This manual contains instructions for Installation, Operation & Maintenance.

Please read this entire manual before you install and use your new room heater. Failure to follow instructions may result in property damage, bodily injury, or even death.

IMPORTANT SAFETY NOTES:

1)When installing your stove, particular attention should be paid to fire protection. If this room heater is not properly installed, a house fire may result. To reduce the risk of fire, follow the installation instructions. Contact local building or fire officials or authority having jurisdiction about restrictions, installation inspection and permit requirements in your area.

2)CAUTION: Never use gasoline or gasoline-type lantern fuel, kerosene, charcoal lighter fluid, or similar liquids to start or “freshen up” a fire in this heater. Keep all such liquids well away from heater while it is in use.

3)During operation, if any part of the stove starts to glow, the stove is in an overfired condition. Close the air controls completely until the glowing has stopped. OVERFIRING VOIDS YOUR WARRANTY!

4)Cool ashes should be disposed of carefully, using a metal container.

5)Do not burn wet or green wood. Store wood in a dry location.

6)DO NOT BURN GARBAGE OR FLAMMABLE FLUIDS SUCH AS GASOLINE, NAPHTHA OR ENGINE OIL. Do not burn treated wood, or wood with salt (driftwood, etc.). Burning materials other than wood (including charcoal) under adverse conditions may generate carbon monoxide in the home, resulting in illness or possible death.

7)Do not permit creosote or soot to accumulate excessively in the chimney or inside the firebox.

8)Check your chimney system thoroughly when installing into an existing metal or masonry chimney. Seek professional advice if in doubt about its condition.

9)Do not connect this unit to a chimney flue already serving another appliance.

10)Comply with all minimum clearances to combustibles as shown in this manual for this appliance.

11)Build fire on brick firebox floor. Do not use grates, andirons or other methods to support fuel.

12)HOT WHILE IN OPERATION! Keep children, pets, clothing and furniture away. Contact can cause skin burns.

13)Do not connect to any air distribution duct or system

14)RISK OF FIRE! Do not operate with stove door open, without the firescreen, or ash removal system door open.

15)For further information refer to NFPA 211 (USA) or CAN/CSA-B365 (Canada).

16)Do not operate without fully assembling all components. Burning your stove without the legs attached (if supplied with unit) will void your warranty, and could present a serious safety hazard

17)Do not oeprate with broken glass..

PRIOR TO FIRST FIRE: Remove all labels from glass. Clean plated surfaces with a glass cleanser and soft cloth to prevent staining from fingerprint oils.

SAVE THESE INSTRUCTIONS

1445 North Highway

250-5763B February 4, 2005

www.quadrafire.com

Colville, WA 99114-2008

R

Isle Royale Wood Stove

and Welcome to the Quadra-Fire Family!

Hearth & Home Technologies welcomes you to our tradition of excellence! In choosing a Quadra-Fire appliance, you have our assurance of commitment to quality, durability, and performance.

This commitment begins with our research of the market, including ‘Voice of the Customer’ contacts, ensuring we make products that will satisfy your needs. Our Research and Development facility then employs the world’s most advanced technology to achieve the optimum operation of our stoves, inserts and fireplaces. And yet we are oldfashioned when it comes to craftsmanship. Each unit is

meticulously fabricated and gold and nickel surfaces are hand-finished for lasting beauty and enjoyment. Our pledge to quality is completed as each model undergoes a quality control inspection. From design, to fabrication, to shipping: Our guarantee of quality is more than a word, it’s QuadraFire tradition, and we proudly back this tradition with a Limited Lifetime Warranty.

We wish you and your family many years of enjoyment in the warmth and comfort of your hearth appliance. Thank you for choosing Quadra-Fire.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

With warm regards,

 

 

 

 

 

 

 

___________________________

___________________________

 

_________________________

 

 

 

 

 

 

 

 

Alan Trusler

 

 

___________________________

 

 

 

 

 

Dan Henry

 

 

 

 

 

 

 

Jason Olmstead

 

 

 

 

Senior Vice President

 

 

 

 

 

 

 

 

 

 

 

 

Dave Fiebelkorn

 

 

 

 

Vice President

 

 

 

 

 

 

Vice President &

 

 

 

Mike Derosier

 

 

 

Dealer Channel

 

 

 

 

 

 

 

 

 

 

 

 

Vice President

 

Materials Manager

 

 

 

Research & Development

 

 

 

 

General Manager

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Marketing & Product Planning

 

 

 

CAUTION:

HOT WHILE IN OPERATION DO NOT TOUCH, KEEP CHILDREN AND CLOTHING AWAY. CONTACT MAY CAUSE SKIN BURNS. KEEP FURNISHINGS AND

 

 

 

OTHER COMBUSTIBLE MATERIAL FAR AWAY FROM THE APPLIANCE. SEE NAMEPLATE AND INSTRUCTIONS.

 

 

 

 

 

 

 

 

 

 

 

 

CHAUD LORS DE L'OPÉRATION. NE PAS TOUCHER. GARDEZ LES ENFANTS ET LES VÊTEMENTS LOIN DE L'ESPACE DÉSIGNÉ DE L'INSTALLATION. LE CONTACT

 

 

ATTENTION PEUT CAUSER DES BRÛLURES À LA PEAU. GARDEZ LES MEUBLES ET LES MATÉRIAUX COMBUSTIBLES LOIN DE L'ESPACE DÉSIGNÉ DE L'APPAREIL. VOIR

 

 

 

 

 

 

 

L'ÉTIQUETTE ET LES INSTRUCTIONS.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LISTED ROOM HEATER, SOLID FUEL TYPE.

