Mitsubishi Electronics PUHY-80TMU-A, 100TMU-A User Manual

0 (0)

A-100TMU A,-80TMU-PUHY Handbook Service

AIR CONDITIONERS CITY MULTI Series Y

Models PUHY-80TMU-A, 100TMU-A

Service Handbook

Safety precautions

Before installation and electric work

sBefore installing the unit, make sure you read all the “Safety precautions”.

sThe “Safety precautions” provide very important points regarding safety. Make sure you follow them.

sThis equipment may have an adverse effect on equipment on the same electrical supply system.

sPlease report to or take consent by the supply authority before connection to the system.

Symbols used in the text

Warning:

Describes precautions that should be observed to prevent danger of injury or death to the user.

Caution:

Describes precautions that should be observed to prevent damage to the unit.

Symbols used in the illustrations

: Indicates an action that must be avoided.

: Indicates that important instructions must be followed.

: Indicates a part which must be grounded.

: Indicates that caution should be taken with rotating parts.

(This symbol is displayed on the main unit label.) <Color: Yellow>

: Indicates that the main switch must be turned off before servicing. (This symbol is displayed on the main unit label.) <Color: Blue>

: Beware of electric shock (This symbol is displayed on the main unit label.) <Color: Yellow>

: Beware of hot surface (This symbol is displayed on the main unit label.) <Color: Yellow>

ELV : Please pay attention to electric shock because this is not Safety Extra Low-Voltage (SELV) circuit.

And at servicing, please shut down the power supply for both Indoor Unit and Outdoor Unit .

Warning:

Carefully read the labels affixed to the main unit.

Warning:

Ask the dealer or an authorized technician to install the air conditioner.

-Improper installation by the user may result in water leakage, electric shock, or fire.

Install the air unit at a place that can withstand its weight.

-Inadequate strength may cause the unit to fall down, resulting in injuries.

Use the specified cables for wiring. Make the connections securely so that the outside force of the cable is not applied to the terminals.

-Inadequate connection and fastening may generate heat and cause a fire.

Prepare for typhoons and other strong winds and earthquakes and install the unit at the specified place.

-Improper installation may cause the unit to topple and result in injury.

Always use an air cleaner, humidifier, electric heater, and other accessories specified by Mitsubishi Electric.

-Ask an authorized technician to install the accessories. Improper installation by the user may result in water leakage, electric shock, or fire.

Never repair the unit. If the air conditioner must be repaired, consult the dealer.

-If the unit is repaired improperly, water leakage, electric shock, or fire may result.

Do not touch the heat exchanger fins.

-Improper handling may result in injury.

If refrigerant gas leaks during installation work, ventilate the room.

-If the refrigerant gas comes into contact with a flame, poisonous gases will be released.

Install the air conditioner according to this Installation Manual.

-If the unit is installed improperly, water leakage, electric shock, or fire may result.

Have all electric work done by a licensed electrician according to “Electric Facility Engineering Standard” and “Interior Wire Regulations”and the instructions given in this manual and always use a special circuit.

-If the power source capacity is inadequate or electric work is performed improperly, electric shock and fire may result.

Securely install the cover of control box and the panel.

-If the cover and panel are not installed properly, dust or water may enter the outdoor unit and fire or electric shock may result.

When installing and moving the air conditioner to another site, do not charge it with a refrigerant different from the refrigerant (R22) specified on the unit.

-If a different refrigerant or air is mixed with the original refrigerant, the refrigerant cycle may malfunction and the unit may be damaged.

If the air conditioner is installed in a small room, measures must be taken to prevent the refrigerant concentration from exceeding the safety limit even if the refrigerant should leak.

-Consult the dealer regarding the appropriate measures to prevent the safety limit from being exceeded. Should the refrigerant leak and cause the safety limit to be exceeded, hazards due to lack of oxygen in the room could result.

When moving and reinstalling the air conditioner, consult the dealer or an authorized technician.

-If the air conditioner is installed improperly, water leakage, electric shock, or fire may result.

After completing installation work, make sure that refrigerant gas is not leaking.

-If the refrigerant gas leaks and is exposed to a fan heater, stove, oven, or other heat source, it may generate noxious gases.

Do not reconstruct or change the settings of the protection devices.

-If the pressure switch, thermal switch, or other protection device is shorted and operated forcibly, or parts other than those specified by Mitsubishi Electric are used, fire or explosion may result.

Contents

 

1 COMPONENT OF EQUIPMENT ...............................................

1

[1]

Appearance of Components............................................

1

[2] Refirigerant Circuit Diagram and Thermal Sensor...........

6

[3] PUHY-80, 100TMU-A ELECTRICAL WIRING

 

 

DIAGRAM .......................................................................

7

[4]

Standard operation data ..................................................

9

[5] Function of dip SW and rotary SW ................................

11

2 TEST RUN ............................................................................... 15

[1]

Before Test Run ............................................................

15

[2]

Test Run Method ...........................................................

19

3 GROUPING REGISTRATION OF INDOOR UNITS WITH

 

M-NET REMOTE CONTROLLER ...........................................

20

4 CONTROL ............................................................................... 26

[1] Control of Outdoor Unit .................................................

26

[2]

Operation Flow Chart ....................................................

31

[3] List of Major Component Functions ............................... 36

[4] Resistance of Temperature Sensor...............................

38

5 REFRIGERANT AMOUNT ADJUSTMENT .............................. 39

[1] Refrigerant Amount and Operating Characteristics.......

39

[2] Adjustment and Judgement of Refrigerant Amount.......

39

6 TROUBLESHOOTING.............................................................

44

[1]

Principal Parts................................................................ 44

[2] Self-diagnosis and Countermeasures Depending on the

 

Check Code Displayed ..................................................

62

[3]

LED Monitor Display ......................................................

83

Propeller fan

Fan motor

- 1 -

Rear Controller Box

INV board

MAIN board

Choke coil(L2)

Interrigent Power Module(IPM)

Magnetic contactor(52C)

Capacitor (C1)(Smoothing capacitor)

Gate Amplifier board(G/A board)

Diode stack(DS)

Power board

Terminal block(TB7)Transmission

Terminal

Terminal

block (TB1)

block (TB3)

Power source

Transmission

- 2 -

Mitsubishi Electronics PUHY-80TMU-A, 100TMU-A User Manual

MAIN board

CNS1 M-NET

Transmission (DC30V)

CNS2 M-NET Transmission (Centralized control) (DC30V)

CN40 M-NET

Transmission

Power supply

CNVCC3 Power source for contorl 1-2 DC30 V 1-3 DC30 V 4-6 DC12 V 5-6 DC5 V

CN51 Indication distance 3-4 Compressor ON/

Off 3-4 trouble

LD1

Service LED

CNRS53

Serial transmission to

INV board

CN3D

SW1,2,3,4 Dip Switch

CN3S

CNFAN1 control for MF1

CN20 CNAC3 power

source

- 3 -

INV board

CNAC2

CN52C

CNRS2

Power source

Control for

Serial transmission

1 L2

52C

to MAIN board

5 N

 

 

CNFAN

 

 

Control for

MF1

CNDC2

1-3 DC310 V

CN15V2

Power supply IPM control 1-2 DC15 V

5-6 DC15 V

9-0 DC15 V

C-D DC15 V

CNVCC4

CNL2

Choke coil

CNVCC2 power supply

CNDR2 IPM control signal

CNCT

CNTH

SW1

- 4 -

G/A board

CNDC1

1 - 3 DC310V

DC310V

CN15V1 Power Supply IPM control 1 - 2 DC15V 5 - 6 DC15V 9 - 0 DC15V C - D DC15V

CNDR1

IPM control signal

Power board

- 5 -

[2] Refirigerant Circuit Diagram and Thermal Sensor

1 PUHY-80TMU-A, 100TMU-A

BV1

Indoor

Unit

 

