Mitsubishi 2033D User Manual

0 (0)

MITSUBISHI ELECTRIC AUTOMATION, INC.

UNINTERRUPTIBLE POWER SUPPLY SYSTEM

2033D SERIES

OWNERS / TECHNICAL MANUAL

Revision 1.3: December 18, 2003

ALN-H0963

MITSUBISHI ELECTRIC 2033D SERIES UPS

MITSUBISHI

2033D SERIES UPS

Page Number:

ELECTRIC

OWNERS / TECHNICAL MANUAL

i

Preface

23D_00s.doc

MITSUBISHI ELECTRIC 2033D SERIES UPS

MITSUBISHI

2033D SERIES UPS

Page Number:

ELECTRIC

OWNERS / TECHNICAL MANUAL

ii

 

TABLE OF CONTENTS

 

LIST OF TABLES ...............................................................................................

iii

LIST OF FIGURES ............................................................................................

iv

HOW TO USE THIS MANUAL ...........................................................................

v

1.0

INTRODUCTION .......................................................................................

1-1

1.1

GENERAL .................................................................................................

1-3

1.2

DEFINITIONS ............................................................................................

1-4

1.3

OVERVIEW ...............................................................................................

1-5

1.4

SPECIFICATIONS ....................................................................................

1-11

2.0

OPERATOR CONTROLS AND INDICATORS .........................................

2-1

2.1

LED DISPLAY ...........................................................................................

2-2

2.2

MBP LAMP....................................................................................................

2-2

2.3

EPO BUTTON ...........................................................................................

2-2

2.4

LIQUID CRYSTAL DISPLAY .....................................................................

2-3

2.5

EXTERNAL SIGNAL TERMINAL BLOCK .................................................

2-8

2.6

EXTERNAL COMMUNCATION CONNECTOR ..........................................

2-13

3.0

INSTALLATION AND OPERATION .........................................................

3-1

3.1

TRANSPORTATION AND INSTALLATION ..............................................

3-1

3.2

INSTALLATION PROCEDURE .................................................................

3-1

3.3

PROCEDURE FOR CABLE CONNECTIONS ...........................................

3-3

3.4

OPERATING PROCEDURES ...................................................................

3-12

3.5

MAINTENANCE BYPASS SET-UP PROCEDURES ....................................

3-13

4.0

RESPONSE TO UPS FAILURE ................................................................

4-1

5.0

PARTS REPLACEMENT ..........................................................................

5-1

6.0

FAULT CODES .........................................................................................

6-1

7.0

WARRANTY & OUT OF WARRANTY SERVICE .....................................

7-1

MITSUBISHI ELECTRIC 2033D SERIES UPS

MITSUBISHI

2033D SERIES UPS

Page Number:

ELECTRIC

OWNERS / TECHNICAL MANUAL

iii

 

List of Tables

 

Table 1.1

Power Specifications ...................................................................

1-11

Table 1.2

UPS Module Information..............................................................

1-11

Table 1.3

Detail of Specifications ................................................................

1-12

Table 1.4

Rating of Contactor and Fuses ....................................................

1-13

Table 3.1

How to Transport and Install the System.....................................

3-1

Table 3.2

List of UPS Weights (lb.)..............................................................

3-1

Table 3.3

Type and number of Battery ........................................................

3-2

Table 3.4

Maximum Permitted Fault Current...............................................

3-3

Table 3.5

Recommended Cable Size and Torque Requirements ...............

3-5

Table 3.6

Crimp Type Compression Lug .....................................................

3-6

Table 6.1

Fault Code ...................................................................................

6-2

MITSUBISHI ELECTRIC 2033D SERIES UPS

MITSUBISHI

2033D SERIES UPS

Page Number:

ELECTRIC

OWNERS / TECHNICAL MANUAL

iv

 

List of Figures

 

Figure 1.1

Single Line Diagram-Normal Operation....................................................

1-5

Figure 1.2

Single Line Diagram-Bypass Operation....................................................

1-6

Figure 1.3

Single Line Diagram-Battery Operation ....................................................

1-7

Figure 1.4

UPS Parts Location ..................................................................................

1-8

Figure 1.5

UPS Parts Location (Continued)...............................................................

1-9

Figure 1.6

External I/F circuit PCB IOAU-05..............................................................

1-9

Figure 2.1

Operation/Display Panel ...........................................................................

2-1

Figure 2.2

Main Screen .............................................................................................

2-3

Figure 2.3

Start/Stop Screen .....................................................................................

2-4

Figure 2.4

PIN Protection Screen ..............................................................................