APPAREIL DE CHAUFFAGE DE PIÈCE, DE TYPE DE COMBUSTIBLE

 

 

 

 

 

 

 

Report / Rapport

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ALSO FOR USE IN MOBILE HOMES. (UM) 84

SOLIDE, POUR USAGE DANS LES MAISONS MOBILES. (UM) 84

 

Tested and Listed

O-T L

Beaverton

 

 

 

 

 

 

Isle Royale

SERIAL NO. / NUMÉRO DE SÉRIE

 

HUD. "For Use with Solid Wood Fuel Only"

HUD. "Pour Usage Avec Bois Solide Seulement"

 

 

 

 

by

Oregon USA

#061-S-18-2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PREVENT HOUSE FIRES

 

PRÉVENTION DES FEUX DE MAISON

 

 

 

OMNI-Test Laboratories, Inc.

 

 

 

 

 

UL 1482, UL 737, ULC S627.

 

 

 

 

 

 

 

 

Install and use only in accordance with

Installez et utilisez en accord avec les instructions d'installation et

 

 

 

 

 

VENT SPECIFICATIONS:

 

 

 

 

 

 

SPÉCIFICATIONS DE LA VENTILATION:

 

 

manufacturer's installation and operating instructions.

d'opération du fabricant. Contactez le bureau de la construction ou le

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MUR SIMPLE: De six (6") (152mm) de diamètre, le connecteur de conduit de minimum

 

Contact local building or fire officials about

bureau des incendies au sujet des restrictions et des inspections

SINGLE WALL: Six inch (6") (152mm) diameter, minimum 24 MSG black or blued steel

 

restrictions and installation inspections in your area.

d'installation dans votre voisinage. Ne pas obstruez l'espace en

connector pipe, with a listed factory-built UL103 HT Class "A" chimney, suitable for use

d'acier noir ou bleu de minimum de 24MSG, avec une cheminée bâtit en usine UL103 HT

Serial Number

Do not obstruct the space beneath heater.

 

dessous de l'appareil.

 

 

 

 

with solid fuels, or a masonry chimney, and the referenced clearances.

 

 

 

de Classe "A", adéquate pour usage avec les combustions solides, ou une cheminée de

WARNING - For Mobile Homes: Do not install in a

AVIS - Pour Les Maisons Mobiles:

Ne pas installer dans une

DOUBLE WAL

L: Six inch (6") (152mm) diameter, listed double wall air insulated

briques, avec espaces libres référés.

 

 

 

 

sleeping room. An outside combustion air inlet must

chambre à coucher. Un tuyau extérieur de combustion d'air doit être

 

 

 

MUR DOUBLE: De six (6") (152mm) de diamètre, le connecteur du conduit d'air isolé pour

be provided and unrestricted while unit is in use. The

installé et ne doit pas être obstrué lorsque l'appareil est en usage. La

connector pipe with listed factory-built UL103 HT Class "A" chimney, or

a masonry

mur double avec une cheminée bâtit en usine UL103 HT de Classe "A:, ou une cheminée

 

structural integrity of the mobile home floor,

ceiling

structure intégrale du plancher, du plafond et des murs de la maison

chimney and the referenced clearances.

 

 

 

 

 

 

 

 

de briques, avec espaces libres alloués.

 

 

 

 

 

and walls must be maintained.

The stove needs to

mobile doit être maintenue intacte. L'appareil de chauffage doit être

*In Canada

must

comply with

Standard CAN/ULC-S629-M87

for

the

650 degree

*Au Canada doit conformer a CAN/ULC-S629-M87 la norme pour 650 degré C cheminée bâtit en

 

fixé à la charpente de la maison mobile. Les composants requis pour

 

be properly grounded to the

frame

of the

mobile

Factory-built chimneys.

 

 

 

 

 

 

 

 

 

 

 

usine.

 

 

 

 

 

 

 

 

l'installation des

maisons mobiles:

Assemblage d'air extérieur,

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

home.

Components required for

mobile

home

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Numéro de Pièce 831-1780.

 

 

 

 

MOBILE HOME: Use double wall pipe by Dura-Vent DVL, Selkirk Metalbestos DS or

MAISON MOBILE:

Utiliser un

conduit de mur double par

Dura-Vent

DVL, Selkirk

 

installation: Outside Air Kit, Part Number 831-1780.

 

 

 

 

Model Name

Refer to manufacturer's instructions and local codes

Référez vous aux instructions du fabricant et des codes locaux pour

Security DL double wall connector pipe. Must be equipped with a spark arrestor.

Apply

Metalbestos DS ou Security DL. Doit être équipé d'un arrêt d'étincelle. Utiliser les espaces

for precautions required for passing chimney through

les précautions requises pour passer une cheminée à travers un mur

double wall clearances below when installing unit.

 

 

 

 

 

 

libres pour mur double comme mentionné ci-bas.