 

BV2

ST1

 

 

TH2

CP2

ST2

 

 

 

safety valve

 

 

Accumulator

SA

 

 

 

 

CJ2

High pressure

 

 

MA

 

SLEV

 

 

 

 

 

 

 

 

 

TH7

 

 

 

 

 

 

 

 

 

ST7

CJ1

63HS

CP1

SV1

 

SV2

 

Comp

 

LEV1

 

 

O/S

ST6

TH1

CV1

 

63H

SCC

 

 

 

 

 

 

 

 

 

TH8

 

 

HEXF

 

 

 

 

 

 

TH5

TH6

HEXB

- 6 -

- 7 -

TB1

L1

Power source

L2

3~208~230V

 

60Hz

L3

Connect to indoor and remote controller

CH1

SV1

21

S4

SV 2

MF

63H

GR

Ground

CN20

(7P)

DSA

3 CN32

2 (3P)

1

6 CN33

5 (6P)

4

3

2

1

6 CN34

5 (6P)

4 Red

3

2

1

5

4CNFAN1

32(5P)

1Red

3 CN38

2 (3P)

1 Green

Green

Black

White

GL3 L2

13 5

F2

6.3A

X 0 1

X02

X04

X05

Detection

Circuit

 

 

 

 

 

 

 

 

 

 

 

 

MC

 

 

 

 

 

 

 

 

Noise filter board

 

 

 

 

U V W

 

 

 

 

 

 

 

 

 

 

 

 

Red

White

Black

 

 

 

 

 

 

 

(POWER-BOARD)

 

 

 

IPM

 

 

DS(Diode stack)

 

 

R 1

 

 

 

 

 

 

 

 

 

 

 

 

FN3

 

 

 

 

U

V

W

 

 

Red

 

FN1

 

 

FN6

 

Red

P

 

 

 

 

 

 

 

 

Gate amp board

 

 

 

+

 

 

 

 

 

 

 

 

 

 

CNE 1

 

 

 

 

 

 

 

 

 

DCL +

 

 

F01

(G/A-BOARD)

 

 

Black

 

 

 

52C

FN2

FN4

C 1

Black

N

3.15A

 

 

(2P) 2

 

 

 

 

 

 

 

 

 

 

 

 

 

-

 

 

 

 

 

 

 

 

 

 

CNDR1

CN15V1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1 2

3 4

Yellow

 

(9P)

(14P)

Ground

 

 

 

 

 

 

 

 

 

 

CNDC1 1 2 3

123456789

1234567891011121314

Red

T B 3

 

T B 7

 

 

 

 

DCCT

 

(3P)

 

 

 

 

 

A

B

A

B Shield

 

 

 

 

 

 

 

 

 

 

L1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

7

1 2 3 4

F1

6.3A CN40

ZNR1~4

(4P)

1 2 3 4

CN41

(4P)

1

2

1

2

3

 

 

CNS1

 

CNS2

 

 

(2P)

 

(3P)

 

 

 

 

Control circuit board

 

 

 

 

(MAIN-BOARD)

 

1

 

 

 

 

 

CNRS3

 

 

 

 

 

2

 

 

 

 

 

(7P)

3

 

 

 

 

 

 

4

 

 

 

 

 

 

5

 

 

 

 

 

 

6

 

 

 

 

 

 

7

 

LD1

 

 

 

CNVCC3

1

 

 

 

 

 

2

 

 

 

 

 

(6P)

3

 

 

 

 

 

 

4

 

 

 

 

 

 

5

 

 

 

 

 

 

6

OFF ON OFF ON OFF ON OFF ON

CNVCC5 1

1

1

1

 

1

(2P)

2

 

 

 

 

 

CNAC3

1

 

 

 

 

 

(5P)

2

 

 

 

 

 

3

 

 

 

 

 

 

4

 

 

 

 

 

 

5

10

10

10

 

10

CNLV1

1

 

 

 

 

 

(5P)

2

SW4

SW3

SW2

SW1

3

Blue

4

 

 

 

 

 

 

5

 

 

 

 

 

CNLV2

1

 

 

 

 

 

(5P)

2

 

 

 

 

 

3

 

 

SWU2 SWU1

Red

4

 

 

 

5

Unit address setting switch

 

1

2

3

4

1 2 3

123456789

1234567891011121314

 

 

 

CNCT CNDC2

CNDR2

CN15V2

52

1

(4P)

(3P)

(9P)

(14P)

C

2

 

CN52CYellow

 

 

 

3

 

(3P)

 

 

 

 

 

1

CNRS2

 

 

 

 

2

Power circuit board

 

 

3

(7P)

 

 

 

4

 

 

 

(INV-BOARD)

 

 

5

 

 

 

 

 

 

 

6

 

 

 

 

 

 

 

7

 

 

 

 

 

1

2 CNVCC2

3 (6P)

4

5

6

1CNVCC4

2(2P)

G

G

1

CNAC2

 

L3

L3

 

2

(5P)

 

 

 

3

 

 

L1

L1

4

 

 

 

 

5

F01

X01

 

 

 

 

 

 

2A

 

 

SLEV

 

 

 

 

LEV1

Green

CNL2

Red

 

Red

 

CNTH

CN30V

 

CNFAN

 

 

(2P)

(2P)

(2P)

 

(3P)

 

 

1 2

1 2

1 2

1 2

3

5

Trouble

 

 

 

 

 

4

Compressor ON/OFF

THHS

L2

R2

 

 

3

CN51

MF

 

2

 

 

 

1

 

1

(5P)

 

 

 

 

 

 

 

 

 

12V

3

 

Compressor ON/OFF

 

 

 

 

 

2

 

Night mode

Red

 

 

 

 

1

CN3D

 

 

 

 

 

CN03

CN02

CN01

CNH

3

(3P)

 

(3P)

(8P)

(2P)

(3P)

 

2

 

Snow sensor

1 2 3

1 2 3 4 5 6 7 8

1 2

1 2 3

1

CN3S

 

 

 

 

 

 

 

 

(3P)

 

 

 

 

Black White

Red

 

Red

SW3-10 are OFF for Model 80.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3 2

1

 

 

and ON for Model 100.

TH6

TH5TH8TH7TH2

TH1

 

 

 

 

63HS

 

 

 

DIAGRAM WIRING ELECTRICAL A-100TMU 80,-PUHY [3]

- 8 -

Symbol

D S

I P M

D C L

D C C T

R 1

R 2

Z N R 1 ~ 4 C 1

5 2 C

M C

Name

Diode stack

Intelligent Power Module

DC reactor

(Power factor improvement)

Current Sensor

Resistor rush current protect

Resistor power regulation

Varistor

Capacitor Smoothing

Magnetic contactor (Inverter main circuit)

Motor Compressor

Symbol

M F

M F 1 D S A C H 1 2 1 S 4

S V 1 , S V 2

6 3 H T H 1

T H 2

T H 5

Name

Symbol

Name

Motor Fan Heat exchanger

T H 6

Thermistor OA temp.detect

Motor Fan Radiator panel

T H 7

liquid outlet temp.

Surge absorber

detect at Sub-cool coil

 

Crankcase heater (Compressor)

T H 8

bypass outlet temp.