2-4

Figure 2.5

Bypass Voltage Abnormal Message Screen.............................................

2-4

Figure 2.6

Measurement Screen ...............................................................................

2-4

Figure 2.7

Setup Screen............................................................................................

2-5

Figure 2.8

Log Select Screen ....................................................................................

2-5

Figure 2.9

Event Log Screen .....................................................................................

2-5

Figure 2.10

Battery Log Screen .................................................................................

2-6

Figure 2.11

Main Screen (Battery Operation) ............................................................

2-6

Figure 2.12

Measurement Screen (Battery Operation) ................................................

2-6

Figure 2.13

Main Screen (Fault Indication) ................................................................

2-7

Figure 2.14

Message Screen .....................................................................................

2-7

Figure 2.15

External Signal Terminal Block.................................................................

2-8

Figure 2.16

Control Wiring for External Contacts ........................................................

2-10

Figure 2.17

Remote "Start" Contact Connections........................................................

2-11

Figure 2.18

External communication connector...........................................................

2-13

Figure 3.1

UPS Terminal Designation ......................................................................

3-7

Figure 3.2

Diagram of input/output bus bars and terminal blocks ............................

3-8

Figure 3.3

Diagram of Power Wire Connect (Parallel Connection) ..........................

3-10

Figure 3.4

Diagram of Power Wire & Control Wire Connect (Parallel Connection ) .

3-11

MITSUBISHI ELECTRIC 2033D SERIES UPS

MITSUBISHI

2033D SERIES UPS

Page Number:

ELECTRIC

OWNERS / TECHNICAL MANUAL

v

How to use this Manual

This manual is designed for ease of use, giving the user easy and quick reference to information.

This manual uses notice icons to draw attention to the user important information regarding the safe operation and installation of the UPS. The notice icons used in this manual are explained below, and should be taken into account and adhered to whenever they appear in the text of this manual.

Warning: A warning notice icon conveys information provided to protect the user and service personnel against hazards and/or possible equipment damage.

Caution: A caution notice icon conveys information provided to protect the user and service personnel against possible equipment damage.

Note: A Note notice icon indicates when the user should make a reference of information regarding the UPS operation, load status and display status. Such information is essential if Mitsubishi field service group assistance and correspondence is required.

Safety Recommendations: If any problems are encountered while following this manual, Mitsubishi field service group assistance and correspondence is recommended.

MITSUBISHI ELECTRIC 2033D SERIES UPS

MITSUBISHI

2033D SERIES UPS

Page Number:

ELECTRIC

OWNERS / TECHNICAL MANUAL

1-1

1.0 INTRODUCTION

Your Mitsubishi Uninterruptible Power Supply System (UPS) is designed to provide many years of reliable protection from power failure, brown-outs, line noise, and voltage transients. To ensure optimum performance of the equipment, follow the manufacturer's instructions. This manual contains descriptions required to operate the UPS. Please read this manual carefully and retain it for future reference.

IMPORTANT SAFETY INSTRUCTIONS

RETAIN THESE INSTRUCTIONS

This manual contains important instructions for the 2033D Series Uninterruptible Power Supply System that should be followed during installation and maintenance of the UPS and batteries.

WARNING 1

Lethal voltages exist within the equipment during operation. Observe all warning and cautions in this manual. Failure to comply may result in serious injury or death. Obtain qualified service for this equipment as instructed.

MITSUBISHI ELECTRIC 2033D SERIES UPS

MITSUBISHI

2033D SERIES UPS

Page Number:

ELECTRIC

OWNERS / TECHNICAL MANUAL

1-2

WARNING 2

This UPS does not include a Bypass input circuit breaker (MCCB) to protect bypass circuit. Bypass input circuit breaker (MCCB) are to be field supplied and installed. Recommended Breaker (MCCB)'s Specifications are as follows:

Capacity (kVA)

Bypass Voltage (Vac)

Bypass Rating (Aac)

Recommended

 

 

 

Breaker (Aac)

30

480

36

45

50

480

60

80

80

480

96

125

AC input and AC output over current protection and disconnect devices shall be field supplied and installed. DC output over current protection and disconnect device shall be field supplied and installed. The over current protection device shall be rated as indicated in TABLE 1.4.

MITSUBISHI ELECTRIC 2033D SERIES UPS

MITSUBISHI

2033D SERIES UPS

Page Number:

ELECTRIC

OWNERS / TECHNICAL MANUAL

1-3

1.1GENERAL

The Mitsubishi 2033D Series UPS is designed to provide continuous and clean electrical power to a critical load. Additionally the UPS monitors power conditions affecting the load. In the event of an input power failure, the UPS will supply power to the critical load for the specified battery time.