 

 

 

a combustible wall or ceiling and maximum offsets.

ou un plafond combustibles, et les compensations maximums.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ESPACES LIBRES MINIMUM DES MATÉRIAUX COMBUSTIBLES:

Inspect and clean chimney frequently - Under Certain

Inspectez et nettoyez la cheminée fréquemment. Sous certaines

 

MINIMUM CLEARANCES TO COMBUSTIBLE MAT RIALS:

 

 

Conditions of Use, Creosote

Buildup May

Occur

conditions, il se peut que la créosote s'accumule rapidement.

 

 

 

 

 

 

En Pouces & (millimètres)

 

 

 

 

Rapidly.

 

 

 

 

Ne pas connecter cet appareil à une cheminée servant un autre

 

 

 

 

 

In Inches & (Millimeters)

 

 

 

 

 

NOTE: Toutes les dimensions "A", "C", et "F" sont à partir du diamètre intérieur de l'entrée

 

 

 

 

 

NOTE: All "A" , "C" and "F" Dimensions are to the inside diameter of the flue collar.

 

Do not connect this unit to a chimney serving another

appareil.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

du conduit.

 

 

 

 

appliance.

 

 

 

Composants Optionnels: Ventilateur Optionnel, Pièce #831-1701.

 

FOR TOP VENT INSTALLATIONS / POUR LES INST

TIONS

CONDUITS DU HAUT:

 

 

 

 

 

 

 

Test Lab &

Optional Components: Optional Blower, Part

 

Puissance Électrique: 115 VAC, 1.2 Amps, 60 Hz.

 

 

 

 

 

 

 

 

 

 

831-1701.

 

 

 

Éloignez le fil électrique de l'appareil. Ne pas

faire passer

le

fil

 

 

 

 

 

 

 

A

 

B

 

C

 

 

 

 

E

F

G

H

I

B

A

C

Electrical Rating: 115 VAC, 1.2 Amps, 60 Hz.

 

électrique au dessus ou en dessous de l'appareil.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SINGLE WALL PIPE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Route power cord away from unit. Do not route cord

DANGER: Il y a risque de décharge électrique.

Déconnectez le fil

 

 

15 (381)

 

16 (406)

 

33 (838)

22 (558)

22 (558)

28(711)

53 (1346)

18 (457)

16 (406)

 

 

 

 

under or in front of appliance.

 

 

 

électrique de la prise de contact avant le service.

 

 

 

CONDUIT DU MUR SIMPLE

 

 

 

 

 

 

29DES(737) 18 (457)

 

 

 

 

 

 

 

 

 

Report No.

DANGER: Risk of electrical shock. Disconnect

Remplacez la vitre seulement avec une vitre céramique de 5 mm

 

 

 

 

 

 

 

 

 

 

 

 

 

 

D

DOUBLE WALL PIPE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

power supply before servicing.

 

 

 

disponible chez votre fournisseur.

 

 

 

 

 

13 (330)

 

14(356)

 

6 (153)

12 (305)

53 (1346)

18 (457)

14 (356)

 

 

 

 

Replace glass only with 5mm ceramic available from

N'élevez pas le

feu. Bâtissez le feu

de bois directement sur

des

CONDUIT DU MUR DOUBLE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

your dealer.

 

 

 

briques.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Do not use grate or elevate fire. Build wood fire

Ne pas surchauffer. Si l'appareil de chauffage ou le tuyau de

INSTALLATION: ALCOVE - Six inch (6") (152mm) diameter listed DOUBLE WALL air insulated connector pipe with UL103 HT listed factory-built Class "A"

 

 

 

 

directly on firebrick.

 

 

 

cheminée rougissent, vous surchauffez.

 

 

 

chimney, or a masonry chimney.

 

Home must be equipped with a spark arrestor.) Maximum depth of Alcove shall be no more than 38"(965mm) with

 

E

 

 

Do not overfire - if heater or chimney connector

Opérez l'appareil seulement lorsque la porte de chargement est

 

 

 

 

 

 

 

 

 

ALLA

 

 

 

 

 

 

 

 

 

 

F

 

a minimum height of 53" (1346mm) to top of unit, and the referenced clearances.

 

 

 

 

 

 

 

 

F

 

glows, you are overfiring.

 

 

 

fermée. Ouvrez la porte seulement lorsque vous devez ajouter des

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Operate only with the fuel loading door closed. Open

combustibles dans le feu.

 

 

 

 

INSTALLATION: ALCÔVE - De six (6") (152mm) de diamètre, le connecteur du conduit d'air isolé pour MUR DOUBLE avec une cheminée bâtit en usine

 

 

 

 

only to add fuel to the fire.

 

 

 

Écran de Cheminée Optionnel: Pièce 834-3610, peut être utilisé

UL103 HT de Classe "A", ou une cheminé

de briques. (Les maisons mobiles doivent être équipées d'un arrêt d'étincelle). La profondeur maximum de

 

 

 

 

Optional Fire Screen Part 834-3610, may be used

seulement pour les installations résidentielles aux États-Unis.

 

 

l'alcôve ne doit pas être de plus de 38" (965mm) avec une hauteur minimum de 53" (1346mm) du haut de l'appareil, et des espaces libres alloués.

 

 

E

 

ONLY in U.S. residential installations.

