Sensor Controller
S3D2
Offers High-speed Input Response of 0.1 ms and Equipped with Built-in Timer
■High-speed response of 0.1 ms.
■Ideal as a two-input Controller.
■Lineup includes the S3D2-BK with flip-flop functions convenient for level control, the S3D2-AKD/CKD/CCD with 24-V power supply, and the S3D2-DK/EK with one input/ output OFF-delay (two circuits) useful for load control and lamp display
■Power source for the Sensor can be supplied up to 200 mA.
■Ultra-slim body with 30-mm width.
■Multi-function model equipped with timer functions also available.
Be sure to read Safety Precautions on page 7.
Ordering Information
Power supply voltage |
Output |
Timer function |
Features |
Model |
|
|
|
No |
Single-function with one input/output (two circuits) |
S3D2-DK |
|
|
|
|
|
||
|
|
Yes |
S3D2-EK |
||
|
|
|
|||
|
|
|
|
|
|
100 to 240 VAC |
Relay |
No |
Single-function with two inputs/one output (AND/OR operation) |
S3D2-AK * |
|
|
|
|
|
||
|
No |
Flip-flop function with two inputs/one output |
S3D2-BK |
||
|
|
||||
|
|
|
|
|
|
|
|
Yes |
Multi-function with two inputs/one output |
S3D2-CK * |
|
|
|
|
|
||
|
Transistor |
Yes |
S3D2-CC * |
||
|
|
||||
|
|
|
|
|
|
|
Relay |
No |
Single-function with two inputs/one output |
S3D2-AKD |
|
|
|
|
|
||
24 VDC |
Yes |
Multi-function with two inputs/one output |
S3D2-CKD |
||
|
|||||
|
|
|
|
||
|
Transistor |
Yes |
S3D2-CCD |
||
|
|
||||
|
|
|
|
|
* Models compatible with Sensors for PNP connections are also available. These model numbers have the suffix B (e.g., S3D2-AKB)
Differences from NPN Models
|
ON |
8 to 12 V (2 mA max.) |
Input signals |
OFF |
0 to 4 V (5 mA min.) |
|
Maximum applied voltage |
12 V |
|
|
|
Note: S3D2-AK(B)/-CK(B)/-CC(B) models with UL certification are available.
These model numbers have the suffix US (e.g., S3D2-AK-US).
http://www.ia.omron.com/ |
(c)Copyright OMRON Corporation 2007 All Rights Reserved. |
1 |
|
||
|
|
|
S3D2
Ratings and Specifications
|
|
Type |
Two inputs/ |
|
|
|
|
Two inputs/one output |
|
|
|||||
|
|
two outputs |
|
|
|
|
|
|
|||||||
|
|
|
|
|
|
|
|
|
|
|
|
||||
|
|
|
Single- |
|
Single-func- |
Single-func- |
|
Flip-flop |
|
|
Single-func- |
|
|
|
|
|
|
|
|
tion (with |
tion (AND/OR |
|
Multi-function |
tion (AND/OR |
|
Multi-function (24 VDC) |
|||||
|
|
|
function |
|
|
function |
|
||||||||
|
|
|
|
OFF-delay) |
operation) |
|
|
|
operation) |
|
|
|
|||
|
|
|
|
|
|
|
|
|
|
|
|
||||
Item |
Model |
S3D2-DK |
|
S3D2-EK |
S3D2-AK |
|
S3D2-BK |
S3D2-CK |
S3D2-CC |
S3D2-AKD |
|
S3D2-CKD |
S3D2-CCD |
||
Rated supply |
100 to 240 VAC ± 10% 50/60Hz |
|
|
|
|
24 VDC ± 10% |
|
|
|||||||
voltage |
|
|
|
|
|
|
|
||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|||
Power consumption |
15 VA max. |
|
|
|
|
|
|
2.5 VA max. (excluding Sensor power supply) |
|||||||
Power supply for |
12 VDC ± 10% (includes all variations) , 200 mA max. (with short-circuit protection) |