4-way valve

detect at Sub-cool coil

 

Solenoid valve

T H H S

Rediator panel temp.detect

(Discharge-suction bypass)

6 3 H S

High pressure sensor

High pressure switch

S L E V

Electronic expansion valve

Thermistor discharge pipe temp.detect

(Oil return)

 

saturation

L E V 1

Electronic expansion valve

evapo.temp.detect

(Sub-cool coil bypass)

 

pipe temp.detect

L 2

Choke coil(Transmission)

Symbol

L D 1

S W 1

S W 2 ~4

S W U 1 ~ 2 T B 1

T B 3

T B 7

GR

Nam e

Luminous diode

Switch display selection self-diagnosis Switch function selection

Switch unit address set Terminal block power source Terminal block transmisson Terminal block transmisson centralized control

Ground terminal

<Operation of self-diagnosis switch (SW1) and LED display>

 

<LED display>

 

 

 

 

 

 

 

 

 

Display

Display at LED lighting (blinking) Remarks SW1 operation

 

LD1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FLAG1 FLAG2

FLAG3 FLAG4

FLAG5 FLAG6 FLAG7

FLAG8

 

 

 

 

 

 

 

 

 

 

Relay output

During

Crankcase

21S4

SV1

SV2

Always

FLAG8 always lights at

ON : 1

 

 

 

 

 

 

 

 

display

compressor

 

 

 

 

 

 

 

 

heater

lighting

OFF : 0

 

 

 

 

 

 

 

 

(Lighting)

run

 

 

 

 

 

microcomputer power ON

1

2

3

4

5

6

7

8

9

10

 

0000~9999

 

 

 

FLAG8

 

 

 

 

 

 

 

 

 

Check display

 

 

 

 

(at factory shipment)

(Blinking)

 

Display the address and error codes by turns

 

FLAG7

 

 

 

 

 

 

 

 

 

 

 

 

FLAG6

FLAG5

FLAG4

FLAG3

FLAG2

FLAG1

[4]Standard operation data

1 Cooling operation

 

Items

Outdoor units

PUHY-80TMU-A

 

PUHY-100TMU-A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Indoor

 

 

 

26.7° C(80° F)/19.4° C(67° F)

 

 

 

Ambient temp.

DB/WB

 

 

 

 

 

 

 

 

 

 

 

 

 

35° C(95° F)

 

 

 

 

 

Outdoor

 

 

 

 

 

 

 

 

 

Quantity

Set

 

4

 

 

 

4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Indoor unit

Quantity in operation

 

 

4

 

 

 

4

 

 

Condition

 

Model

24

24

20

10

48

16

24

10

 

Main pipe

 

 

5(16.4)

 

 

5(16.4)

 

 

 

 

 

 

 

 

 

Piping

Branch pipe

m

5(16.4)

5(16.4)

5(16.4)

5(16.4)

5(16.4)

5(16.4)

5(16.4)

5(16.4)

 

(Ft)

 

 

 

 

 

 

 

 

 

 

 

 

 

Total piping length

 

 

25(82)

 

 

25(82)

 

 

Indoor unit fan notch

Hi

Hi

Hi

Hi

Hi

Hi

Hi

Hi

 

Refrigerant volume

kg(oz)

 

10.2(360)

 

 

12.5(441)

 

Compressor volts/Frequency

V

208

230

208

230

 

 

 

 

 

 

 

 

 

 

 

 

V/Hz

134/76

134/76

171/98

171/98

Outdoor unit

 

A

27.4

24.8

35.2

31.8

opening

Indoor unit

 

 

440

440

380

300

450

320

440

300

SC (LEV1)

Pulse

 

75

 

 

 

81

 

 

LEV

Oil return (SLEV)

 

 

111

 

 

157

 

Pressure

High pressure/Low pressure

MPa(psi)

 

2.00/0.50

 

 

1.99/0.46

 

(after O/S)

(before MA)

 

(290/72)

 

 

(288/67)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Discharge (TH1)

 

 

85(185)

 

 

95(203)

 

 

 

Heat exchanger outlet (TH5)

 

 

40(104)

 

 

42(108)

 

 

 

Inlet

 

 

7(45)

 

 

5(41)

 

 

 

Accumulator

 

 

 

 

 

 

 

 

 

temperature

 

Outlet

 

 

9(48)

 

 

7(45)

 

Outdoor

Suction (Comp)

 

 

7(45)

 

 

10(50)

 

unit

 

 

 

 

 

low pressure saturation

° C

 

 

 

 

 

 

 

 

 

 

6(43)

 

 

4(39)

 

 

temperature (TH2)

(° F)

 

 

 

 

 

 

 

 

 

 

 

 

 

Sectional

 

 

 

 

 

 

 

 

 

 

Shell bottom (Comp)

 

 

60(140)

 

 

60(140)

 

 

SCC outlet (TH7)

 

 

27(81)

 

 

27(81)

 

 

 

 

 

 

 

 

 

 

Bypass outlet (TH8)

 

 

8(46)

 

 

6(43)

 

 

Indoor

LEV inlet

 

 

26(79)

 

 

26(79)

 

 

 

 

 

 

 

 

 

 

 

 

 

unit

Heat exchanger outlet

 

 

10(50)

 

 

10(50)

 

 

 

 

 

 

 

 

 

 

 

 

- 9 -

 

 

 

 

 

 

 

2 Heating operation

 

 

Items

 

 

Outdoor units

 

 

 

 

 

 

 

 

 

 

 

 

 

Indoor

 

 

 

 

 

 

 

 

 

 

 

 

Ambient temp.

 

 

 

DB/WB

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Outdoor

 

 

 

 

 

 

 

 

Quantity

 

Set

 

 

 

 

 

 

 

 

 

Condition

 

Indoor unit

 

Quantity in operation

 

 

 

 

 

 

 

 

 

Model

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Main pipe

 

 

 

 

Piping

 

 

 

 

m

 

 

 

Branch pipe

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Total piping length

 

 

 

 

 

 

 

 

 

 

 

 

Indoor unit fan notch

 

 

 

Refrigerant volume

 

kg

 

 

 

 

 

 

 

 

 

V

Compressor volts/Frequency

 

 

 

 

 

 

 

 

 

 

 

 

V/Hz

Outdoor unit

 

 

 

 

A

LEVopening

 

Indoor unit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Pulse

 

Oil return (SLEV)

 

 

 

SC (LEV1)

 

Pressure

 

High pressure/Low pressure

 

MPa(psi)

 

 

 

 

 

(after O/S)

(before MA)

 

 

 

 

 

 

 

 

 

 

Discharge (TH1)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Heat exchanger inlet (TH5)

 

 

 

 

 

 

 

 

 

 

 

 

temperature

 

 

 

 

Suction (Comp)

Inlet

 

° C

 

 

 

 

 

 

 

 

Outdoor

 

Accumulator

 

 

 

 

 

 

Outlet

 

 

 

 

 

 

 

 

 

 

 

unit

 

 

 

 

 

 

 

 

 

 

 

 

 

Sectional

 

 

 

 

 

 

 

 

(° F)

 

 

 

 

 

 

 

 

 

 

 

 

low pressure saturation

 

 

 

 

 

 

 

 

 

 

 

 

 

 

temperature (TH2)

 

 

 

 

 

 

 

Shell bottom (Comp)

 

 

 

 

 

 

 

 

 

 

 

 

Indoor

 

Heat exchanger inlet

 

 

 

 

 

 

 

 

 

 

 

 

unit

 

 

 

 

 

 

 

 

 

LEV inlet

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PUHY-200TM-A

 

 

 

PUHY-250TM-A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

21.1° C(70° F)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

8.3° C(47° F)/6.1° C(43° F)

 

 

 

4

 

 

 

 

4

 

 

 

 

 

 

 

 

 

 

4

 

 

 

 

4

 

 

24

 

24

 

20

 

10

48

 

16

 

24

 

 

 

 

 

 

10

 

 

 

 

 

 

 

 

 

 

 

 

 

5(16.4)

 

 

 

5(16.4)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5(16.4)

 

5(16.4)

 

5(16.4)

 

5(16.4)

5(16.4)

5(16.4)

 

5(16.4)

5(16.4)

 

 

 

 

 

 

 

 

 

 

 

 

25(82)

 

 

 

25(82)

 

 

 

 

 

 

 

 

 

 

 

 

 

Hi

 

 

