipping or long duration storage. To recharge the battery, simply let UPS be plugged into an AC outlet and switch it on.

3.2 Connect the loads

Plug your primary equipment (e.g. computer, monitor and critical data storage device, etc.) to the Battery Power-Suppliedoutlets. Plug your peripheral equipment (e.g. printer, scanner, fax, or audio device) to the bypass outlets. Do not plug laser printer to the UPS output outlets, as its power demand is much higher than typical peripherals and may cause the circuit breaker to trip. It is suggested to connect the similar heavy loads (like laser printer) to the bypass outlets.

3.3 Connect the telephone

If you wish to protect a fax or a modem, connect the telephone cable from the wall outlet to the “IN” jack. Connect the telephone cable (provided) from the “OUT” jack to the fax or modem. To protect a10Base-T(UTP) network interface, obtain and use a UTP cable to connect the “OUT” jack to your computer.

3.4 Connect to the utility power

Plug UPS to a 2-pole,3-wiregrounding receptacle. Make sure the branch is protected and does not service equipment requiring heavy electricity (e.g. refrigerator, air conditioner, copier, etc.). Avoid using extension cords; if used, make sure they are rated for at least 15 Amps (A).

3.5 UPS self-test

UPS will conduct a self-testonce switched on it each time. Do not add or take off any equipment while UPS conductsself-test;await it until the Power indicator lights up. Besides this, switch on your equipment after switch on UPS.

3.6 Battery auto-charging

Once the power cord is connected, the battery of UPS will be automatically charged by itself.

3.7 Overload protection

If an overload situation is detected during self-test,UPS audible alarm will activate, emit a long beep and automatically shut down the system. Unplug at least one piece of equipment from the Battery Supplied Outlets. Switch off UPS, wait 5 seconds and check to make sure the circuit breaker is set then switch on, again.

3.8 Optimal battery status

To maintain the optimal status of battery, let UPS be always plugged in.

3.9 Self-protectionfeature

UPS is equipped with self-protectionfeature preventing people from playing with the unit to subsequently damaging the unit. It is programmed so that once switched off, the user must wait 5 seconds before switching UPS on again.

3.10 Storage

To store UPS, cover it and store it with the battery fully charged. During extended storage, recharge the battery every three months to ensure battery life.

3.11 Power failure

When the event of power failure occurs after turning on UPS, and prior to the self-testsequence, UPS will automatically shut down and not restart until utility power is restored. This is necessary to check the quality of power that is delivered to your connected equipment.

6

3.12 Installation with accessories of “Rack-mount”types:

Please install the rack-mounttype units according to the following illustration.

Installation with bottom

Installation with

bottom

Installation with rear

plate.

bracket.

 

bracket

Part

Part

 

Part

RMB-05

RMB-06(1U)

 

RMB-01(1U),-02(2U),

1 SET.

RMB-07(2U~4U).

 

-03(3U),-04(4U)

 

2 PCS.

 

2 PCS.

Step 1

Step 1

 

Step 1

Step 2

Step 2

 

Step 2

 

 

 

 

Step 3

Step 3

 

Step 3

Step 4

Step 4

 

Step 4

 

7

 

 

Installation

with

bottom Installation

with

bottom Installation

with

rear

plate.

 

 

bracket.

 

bracket

 

 

Part

 

 

Part

 

Part

 

 

RMB-08(1U),-09(2U)

RMB-12

 

RMB-13,-14

 

 

,-10(3U),-11(4U)

 

2 PCS.

 

4 PCS.

 

 

2 PCS.

 

 

 

 

 

 

 

Step 1

 

 

Step 1

 

Step 1

 

 

Step 2

 

 

Step 2

 

Step 2

 

 

Step 3

 

 

Step 3

 

Step 3

 

 

Step 4

 

 

Step 4

 

Step 4

 

 

 

 

 

 

8

 

 

 

4. OPERATION

4.1 Simple test

It is recommended that the user perform a simulation test when using UPS for the first time or when adding an additional piece of equipment. Conduct a simulation-test:first, switch on UPS and wait for the power indicator to light up, then simply unplug UPS to simulate the event of utility failure.

4.2 Check the power requirement of your equipment

4.2.1.Make sure the total power of your equipment does not exceed rating capacity.