24 VDC (supplied from power supply) |
|||||||||||||
Sensor |
|
||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|||
Connected Sensor |
NPN transistor output (with sinking current of 18 mA min.) or contact output |
|
|
|
|
||||||||||
|
|
ON |
0 to 4 V (5 mA min.) |
|
|
|
|
|
|
|
|
|
|||
|
|
OFF |
8 to 12 V (2 mA max.) |
|
|
|
|
|
8 to 30 V (2 mA max.) |
|
|||||
Input |
|
Short- |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
circuit |
11 mA TYP (18 mA max.) |
|
|
|
|
|
|
|
|
|
||||
signals |
|
|
|
|
|
|
|
|
|
|
|||||
|
current |
|
|
|
|
|
|
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
|
|
Maximum |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
applied |
30 V |
|
|
|
|
|
|
|
|
|
|
||
|
|
voltage |
|
|
|
|
|
|
|
|
|
|
|
|
|
Input response time |
0.1 ms |
|
|
|
IN1 2 ms |
0.1 ms |
|
|
|
|
|
||||
|
|
|
IN2 2 ms |
|
|
|
|
|
|||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
Output minimum |
10 ms max. |
|
|
|
|
|
0.5 ms max. |
10 ms max. |
|
0.5 ms max. |
|||||
pulse width |
|
|
|
|
|
|
|||||||||
|
|
|
|
|
|
|
|
|
|
|
|
||||
|
|
|
|
|
|
|
|
|
|
NPN open |
|
|
|
NPN open |
|
|
|
|
|
|
|
|
|
|
|
collector output, |
|
|
|
collector output, |
|
|
|
|
|
|
|
|
|
|
|
30 VDC, 100 mA |
|
|
|
30 VDC, 100 mA |
|
Control output |
Relay output SPST-NO |
Relay output SPDT (shared common) |
(NO, NC) |
Relay output SPDT |
(NO, NC) |
||||||||||
× 2 |
|
|
Residual voltage |
Residual voltage |
|||||||||||
|
|
250 VAC, 3 A (cosI = 1) |
|
250 VAC, 3 A (cosI = 1) |
|||||||||||
|
|
|
250 VAC, 2A (cosI = 1) |
|
(ON)1.5 V max. |
(ON)1.5 V max. |
|||||||||
|
|
|
|
|
|
|
|
|
|
||||||
|
|
|
|
|
|
|
|
|
|
Leakage current |
|
|
|
Leakage current |
|
|
|
|
|
|
|
|
|
|
|
(OFF): 0.1 mA |
|
|
|
(OFF): 0.1 mA |
|
|
|
|
|
|
|
|
|
|
|
max. |
|
|
|
max. |
|
Output response |
10 ms max. |
|
|
|
|
|
0.5 ms max. |
10 ms max. |
|
0.5 ms max. |
|||||
time |
|
|
|
|
|
|
|
||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|||
|
|
|
|
|
OFF-delay |
|
|
|
One-shot, ON-delay, |
|
|
One-shot, ON-delay, |
|||
|
|
|
|
|
|
|
|
and OFF-delay |
|
|
and OFF-delay |
||||
|
|
|
|
|
|
|
|
|
|
|
|||||
Timer functions * |
--- |
|
0.1 to 1 s |
|
--- |
|
|
--- |
|
|
|
||||
|
|
0.1 to 1 s |
0.01 to 0.1 s |
|
0.1 to 1 s |
0.01 to 0.1 s |
|||||||||
|
|
|
|
|
1 to 10 s |
|
|
|
|
|
|||||
|
|
|
|
|
|
|
|
1 to 10 s |
0.1 to 1 s |
|
|
1 to 10 s |
0.1 to 1 s |
||
|
|
|
|
|
selectable |
|
|
|
|
|
|||||
|
|
|
|
|
|
|
|
selectable |
selectable |
|
|
selectable |
selectable |
||
|
|
|
|
|
|
|
|
|
|
|
|||||
|
|
|
|
|
|
(Output |
|
x Signal input |
x Signal input reverse |
x Signal input |
|
x Signal input reverse |
|||
|
|
|
|
|
|
reversible) |
|
reverse |
|
||||||
Other functions |
Signal input reverse |
AND/OR |
|
reverse |
x Sync mode selection |
x AND/OR |
|
x Sync mode selection |
|||||||
operating |
|
x Flip-flop |
x AND/OR operating mode |