Hi

 

Hi

 

Hi

Hi

 

Hi

 

Hi

Hi

 

 

 

 

 

 

 

 

 

 

 

 

 

10.2(360)

 

 

 

12.5(441)

 

208

 

230

208

 

230

 

 

149/85

 

149/85

174/100

 

174/100

27.5

 

24.9

35.6

 

32.2

510

 

 

510

 

450

 

300

350

 

 

510

 

 

 

 

 

 

380

 

300

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0

 

 

 

 

0

 

 

 

 

 

 

 

 

 

 

 

 

87

 

 

 

111

 

 

1.72/0.36

 

 

 

1.72/0.36

 

 

(249/52)

 

 

 

(249/52)

 

 

80

 

 

 

 

85(185)

 

 

 

 

 

 

 

 

 

6(46)

 

 

 

8(46)

 

 

 

 

 

 

 

 

 

 

 

 

 

–1(30)

 

 

 

–2(28)

 

 

 

 

 

 

 

 

 

 

 

 

 

–1(30)

 

 

 

–2(28)

 

 

 

 

 

 

 

 

 

 

 

 

 

–1(30)

 

 

 

–2(28)

 

 

 

 

 

 

 

 

 

 

 

 

 

–2(28)

 

 

 

–2(28)

 

 

 

 

 

 

 

 

 

35(95)

 

 

 

44(111)

 

 

 

 

 

 

 

 

 

71(160)

 

 

 

71(160)

 

 

 

 

 

 

 

 

 

33(91)

 

 

 

33(91)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

- 10 -

[5]Function of dip SW and rotary SW

(1) Outdoor unit

Switch

Function

Function According to Switch Operation

Switch Set Timing

When Off

When On

When Off

 

When On

 

 

 

 

 

SWU

1~2

Unit Address Setting

Set on 00 or 51~100 with the dial switch. ( 2)

Before power is turned on.

SW1

1~8

For self diagnosis/

LED Monitering Display

During normal operation when

 

 

operation monitoring

 

 

power is on.

 

 

 

9~10

 

Should be set on OFF.

SW2

1

Centralized Control

Centralized control not

Centralized control

Before power is turned on.

 

 

Switch

 

connected.

connected.

 

 

 

 

2

Deletion of connection

Storing of refrigeration

Deletion of refrigeration

Before power is turned on.

 

 

information.

system connection

system connection

 

 

 

 

 

 

 

information.

information.

 

 

 

 

3

Deletion of error history.

Deletion

During normal operation when

 

 

 

 

 

 

power is on.

 

 

 

4

Adjustment of

Ordinary control

Refrigerant volume

During normal

 

Invalid 2 hours

 

 

Refrigerant Volume

 

adjustment operation.

operation when

 

after compressor

 

 

 

 

 

 

power is on.

 

starts.

 

5

 

 

 

6

Disregard ambient air

Errors valid.

Disregard errors.

During normal operation when

 

 

sensor errors, fluid

 

 

power is on.

 

 

 

 

overflow errors.

 

 

 

 

 

 

7

Forced defrosting

Ordinary control

Start forced defrosting.

During normal

 

10 minutes or

 

 

 

 

 

 

operation when

 

more after

 

 

 

 

 

 

power is on.

 

compressor

 

 

 

 

 

 

 

 

starts.

 

8

Defrost prohibited timer

50 min.

90 min.

During normal operation when

 

 

 

 

 

 

power is on. (Except during

 

 

 

 

 

 

defrosting)

 

 

 

9

 

 

 

10

 

 

SW3

1

SW3-2 Function Valid/

SW3-2 Function Invalid

SW3-2 Function Valid

During normal operation when

 

 

Invalid

 

 

 

power is on.

 

 

 

2

Indoor Unit Test

Stop all indoor units.

All indoor units test

When SW3-1 is ON after power is

 

 

Operation

 

 

operation ON.

turned on.

 

 

 

3

Defrosting start

-2° C

0 ° C

During normal operation when

 

 

temperature of TH5.

(28.4° F)

(32° F)

power is on.

 

 

 

4

Defrosting end

8HP: 12° C(53.6° F)

15° C

During normal operation when

 

 

temperature of TH5.

10HP: 8° C(46.4° F)

(59° F)

power is on. (Except during

 

 

Opening angle of IC

(no operation)

2000

defrosting)

 

 

 

 

except when heater

 

 

 

 

 

 

 

thermostat is ON during

 

 

 

 

 

 

 

defrosting.

 

 

 

 

 

 

5

 

 

 

6

 

When switching on the power.

 

7

Target Pd (High pressure)

18kg/cm2G

20kg/cm2G

During normal operation when

 

 

 

 

(256psi)

(284psi)

power is on.

 

 

 

8

 

 

 

9

 

 

 

10

Models

 

Model 80

Model 100

When switching on the power.

SW4

1

 

 

 

2

 

 

 

3

 

 

 

4

 

 

 

5

LED Display

"° F" "psig" Display

"° C" "kgf/cmG "Display

When switching on the power

 

6

 

 

 

7

 

 

 

8

 

 

 

9

Fan characteristics

Standard

High external

When switching on the power

 

 

(

)

 

static pressure

 

 

 

 

10

 

 

1

 

 

 

 

 

 

 

Note:

1.SWU1~2=00 when shipped from the factory. Other factory settings are indicated by shaded portions.

2.If the address is set from 01 to 50, it automatically becomes 100.

- 11 -

2.SW4-9 setting

Fan characteristics curve:DIPSW4-7OFF[FactorySetting],208V•230V/60Hz Fan characteristics curve:DIPSW4-7ON,208V/60Hz

Fan characteristics curve:DIPSW4-7ON,230V/60Hz

 

50

 

 

 

 

 

 

 

 

 

 

 

 

 

Continuous operation range

 

 

 

 

45

 

 

 

 

 

 

 

 

 

 

40

 

 

 

 

 

Standard Airflow rate

 

 

 

 

 

 

 

200(m3/min)

 

 

(Pa)

35

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

pressure

30

 

 

 

 

 

 

 

 

 

25

 

 

 

 

 

 

 

 

 

static

 

 

 

 

 

 

 

 

 

20

 

 

 

 

 

 

 

 

 

External

 

 

 

 

 

 

 

 

 

15

 

 

 

 

 

 

 

 

 

 

10

 

 

 

 

 

 

 

 

 

 

5

 

 

 

 

 

 

 

 

 

 

0

 

 

 

 

 

 

 

 

 

 

150

160

170

180

190

200

210

220

230

240

Airflow rate (m3/min)

- 12 -

(2)Indoor unit DIP SW1, 3

Switch

SW name

Operation by SW

Switch set timing

Remarks

 

 

 

 

OFF

ON

OFF

ON

 

 

 

 

 

 

 

 

 

 

 

 

 

1

Room temp. sensor position

Indoor unit inlet

Built in remote controller

 

 

 

 

2

Clogged filter detect.

None

Provided

 

 

 

 

3

Filter duration

100h

2500h

 

 

 

 

 

 

 

 

 

 

 

 

4

OA intake

Ineffective

Effective

 

 

Always ineffective for PKFY-NAMU

 

5

Remote display select.