 

 

Brevet US 4,766,876; 5,113,843;

 

 

 

 

 

 

 

 

 

P

C

 

 

D

 

E

F

G

H

I

 

 

 

 

US Patents 4,766,876; 5,113,843;

 

 

 

 

 

 

 

 

 

A

 

B

 

 

 

 

 

 

 

 

5,341,794; 6,688,302 B2

 

 

 

DOUBLE W

 

PIPE

 

 

13 (330)

14 (356)

 

29 (737)

18 (457)

 

N/A

N/A

53 (1346)

18 (457)

14 (356)

 

 

 

 

5,341,794; 6,688,302 B2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CONDUIT DU MUR DOUBLE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

H

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FLOOR PROTECTION:

 

 

PROTECTION DU PLANCHER:

 

 

 

FOR REAR VENT INST

TIONS / POUR LES INSTALLATIONS DES CONDUITS ARRIÈRES:

 

 

 

 

 

 

G

 

Floor protector must be a 1" min. thickness

Le protecteur de plancher doit être d'un minimum de 1"

 

 

 

 

 

 

 

 

(k value=.45), non-combustible material or

d'épaisseur (k value=.45), de matériel incombustible ou

IN A

 

Y FIREPLACE(MobileOR THROUGH THE WALL: Six inch (6") (152mm) diameter listed double wall air insulated connector pipe with UL103 HT

 

 

 

 

equivalent, extending beneath heater and to

équivalent, s'étendant du dessous de l'appareil de chauffage

listed factory-built Class "A" chimney, or a masonry chimney. (Mobile Home must be equipped with a spark arrestor). Additional specifications include a

 

 

 

 

front/sides/rear as indicated on the diagram

à l'avant, aux cotés et à l'arrière comme indiqué sur le

 

 

I

 

below. Exception: Non-combustible floor

diagramme suivant. Exception: Les protections

maximum 8" deep mantel without heat shield and the following clearances.

 

 

 

 

 

 

 

 

 

 

 

protections must extend beneath the flue

incombustibles du plancher doivent s'étendre en dessous du

DANS UNE CHEMINÉE EN BRIQUES OU À TRAVERS LE MUR: De six (6") (152mm) de diamètre, le connecteur du conduit d'air isolé pour MUR

 

 

 

 

pipe when installed with horizontal venting

conduit de cheminée lorsqu'installées avec une ventilation à

 

 

 

 

 

 

 

 

 

 

ALLA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

and extend 2" (51mm) beyond each side.

l'horizontale et s'étendre de 2" (51mm) de chaque côté.

 

 

DOUBLE avec une cheminée bâtit en usine UL103 HT de Classe "A", ou une cheminée de briques. (Les maisons mobiles doivent être équipées d'un

 

 

 

 

NOTE: If Hearth Leg kit is

 

 

 

203mm (8")

NOTE: Si l'assemblage

 

arrêt d'étincelle). Les spécifications additionnelles inclues un manteau de cheminée de 8" de profondeur maximum sans les protecteurs de chaleur et les

 

 

8" max

 

 

 

 

 

 

des pieds de l'âtre est

 

espaces libres suivants.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

G

 

used in rear vent

 

 

 

 

 

utilisé près de

 

MASONR

 

 

B

 

 

C

 

D

 

 

E

 

 

F

G

H

I

 

 

 

 

installation, Floor

 

 

 

203mm

203mm

l'installation de la

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fuel loading door

39-1/4"

(8")

(8") 1251mm

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

36/14*

 

 

 

 

G

 

Protector must extend 18"

 

 

 

(49-1/4")

ventilation arrière, le

 

 

 

N/A

 

 

N/A

 

33 (838)

 

22 (559)

 

 

N/A

 

 

N/A

N/A

14/9 (356/229)

 

 

 

 

 

Minimum

 

Minimum

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

protecteur de plancher

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(914/356)

0" in Masonry Wall (Dans le Mur de Briques)

 

 

 

 

(457mm) in front of the

 

 

8"

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16" from glass

 

 

doit s'étendre de 18"

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

fuel loading door opening.

 

457mm (18")

 

 

 

 

 

 

 

 

*(G) with shield spaced 1" (25mm) away from bottom mantel surface

 

 

 

 

 

 

 

 

USA

 

CANADA

(457mm) en avant de la

 

 

 

 

 

 

 

 

 

 

 

 

I

 

 

 

36-3/4"

 

1137mm (44-3/4")

porte de l'ouverture de

 

 

 

 

 

 

 

*(G) Avec le protecteur éloigné de 1" (25mm) du dessous de la surface du manteau de cheminée.

 

 

 

 

 

 

 

 

Minimum

chargement.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Shown with Hearth Legs

 

 

 

Minimum

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Manufactured by:

 

 

 

 

 

 

2005

2006 2007

Jan.

Feb.

Mar.

Apr.

 

May

June

July

Aug.

Sept.

Oct.

Nov.

Dec.

 

U.S. ENVIRONMENTAL PROTECTION AGENCY -

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Certified to comply with July 1990 particulate emission

 

Fabriqué par:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1445 N. Highway, Colville, WA 99114

 

 

DO NOT REMOVE THIS LABEL / NE

 

 

Made in U.S.A./

 

 

 

 

 

standards.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

www.quadrafire.com

 

 

PAS ENLEVER L'ÉTIQUETTE

 

 

 

Fait Aux États-Unis

 

 

 

 

 

 

 

250-5772

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LABEL LOCATION: ON THE BACK OF THE STOVE

 

 

 

 

Page 2

250-5763B

February 4, 2005

R

Isle Royale Wood Stove

 

 

PRE-USE CHECK LIST

 

 

 

1.