operating |
|
x AND/OR operating mode |
|||||||||
|
|
|
|
|
|
|
|
||||||||
|
|
|
|
|
|
mode |
|
function |
selection |
|
mode |
|
selection |
|
|
|
|
|
|
|
|
selection |
|
|
|
|
selection |
|
|
|
|
Maximum allowable |
|
|
|
|
|
|
|
|
|
|
|
|
|||
time of momentary |
20 ms max. |
|
|
|
|
|
|
|
|
|
|
||||
power failure |
|
|
|
|
|
|
|
|
|
|
|
|
|||
Ambient |
|
Operating : 10 to +55qC, Storage: 25 to +65qC (with no icing) |
|
|
|
|
|
||||||||
temperature range |
|
|
|
|
|
||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
||||
Ambient humidity |
Operating/storage: 35% to 85% |
|
|
|
|
|
|
|
|
||||||
range |
|
|
|
|
|
|
|
|
|
||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|||
|
|
|
|
|
|
|
|
|
|
|
Operating power supply: 480 V (p-p) min.; pulse |
||||
Noise immunity |
Operating power supply: 1,500 V (p-p) min.; pulse width: 100 ns, 1 Ps; rise time: 1 ns |
width: 100 ns, 1 Ps; rise time: 1 ns |
|||||||||||||
Input/output: |
|
|
|||||||||||||
Input/output: 1,200 V (p-p) min.; pulse width: 100 ns, 1 Ps; rise time: 1 ns |
|
|
|||||||||||||
|
|
|
1,000 V (p-p) min.; pulse width: 100 ns, 1 Ps; |
||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|||||
|
|
|
|
|
|
|
|
|
|
|
rise time: 1 ns |
|
|
||
Dielectric strength |
1,500 VAC min.(between power supply terminals and I/O terminals, and between non-cur- |
1,500 VAC min. |
|
||||||||||||
(between power supply terminals and non-cur- |
|||||||||||||||
rent-carrying parts) |
|
|
|
|
|
||||||||||
|
|
|
|
|
|
|
|
rent-carrying parts) |
|
||||||
|
|
|
|
|
|
|
|
|
|
|
|
||||
Vibration |
|
10 to 55 Hz, double-amplitude of 0.75 mm for 2 hours each of the X, Y, and Z directions |
|
|
|
|
|||||||||
(destruction) |
|
|
|
|
|||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
||||
Weight |
|
Approx. 140 g |
|
|
|
|
|
|
|
|
|
||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
* The timer will not operate in response to input signals received within 50 ms after the Controller power is turned ON.
http://www.ia.omron.com/ |
(c)Copyright OMRON Corporation 2007 All Rights Reserved. |
2 |
|
||
|
|
|
S3D2
Output Circuit Diagrams |
|
||
Note: Numbers in parentheses indicate terminal pin numbers. |
|
||
Relay Output Model |
|
Open Collector Model |
|
S3D2-AK/-AKD/ |
S3D2-DK/-EK |
S3D2-CC/-CCD |
|
-CK/-CKD/-BK |
|
|
|
|
|
|
NC (6) |
|
|
NO |
OUT2 (6) |
NC |
|
NC (6) |
|
|
250 VAC 3 A |
30 VDC 100 mA |
|
NO |
Relay contact |
NO (5) |
|
|
NO |
||
|
|
NO (5) |
OUT1 (5) |
|
|
|
COM (4) |
|
|
COM (4) |
COM (4) |
Input Circuit Diagrams
Note: Numbers in parentheses indicate terminal pin numbers.
Voltage output sensor |
S3D2 |
+12 V * |
|
+12 V * |
|
R |
10 to |
(7), (10) |
820 Ω |
|
|||
OUT |
18 mA |
IN |
S3D2 |
Sensor |
|
(8), (11) |
main |
main |
|
||
|
circuit |
||
circuit |
|
0 V |
|
0 V |
|
|
|
|
|
(9), (12) |
|
Note: Terminals (7) and (10), and (9) and (12) are connected internally.
