3RG4011-0AG33-PF |
NO / Schließer |
Cable / Kabel (eingegossen) |
|
|
|
3RG4011-7AG33-PF |
NO / Schließer |
Connector / Stecker M8 |
|
|
|
3RG4011-0AF33-PF |
NC / Öffner |
Cable / Kabel (eingegossen) |
|
|
|
3RG4011-7AF33-PF |
NC / Öffner |
Connector / Stecker M8 |
|
Size / Bauform |
|
cylindrical M8 / zylindrisch M8 |
|
||||
|
|
|
|
|
|
||
Mounting / Einbau |
|
embeddable / bündig |
|
||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Operating distance / Schaltabstand |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Rated operating distance / |
sn |
1,5 mm |
|
|
|
|
|
Bemessungsschaltabstand |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Effective operating distance / |
sr |
1,35 ... 1,65 mm |
|
|
|
|
|
Realschaltabstand |
|
|
|
|
|
|
|
Assured operating distance / |
sa |
1,20 mm |
|
|
|
|
|
Gesicherter Schaltabstand |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Standard target mild steel / |
|
8 x 8 x 1 mm |
|
|
|
|
|
Meßplatte Stahlfahne St 37 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Repeat accuracy / Reproduzierbarkeit |
R |
0,05 mm |
|
|
|
|
|
|
|
|
|
|
|
|
|
Hysteresis / Hysterese |
H |
0,01 ... 0,33 mm |
|
|
|
|
|
|
|
|
|
|
|
||
Reduction factors / Reduktionsfaktoren |
|
Al: |
0,38 |
Cu: |
0,20 |
||
|
|
|
|
|
|
||
|
|
Ms: |
0,45 |
Stainl. steel / Edelst.: |
0,80 |
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Power supply voltage / |
|
|
|
|
|
|
|
Versorgungsspannung |
|
|
|
|
|
|
|
Rated operational voltage / |
Ue |
24 V DC |
|
|
|
|
|
Bemessungsbetriebsspannung |
|
|
|
|
|
|
|
Operating voltage range / |
UB |
15... 34V DC |
|
|
|
|
|
Betriebsspannungsbereich |
|
|
|
|
|
|
|
|
|
|
|
||||
No-load supply current / Leerlaufstrom |
lo |
17 mA (24 V DC); 30 mA (34 V DC) |
|
||||
|
|
|
|
|
|
|
|
max. ripple content / zul. Restwelligkeit |
|
10% |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Output / Ausgang |
|
|
|
|
|
|
|
|
|
|
|
||||
Output / Ausgangsart |
|
3 wire DC pnp / 3 Leiter DC pnp |
|
||||
|
|
|
|||||
Rated operational current / |
le |
200 mA (to / bis 50 Cel); 150 mA (to / bis 85 Cel) |
|||||
Bemessungbetriebsstrom |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Output voltage drop / Spannungsfall max. |
Ud |
2,5 V |
|
|
|
|
|
|
|
|
|
|
|
|
|
Off-state current / Reststrom |
|
0,01 mA |
|
|
|
|
|
|
|
|
|
|
|
|
|
Short-circuit strength / Kurzschlußfestigkeit |
|
built-in / eingebaut |
|
|
|
|
|
|
|
|
|
|
|
|
|
Overload withstand capability / |
|
built-in / eingebaut |
|
|
|
|
|
Überlastfestigkeit |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Times / Zeiten |
|
|
|
|
|
|
|
Frequency of operating cycles / |
f |
1500 Hz |
|
|
|
|
|
Schaltfrequenz |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Time delay before availability / |
|
|
|
|
|
|
|
Bereitschaftsverzug |
tv |
40 ms |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Temperatures / Temperaturen |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Rated temperature / |
Tu |
25 Cel |
|
|
|
|
|
Bemessungstemperatur |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Ambient temperature range / |
Ta |
-25...+85 Cel |
|
|
|
|
|
zul. Umgebungstemperatur |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Storage temperature range / |
Ts |
-40...+85 Cel |
|
|
|
|
|
zul. Lagertemperatur |
|
|
|
|
|
|
|
Subject to modifications without notice |
|
|
Copyright Pepperl+Fuchs |
|
|
|
|
|
|
|
|
1