 

Place the unit in a location near the final instal-

 

 

lation area and follow the procedures below.

2.

 

Open the stove and remove all the parts and

 

 

articles packed inside. Inspect all the parts and

 

 

cast iron body for shipping damage. Contact

 

 

your dealer if any irregularities are noticed.

3.

 

All safety warning have been read and fol-

 

 

lowed.

4.

 

This Owner's Manual has been read.

5.

 

Floor protection requirements have been met.

6.

 

Chimney connector is properly installed.

7.

 

The proper clearances from the stove and chim-

 

 

ney to combustibles materials have been met.

8.

 

The masonry chimney is inspected by a pro-

 

 

fessional and is clean, or the factory-built

 

 

metal chimney is installed according to the

 

 

manufactuer'rs instrucitons and clearances.

9.

 

The chimney meets the required minimum

 

 

height.

10.

 

All labels have been removed from the glass

 

 

doors.

11.

 

Plated surfaces have been wiped clean.

CAUTION!

DO NOT TILT THE UNIT ON THE CAST IRON LEGS.

Lift the unit upright and place it into position on the floor protector.

TABLE OF CONTENTS

 

Listings & Safety Notices ........................................

3

Serial Number Label Location.................................

2

Pre-Use Checklist.....................................................

3

Dimensions...............................................................

5

Vent Specifications ..................................................

5

Clearances

 

Top & rear vent installations.................................

6

Floor protection....................................................

7

Locations your stove............................................

7

Alternate floor protection calculation....................

8

Installation

 

Reversible flue collar............................................

8

Rear flue deflector cover plate.............................

8

Chimney height requirements & draft ..................

9

2-10-3 Rule ..........................................................

9

Flue & venting systems........................................

10

Chimney connector..............................................

10

Masonry chimney.................................................

10

Solid pack chimney with

 

Metal supports as a thimble.................................

11-12

Masonry fireplace.................................................

13

Metal prefabricated chimney................................

14

Mobile home installation ......................................

15

Outside air kit installation.....................................

16

Blower .................................................................

16

Operation

 

Burning process...................................................

17

Air controls...........................................................

17

Heat output setting...............................................

18

Operation of top-load option ................................

18

Building a fire .......................................................

19

Opacity.................................................................

19

Burn rates ............................................................

20

Wood selection and storage ................................

20

Blower operating instructions...............................

20

Maintenance

 

Creosote formation & removal .............................

21

Chimney cleaning ................................................

21

Ash removal.........................................................

21

Overfring ..............................................................

21

Firebrick ...............................................................

21

Glass care & replacement....................................

21

Plated Surfaces....................................................

22

Brick replacement ................................................

23

Door & gasket .....................................................

23

Exploded view ..........................................................

24

Accessories & Service Part.....................................

25

Service & Maintenance Log.....................................

26

Warranty....................................................................

27

Contact Information .................................................

28

February 4, 2005

250-5763B

Page 3

R

Isle Royale Wood Stove

LISTINGS and SAFETY NOTICES

These installation instructions describe the installation and operation of the QUADRA-FIRE ISLE ROYALE woodstove. This stove meets the U.S. Environmental ProtectionAgency’s 1990 particulate emission standards. The stove is listed by OMNI-Test Laboratories, Inc. to UL Safety Standard 1482, and ULC S627, and (UM) 84-HUD., Report number 061-S-18-2. This stove is approved for mobile home installations when not installed in a sleeping room and when an outside combustion air inlet is provided. The structural integrity of the mobile home floor, ceiling, and walls must be maintained. The stove must be properly grounded to the frame of the mobile home and only use listed double-wall pipe. Outside Air Kit, Part 831-1780 must be installed in a mobile home installation.

Check with your local building code agency before you begin your installation to ensure compliance with local codes, including the need for permits and follow-up inspections. Be sure local building codes do not supersede UL specifications and always obtain a building permit so that insurance protection benefits cannot be unexpectedly cancelled. If any assistance is required during installation, please contact your local dealer.

Inspect and clean vent system frequently in accordance with the instructions contained in this manual. Do not connect this unit to a chimney serving another appliance.

When using optional Blower, Part 831-1701, route power cord away from unit. Do not route cord under or in front of appliance.

Do not elevate fire. Build wood fire directly on firebrick.

Do not overfire - if heater or chimney connector glows, you are overfiring. Stove thermometer recommended.

Operate only with the door closed unless using a firescreen. Open only to add fuel to the fire. Operating with the door open can cause hot embers or sparks to fall out and a fire may result.

INSTALLATION MATERIALS NEEDED FOR YOUR SAFETY

CHIMNEY CONNECTOR (also known as flue pipe or stove pipe): The chimney connector joins the stove to the chimney (see page 10). It must be 6 inch (152mm) minimum diameter 24 MSG black or blued steel, or an approved air-insulated double wall venting pipe.

THIMBLE: A manufactured or site-constructed device installed in combustible walls through which the chimney connector passes to the chimney (see page 11-12). It is intended to keep the walls from igniting.

CHIMNEY SYSTEMS:

1.APPROVED MASONRY(see specifications on page 13) with at least 5/8 inch (16mm) fire clay lining joined with refractory cement or other listed system suitable for use with wood stoves.

