PVI Industries 20 N 119A-MXS User Manual

0 (0)
PVI Industries 20 N 119A-MXS User Manual

LOW NOx MAXIM • PACKAGED GAS WATER HEATER

NICKELSHIELD® NICKEL-PLATED STORAGE TANK

119 GALLON TANK SERIES

 

MODEL NUMBER

20 N 119A-MXS

 

GPH Recovery at 40° to 120° F

245

 

GPH Recovery at 40° to 140° F

195

 

Input Btu/h

199,000

 

Minimum gas inlet pressure – " W.C.

5.5

A

Cold Inlet - NPT

2

B

Hot Outlet - NPT

2

C

Drain - NPT

1

D

I - Beam Skids

3 X 34-1/2

E

Overall Depth

47

F

Overall Height

75

G

Flue Outlet Diameter

5

H

Gas Inlet - NPT

1/2

J

Motor HP 120 V, 1Ø, 60 Hz.

1/6

 

Motor Amps

1.75

L

Height to Outlet

65

M

Height to Inlet

28

 

Approx. Shipping Weight - lbs

1070

Recoveries based on 82% thermal efficiency. ASHRAE 90.1 compliant. Dimensions are in inches unless otherwise specified.

For standard and optional equipment, see Form # PV6382.

34 1/2

1

B

2

F

L

H

C

 

M

 

 

 

J

 

 

23

D

 

 

1.Control Enclosure

2.ASME Temperature & Pressure Relief Valve

3.3” NPT Handhole

41

G

A

3

E

STANDARD GAS PRESSURE REQUIREMENTS:

 

VENTING REQUIREMENTS:

 

 

 

 

-.02" TO -.06" W.C. (NEGATIVE PRESSURE).

SEE TABLE FOR MINIMUM PRESSURE BY MODEL NUMBER.

 

MAXIMUM STATIC PRESSURE: 9" W.C.

 

 

 

TYPE B VENTING.

FOR GAS PRESSURES OUTSIDE OF THIS RANGE,

 

THE ENTIRE VENT SYSTEM SHOULD NEVER BE SIZED BASED UPON THE

CONTACT YOUR PVI REPRESENTATIVE.

 

 

 

VENT CONNECTION DIAMETER EXCLUSIVELY.

 

 

 

 

FOR PROPER VENT SIZING, CONSULT THE NATIONAL FUEL GAS CODE

 

 

 

 

 

 

 

 

UNDER "FAN-ASSISTED".

STANDARD ELECTRICAL REQUIREMENTS:

 

 

 

CONTROL VOLTAGE: 120V, 1Ø, 60 HZ., 2 AMPS

 

 

PVI RESERVES THE RIGHT TO CHANGE THE DESIGN AND

 

 

 

 

SPECIFICATION WITHOUT NOTICE.

 

 

 

 

Product is patented in the U.S., Canada, and Mexico.

 