Fan output display

Thermo. ON signal display

 

 

 

SW1

6

Humidifier control

At stationary heating

Always at heat.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

7

Heating thermo. OFF airflow

Very low speed

Low speed

 

 

 

 

8

Heating thermo. OFF airflow

SW1-7 setting

Set airflow

 

 

 

 

9

Power failure automatic

Ineffective

Effective

 

 

 

 

return

 

 

 

 

 

 

 

 

 

 

 

10

 

 

 

 

1

Model selection

Heat pump

Cool.only

At unit stopping

 

 

2

Cooling capacity saving

None

Provided

(at remote

 

 

Louver for PKFY-NAMU,

controller OFF)

 

 

 

effective/ineffective

 

 

 

 

 

 

3

Vane

None

Provided

 

 

 

 

 

 

 

 

 

 

 

 

4

Vane swing function

None

Provided

 

 

Not provided for PKFY-NAMU

 

 

 

Provided for PLFY-NGMU (ON) setting

 

 

 

 

 

 

 

SW3

5

Vane horizontal angle

1st setting

2nd setting

 

 

 

 

6

Vane angle set for cooling

Down blow B, C

Horizontal

 

 

Always down blow B,C for

 

 

 

PKFY-NAMU

 

 

 

 

 

 

 

 

7

 

 

 

 

8

Heating 4deg (7.2 deg) up

Effective

Ineffective

 

 

 

 

Note : ° C scale (° F scale)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

9

 

 

 

 

 

 

 

 

 

 

 

 

10

 

 

 

 

 

 

 

 

 

 

 

Note 1: The shaded part indicates the setting at factory shipment. (For the SW not being shaded, refer to the table below.)

2:The DipSW setting is only effective during unit stopping (remote controller OFF) for SW1, 2, 3 and 4 commonly and the power source is not required to reset.)

3:When both SW1-7 and SW1-8 are being set to ON, the fan stops at the heating thermostat of OFF.

 

Model

PLFY-NAMU-A

PDFY-NMU-A

 

PKFY

 

 

 

 

 

 

Switch

NAMU-A

 

NGMU-A

 

 

 

 

 

3

ON

ON

 

OFF

 

 

 

 

 

 

 

 

SW1

 

6

ON

ON

 

OFF

 

 

 

 

 

 

 

 

7

OFF

OFF

 

OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

3

ON

OFF

 

ON

 

 

 

 

 

 

 

 

SW3

 

4

ON

OFF

OFF

 

ON

 

 

 

 

 

 

 

 

6

OFF

OFF

 

OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

8

OFF

OFF

 

OFF

 

 

 

 

 

 

 

 

Setting of DIP SW2

Model

 

08

 

 

10

 

 

 

12

 

 

16

 

 

20

 

24

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Capacity (model name) code

 

4

 

 

5

 

 

 

6

 

 

8

 

 

10

 

13

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SW2 setting

ON

 

 

 

ON

 

 

 

 

 

 

ON

 

 

 

 

ON

 

 

ON

 

 

ON

 

 

OFF

 

 

 

OFF

 

 

 

 

 

 

OFF

 

 

 

 

OFF

 

 

OFF

 

 

OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Model

 

32

 

 

40

 

 

 

48

 

 

 

 

 

 

 

 

 

 

Capacity (model name) code

 

16

 

 

20

 

 

 

25

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SW2 setting

ON

 

 

 

ON

 

 

 

 

 

 

 

ON

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OFF

 

 

 

OFF

 

 

 

 

 

 

 

OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

- 13 -

Setting of DIP SW4

 

 

 

 

 

 

Setting of DIP SW5

 

 

 

 

 

 

 

 

 

 

 

 

 

Model

Circuit board used

 

 

SW4

 

 

 

 

 

 

 

1

2

 

3

4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PDFY-10 ~ 32

 

ON

OFF

 

ON

OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PLFY-12 ~ 24

Phase control

OFF

OFF

 

OFF

ON

 

 

 

 

 

 

 

 

 

 

 

 

 

PLFY-32 ~ 48

ON

OFF

 

OFF

ON

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PKFY-P-8

 

OFF

OFF

 

ON

ON

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PKFY-P-12

 

 

 

 

 

 

 

 

PDFY-40, 48

Relay selection

OFF

OFF

 

ON

 

 

 

 

 

 

- 14 -

2TEST RUN

[1]Before Test Run

(1) Check points before test run

1 Neither refrigerant leak nor loose power source/ transmission lines should be found, if found correct immediately.

2 Confirm that the resistance between the power source terminal block and the ground exceeds 2MΩ by measuring it with a DC500V megger. Do not run if it is lower than 2MΩ .

Note : Never apply the megger to the MAIN board. If applied, the MAIN board will be broken.

3Confirm that the Ball valve at both gas and liquid sides are fully opened. Note : Close the cap.

4Be sure that the crankcase heater has been powered by turning the main power source on at least 12 hours before starting the test run. The shorter powering time causes compressor trouble.

(2)Caution at inverter check

Because the inverter power portion in outdoor unit electrical part box have a lot of high voltage portion, be sure to follow the instructions shown below.

During energizing power source, never touch inverter power portion because high voltage (approx. 320V) is

1applied to inverter power portion.

When checking,

1Shut off main power source, and check it with tester, etc.

2Allow 10 minutes after shutting off main power source.

3Open the MAIN board mounting panel, and check whether voltage of both ends of electrolytic capacitor is 20V or less.

- 15 -

(3) Check points for test run when mounting options

Built-in optional parts

 

Content of test run

Check point

Result

 

 

 

 

 

Mounting of drain

1

Release connector of pump circuit,

Local remote controller displays code

 

water pump

 

check error detection by pouring

No. “2503”, and the mechanism stops.

 

mechanism

 

water into drain pan water inlet.

 

 

 

No overflow from drain pan.

 

 

 

 

 

 

 

 

 

 

 

2

After that, connect connector of

Drain water comes out by operation of

 

 

 

circuit.

drain pump.

 

 

 

 

 

 

 

3

Check pump operations and drain-

Sound of pump operations is heard, and

 

 

 

age status in cooling (test run) mode.

drain water comes out.

 

 

 

 

 

Mounting of perme-

Check humidifier operations and water

No water leak from connecting portions

 

able film humidifier

supply status in heating (test run) mode.

of each water piping.

 

 

 

 

 

 

 

 

 

Water is supplied to water supply tank,

 

 

 

 

and float switch is operating.

 

 

 

 

 

 

(4) Attention for mounting drain water pump mechanism

Work

 

Content of test run

 

Check point

Result

 

 

 

 

 

 

Disassembling and

1

Lead wire from control box not

 

 

 

assembling of drain

 

damaged.

 

 

 

water pump

 

 

 

 

 

 

 

 

 

 

mechanism

2

Rubber cap properly inserted in to

 

pipe

 

 

 

drain water outlet of drain pan?

 

 

 

 

 

 

 

 

 

 

3

Insulation pipe of gas and liquid

 

 

 

 

pipes dealt with as shown on next

 

 

 

 

 

 

 

 

 

 

page?

 

 

 

 

 

 

 

 

 

 

4

Drain pan and piping cover mounted

 

 

 

 

 

without gap?

 

 

 

 

 

 

 

 

 

 

5

Drain pan hooked on cut projection

 

 

 

 

of the mechanism?

 

 

 

 

 

 

 

 

 

 

 

 

Mounting of float

Float switch installed without contacting the

1 Float switch moves smoothly.

 

switch

drain pan?

 

 

 

2

Float switch is mounted on

 

 

 

 

 

 

 

 

mounting board straight without

 

 

 

 

 

 

 

 

 

 

deformation.

 

 

 

 

 

 

 

 

 

3 Float switch does not contact the

 

 

 

 

 

copper pipe.

 

 

 

 

 

 

Electric wiring

1

No mistakes in wiring?

Wiring procedure is exactly followed.

 

 

 

 

 

 

 

2

Connectors connected securely and

Connector portion is tightly hooked.

 

 

tightly?

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3

No tension on lead wire when sliding

 

 

 

 

control box?

 

 

 

 

 

 

 

 

 

 

 

 

 

 

- 16 -

(5)Check points for system structure

Check points from installation work to test run.

Classification Portion

Check item

Trouble

 

 

 

 

 

 

Installation and

 

Instruction for selecting combination of outdoor unit,

 

 

piping

1

and indoor unit followed? (Maximum number of indoor

Not operate.