2.PREFABRICATED 6 inch (152mm) listed high temperature (UL 103 HT or ULC S629) chimney. Components required by manufacturers for installation such as the chimney support base, firestop (as appropriate), attic insulation shield, insulated tee, etc., are necessary to assure a safe chimney installation. Use only components manufactured for the chimney. Chimney installation should meet NFPA 211 standards.

FIRE SAFETY: To provide reasonable fire safety, the following should be given serious consideration:

1.Install at least one smoke detector on each floor of your home to ensure your safety. They should be located away from the heating appliance and close to the sleeping areas. Follow the smoke detector manufacturer’s placement and installation instructions, and be sure to maintain regularly.

2.Aconveniently located ClassAfire extinguisher to contend with small fires resulting from burning embers.

3.A practiced evacuation plan, consisting of at least two escape routes.

4.A plan to deal with a chimney fire as follows: In the event of a chimney fire:

A.Notify fire department.

B.Prepare occupants for immediate evacuation.

C.Close all openings into the stove.

D.While awaiting fire department, watch for ignition of adjacent combustibles from overheated stove pipe, hot embers or sparks from the chimney.

VENTING SYSTEM

The venting system consists of a chimney connector and a chimney. These get extremely hot during use. Temperatures inside the chimney may exceed 2000°F (1100°C) in the event of a creosote fire. To protect against the possibility of a house fire, the chimney connector and chimney must be properly installed and maintained. An approved thimble must be used when a connection is made through a combustible wall to a chimney. A chimney support package must be used when a connection is made through the ceiling to a prefabricated chimney. These accessories are absolutely necessary to provide safe clearances to combustible wall and ceiling material. Follow venting manufacturer’s clearances when installing venting system.

This stove may be connected to a lined masonry chimney or a listed high temperature prefabricated approved metal chimney. Do not connect it to a chimney serving another appliance. To do so will affect the safe operation of both appliances.

WARNING! NEVER DRAW OUTSIDE COMBUSTION AIR FROM A WALL, FLOOR OR CEILING CAVITY OR FROM ANY ENCLOSED SPACE SUCH AS AN ATTIC OR GARAGE.

WARNING ! DO NOT ATTEMPT TO OPERATE THIS WOODSTOVE WITHOUT READING AND UNDERSTANDING THESE OPERATING INSTRUCTIONS THOROUGHLY. FAILURE TO OPERATE THIS APPLIANCE PROPERLY MAY CAUSE A HOUSE FIRE.

WARNING! THEOUTSIDESURFACESOFTHISUNITWILLBECOME EXTREMELY HOT DURING USE. ALWAYS KEEP CHILDREN AWAY WHILE IT IS OPERATING AND DO NOT LET ANYONE OPERATE THIS APPLIANCE UNLESS THEY ARE FAMILIAR WITH THESE OPERATION INSTRUCTIONS.

 

 

 

 

Page 4

250-5763B

February 4, 2005

Quadra-Fire Isle Royale User Manual

R

Isle Royale Wood Stove

DIMENSIONS

LABEL IS LOCATED ON THE BACK OF THE STOVE

FRONT VIEW

 

SIDE VIEW

 

 

22-3/4" (578mm)

29" (737mm)

 

16-3/4"

 

 

(425mm)

 

 

C

 

 

L

 

 

30"

 

30" (762mm

(762mm)

 

 

 

 

26-7/16"

 

 

(570mm)

 

 

8-1/4"

 

 

(210mm)

28-3/4" (730mm)

 

16-1/2"

 

(419mm)

 

 

24-5/8" (625mm)

27"

(686mm)

5-1/4" (133mm)

C

L

25"

(635mm)

21-5/8" (549mm)

SIDE VIEW

Shown with Hearth Legs and Horizontal

Flue Kit

NOTE: If Hearth Legs are installed, you may install an Outside Air Kit or a Blower, NOT BOTH.

VENT SPECIFICATIONS:

Single Wall: Six inch (6") (152mm) diameter, minimum 24 MSG black or blued steel connector pipe, with a listed factorybuilt chimney type UL103 HT* suitable for use with solid fuels, or a masonry chimney, and the referenced clearances.

Double Wall/Mobile Home: Six inch (6”) (152mm) diameter, listed double wall air insulated connector pipe with listed factory-built UL103 HT* Class “A” chimney, or a masonry chimney (Mobile Home must be equipped with a spark arrestor), and the referenced clearances. Use only double-wall connector pipe, Dura-Vent DVL, Selkirk metalbestos DS, Security DL double wall connector or any listed double-wall connector pipe.

*In Canada must comply with CAN/ULC-S269 or the 650° Factory-built chimney.

 

 

 

 

February 4, 2005

250-5763B

Page 5

R

Isle Royale Wood Stove

CLEARANCES TO COMBUSTIBLES (UL and ULC)

B

A

 

C

 

 

 

 

 

 

 

 

 

 

 

 

 

H

 

 

 

 

 

D

8" max

 

 

 

 

 

ceilingG

 

 

 

 

 

 

 

 

 

 

 

 

Ceiling G

 

 

 

 

 

 

mantel G

 

 

 

 

 

 

 

CL

 

 

 

 

 

 

26-7/16" (672mm)

 

 

E

F

 

I

or

 

 

 

21-5/8" (549mm) if

 

 

 

 

 

 

 

F

 

 

Hearth Legs

 

 

 

 

Shown with Hearth Legs

installed

 

 

 

 

 

 

 

 

 

 

E

 

 

MINIMUM CLEARANCES TO COMBUSTIBLE MATERIALS In Inches & (Millimeters)

NOTE: "A" ,"C" and "F" Dimensions are to the inside diameter of the flue collar.