4.2.2.Also make sure the equipment you plugged into the Battery Power-Suppliedoutlets does not require total power exceeding the capacity of the UPS. Otherwise, overload may occur and cause the circuit breaker to trip. If the power requirement of your equipment differs from VA, convert the requirement power into VA by doing the calculations below:

4.2.3.If the power requirement of your equipment is listed other than VA, convert the requirement into VA by doing the calculations below.

 

 

Watt (W) X 1.67 =

 

 

 

VA, or

 

 

 

Amps(A) X 120=

 

 

VA (For 100-120V

model)

Watt (W) X 1.67 =

 

 

 

VA, or

 

 

 

Amps(A) X 230=

 

 

 

VA (For 220-240

 

 

 

 

 

 

 

 

 

 

 

model)

 

 

 

 

 

 

 

 

 

 

 

 

 

4.3 Limited rating power of UPS

When utility failure occurs, the UPS output outlets will supply power to your equipment from its battery and the alarm will beep every 5 seconds. Be sure that your equipment is running under the limited rating power. To restore the utility by plugging UPS back in to the existing power source. Repeat the test a few times to make sure UPS works properly and to find out the expected runtime.

9

5. SOFTWARE ANDCOMPUTERINTERFACE

5.1 Power Monitoring Software

The UPSMON series software (or other power monitoring software) is applied standard RS-232interface to perform monitoring functions, and then provides an orderly shutdown of a computer in the event of power failure. Moreover, UPSMON displays all the diagnostic symptoms on monitor, such as Voltage, Frequency, Battery level and so on. The software is available for DOS, Windows 3.1x, Windows 95/97/2000/ME/XP, Windows NT or later, Novell Netware, Linux and others. Call your dealer for more information on computer OS compatible solutions.

5.2 Interface Kits

A series of interface kits is available for operation systems that provide UPS monitoring. Each interface kit includes the special interface cable required to convert status signals from the UPS into signals which individual operating system recognize. The interface cable at UPS side must be connected to REMOTE PORT, at computer side can be either COM 1 or COM 2. The other installation instructions and powerful features please refer to READ.ME file.

5.3 The characteristics of computer interface port

The computer interface port has the following characteristics:

The communication port on the back of the UPS may be connected to host computer. This port allows the computer to monitor the status of the UPS and control the operation of the UPS in some cases. Its major functions normally include some or all of the following:

To broadcast a warning when power fails.

To close any open file before the battery is exhausted.

To turn-offthe UPS.

Some computers are equipped with a special connector to link with the communication port. In addition, special plug-incord may be needed. Some computers may need special UPS monitoring software. Contact your dealer for the details on the various interface Kits.

Attention: UPSMON software and interface port function just available for model name with “P” affix. The standardRS-232cable (pin to pinD-SUB9 pin cable) can be connected between UPS REMOTE PORT and computer COM port for the UPSMON series software. UPSMON software can be free download fromhttp:// www. pcmups .com.tw

10

6. BATTERYCABINET

6.1 Battery’s life of UPS

The battery’s life of UPS is about 3-6years under normal usage.

6.2 Battery Replacement

Once the UPS’s battery is no longer useful and must be replaced. Please call the service personnel to replace it.

APPENDIX ATROUBLESHOOTING

UPS has a self-protectfeature that prevents the UPS from being damaged as a result of overheating. If the temperature is higher than 55°C, wait for a while and let the UPS become cool.

Problems

Possible Cause

Solution

Full-timeBypass

Circuit breaker button

Unplug at least one piece of equipment

outlets stop providing

popped up as a result of

from the Full-timeBypass outlets.

power to the

overload.

Switch off UPS, wait 5 seconds, reset

equipment

 

the circuit breaker (press down breaker

 

 

button), then switch on UPS.

UPS doesn’t perform

Battery undercharged or

Recharge the battery by leaving the

to its expected

depleted due to frequent

UPS plugged in and switched on.

runtime.

power outages.

 

 

The power required by your

Unplug at least one piece of equipment

 

equipment slightly exceeds

from the UPS outlets.

 

the capacity of the UPS.

 

 

The battery is slightly

Call the service personnel to replace the

 

worn-out.

battery.

UPS cannot be

Special UPS is designed to

Switch UPS off, wait for 5 seconds, then

turned on.

prevent damage from

switch UPS on.

 

flipping.

 

 

The battery is worn-out.

Replace the battery by following the

 

 

instructions in this manual.