 

 

units which can be connected, connecting model name,

 

 

 

and total capacity.)

 

 

 

 

 

 

 

 

2

Follow limitation of refrigerant piping length? For example,

 

 

 

70m (229ft) or less (total length : 220m (721ft)) at the farthest.

Not cool (at cooling).

 

 

3

Connecting piping size of branch piping correct?

Not heat (at heating).

 

 

 

 

 

 

4

Refrigerant piping diameter correct?

 

 

 

 

 

 

 

 

 

 

5

Refrigerant leak generated at connection?

Not cool, not heat, error stop.

 

 

 

 

 

 

 

6

Insulation work for piping properly done?

Condensation drip in piping.

 

 

 

 

 

 

 

7

Specified amount of refrigerant replenished?

Not cool, not heat, error stop.

 

8Pitch and insulation work for drain piping properly done? Water leak, condensation drip in drain piping.

Power source

1

Specified switch capacity and wiring diameter of main

Error stop, not operate.

wiring

power source used?

 

 

 

 

 

 

 

2

Proper grounding work done on outdoor unit?

Electric shock.

 

 

 

 

 

3

The phases of the L line (L1, L2, L3) correct?

Error stop, not operate.

- 17 -

DRY COOL

CENTRALLY CONTROLLED

 

SENSOR

DRY COOL

CENTRALLY CONTROLLED

 

SENSOR

AUTO FAN

DAILY TIMER

AUTO AUTO

FAN

INSIDE

AUTO FAN

DAILY TIMER

AUTO AUTO

FAN

INSIDE

CLOCK ON OFF

FILTER

CLOCK ON OFF

FILTER

 

SPEED

 

SPEED

HEAT

CHECK SET TEMP.

REMAINDER

 

 

HEAT

CHECK SET TEMP.

REMAINDER

 

 

STAND BY

VENTILATION

TEST RUN

STAND BY

VENTILATION

TEST RUN

DEFROST

EROR CODE NOT AVAILABLE

 

DEFROST

EROR CODE NOT AVAILABLE

 

SET TEMP.

 

ON/OFF

SET TEMP.

 

ON/OFF

1

2

3

MODE

TIMER

CLOCK ON OFF FAN SPEED

AIR DIRECTION FILTER

MODE

TIMER

CLOCK ON OFF FAN SPEED

AIR DIRECTION FILTER

 

 

 

 

 

 

 

 

LOUVER

VENTILATION CHECK TEST

 

 

LOUVER

VENTILATION CHECK TEST

 

 

 

PAR-F27MEA-US

TIMER SET

 

PAR-F27MEA-US

TIMER SET

 

Classification

Portion

Check item

Trouble

 

 

 

 

Transmission

1

Limitation of transmission line length followed? For example,

Erroneous operation, error stop.

line

200m (656ft) or less (total length : 500m (1640ft)) at the farthest.

 

 

 

 

 

 

2

1.25mm2 (AWG16) or more transmission line used?

Erroneous operation, error stop.

 

 

(Remote controller 10m (32ft) or less 1.25mm2 (AWG16))

 

 

3

2-core cable used for transmission line?

Error stop in case multiple-core

 

 

 

cable is used.

 

 

 

 

 

4

Transmission line apart from power source line by 5cm (2in) or more?

Erroneous operation, error stop.

 

 

 

 

 

5

One refrigerant system per transmission line?

Not operate.

 

 

 

 

 

6

The short circuit connector is changed form CN41 to

Not operate.

 

 

CN40 on the MAIN board when the system is centralized

 

 

 

control? (Just one outdoor unit. Not all outdoor units.)

 

 

 

 

 

 

7

• No connection trouble in transmission line?

Error stop or not operate.

 

 

 

 

 

8

Connection of wrong remote controller line terminals?

Never finish the initial mode.

 

 

• MA Remote controller : TB15

 

 

 

• M-NET Remote controller : TB5

 

 

 

 

 

System set

1

Address setting properly done? (M-NET Remote

Error stop or not operate.

 

controller, indoor unit and outdoor unit.)

 

 

 

 

 

 

 

 

 

2

Setting of address No. done when shutting off power

Can not be properly set with power

 

source?

source turned on.

 

 

 

 

 

 

 

3

Address numbers not duplicated?

Not operate.

 

 

 

 

 

4

Turned on SW3-8 on indoor unit circuit board when

Set temperature not obtained at

 

mounting room thermistor sensor?

heating operations (Thermostat

 

 

 

 

 

stop is difficult)

 

 

 

 

Before starting

1

Refrigerant piping ball valve (Liquid pressure pipe, gas

Error stop.

 

 

pressure pipe) opened?

 

2Turn on power source 12 hours before starting operations? Error stop, compressor trouble.

-18 -

AIR DIRECTION
FAN SPEED

[2]

Test Run Method

 

 

 

 

 

 

 

Operation procedure

 

 

1

Turn on universal power supply at least 12 hours before starting → Displaying “HO” on display panel for about two

 

minutes

 

 

 

 

 

2

Press

TEST

button twice → Displaying “TEST RUN’’ on display panel

 

 

 

 

3

Press

MODE

button → Make sure that air is blowing out

 

 

 

 

 

Press

MODE

button to change from cooling to heating operation, and vice versa Make sure that warm or cold

4air is blowing out

5 Press

FAN SPEED adjust button →

Make sure that air blow is changed

 

 

 

Press

AIR DIRECTION or LOUVER

button to change direction of air blowing make sure that horizontal or

6downward blow is adjustable.

7Make sure that indoor unit fans operate normally

8Make sure that interlocking devices such as ventilator operate normally if any

9 Press ON/OFF button to cancel test run → Stop operation

Note 1: If check code is displayed on remote controller or remote controller does not operate normally.

2:Test run automatically stops operating after two hours by activation of timer set to two hours.

3:During test run, test run remaining time is displayed on time display section.

4:During test run, temperature of liquid pipe in indoor unit is displayed on remote controller room temperature display section.

5: When pressing adjust button, depending on the model, “NOT AVAILABLE” may be displayed on remote controller. However, it is not a malfunction.

6: When pressing or LOUVER button, depending on the model, “NOT AVAILABLE” may be displayed on remote controller. However, it is not a malfunction.

- 19 -

3GROUPING REGISTRATION OF INDOOR UNITS WITH M-NET REMOTE CONTROLLER

(1)Switch function

• The switch operation to register with the remote controller is shown below:

i

ii

DRY COOL

CENTRALLY CONTROLLED

 

SENSOR

AUTO FAN

DAILY TIMER

AUTO AUTO

FAN

INSIDE

CLOCK ON

OFF

 

 

SPEED

FILTER

HEAT

CHECK SET TEMP.

REMAINDER

 

 

 

STAND BY

 

EROR CODE

VENTILATION

TEST RUN

 

C Switch to assign

DEFROST

 

NOT AVAILABLE

 

 

 

 

 

 

 

 

indoor unit address

 

SET TEMP.

 

ON/OFF

 

F Delete switch

 

 

 

 

 

A Registration/

G Registered mode

MODE

TIMER

CLOCK ON OFF FAN SPEED AIR DIRECTION FILTER

ordinary mode

selector switch

 

 

 

 

 

 

selector switch

E Confirmation switch

LOUVER

VENTILATION CHECK TEST

DRegistration switch

PAR-F27MEA-US

TIMER SET

B Registration/ ordinary mode selector switch

HSwitch to assign interlocked unit address

Name

Symbol

Name of actual switch

Description

 

of switch

 

 

 

 

 

 

 

 

 

 

Registration/ordinary

A +

B

FILTER + LOUVER

This switch selects the ordinary mode or registered mode (ordinary

mode selection switch

 

 

 

mode represents that to operate indoor units).