If the input power is not restored promptly, back up power from the UPS battery permits the orderly shutdown of equipment supported by the UPS. The UPS is simple to start-up, operate and maintain.

The 2033D Series UPS is available in three (3) kVA sizes-30, 50 and 80kVA, and also in two (2) output voltages - 208V and 480V. Specifications for each kVA and voltage model appear in Section 1.4. 30kVA model have batteries included in the UPS module cabinet. 50 and 80kVA models have external batteries. The principles of operation described herein are applicable to all models.

This manual provides an overview of the 2033D Series components and their functions. The appearance and purpose of operator controls and indicators is described with procedures for operation, start-up, shutdown and basic maintenance included.

MITSUBISHI ELECTRIC 2033D SERIES UPS

MITSUBISHI

2033D SERIES UPS

Page Number:

ELECTRIC

OWNERS / TECHNICAL MANUAL

1-4

1.2Definitions

UNINTERRUPTIBLE POWER SUPPLY SYSTEM (UPS) - All components within the UPS Module Cabinet and associated batteries that function as a system to provide continuous, conditioned AC power to a load. This is sometimes referred to as the "System".

UPS MODULE CABINET - The metal enclosure which contains the Converter, the Inverter, the Chopper, the Static Transfer Switch, the Internal Bypass line, the operator controls, and the internal control system required to provide specified AC power to a load.

UPS MODULE - The Converter and Inverter assemblies which, under the direction of the internal control system and operator controls, provide specified AC power to a load.

CONVERTER/BOOSTER - The UPS components which contain the equipment and controls necessary to convert input AC power to regulated DC power required for battery charging and for supplying power to the Inverter.

INVERTER - The UPS components which contain the equipment and controls necessary to convert DC power from the Converter, or the battery, to AC power required by the critical load.

CHOPPER - The UPS components which contain the equipment and controls necessary to charge the battery and supply power to the Inverter from battery.

STATIC TRANSFER SWITCH - The device which connects the critical load to the bypass line when the UPS module cannot supply continuous power.

BYPASS LINE - The line which conducts electricity directly from the input power source to the critical load during Maintenance or whenever the UPS is not completely operational.

INPUT POWER - Power provided by the electrical utility company, or auxiliary generator, which is connected to the UPS for supplying the critical load.

BATTERY - The rechargeable battery strings which supply DC power to the inverter to maintain continuous AC power to the load during AC input power failure conditions

MITSUBISHI ELECTRIC 2033D SERIES UPS

MITSUBISHI

2033D SERIES UPS

Page Number:

ELECTRIC

OWNERS / TECHNICAL MANUAL

1-5

1.3Overview

The UPS provides two power paths between the utility source and the critical load.

Figure 1.1 shows the path for normal operation, with the load powered from the inverter. Figure 1.2 shows the path for bypass operation, with the load supplied through the static bypass line.

Figure 1.3 shows the path for battery operation, with the load supplied from the inverter.

A) Normal Operation.

FIGURE 1.1 Single Line Diagram - Normal Operation. Load powered by inverter

CB

 

 

 

 

Maintenance

AC Bypass

 

 

Static Transfer

 

 

 

 

Bypass

Input

 

 

Switch

 

 

 

 

Switch

 

 

52RS

 

 

 

 

 

 

 

CB

 

CONVERTER

INVERTER

 

 

 

 

 

 

 

AC input

 

 

 

 

Output

 

 

 

 

 

User

52RC

FI

FO

52C

52CS

supplied

 

 

 

 

 

 

FB

 

 

 

 

 

 

 

 

 

 

72B

 

Power Flow

 

 

 

 

 

 

 

BATTERY

 

 

Not in Use

 

 

50kVA,

80kVA:

 

 

 

 

UPS Module

 

 

 

External Battery

During normal operation, the path through the inverter is used to power the load.

Referring to Figure 1.1: Input AC power is converted to DC by the Converter. DC power is utilized to charge the UPS battery and to provide power to the Inverter. The Inverter converts the DC power to clean AC power to supply the critical load.

The conversion - inversion process eliminates any voltage transients or fluctuations existing in the input power before it reaches the critical load.

