Installation for 4-1/2 in. (114 mm) dial Temperature MURPHYGAGE® and SWICHGAGE®

Model Series: SPLG, SPLC, SPLBP, 45TE and 45TEBP Options: -OS and -ES

SPL-92106N Revised 04-04 Section 10

(00-02-0167)

Please read the following instructions before installing. A visual inspection is recommended before mounting. General Information and these installation instructions are intended for all 4-1/2 in. (114 mm) dial temperature models.

GENERAL INFORMATION

WARNING

BEFORE BEGINNING INSTALLATION OF THIS MURPHY PRODUCT

Disconnect all electrical power to the machine.

Make sure the machine cannot operate during installation.

Follow all safety warnings of the machine manufacturer.

Read and follow all installation instructions.

SPLC and SPLFC SWICHGAGE® instruments have high and low limit contacts to monitor, alarm or shutdown. The SPLC has a flanged case. SPLFC has a flush mount case intended for installation within a panel. A method to override the low limit contact for startup is provided on most models (see Operation Test Instructions on page 3).

45TE and 45TEF Series are versions of the SPL Series with 2-snap acting SPDT switches instead of the pointer type contacts. The 45TE Series does not include low contact lockout. SPLBP and 45TEBP models are designed to start and stop electric motor driven equipment. The pilot duty contacts are connected to a latching control relay for automatic ON/OFF control, either directly or through a motor starter.

Options -OS and -ES

The -OS (oil sealed case) and the -ES (environment sealed case) options for corrosive environment feature flush mount case design to be installed within a panel.

Precautions

Do NOT exceed rated temperature range.

Use shock mounts as necessary to protect from vibration.

Cutting or sharp bending the capillary will cause permanent damage to the SWICHGAGE® and will void the warranty.

Excess capillary should be carefully coiled and secured away from damage.

Do not route capillary along exhaust manifold.

Avoid routing capillary at level higher than gage mounting.

*

®

**

Specifications

Dial: White on black, dual scale, °F and °C standard, 4-1/2 in. (114 mm) diameter.

Case: Die cast aluminum, surface or panel mount.

Capillary: PVC armored copper tube, 5 ft. (1.5 m) long standard. Sensing Bulb: Copper bulb std.: 1/2 in. (13 mm) OD;

Length 7 in. (178 mm). Pressure rating: 600 psi (4.1 MPa) [41 bar]. Connection: 1/2 NPTM compression fitting.

NOTE: Use of thermowell is highly recommended.

Switch Reset Deadband: Approximately 10% FS.

Snap-Acting Switches: See wiring information (page 4).

Dry Relay Contact (“BP” Models): 10 A @ 28 VDC or 10 A @ 120 VAC.

Wire Connections (Surface Mount): 1/2 NPTF conduit/terminal block. Wire Connections (Panel Mount): Wire leads, 18 AWG

(1.0 mm2) x 9 in. (229 mm) long.

Wire Connections (-ES, -OS, -CC): 1/2 NPTM conduit and wire leads, 24 AWG (0.22 mm2) x 33 in. (838 mm) long.

Overrange: Do not exceed 10% FS above full range.

Item Weight: 8 lbs (3.6 kg) approx. Explosion-proof models: 22 lb. (10 kg) approx.

Item Dimensions: 16 x 11 x 5-1/2 in. (406 x 279 x 140 mm) approximately. Explosion-proof: 12 x 12 x 9 in. (305 x 305 x 229 mm) approximately.

Accuracy

Temperature Range

Lower 1/4

Middle 1/2

Upper 1/4

 

 

 

 

15 to 250°F

± 8°F

± 2°F

± 2°F

(9 to 121°C)

(± 4°C)

(± 1°C)

(± 1°C)

130 to 350°F

± 8°F

± 2°F

± 3°F

(54 to 177°C)

(± 4°C)

(± 1°C)

(± 1.5°C)

 

 

 

 

260 to 450°F

± 8°F

± 2°F

± 3°F

(127 to 232°C)

(± 4°C)

(± 1°C)

(± 1.5°C)

 

 

 

 

*Selected configurations are CSA approved. Consult factory for details.

**Products covered by this literature comply with EMC Council directive 89/336/EEC regarding electromagnetic compatibility as noted. Does not cover “BP” models.

SPL-92106N page 1 of 4

Murphy SPLBP, 45TE, SPLG, 45TEBP, SPLC User Manual

CASE MOUNTING

Wall Mount

Flanged case design intended for wall mount. Shown with shock mounts (optional).

 

8-7/16 in.

 

 

(214 mm)

 

 

7-7/8 in.

3-3/8 in.

 

(86 mm)

 

(200 mm)

 

 

4-1/32in.

3-15/16 in.

1/2 in.

(100 mm)

(13 mm)

(102 mm)

 

conduit

 

 

9/32 in. (7 mm) dia. 3 holes

DETAIL

shock mount

gage

panel

1/4-20 nut & lockwasher (2 each required)

Flush Mount

A round case design to be mounted within a panel from 1/32 in. (1 mm) to 1/8 in. (3 mm) thick.

5-7/16 in.

(138 mm)

120

120

Mounting Hole 4-3/4 in. (121 mm) diameter

120

panel

1/4 in. (6 mm) dia. holes (3 places.) on 5-13/64 in. (132 mm) B.C.,120 apart, clocking as shown

2-57/64 in.

(73 mm)

Optional 1/2 in. (13 mm) conduit

Options -OS, -ES (flush mount case)

5-7/16 in.

 

 

 

 

 

 

 

2-57/64 in.

(138 mm)

 

 

 

 

 

 

 

(73 mm)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6-3/4 in.

(171 mm)

1/2 in. (13 mm) conduit

Optional

Back

Connection

2-23/32 in.

(69 mm)

Explosion-proof Case Mount

Explosion-proof case can be mounted from face or rear.

8 in.

 

 

 

6-25/64 in.

(203 mm)

 

 

 

 

 

(162 mm)

 

 

 

 

 

 

 

1/2 in.NPT optional rear or side

conduit

8 in.

(203 mm)

3/8-16 UNC-2B thread

7/8 in. (22 mm) deep, 8 plc's

Flush mount/Wall mount*

 

 

 

 

6-3/4 in.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(171 mm)

 

 

 

 

 

 

 

 

 

 

 

 

 

3-3/8 in.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

7-35/64 in.

 

 

 

 

 

 

(86 mm)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(192 mm)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

diameter

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3-3/8 in.

 

*Mounting hole

 

 

 

 

 

 

 

 

 

(86 mm)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

not required for

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Wall mount

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13/32 in.

 

 

 

 

 

 

 

 

 

 

 

 

6-3/4 in.

 

 

 

 

 

 

 

 

 

 

 

 

(171 mm)

(10 mm)

 

 

 

 

 

 

 

 

 

 

 

 

diameter

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4 places

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SPL-92106N page 2 of 4