 

 

 

 

 

 

 

 

To select the registered mode, press the

FILTER + LOUVER

 

 

 

 

button continuously for over 2 seconds under stopping state.

 

 

 

 

[Note] The registered mode can not be obtained for a while after

 

 

 

 

powering.

 

 

 

 

 

Pressing the FILTER + LOUVER button displays “CENTRALLY

 

 

 

 

CONTROLLED”.

 

 

 

 

 

 

Switch to assign indoor

C

 

of TEMP

This button assigns the unit address for “INDOOR UNIT ADDRESS

unit address

 

 

 

NO.”

 

 

 

 

 

 

 

 

 

 

 

Registration switch

D

 

TEST RUN

This button is used for group/interlocked registration.

 

 

 

 

 

 

 

 

Confirmation switch

E

TIMER

This button is used to retrieve/identify the content of group and

 

 

 

interlocked (connection information) registered.

 

 

 

 

 

Delete switch

F

 

CLOCK→

This button is used to retrieve/identify the content of group and

 

 

 

ON→ OFF

interlocked (connection information) registered.

 

 

 

 

 

Registered mode

G

 

 

This button selects the case to register indoor units as group (group

selector switch

 

 

 

setting mode) or that as interlocked (interlocked setting mode).

 

 

 

MODE

 

 

 

The unit address is shown at one spot

for the group setting mode

 

 

 

 

 

 

 

 

while at two spots for the interlocked setting mode.

 

 

 

 

 

Switch to assign

H

 

of TIMER SET

This button assigns the unit address of “OA UNIT ADDRESS NO.”

interlocked unit address

 

 

 

 

 

 

 

 

 

 

 

- 20 -

(2) Attribute display of unit

At the group registration and the confirmation/deletion of registration/connection information, the type (attribute) of the unit is displayed with two English characters.

Display

Type (Attribute) of unit/controller

Indoor unit connectable to remote controller

Outdoor unit

Local remote controller

System controller (MJ)

[Description of registration/deletion/retrieval]

The items of operation to be performed by the remote controller are given below. Please see the relating paragraph for detail.

1Group registration of indoor unit

The group of the indoor units and operating remote controller is registered.

It is usually used for the group operation of indoor units with different refrigerant system.

2Retrieval/identification of group registration information of indoor units

The address of the registered indoor units in group is retrieved (identified).

3Retrieval/identification of registration information

The connection information of any unit (indoor/outdoor units, remote controller or the like) is retrieved (identified).

4Deletion of group registration information of indoor units

The registration of the indoor units under group registration is released (deleted).

5Deletion of the address not existing

This operation is to be conducted when “6607” error (No ACK error) is displayed on the remote controller caused by the miss setting at test run, or due to the old memory remained at the alteration/modification of the group composition.

Caution:

When MELANS (G-50 for example) is being connected, do not conduct the group/pair registration using

the remote controller. The group/pair registration should be conducted by MELANS. (For detail, refer to the instruction exclusively prepared for MELANS.)

- 21 -

(3) Group registration of indoor unit

1)Registration method

Group registration of indoor unit ........................................................................ 1

The indoor unit to be controlled by a remote controller is registered on the remote controller.

[Registration procedure]

1 With the remote controller under stopping or at the display of “HO”, continuously press the FILTER + LOUVER button ( A + B) at the same time for 2 seconds to change to the registration mode. (See the figure below.)

2Assign the indoor unit address to “INDOOR UNIT ADDRESS NO.” by operating the (Room temperature adjustment) ( C).

Then press the TEST RUN button (D) to register. In the figure below, the “INDOOR UNIT ADDRESS NO.” is being set to 001.

3 After completing the registration, press the

FILTER + LOUVER button ( A+ B) at the same time for 2 seconds to

change to the original ordinary mode (with the remote controller under stopping).

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Ordinary mode

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

• Remote controller under stopping

• “HO” under displaying

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

˚C

 

 

 

 

 

 

 

˚C

 

 

 

 

 

 

 

INDOOR UNIT

 

ERROR CODE

 

 

 

 

INDOOR UNIT

 

ERROR CODE

 

 

 

 

 

ADDRESS NO

 

OAUNITADDRESSNO

 

 

 

 

ADDRESS NO

 

OAUNITADDRESSNO

 

 

11

Group setting mode

˚C

ERROR CODE

OAUNITADDRESSNO

• Registration complete

˚C

ERROR CODE

OAUNITADDRESSNO

Indicates the type of unit (Indoor unit in this case)

2 + 3

• Registration error

˚C

ERROR CODE

OAUNITADDRESSNO

“88” flickers indicating registration error. (when the indoor unit registered is not existing)

2 Assign the

1 Change to the

3Press the

address (C)

registration

registration

 

mode ( A+ B)

switch (D)

 

 

System example

 

 

 

Indoor units

 

 

Group

 

Remote controller

 

 

 

 

- 22 -

 

Confirm the indoor unit address No.

Confirm the connection of the transmission line.

2)Method of retrieval/confirmation

Retrieval/confirmation of group registration information on indoor unit............... 2

The address of the indoor unit being registered on the remote controller is displayed.

[Operation procedure]

1With the remote controller under stopping or at the display of “HO”, continuously press the FILTER + LOUVER button (A+ B) at the same time for 2 seconds to change to the registration mode.

2In order to confirm the indoor unit address already registered, press TIMER button (E). (See figure below.) When the group of plural sets is registered, the addresses will be displayed in order at each pressing of TIMER button (E).

3After completing the registration, continuously press the FILTER + LOUVER button ( A+ B) at the same time for 2 seconds to change to the original ordinary mode (with the remote controller under stopping).

• Registered

 

SET TEMP.

ON/OFF

MODE

TIMER

CLOCK ON OFF FAN SPEED

AIR DIRECTION FILTER

 

 

LOUVER

VENTILATION CHECK TEST

PAR-F27MEA-US

TIMER SET

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

˚C

 

 

 

 

 

 

 

 

ERROR CODE

 

 

 

 

 

 

OAUNITADDRESSNO

 

1

Indicates the type of unit

 

(Indoor unit in this case)

 

• No registration.

˚C

ERROR CODE

OAUNITADDRESSNO

1Press the switch for confirmation (E)

Note: Only one address will be displayed when the registration is one even the switch is how often pressed

Retrieval/confirmation of registration information ................................................ 3

The registered information on a certain unit (indoor unit, outdoor unit, remote controller or the like) is displayed.

[Operation procedure]

 

1 With the remote controller under stopping or at the display of “HO”, continuously press the

FILTER + LOUVER button

(A + B) at the same time for 2 seconds to change to the registration mode.

 

2 Operate MODE button (G) for the interlocked setting mode. (See figure below.)

 

3 Assign the unit address of which registration information is desired to confirm with the

(TIMER SET) switch

(H). Then press the TIMER button (E) to display it on the remote controller. (See figure below.) Each pressing of TIMER button (E) changes the display of registered content. (See figure below.)

4 After completing the retrieval/confirmation, continuously press the FILTER + LOUVER button (A + B) at the same time for 2 seconds to change to the original ordinary mode (with the remote controller under stopping).

- 23 -

 

 

 

• Registered

 

 

 

 

ß C

 

 

 

 

(Alternative

 

 

 

 

display)

 

 

 

ß C

 

 

SET TEMP.

 

ON/OFF

 

MODE

TIMER CLOCK

ON OFF FAN SPEED

AIR DIRECTION FILTER

 

 

 

LOUVER

VENTILATION CHECK TEST

 

PAR-F27MEA-US

TIMER SET

 

 

2

 

 

 

ß C

 

 

 

 

 

 

 

1 + 2

 

 

 

 

(Alternative

 

 

 

 

display)

2 Press the switch for

1Set the address

 

confirmation (E)

 

ß C

 

 

 

 

˚C

 

 

 

 

INDOOR UNIT

ERROR CODE

 

 

 

ADDRESS NO

OAUNITADDRESSNO

* Same display will appear when

the unit of “007” is not existing.