* The AC Bypass Input circuit breaker (MCCB) for protection of the UPS and cables are field supplied and field installed. (See WARNING 2 on page 1-2)

MITSUBISHI ELECTRIC 2033D SERIES UPS

MITSUBISHI

2033D SERIES UPS

Page Number:

ELECTRIC

OWNERS / TECHNICAL MANUAL

1-6

B) Internal Static Bypass Line

FIGURE 1.2 Single Line DiagramBypass Operation. Load fed through static bypass line.

CB

 

 

 

 

Maintenance

AC Bypass

 

 

Static Transfer

 

 

 

 

Bypass

Input

 

 

Switch

 

 

 

 

Switch

 

 

52RS

 

 

 

 

 

 

 

CB

 

CONVERTER

INVERTER

 

 

 

 

 

 

 

AC input

 

 

 

 

Output

 

 

 

 

 

User

52RC

FI

FO

52C

52CS

supplied

 

 

 

 

 

 

FB

 

 

 

 

 

 

 

 

 

 

72B

 

Power Flow

 

 

 

 

 

 

 

 

 

 

Not in Use

 

 

BATTERY

50kVA,

80kVA:

 

 

 

 

UPS Module

 

 

 

External Battery

Referring to Figure 1.2, the Internal Static Bypass line is a Hard wired line through Static Transfer Switch which supplies the critical load with unconditioned input power. The purpose of this line is to route power to the critical load while the UPS module is de-energized during Start-up before the system is fully operational.

The internal control system determines the operation of the two paths, with the load powered from the inverter being the normal operation.

MITSUBISHI ELECTRIC 2033D SERIES UPS

MITSUBISHI

2033D SERIES UPS

Page Number:

ELECTRIC

OWNERS / TECHNICAL MANUAL

1-7

C) Inverter supply at battery operation

 

 

 

FIGURE 1.3 Single Line Diagram - Battery Operation

 

 

CB

 

 

 

 

Maintenance

AC Bypass

 

 

Static Transfer

 

 

 

 

Bypass

Input

 

 

Switch

 

 

 

 

Switch

 

 

52RS

 

 

 

 

 

 

 

CB

 

CONVERTER

INVERTER

 

 

 

 

 

 

 

AC input

 

 

 

 

Output

 

 

 

 

 

User

52RC

FI

FO

52C

52CS

supplied

 

 

 

 

 

 

FB

 

 

 

 

 

 

 

 

 

 

72B

 

Power Flow

 

 

 

 

 

 

 

BATTERY

 

 

Not in Use

 

 

50kVA,

80kVA:

 

 

 

 

UPS Module

 

 

 

External Battery

Referring to Figure 1.3: In the event of AC input source failure or interruption, the converter will de-energize and the battery will immediately discharge and supply DC power to the inverter to maintain continuous AC power to the load. This operation will continue until:

a)The battery capacity expires and the inverter turns off, or

b)Input power is restored after which the converter will power the inverter and critical load and simultaneously recharge the batteries.

A fully charged battery will provide power for the specified time at the rated load, or longer, at a reduced load.

When power is restored after a low battery shutdown, the converter automatically restarts operation, recharges the batteries and the Inverter is automatically restarted without operator intervention. Load is automatically assumed by the inverter without operator intervention.

The power drawn by the load is equally shared between all system UPS during battery operation.

MITSUBISHI ELECTRIC 2033D SERIES UPS

MITSUBISHI

2033D SERIES UPS

Page Number:

ELECTRIC

OWNERS / TECHNICAL MANUAL

1-8

 

FIGURE 1.4-a UPS Parts Location (30kVA)

 

 

UPS module

 

 

FRONT VIEW

 

 

Converter Unit

 

Inverter

 

 

unit

 

 

 

 

Chopper Unit

 

 

 

 

 

DC

 

52RS

 

Capacitor

 

52RC

 

52CS

 

72B

 

 

 

 

1.

External I/F

 

 

 

Circuit PCB

 

52C

 

IOAU-05

 

 

 

2. Grounding Bar

 

 

 

 

Parallel

 

 

 

I/F PCB

 

 

 

GND

GND ELEC

 

 

 

TERM

 

 

FIGURE 1.4-b UPS Parts Location (50kVA, 80kVA)

 

 

UPS module

 

 

FRONT VIEW

 

 

 

 

Inverter

 

 

 

unit

 

Converter

 

 

 

Chopper Unit

 

 

 

52RS

 

52C

 

 

 

 

52RC

 

52CS

 

 

 

1.