OMNI Test Laboratories, Inc Report Ntumber 061-S-18-2

 

A

B

C

D

E

F

G

H

I

FOR TOP VENT INSTALLATIONS:

 

 

 

 

 

 

 

SINGLE WALL PIPE

15 (381)

16 (406)

33 (838)

22 (558)

22 (558)

28 (711)

53 (1346)

18 (457)

16 (406)

DOUBLE WALL PIPE

13 (333)

14 (356)

29 (737)

18 (457)

6 (153)

12 (305)

53 (1346)

18 (457)

14 (356)

INSTALLATION: ALCOVE Six inch (6") (152mm) diameter listed Double Wall air insulated connector pipe with UL 103 HT listed factory-built Class "A" chimney, or a masonry chimney. (Mobile Home must be equipped with a spark arrestor). Maximum depth of Alcove shall be no more than 48 inch(1220mm). Please refer to the clearances below for minimum Alcove height requirements to top of unit.

DOUBLE WALL PIPE 13 (333) 14 (356) 29 (737) 18 (457) N/A N/A 53 (1346) 18 (457) 14 (356)

F

OR

REAR VENT INSTALLATIONS:

IN A MASONRY FIREPLACE OR THROUGH THE WALL: Six inch (6") (152mm) diameter listed double wall air insulated connector pipe with UL 103HT listed factory-built Class "A" chimney, or a masonry chimney. (Mobile Home must be equipped with a spark arrestor). Additonal specifications include a maximum 8 inch (203mm) deep mantel without heat shield and the following clearances.

A

B

C

D

E

 

F

G

H

I

N/A

N/A)

33 (838)

22 (558)

N/A

N/A

36

(914) ceiling

N/A

14 (356)

9 (229)

 

 

 

 

 

 

14

(356)* mantel

 

0 (00) In

Masonry Wall

* (G mantel) with shield spaced 1 inch (25mm) away from bottom mantel surface.

 

 

 

 

Page 6

250-5763B

February 4, 2005

R

Isle Royale Wood Stove

FLOOR PROTECTION

The floor must be non-combustible material, extending beneath heater and to the front, sides and rear as indicated. The floor must be non-combustible or otherwise adequately protected from radiant heat given off by the unit and from sparks and falling embers. A layer of thin brick or ceramic tile over a combustible floor is not sufficient. See Alternate floor protection calculation sample on page 8.

In USAinstallations, it is necessary to install a floor protector of 1 inch ("k" value = .45) thick metal clad millboard or equivalent at least 16 inches in front and 8 inches to both sides of the loading door. If Hearth Leg kit is used in rear vent installation, floor protector must extend 18 inches (457mm) in front of the fuel loading door opening. See *exception below.

In Canada, similar floor protection must be provided 18 inches (457mm) in front and 8 inches (203mm) from the sides and rear of the stove. See *exception below.

*EXCEPTION: Non combustile floor protections must extend beneath the flue pipe when installed with horizontal venting and extend 2 inches (51mm) beyond each side.

LOCATING YOUR STOVE

WHEN LOCATING YOUR STOVE consider safety, convenience, traffic flow, and the fact that the stove will need a chimney and chimney connector. It is a good idea to plan your installation on paper, using exact measurements for clearances and floor protection, before actually beginning the installation. If you’re not using an existing chimney, place the stove where there will be a clear passage for a factory-built listed chimney through the ceiling and roof.

AVOID FIRE: Maintain the designated clearances to combustibles. Insulation must not touch the chimney. You must maintain the designated air space clearance around the chimney. This space around a chimney is necessary to allow natural heat removal from the area. Insulation in this space will cause a heat buildup, which may ignite wood framing. NOTE:

Clearances may only be reduced by means approved by the regulatory authority having jurisdiction.

WE RECOMMEND that you have a qualified building inspector and your insurance company representative review your plans before and after installation.

Fuel loading door

39-1/4"

 

 

Minimum

16" from glass - std legs

8"

18" from glass - hearth legs

 

USA

36-3/4"

 

Minimum

 

203mm (8")

203mm

203mm

1251mm

(8")

(8")

 

 

(49-1/4")

Minimum

457mm (18")

CANADA

1137mm (44-3/4") Minimum

must extend length of flue and 2" (51mm) beyond each side of pipe

USA - Required

CANADA - Recommended

 

 

 

 

February 4, 2005

250-5763B

Page 7

R

Isle Royale Wood Stove

Calculating Alternate Floor Protection

Material

Thermal Conductivity: k value

The k value indicates the amount of heat (in BTU’s) that will flow in 1 hour through 1 square foot of a uniform material 1 inch thick for each degree (F) of temperature difference from one side of the material to the other. The LOWER the k factor means less heat is being conducted through the non-combustible material to the combustible material beneath it. The k value of a material must be equal or smaller then the required k value to be acceptable.

(BTU) (inch) (foot2 (hour) (oF)

Thermal Resistance: R value

The R value is a measure of a material’s resisteance to heat transfer. R value is convenient when more than one material is used since you can add the R values together, whereas you can not do this for k value. The HIGHER the R factor means less heat is being conducted through the noncombustible material to the combustible material beneath it. The R value of a material must be equal or larger then the required R value to be acceptable.

