Norgren 10-028-037, 10-028-545, 10-028-046, 10-028-047, 10-028-048 Maintenance Manual

10-028
Installation & Maintenance
Instructions
ADJUSTMENT
1. Turn on system pressure.
2. Adjust lubricator drip rate under a steady flow condition. Air flow should be at the rate the lubricator will be used. Monitor drip rate thru sight feed dome (1).
3. Determine the air flow (scfm) thru the lubricator. Refer to the shaded area in the Drip Rate Chart and determine the drip rate corresponding to the air flow. Select an initial drip rate toward the rich side of the shaded area for inlet pressure less than 6,2 bar (90 psig), or toward the lean side for inlet pressure more than 6,2 bar (90 psig). Turn adjustment counterclockwise to increase and clockwise to decrease the drip rate. Total travel of adjustment (1) is 320°.
4. Monitor the device being lubricated for a few days following initial adjustment. Adjust the drip rate if the oil delivery at the device appears either excessive or low.
DISASSEMBLY
1. Shut off inlet pressure. Reduce pressure in inlet and outlet lines to zero. Loosen fill plug. Lubricator may be disassembled without removal from the air line.
2. Remove reservoir:
1-Quart Reservoir: Turn reservoir (40) counterclockwise and remove from adapter (28). All Other Reservoirs: Remove screws (6, 7) and separate reservoir from body.
3. Disassemble in general accordance with the item numbers on exploded view. Unscrew siphon tube assembly (10), taking care not to lose check ball (11). Do not remove siphon tube from fitting. Charge valve (9) is not used with 2 and 5-gallon reservoirs. Do not remove drain (30, 31, 32) unless replacement is necessary. Remove and replace only if it malfunctions.
4. Disassembly of the reservoirs is not normally required.
CLEANING
1. Clean plastic reservoir and sight feed dome with warm water only. Clean other parts using warm water and soap.
2. Dry parts. Blow out internal passages in body with clean, dry compressed air.
3. Inspect parts. Replace parts found to be damaged. If plastic reservoir shows signs of cracking or cloudiness, replace with a metal reservoir.
TECHNICAL DATA
Fluid: Compressed air Maximum pressure:
Transparent bowl: 10 bar (150 psig) Metal bowl: 17 bar (250 psig)
Operating temperature*:
Transparent bowl: -20° to 50°C (0° to 125°F) Metal bowl: -20° to 80°C (0° to 175°F)
* Air supply must be dry enough to avoid ice formation at
temperatures below +2°C (+35°F).
Start point (minimum flow required for lubricator
operation) at 6,3 bar (90 psig) inlet pressure: 49 dm
3
/s
(103 scfm)
Typical flow at 6,3 bar (90 psig) inlet pressure and 0,35 bar
(5 psig) pressure drop: 268 dm
3
/s (568 scfm)
Reservoir sizes:
Model Nominal Capacity Working Capacity 10-028-037 0,25 liter (1/2 pt) 0,15 liter (5 fluid oz) 10-028-545 1 liter (1 qt) 0,56 liter (19 fluid oz) 10-028-046 2 liter (2 qt) 1,33 liter (45 fluid oz) 10-028-047 8 liter (2 gal) 3,34 liter (113 fluid oz) 10-028-048 20 liter (5 gal) 9,34 liter (316 fluid oz)
Materials:
Body: Aluminum Reservoir:
Transparent 0,25 liter (1/2 pint): Polycarbonate Metal:
1 liter (1 quart): Aluminum 2, 8 and 20 liter (2 quart, 2 and 5 gallon): Steel
(2 and 5 gallon reservoirs are rated to ASME
Pressure Vessel Code, Section VIII) Metal bowl liquid level indicator lens: Pyrex Sight-feed dome:
Standard: Polycarbonate Optional: Pyrex and aluminum
Elastomers: Neoprene and nitrile
REPLACEMENT ITEMS
Liquid level lens kit
1-quart reservoir (33, 35, 36, 37, 38, 39) .......2273-22 *
2-quart reservoir (42, 43, 44, 45, 51) ................2273-04
2 and 5 gallon reservoirs (54, 55, 56, 57)..........2274-01
Pyrex sight feed dome.............................................5605-50
Quick fill cap..............................................18-011-008
Bowl guard for 1/2-pint reservoir ..............18-012-003
Wall mounting strap
2 gallon reservoir..................................18-001-056
5 gallon reservoir..................................18-001-039
* Current 1-quart reservoir models (Model 10-028-545)
use liquid level lens kit 2273-22. Early 1-quart reservoir models (Model 10-028-045) are identical in appearance to the 2-quart reservoir and use liquid level lens kit 2272-02.
