Powerware 9125 PowerPass User Manual

Page 1
Powerware® 9125
PowerPass
User's Guide
www.powerware.com
Page 2
Requesting a Declaration of Conformity
Harmonic Standards: EN 50091-1-1 and EN 50091-2
EU Directives: 73/23/EEC, Council Directive on equipment designed for use within certain voltage limits
The EC Declaration of Conformity is available upon request for products with a CE mark. For copies of the EC Declaration of Conformity, contact:
Powerware Corporation Koskelontie 13 FIN-02920 Espoo Finland Phone: +358-9-452 661 Fax: +358-9-452 665 68
93/68/EEC, Amending Directive 73/23/EEC 89/336/EEC, Council Directive relating to electromagnetic compatibility 92/31/EEC, Amending Directive 89/336/EEC relating to EMC
Class B EMC Statements
FCC Part 15
NOTE This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to
part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:
Reorient or relocate the receiving antenna.
Increase the separation between the equipment and the receiver.
Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
Consult the dealer or an experienced radio/TV technician for help.
ICES-003
This Class B Interference Causing Equipment meets all requirements of the Canadian Interference Causing Equipment Regulations ICES003.
Cet appareil numérique de la classe B respecte toutes les exigences du Reglement sur le matériel brouilleur du Canada.
Powerware and PowerPass are registered trademarks of Powerware Corporation.
Copyright 2000 Powerware Corporation, Raleigh, NC, USA. All rights reserved. No part of this document may be reproduced in any way without the express written approval of Powerware Corporation.
Page 3
C H A P T E R 1
INSTALLATION
Safety Warnings
The PowerPass is designed to operate with a Powerware uninterruptible power system (UPS) and allows you to:
Replace or upgrade the UPS without losing power to your equipment
(see Using Maintenance Bypass" on page 7).
Provide surge protection if the UPS is not present.
Provide extra surge protection when the UPS is present.
Protect a laser printer against power surges without overloading the
UPS (not available on 2000 VA, 120V models).
9125
I M P O R T A N T S A F E T Y I N S T R U C T I O N S
SAVE THESE INSTRUCTIONS. This manual contains important instructions that you should follow during installation and maintenance of the UPS and batteries. Please read all instructions before operating the equipment and save this manual for future reference.
C A U T I O N
There are NO USER SERVICEABLE PARTS inside the PowerPass. All repairs and
service should be performed by AUTHORIZED SERVICE PERSONNEL ONLY.
To reduce the risk of fire or electric shock, install this UPS in a temperature and
humidity controlled, indoor environment, free of conductive contaminants. Ambient
temperature must not exceed 40°C (104°F). Do not operate near water or
excessive humidity (95% max).
Powerware® 9125 PowerPass® User's Guide 164201324 A Uncontrolled Copy
3
Page 4
Installation
The following instructions describe the PowerPass installation only. Follow the instructions in your Powerware 9125 User's Guide for installing the UPS and optional Extended Battery Modules (EBMs).
1. Install the UPS and optional EBMs according to the user's guide. Do not start up the UPS before installing the PowerPass. Continue to Step 6.
If the UPS is already installed and operating, prepare your equipment for shutdown and continue to Step 2.
2. Turn off the equipment that is connected to the UPS.
3. Press and hold the Off
button for approximately three seconds. The UPS switches to Standby mode and removes power from the UPS output receptacles.
4. Unplug the UPS from the power outlet; the UPS shuts down in five seconds. All front panel indicators flash briefly prior to shutdown.
On 240V units, also disconnect the input power cord from the UPS.
5. Disconnect the power cord(s) between the protected equipment and the UPS.
6. Remove the two screws on the UPS rear panel and discard (see Figure 1).
Screw
Screw
Figure 1. Removing the UPS Screws
7. Verify that both Bypass switches on the PowerPass are in the UPS position (see Figure 2 through Figure 4).
8. Plug the PowerPass into the rear panel of the UPS.
9. Secure the PowerPass with the two mounting screws and
retaining washers. Do not overtighten.
4
Powerware® 9125 PowerPass® User's Guide 164201324 A Uncontrolled Copy
Page 5
Installation
10. Reconnect the power cord(s) of the protected equipment to the power output receptacles located on the PowerPass (see page 7 for more information on load segments).
NOTE The receptacle marked LASER is provided for laser printers. The power from this outlet does NOT come from the UPS output, but from utility power. Therefore, in the event of a power outage, this outlet loses power.
11. Plug the UPS power cord into the UPS-input connector (or input connector for 240V models) on the PowerPass.
12. Plug the power cord into a power outlet. All UPS front panel indicators flash briefly and the UPS conducts a selftest.
When the self-test is complete, the
indicator flashes,
indicating the UPS is in Standby mode.
13. Start the UPS by pressing the On
button. The  indicator stops flashing and the bar graph indicators display the percentage of load being applied to the UPS.
The UPS is now in Normal mode and supplying power to your equipment.