* S3D2-AKD/-CKD/-CCD: +24 V
Open collector output sensor |
|
|
S3D2 |
+12 V * |
|
+12 V * |
|
|
10 to |
|
820 Ω |
OUT |
18 mA |
IN |
S3D2 |
Sensor |
|
|
main |
main |
|
|
|
|
|
circuit |
|
circuit |
|
0 V |
|
0 V |
|
|
|
|
* S3D2-AKD/-CKD/-CCD: +24 V |
Connections
Connection Methods |
|
|
|
|
|
|
|
|
|
|
|
|
||
S3D2-AK/-AKD |
S3D2-CK/-CKD |
S3D2-CC/-CCD |
S3D2-BK |
S3D2-DK/-EK |
||||||||||
INPUT |
|
INPUT |
|
INPUT |
|
INPUT |
|
INPUT |
|
|||||
7 |
8 |
9 |
7 |
8 |
9 |
7 |
8 |
9 |
7 |
8 |
9 |
7 |
8 |
9 |
+12 V |
IN 1 |
0 V |
+12 V |
IN 1 |
0 V |
+12 V |
IN 1 |
0 V |
+12 V |
IN 1 |
0 V |
+12 V |
IN 1 |
0 V |
10 |
11 |
12 |
10 |
11 |
12 |
10 |
11 |
12 |
10 |
11 |
12 |
10 |
11 |
12 |
+12 V |
IN 2 |
0 V |
+12 V |
IN 2 |
0 V |
+12 V |
IN 2 |
0 V |
+12 V |
IN 2 |
0 V |
+12 V |
IN 2 |
0 V |
POWER IN 1 IN 2 |
OUT |
POWER IN 1 IN 2 |
OUT |
POWER IN 1 IN 2 |
OUT |
POWER IN 1 IN 2 |
OUT |
POWER |
OUT1 OUT2 |
|||||
S3D2-AK |
|
S3D2-CK |
|
S3D2-CC |
|
S3D2-BK |
|
S3D2-EK |
|
|||||
SENSOR CONTROLLER |
|
SENSOR CONTROLLER |
|
SENSOR CONTROLLER |
|
SENSOR CONTROLLER |
|
SENSOR CONTROLLER |
|
|||||
SOURCE:100 to 240VAC 50/60Hz |
SOURCE:100 to 240VAC 50/60Hz |
SOURCE:100 to 240VAC 50/60Hz |
SOURCE:100 to 240VAC 50/60Hz |
SOURCE:100 to 240VAC 50/60Hz |
||||||||||
OUTPUT:3A 250VAC |
|
OUTPUT:3A 250VAC |
|
OUTPUT:100mA 30VDC |
|
OUTPUT:3A 250VAC |
|
OUTPUT:2A 250VAC |
|
|||||
|
RESISTIVE LOAD |
|
RESISTIVE LOAD |
|
RESISTIVE LOAD |
|
RESISTIVE LOAD |
|
RESISTIVE LOAD |
|||||
DC POWER SUPPLY |
|
DC POWER SUPPLY |
|
DC POWER SUPPLY |
|
DC POWER SUPPLY |
|
DC POWER SUPPLY |
|
|||||
|
12VDC 200mA |
|
|
12VDC 200mA |
|
|
12VDC 200mA |
|
|
12VDC 200mA |
|
|
12VDC 200mA |
|
OUTPUT |
|
OUTPUT |
|
OUTPUT |
|
OUTPUT |
|
OUTPUT |
|
|||||
4 |
5 |
6 |
4 |
5 |
6 |
4 |
5 |
6 |
4 |
5 |
6 |
4 |
5 |
6 |
COM |
NO |
NC |
COM |
NO |
NC |
COM |
NO |
NC |
COM |
NO |
NC |
COM |
OUT1 |
OUT2 |
1 |
2 |
3 |
1 |
2 |
3 |
1 |
2 |
3 |
1 |
2 |
3 |
1 |
2 |
3 |
100to240VAC |
FG |
100to240VAC |
FG |
100to240VAC |
FG |
100to240VAC |
FG |
100to240VAC |
FG |
|||||
OMRON Corporation MADE IN JAPAN |
OMRON Corporation MADE IN JAPAN |
OMRON Corporation MADE IN JAPAN |
OMRON Corporation MADE IN JAPAN |
OMRON Corporation MADE IN JAPAN |
(1), (2): Power supply terminals For S3D2-AKD/-CKD/-CCD Sensors, provide 24 VDC. The polarity of terminal (2) is positive, and terminal (1) is
negative. For other models, supply 100 to 240 VAC.
(3): FG terminal Ground with a ground resistance of 100 : max. in locations subject to excessive noise.
(4) to (6): Output terminals
(7), (10): Power supply terminals for S3D2-AKD/-CKD/-CCD Sensors (+24 V), and other models (+12 V)
(9), (12): Power supply terminals for the Sensor (0 V) (8), (11): Output terminals for the Sensor
Connect the Sensor output lines.
http://www.ia.omron.com/ |
(c)Copyright OMRON Corporation 2007 All Rights Reserved. |
3 |
|
||
|
|
|