INSTALLATION
1. Shut-off air pressure. Support weight of lubricator with 2 and 5 gallon reservoirs on shelf, floor, etc. Install lubricator in air line -
vertically (reservoir down),
with air flow in direction of arrow on body,
downstream of filters and regulators,
upstream of cycling valves,
as close as possible to the device being lubricated,
NOTE
Oil-Fog lubricators are generally installed no more than 5,2m (15 feet) from the device being lubricated. The 10-028 lubricator, however, will perform satisfactorily at distances greater than 5,2m (15 feet) if installed at a location sufficiently higher than the device being lubricated, and the pipe network does not contain low spots or complex bends.
2. Connect piping to proper ports using pipe thread sealant on male threads only. Do not allow sealant to enter interior of unit.
RECOMMENDED LUBRICANTS
Use a good quality, non-detergent, light, misting type oil for compressed air tools. See Norgren publication N/AL.8.900.935.
FILL RESERVOIR
Shut off inlet air pressure and reduce pressure in reservoir to zero. Remove fill plug, add oil, and reinstall fill plug. Fill to maximum fill line on transparent reservoir. Oil level must always be visible in liquid level lens on metal reservoir. DO
NOT OVERFILL. Do not remove the fill plug on lubricators with 2 and 5-gallon reservoirs when the reservoir is pressurized, as oil will blow out the fill plug hole. The fill
plug on lubricators with smaller reservoirs may be removed and the reservoir refilled when the reservoir is pressurized.
IM-450.410.01
(7/01)
Replaces NIP-364
© Norgren 2001
Oil-Fog Tool Lubricator
DRIP RATE CHART
PORT SIZE: 1-1/2"
120
INLET PRESSURE: 4 to 8 bar (60 to 100 psig)
100
80
60
40
20
DRIP RATE - DROPS PER MINUTE
0
0 100 200 300 dm3/s
0 200 400 600 scfm
AIR FLOW
RICH
LEAN
3
4
6
7
9
8
10
29
30
32
31
41
42
53
54
1
2
5
1/2 pint (0.25 liter)
11
1 quart (1 liter) Reservoir
28
39
40
34
35
2 quart (2 liter) Reservoir
46
44 43
45
43 44
47
48
2 and 5 gallon (8 and 20 liter) Reservoir
58
56 55
57
55 56
59
60
Reservoir
35
13
12
34
33
36
37
38
36
33
52
49
50
51
62
61
63
a subsidiary of IMI plc
10-028
Installation & Maintenance
Instructions
ASSEMBLY
1. Lubricate o-rings with o-ring grease.
2 If the 1/4 turn manual drain (30, 31, 32 ) was removed,
lubricate the portion of the drain body (30) that contacts the bowl, and the hole in the manual drain body that accommodates the stem of drain valve (31) with o-ring grease. Press body (30) thru hole from inside of bowl. Place retainer o-ring (32) over body (30) and position in groove. Press drain valve (31) thru hole in body (30).
3. Assemble the liquid indicator parts (33 thru 38) to bowl. Apply a 0,9 to 1,8 kg (2 to 4 pound) clamping force to upper and lower brackets (34) to pull brackets together. Tighten screws (33) to 0,9 to 1,1 N-m (8 to 10 inch­pounds).
4. Assemble lubricator as shown on exploded view. Pay particular attention to the following:
Tighten sight feed dome (1) to 2,3 to 2,8 N-m (20 to
25 inch-pounds).
Apply increasing torque to the six reservoir adapter
screws (6, 7) in a crisscross pattern. Apply final torque of 2,26 to 3,39 N-m (20 to 30 inch-pounds).
Turn bowl (40) into adapter (28) until arrowhead on
bowl is aligned with or to the right of slot in adapter.
WARNING
These products are intended for use in industrial compressed air systems only. Do not use these products where pressures and temperatures can exceed those listed under Technical Data.
The polycarbonate sight feed dome and reservoir can be damaged and possibly burst if exposed to such substances as certain solvents, strong alkalies, compressor oils containing ester-based additives or synthetic oils. Fumes of these substances in contact with the polycarbonate sight feed dome and reservoir, externally or internally, can also result in damage. Clean with warm water only
Use pyrex sight feed dome and metal reservoir in applications where the lubricator might be exposed to substances that are incompatible with polycarbonate.
In lubrication applications some oil mist may escape from the point of use to the surrounding atmosphere. Users are referred to safety and health standards for limiting oil mist contamination and utilization of protecting equipment
Before using these products with fluids other than air, for nonindustrial applications, or for life-support systems consult Norgren.
IM-450.410.02
(7/01)
Replaces NIP-364
© Norgren 2001
Oil-Fog Tool Lubricator
3
4
6
7
9
8
10
29
30
32
31
1
2
5
1/2 pint (0.25 liter)
11
1 quart (1 liter) Reservoir
28
39
35
40
Reservoir
13
12
34
33
36
37
38
36
33
34
35
2 quart (2 liter) Reservoir
41
42
53
54
46
44 43
45
43 44
47
48
2 and 5 gallon (8 and 20 liter) Reservoir
58
56 55
57
55 56
59
60
52
49
51
50
62
61
63
a subsidiary of IMI plc
Loading...