 

Mechanical problem.

Contact your sales representative.

11

APPENDIX BSPECIFICATIONS

MODEL

 

 

KIN-

 

KIN-

KIN-

KIN-

 

KIN-

 

KIN-

 

 

 

600

 

1000

1200

1500

 

2200

 

3000

 

 

 

AP/RM

AP/RM

AP/RM

AP/RM

AP/RM

AP/RM

INPUT

Capacity

(UPS

600

 

1000

1200

1500

 

2200

 

3000

 

 

outlets)

VA/

 

VA/

VA/

VA/

 

VA/

 

VA/

 

 

 

360W

 

600W

720W

900W

 

1320W

1800W

 

 

(Bypass

500VA

500VA

500VA

500VA

 

N/A

 

N/A

 

 

outlets)

 

 

 

 

(220

 

 

 

 

 

 

 

 

 

 

 

~240V

 

 

 

 

 

 

 

 

 

 

 

only)

 

 

 

 

 

Voltage

 

 

 

+/

-25%at

line input

 

 

Frequency

50 or 60 Hz +/-10%(auto sensing)

OUTPUT

Voltage (on

 

Simulated sine wave at 100V or

 

 

battery)

110V/115V/120Vor 220V/230V/240V +/- 5%

 

Frequency

 

 

50 or 60 Hz +/- 0.5%

 

 

(on battery)

 

 

 

 

 

 

 

 

 

 

Voltage

AVR automatically increase output voltage

 

Regulation

15% above input voltage if –9%to–25%of

 

(AVR)

nominal. AVR decrease output voltage 13%

 

 

 

below input voltage if +9% to +25% of

 

 

 

 

 

 

nominal

 

 

 

 

Transfer Time

2/4 milliseconds, including detection time

P R O T E C T IO N

EMI/RFI filter

 

10dB at 0.15MHz,50dB at 30MHz

 

A n d

Overload

UPS automatic shutdown if overload

FILT E R IN G

Protection

exceeds 110% of nominal at 60 seconds and

 

 

 

 

 

130% at 3 seconds

 

 

Unit Input

 

 

 

Circuit Breaker

 

 

 

 

 

 

For overload & Short circuit protection

 

10Base-TCable

Network(UTP,RJ-45)compatible jacks

 

Port

 

 

 

 

 

 

 

 

 

 

Short Circuit

UPS output cut off immediately or input fuse

 

 

 

 

 

 

protection

 

 

 

BATTERY

Type

Sealed, Maintenance-freelead acid

 

Typical

 

8 hours (to 90% of full capacity)

 

 

Recharge Time

 

 

 

 

 

 

 

 

 

 

Protection

Automatic self-test& discharge protection,

 

 

 

 

 

Replace battery indicator

 

 

Back-upTime

3– 180 min (depending on computer load)

12

PHYSICAL

Net W eight

9.35

11.5

16

.3

16

.3

28

.4

32.7

 

Kg (lbs)

(20.5)

(25.3)

(35

.9)

(35

.9)

(62

.6)

(71.9)

 

Shipping W eight

11

 

13

19

.3

19

.3

31

.1

36.3

 

Kg (lbs)

(24.2)

(28.6)

(42

.5)

(42

.5)

(68

.5)

(80)

 

Dimension

483*362*44

483*357*84

483*35

483*48

 

(mm) W *D*H

 

(1U)

 

(2U)

 

1*130

5.5*130

 

 

 

 

 

 

 

 

 

(3U)

(3U)

ALARM

Battery Back-up

 

Slow beeping sound (about 0.47Hz)

 

Battery Low

Rapid beeping sound (about 1.824Hz)

 

Overload

 

 

Continue beeping sound

 

INTERFACE

RS-232Cport

RS-232CBi-directionalcommunication port

 

Interface

 

 

 

 

 

 

 

 

 

 

E N V IR O N ME N T

Ambient

 

3,500 meters max. elevation, 0-95%

 

Operation

humidity non-condensing,0-40deg C

 

Audible Noise

 

< 40dBA (1 meter from surface)

 

Storage

 

 

 

15000 meter max.

 

 

 

Condition

 

 

 

 

 

 

 

 

 

 

©2002. August. 07 Version 3.0 All right Reserved.

All trademarks are property of their respective owners. Specifications subject to change without notice.

6 6 1 - KR 6 0 - 0 0 1

13