NIBCO F-617-0, F-617-13, F-617-ON, F-637-31, F-637-33 Installation Manual

...
0 (0)
NIBCO F-617-0, F-617-13, F-617-ON, F-637-31, F-637-33 Installation Manual

INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS

Review Date: 01/18/2012

Original Date: NA

Installation and Maintenance Guidelines for NIBCO® Cast Iron, Alloy Iron and Ductile Iron Gate Valves

2” to 24” Class 125, 150, 175 and 250

Figure Numbers

F-617-0

F-617-13

F-617-ON

F-637-31

F-637-33

F-667-0

F-619

F-619-N

F-639-31

F-639-33

F-607-OTS

F-609

CAUTION: Only qualified personnel should undertake the procedures outlined in this document. NIBCO INC., its agents, representatives and employees assumes no liability for the use of these procedures. These procedures are offered as suggestions only.

NIBCO Technical Services • Phone: 1.888.446.4224 • Fax: 1.888.336.4224

1

1.0GENERAL INFORMATION

1.1SCOPE

These instructions are furnished for use in the installation, operation and maintenance of NIBCO 2” to 24” Class 125, 150, 175 and 250 bolted bonnet solid wedge gate valves having handwheel operation.

1.2GENERAL DATA

A.MANUFACTURER

NIBCO INC.

1516 Middlebury Street Elkhart, IN 46516 Phone: (574) 295-3000

B.FIGURE NUMBERS AND DESCRIPTIONS

Cast Iron:

F-617-0 Class 125, flanged end, rising stem, I.B.B.M., O.S.&Y. F-617-ON Class 125, flanged end, rising stem, all iron, O.S.&Y. F-619-0 Class 125, flanged end, non-rising stem, I.B.B.M.

F-619-N Class 125, flanged end, non-rising stem, all iron F-667-0 Class 250, flanged end, rising stem, I.B.B.M., O.S.&Y.

F-669-0 Class 250, flanged end, non-rising stem, I.B.B.M., O.S.&Y. F-607-OTS WWP 175, flanged end, rising stem, I.B.B.M., O.S.&Y. F-609 WWP 175, flanged end, non-rising stem, I.B.B.M.

Alloy Iron:

F-617-13 Class 125, flanged end, rising stem, 3% nickel, stainless trim, O.S.&Y.

Ductile Iron:

F-637-31 Class 150, flanged end, rising stem, D.I.B.B.M., O.S.&Y. F-637-33 Class 150, flanged end, rising stem, stainless trim, O.S.&Y. F-639-31 Class 150, flanged end, non-rising stem, D.I.B.B.M. F-639-33 Class 150, flanged end, non-rising stem, stainless trim

ANSI B16.5 150 Class flanges will match up with ANSI B16.1 125 Class iron flanges

ANSI B16.5 300 Class flanges will match up with ANSI B16.1 250 Class iron flanges

C.IDENTIFICATION PLATES

An aluminum identification plate is attached beneath the handwheel nut. This identification plate gives the figure number of the valve, some general information about the trim and location of NIBCO’s corporate offices.

NIBCO Technical Services • Phone: 1.888.446.4224 • Fax: 1.888.336.4224

2

When more detailed information is required, the NIBCO catalog should be referred to using the valve figure number as the guide.

D.SERVICE

When installing valves for service in corrosive media, the NIBCO Chemical Resistance Guide may be consulted for specific data or contact can be made with NIBCO Technical Services. It is, however, the obligation of the user to make the ultimate decision of fitness for use.

E.PRESSURE TEMPERATURE RATINGS

Pressure and temperature ratings may be found in the Engineering section of the latest printing of NIBCO catalog for the specific product needed. This information is taken from applicable ANSI Standards.

F.CODES & REGULATIONS

A valve specified for use in compliance with the ASME Boiler and Pressure Vessel Code, the ANSI Pressure Piping Code, government or other regulations, is subject to any limitation of that code or regulation and to other related applicable ANSI Standards.

G.PRODUCTION TEST PROCEDURES

Valves are pneumatically shell and seat tested at a pressure of 80 psi in accordance with Federal Specifications and MSS SP-70 Manufacturers Standardization Society requirements.

I.F-637 and F-639 Ductile valves – Have a Hydrostatic shell test of

440 PSI.

II.F-637 and F-639 Ductile valves – Pneumatic seat test each seat of 80 PSI. Allowable leakage per MSS SP-70.

F-637 – Hydrostatic seat test equal to maximum service pressure for which the valve is rated. Allowable leakage per MSS SP-70.

III.All other valves are tested in accordance with MSS SP-70.

H.PRINCIPAL DIMENSIONS

Principal dimensions of the valve are specified in the appropriate catalog 5-100.

1.3DETAILED DESCRIPTION

The gate valves listed above and covered in these guidelines are ductile iron, cast iron, alloy iron, bolted bonnet, outside screw and yoke - rising stem and inside screw - non rising stem valve types. The valve is operated with the handwheel. They are used to start or stop the flow of fluids in piping system. Clockwise rotation of the handwheel closes the valve. These valves should be used in the full on or full off position only.

NIBCO Technical Services • Phone: 1.888.446.4224 • Fax: 1.888.336.4224