Bypass Switches
Power Cord
Powerware® 9125 PowerPass® User's Guide 164201324 A Uncontrolled Copy
Mounting Screw
UPS-Input Connector
Figure 2. PowerPass for 7001500 VA, 120V UPS
Power Output Receptacles
Load Segment 1
Load Segment 2
Laser Printer Receptacle
Mounting Screw
5
Page 6
Installation
Power Cord
Circuit Breakers
Circuit Breaker Access
UPS-Input Connector
Figure 3. PowerPass for 2000 VA, 120V UPS
Power Output ReceptaclesBypass Switches Mounting Screw
Load Segment 2
Load Segment 1
Mounting Screw
Power Output ReceptaclesBypass Switches Laser Printer ReceptacleMounting Screw
Load Segment 2
Load Segment 1
Circuit Breaker
Access
Input Connector
Mounting Screw
Figure 4. PowerPass for 7002000 VA, 240V UPS
6
Powerware® 9125 PowerPass® User's Guide 164201324 A Uncontrolled Copy
Page 7
C H A P T E R 2
OPERATION
The PowerPass allows for the removal of the UPS while providing power to your protected equipment. This Maintenance Bypass feature is useful when replacing the UPS for maintenance or upgrades.
Load Segments
Load segments are sets of receptacles that can be controlled by power management software, providing an orderly shutdown and startup of your equipment. For example, during a power outage, you can keep key pieces of equipment running while you turn off other equipment. This feature allows you to save battery power. See your power management software manual for details.
NOTE If the power management software is not used, the individual load segments cannot be controlled.
NOTE When the PowerPass is in Bypass mode, all load segments are switched to utility power and cannot be controlled until the PowerPass is switched back to the UPS.
Each PowerPass has two load segments as shown in Figure 2 on page 5 through Figure 4 on page 6.
Using Maintenance Bypass
Use the following procedure to transfer your equipment to Maintenance Bypass (AC Line operation) and remove the UPS:
1. Toggle both Bypass switches on the PowerPass to the BYPASS position (see Figure 2 on page 5 through Figure 4 on page 6). The PowerPass is now powering your equipment from utility power.
2. Press and hold the Off seconds. The UPS switches to Standby mode.
Powerware® 9125 PowerPass® User's Guide 164201324 A Uncontrolled Copy
button for approximately three
7
Page 8
Operation
3. If an optional EBM is installed, unplug the EBM cable from the battery connector on the UPS rear panel.
120V models only. Disconnect the UPS power cord from the
4.
PowerPass UPS-input connector.
5. Loosen the two PowerPass mounting screws.
6. Remove the PowerPass from the UPS, being careful not to
loosen the power cords plugged into the PowerPass.
Use the following procedure to reinstall the UPS and transfer your equipment from Maintenance Bypass (AC Line operation) to the UPS:
1. If an optional EBM is installed, reconnect the EBM cable to the battery connector on the UPS rear panel.
120V models only. Plug the UPS power cord into the PowerPass
2.
UPS-input connector.
3. Plug the PowerPass into the rear panel of the UPS.
All UPS front panel indicators flash briefly and the UPS conducts a selftest. When the self-test is complete, the indicator flashes, indicating the UPS is in Standby mode.
4. Tighten the two PowerPass mounting screws. Do not overtighten.
5. Start the UPS by pressing the On
The
6. Toggle both Bypass switches on the PowerPass to the UPS position.
The bar graph indicators display the percentage of load being applied to the UPS. The UPS is now in Normal mode and supplying power to your equipment.
indicator stops flashing.
button.
8
Powerware® 9125 PowerPass® User's Guide 164201324 A Uncontrolled Copy
Page 9
C H A P T E R 3
SPECIFICATIONS
Table 1. Mechanical
PowerPass Models 05146519-001 for 7001500 VA, 120V UPS
05146519-002 for 7002000 VA, 240V UPS 05146520-001 for 2000 VA, 120V UPS
Dimensions (WxDxH) 11.0" x 4.5" x 3.5" (27.9 x 11.4 x 8.9 cm)
Weight 2.5 lb (1.1 kg)
Table 2. Technical
120V Models 240V Models
Surge Supression 180V MOVs across input L and N;
100 joule, 6500A peak current rating
320V MOVs each across L to G and N to G;
160 joule; 6500A peak current rating
Electrostatic Discharge Withstands 25 kV
Input Connection to PowerPass
Input Connection to UPS 7001500 VA: 5-15R mates with
Output Receptacles 7001500 VA: (6) 5-15R; (1) 5-15R for
UPS AC Output to PowerPass (Plug)
Operating Temperature 0°C to 40°C (32°F to 104°F)
Storage Temperature -20°C to 60°C (-4°F to 140°F)
Relative Humidity 596% noncondensing
7001500 VA: 6-ft, 5-15P power cord
2000 VA: 6-ft, 5-20P power cord
UPS 5-15P power cord
2000 VA: 5-20R mates with
UPS 5-20P power cord
laser printer (unprotected)
2000 VA: (6) 5-15R
(2) 5-15P connect to UPS AC output (2) IEC 320-C13 plugs connect to
Optimal battery performance: 25°C (77°F)
320V MOVs across input L1 and L2;
160 joule, 6500A peak current rating
IEC 320-C14 input connector
IEC-320 plug mates with
UPS IEC-320 receptacle
laser printer (unprotected)
(6) IEC 320-C13;
(1) IEC 320-C13 for
UPS AC output
Powerware® 9125 PowerPass® User's Guide 164201324 A Uncontrolled Copy
9
Page 10
Specifications
10
Powerware® 9125 PowerPass® User's Guide 164201324 A Uncontrolled Copy
Page 11
Page 12
*164201324A*
164201324 A
12
Powerware® 9125 PowerPass® User's Guide 164201324 A Uncontrolled Copy