External I/F

 

 

 

Circuit PCB

 

72B

 

IOAU-05

 

 

 

 

 

Parallel

 

 

 

I/F PCB

 

 

GND

2. Grounding Bar

 

 

GND ELEC TERM

MITSUBISHI ELECTRIC 2033D SERIES UPS

Mitsubishi 2033D User Manual

MITSUBISHI

2033D SERIES UPS

Page Number:

ELECTRIC

OWNERS / TECHNICAL MANUAL

1-9

FIGURE 1.5 UPS Parts Location (Continued)

UPS module

BACKSIDE OF FRONT DOOR(Right side)

SYNC.LED

5

INVERTER

INVERTER

6

START

STOP

 

|

|

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

|

 

|

 

 

|

 

 

 

|

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FAULT

MAINTENANCE

TEST

BOOT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RESET

BUTTON

SWITCH

SWITCH

7

 

8

 

9

 

 

 

10

 

FIGURE 1.6 External I/F PCB IOAU-05

3. External Contact Signal Terminal

IOAU-05

4. RS232C D-sub Connector

MITSUBISHI ELECTRIC 2033D SERIES UPS

MITSUBISHI

2033D SERIES UPS

Page Number:

ELECTRIC

OWNERS / TECHNICAL MANUAL

1-10

Description of Figures 1.4, 1.5, and 1.6:

1.External I/F Board (IOAU-05) : FOR SERVICE PERSONNEL ONLY (FIGURE 1.6):

-(3) External contact signal terminal

-(4) RS232C communication connector

2.Grounding Bar (E)

3.External Contact Signal Terminal Block - Terminal block to connect contact signal input/output lines to and from the external devices. Refer to Figure 2.15 section 2.5 for details.

4.RS232C Communication Connector - Refer to Figure 2.18 section 2.6 for details.

5.“INVERTER” START Switch - This switch is used to transfer the UPS from static bypass to inverter during maintenance purposes. Transfers will lock-out if the bypass voltage is more than +10%,-10% of nominal.

*Uninterrupted switching is made at the time of synchronous operation. Switching is impossible at the time of asynchronous operation.

6.“INVERTER STOP” Switch - This switch is used to transfer the UPS from inverter to static bypass during maintenance purposes. Do not operate it under normal operation. Transfers will lock-out if the bypass voltage is more than +10%,-10% of nominal.

*Uninterrupted switching is made at the time of synchronous operation. Switching is impossible at the time of asynchronous operation.

7.“FAULT RESET” Switch (FOR SERVICE PERSONNEL ONLY) - This switch resets errors resulting from alarm conditions. (Do not operate this switch while inverter and converter are in operation.)

8.Maintenance (Set) Button (FOR SERVICE PERSONNEL ONLY) - This switch sets the UPS menu parameters.

9.“Test mode” Switch (FOR SERVICE PERSONNEL ONLY) - This switch changes system operation to the test-mode. (This switch should not be operated by personnel other than an Authorized Service Engineer).

10.“BOOT” Switch (FOR SERVICE PERSONNEL ONLY) - This switch boots the processor in the main control circuit resulting from alarm conditions. (Do not operate this switch while inverter and converter are in operation).

MITSUBISHI ELECTRIC 2033D SERIES UPS

MITSUBISHI

2033D SERIES UPS

Page Number:

ELECTRIC

OWNERS / TECHNICAL MANUAL

1-11

1.4Specifications

The UPS name plate displays the rated kVA as well as nominal voltages and currents. The name plate is located on the inside of the UPS front door.

TABLE 1.1 Power Specifications

 

Rated output

Input voltage

Bypass input voltage

Output voltage

 

 

 

Power

3 phase / 3 wire

3 phase / 3 wire

3 phase / 3 or 4 wire

 

 

30kVA / 24kW

480V

 

 

480V

208V or 480V

 

 

50kVA / 40kW

480V

 

 

480V

208V or 480V

 

 

80kVA / 64kW

480V

 

 

480V

208V or 480V

 

 

TABLE 1.2 UPS Module Information

 

 

 

 

 

 

 

 

UPS

CABLE

 

WIDTH

DEPTH

HEIGHT

 

WEIGHT

HEATING

 

 

[kVA]

ENTRY

 

[in / mm]

[in / mm]

[in / mm]

 

[lb./ kg]

[kBTU/h]

 

 

 

 

 

 

 

 

 

 

 

 

30

BOTTOM

 

33.9 / 860

31.5 / 800

70.9 / 1800

 

2060 / 930

9.1

 

 

50

BOTTOM

 

33.9 / 860

31.5 / 800

70.9 / 1800

 

1810 / 820

13.5

 

 

80

BOTTOM

 

33.9 / 860

31.5 / 800

70.9 / 1800

 

1990 / 900

21.6

 