Converting k to R:

Divide 1 by k and multiply the results times the thickness in inches of the material.

R = 1/k x inches of thickness

Converting R to k:

Divide the inches of thickness by R. k = inches of thickness/R

Calculatons:

Example: Floor protection requires k value of 0.84 and 3/4 inch thick.

Alternative material has a k value of 0.6 and is 3/4 inch thick.

Divide 0.6 by .75 = k value of 0.80. This k value is smaller than 0.84 and therefore is acceptable.

REVERSIBLE FLUE COLLAR

The flue collar is reversible for either a top or rear venting installation. The unit is shipped with the flue collar in the top vent position.

CONVERTING COLLAR FOR REAR VENT INSTALLATION

1.Remove 5 Phillips head screws from the rear shield, lift shield up and set aside.

2.Remove bolts from each side of the flue transition (2 total). (Place your free hand in flue opening to locate and retrieve nuts attached to bolts.)

3.Turn vent to horizontal position. Inspect sealant to ensure a leak free application.

4.Re-assemble in reverse order.

REAR FLUE DEFLECTOR COVER PLATE

This cover plate is used when the flue collar is turned for a rear vent application.

Please note this cover plate will not work with the Low-Profile Kit

Mounting Screws

1. After the flue collar has been reversed for a rear vent installation, install the cover plate on the stove with the two screws provided.

Bend Flange Down

2.Bend the cover plate flange down.

3.Secure the cover plate with the remaining two screws.

 

 

 

 

Page 8

250-5763B

February 4, 2005

R

Isle Royale Wood Stove

CHIMNEY HEIGHT REQUIREMENTS / DRAFT

To be sure that your stove burns properly, the chimney draft (static pressure) should be approximately -.04” water column (W.C.) during a low burn and -.10” W.C. during a high burn, measured 6 inches (152mm) above the top of the stove after one hour of operation at each burn setting.

NOTE: These are guidelines only, and may vary somewhat for individual installations.

The stove was designed for and tested on a 6 inch (152mm) chimney, 12 ft.-14 ft. (360-420cm) high, measured from the base of the stove. The further your stack height or diameter varies from this configuration, the possibility of performance problems increases. In addition, exterior conditions such as roof line, surrounding trees, prevailing winds and nearby hills can influence stove performance.

A masonry chimney or a listed factory-built UL103 HT Class “A” chimney must be the required height above the roof and any other nearby obstructions. The chimney must be at least 3 ft. (91cm) higher than the highest point where it passes through the roof and at least 2 ft. (61cm) higher than the highest part of the roof or structure that is within 10 ft. (305cm) of the chimney, measured horizontally. See 2-10-3

Rule below.

These are safety requirements and are not meant to assure proper flue draft.

We recommend using a minimum total system height of 12 ft. (360cm), measured from the flue collar to the top of the chimney (not including chimney cap).

 

2-10-3 RULE

3 ft Min

2 ft Min (61cm)

 

(91cm)

 

 

10 ft Min

 

(305cm)

A proper amount of flue draft is required to assure the safe and efficient operation of the this woodstove. Flue draft is measured as negative pressure in the chimney. The amount of negative pressure determines the strength of the draft. This draft performs two important roles in the operation of the woodstove. It draws the combustion air into the firebox, and pulls the smoke out of the chimney.

Three factors work together as a system to create the flue draft; 1) availability of combustion air; 2) heat generated from the fire, and 3) diameter and height of the flue system..

Increasing or decreasing any one of them will affect the other two and thus change the amount of draft in the entire system.

Asource of air (oxygen) is necessary in order for combustion to take place. The combustion air enters the firebox below the ash catcher and is directed to the upper front of the firebox. These openings are regulated by the Primary Air Slide Control and Start-up Air Control, (see page 17 for operation of these controls). It is important to realize that whatever combustion air is consumed by the fire must be replaced. If you are using room air, the air is replaced via air leakage that occurs around windows and under doors, etc. However, in most newly constructed houses, mobile homes, or even existing homes that are fitted with tightly sealed doors and windows, the area from which the combustion air is taken is relatively air tight. In these cases, an outside air source must be made available to feed combustion air from outside the home into the stove. An Outside Air Kit is available as an option, Part 831-1780. The kit is a requirement for mobile home installations.

A specific volume of air, determined by the diameter and height of the chimney connector and chimney, is contained within the flue system. As heat from the fire enters the flue, it warms this air causing it to rise. The air moving up the flue draws smoke and more heated air from the fire with it, thus establishing draft. The amount of draft depends on the temperature of the heated air and the volume of air that is contained in the flue system.

If the fire is difficult to start, and smoke spills out of the door, or you find it hard to establish and maintain a moderately high burn rate, then the flue draft is too low and corrective measures must be taken.

If you still suspect you have a low draft problem, it may be necessary to increase the volume of air in your flue system. Since the diameter of your flue system is matched with the size of the flue collar and should not be changed, the height of the system will need to be increased. Add chimney a little at a time until the draft improves, and ensure that the flue collar and venting section are sealed.

Your local dealer is the expert in your geographic area and can usually make suggestions or discover problems that will easily correct your flue draft problem, allowing your woodstove and its flue system to operate correctly and provide safe and economical heat for your home.

 

 

 

 

February 4, 2005

250-5763B

Page 9