Murphy 1501 User Manual

0 (0)
Murphy 1501 User Manual

Series 1501 Selectronic®

Micro-Controller/Annunciator

S15-96122B

Revised 07-06

Catalog Section 50

Description

The Series 1501 instrument is a microprocessorbased alarm, shutdown and control system with tachometer/hourmeter function. It annunciates in alphanumeric characters the protective device that has signaled an alarm or caused equipment shutdown. Information is called up and adjustments are made on a six-button keypad on the face of the unit. Configurations such as: Alarm or Shutdown Nomenclature, Preset Timers, and Tachometer Calibration can be made in the field.

Murphy’s Series 1501 system has seven SPDT relays. On the standard model, the relays are assigned to the following functions: Lube, Crank, Ignition/Motor, Fuel Valve, Load, Alarm, Shutdown.

The complete Series 1501 system consists of a head (monitor), sensor input terminal strip (two needed for 64 sensor models), 36 inch (914 mm) flat ribbon cable(s) for connecting the terminal block to the head/monitor, and a Class I, Div. 1, explosion-proof power supply.

The Series 1501 system is powered from 120 VAC or 12 or 24 VDC. The head/monitor is rated intrinsically safe and includes a communication port: RS232 or RS485 (Modbus RTU slave). This port allows for remote control functions such as Start/Stop, Load/Unload, etc., and for access to Series 1501 registers.

Alarm/Shutdown for 32 or 64 N.O. or N.C. Sensors

Operating Sequence Selection

Field Adjustable Sensor Nomenclature

Selectable Sensor Lockouts Class A, B, C or P

Built-In Tachometer/Overspeed Function

RS232 or RS485 Modbus RTU Communications

Two Start/Run Timers and Elapsed Time Meter

CSA Certified or NRTL Approved for Use in Class I, Div. 1 Grps. C & D Hazardous Locations

NRTL/C

Applications

The Series 1501 system can be configured to monitor applications such as: Air and Gas Compressors, Natural Gas Refueling, and other Industrial Operations. For a list of applications and our cataloged programs contact a Murphy sales representative. Custom programming available at additional charge.

Features

32 or 64 sensor inputs (N.O. or N.C.) for alarm or shutdown.

Easy operation/adjustments Six-button keypad.

RS232 or RS485 Modbus RTU communications.

Automatic Engine Control.

Two Start-Run Timers.

Seven Control Relay Outputs.

Pre/Postlube Time Delay.

Automatic Compressor Loading.

Specifications

Power Consumption: 120 VAC (7.5 VA); 12 VDC (3.5 watts); 24 VDC (3.5 watts).

Sensor Inputs: 32 to 64 N.O. and/or N.C. inputs such as Murphy Swichgage® instruments. Field selectable as a Class A, B1, B2 , C , P or ESD for shutdown, alarm, or control function.

Outputs: 7-SPDT relay outputs, 5 A, 1/16 HP, 125/250 VAC/ 1 A, 30 VDC.

NOTE: For hazardous areas an approved isolation barrier must be used between sensor switch and input terminals if the sensor output comes from any energy storing device such as a relay or transistor.

Adjustable Time Delays:

(standard Series 1501)

Prelube

Rest

Process Delay

Permissive

Run Delay

Idle/Cooldown

Purge

Postlube

Fuel Delay

Crank

Load Delay

Test

Class B1 Sensor Lockout

Class B2 Sensor Lockout

Before Ignition Ground or Electric Motor Stop (for up to 59 seconds)

Sensor Inputs Terminal Block: Rail mount DIN type; 32 terminals, screw type.

Opto-Isolated Tach/Run Input: Magnetic pickup, 4.5 to 120 Vrms, 0-10 kHz. CD ignition, positive or negative ground, 100 to 300 VDC, 3-666 Hz. 12 to 125 VDC or 120 Vrms, 50/60 Hz may be used for run signals.

Operating Temperatures: 32 to 122°F (0 to 50°C).

Storage Temperatures: -4 to 158°F (-20 to 70°C). Case: ABS plastic, 1/4 DIN (90 x 90 mm).

Interface Output: Factory configured for RS232; field-selectable for RS485 (specify for factory configured RS485).

Alphanumeric Display: 2 lines, each line with 16 characters (32 characters total).

Power Supply Enclosure: Explosion-proof, Class I, Division 1. Intrinsically safe barrier built into the power supply, 120 VAC with 7 form “C” relay outputs for the following functions (with standard S1501):

Lube Load

Crank Alarm

Ignition/Motor

Shutdown Fuel Valve

S15-96122B page 1 of 2