• No registration

˚C

ERROR CODE

OAUNITADDRESSNO

3)Method of deletion

• Deletion of group registration information of indoor unit ...................................... 4

[Operation procedure]

1With the remote controller under stopping or at the display of “HO”, continuously press the FILTER + LOUVER button ( A + B) at the same time for 2 seconds to change to the registration mode.

2 Press the TIMER button (E) to display the indoor unit address registered. (As same as 2)

3 In order to delete the registered indoor unit being displayed on the remote controller, press the TIMER CLOCK → ON→ OFF (F) button two times continuously. At completion of the deletion, the attribute display section will be shown as “– – “. (See figure below.)

Note: Completing the deletion of all indoor units registered on the remote controller returns to “HO” display.

4 After completing the registration, continuously press the FILTER + LOUVER button ( A+ B) at the same time for 2 seconds to change to the original ordinary mode (with the remote controller under stopping).

• Deletion completed

 

SET TEMP.

ON/OFF

MODE

TIMER

CLOCK ON OFF FAN SPEED

AIR DIRECTION FILTER

1

 

 

 

 

 

 

 

 

˚C

 

 

 

In case of group re-

INDOOR UNIT

ERROR CODE

 

ADDRESS NO

OAUNITADDRESSNO

 

gistration with other

“–” indicates the

indoor unit is existing

deletion completed.

• Deletion completed

1

LOUVER

VENTILATION CHECK TEST

PAR-F27MEA-US

TIMER SET

1Press the switch for confirmation ( E ) twice continuously.

In case of no group registration with other indoor unit is existing

˚C

 

INDOOR UNIT

ERROR CODE

ADDRESS NO

OAUNITADDRESSNO

- 24 -

4)Deletion of information on address not existing

Deletion of information on address not existing ................................................... 5

This operation is to be conducted when “6607” error (No ACK error) is displayed on the remote controller caused by the miss setting at test run, or due to the old memory remained at the alteration/modification of group composition, and the address not existing will be deleted.

Note: The connection information (connection between indoor unit and outdoor unit) on the refrigerant system can not be deleted.

An example to delete the system controller of “250” from the indoor unit of “007” is shown below.

[Operation procedure]

1With the remote controller under stopping or at the display of “HO”, continuously press the FILTER + LOUVER button (A+ B) at the same time for 2 seconds to change to the registration mode.

2Operate MODE button (G) for the interlocked setting mode ( ii ). (See the figure below.)

3Assign the unit address existing to “OA UNIT ADDRESS No.” with the (TIMER SET) switch (H), and press TIMER button (E) to call the address to be deleted. (See the figure below.) As the error display on the remote controller is usually transmitted from the indoor unit, “OA UNIT ADDRESS No.” is used as the address of the indoor unit.

4Press the TIMER CLOCK → ON→ OFF button (F) twice. (See the figure below.)

5After completing the deletion, continuously press the FILTER + LOUVER button ( A+ B) at the same time for 2 seconds to return to the original ordinary mode (with the remote controller under stopping).

• Deletion completed

 

 

 

When both indoor

 

 

 

 

 

unit and interlocked

 

 

 

ß C

 

unit addresses are

ß C

ERROR CODE

INDOOR UNIT

ERROR CODE

existing

INDOOR UNIT

ADDRESS NO

OAUNITADDRESSNO

ADDRESS NO

OAUNITADDRESSNO

 

(Alternative

 

(Alternative

 

 

 

display)

 

 

display)

3

 

 

 

 

 

 

ß C

 

 

ß C

 

 

 

3

INDOOR UNIT

ERROR CODE

INDOOR UNIT

ERROR CODE

ADDRESS NO

OAUNITADDRESSNO

ADDRESS NO

OAUNITADDRESSNO

 

 

 

 

 

 

 

 

 

 

1+ 2

 

 

 

 

 

 

 

• Deletion completed

 

 

 

 

ß C

 

 

 

 

 

INDOOR UNIT

ERROR CODE

 

 

 

 

ADDRESS NO

OAUNITADDRESSNO

 

 

 

Deletion of

(Alternative

 

 

 

address not

 

display)

 

 

 

existing

 

 

 

SET TEMP.

ON/OFF

ß C

 

 

 

 

 

INDOOR UNIT

ERROR CODE

 

 

 

 

ADDRESS NO

OAUNITADDRESSNO

MODE

TIMER CLOCK ON OFF FAN SPEED

AIR DIRECTION FILTER

 

 

 

 

 

 

LOUVER

VENTILATION CHECK TEST

 

 

PAR-F27MEA-US

 

TIMER SET

 

 

 

2Press the switch for

3Press the deletion switch (F) twice

confirmation (E)

1 Set the address (H)

 

- 25 -

4 CONTROL

[1]Control of Outdoor Unit

(1)Initial processing

When turning on power source, initial processing of microcomputer is given top priority.

During initial processing, control processing corresponding to operation signal is suspended. The control processing is resumed after initial processing is completed. (Initial processing : Data processing in microcomputer and initial setting of each LEV opening, requiring approx. 2 minutes at the maximum.)

(2)Control at staring

In case unit is started within 2 hours after turning on power source at low outdoor air temperature (+5˚C (41 ° F) or

less), the unit does not start operating for 30 minutes at the maximum

.

(3)Bypass, capacity control

Solenoid valve consists of bypass solenoid valve (SV1, SV2) bypassing between high pressure side and low pressure side. The following operation will be provided.

1)Bypass solenoid valves SV1 and SV2 (both "open" when turned on)

Item

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SV1

 

 

 

 

 

 

 

 

 

 

 

SV2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ON (Open)

 

OFF (Close)

 

 

ON (Open)

 

 

 

 

 

 

 

 

 

 

 

 

OFF (Close)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

When starting compressor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Turned on for 4 minutes

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

After thermost "ON is returned

 

 

 

 

 

 

 

 

 

Turned on for 2 minutes

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

and after 3 minutes restart

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

When compressor stops in

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Always turned on

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

cooling or heating mode

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

After operation stops

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Turned on for 3 minutes

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

During defrosting operations

 

 

 

 

 

 

 

 

 

Always turned on

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(See figure below 1)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

During oil recovery operations

 

 

Always turned on in oil recovery

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

operation after low frequency

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

continuous operations

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

During 20Hz operations, at fall

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

When low pressure

 

When low pressure

in low pressure saturation

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

saturation temp. (ET)

 

saturation temp.

temperature. (ET) (3 minutes or

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

is -30˚C (-22° F) or less

 

(ET) is -15˚C (5° F) or

more after starting)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

more

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

When high pressure rises (Pd)

 

 

When Pd reaches

When Pd is

When Pd reaches

 

When Pd is 23kg/

 

 

 

 

 

 

 

 

 

 

 

 

27.5kg/cm2G

 

 

 

 

 

 

24kg/cm2G (341psi) or

26kg/cm2G (370psi)

 

cm2G (327psi) or less

 

 

 

 

 

 

 

 

 

 

 

 

(391psi) or more

less 30 seconds

or more

 

after 30 seconds

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

When high pressure rises (Pd)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Turned on when high

 

When high pressure

during 20Hz operations

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

pressure (Pd) ex-

 

(Pd) is 20kg/cm2G

(3 minutes after starting)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ceeds pressure limit

 

(284psi) or less

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

When discharge temperature

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

When temp. exceeds

 

When discharge

rises

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

130˚C (266° F) and Pd reaches

 

temp. is 115˚C

(3 minutes after starting)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

15kg/cm2G (213psi) or more

 

(239° F) or less

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Ex. SV1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Compressor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Bypass

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

solenoid

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

valve

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Thermo.

 

Thermo.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Start

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Stop

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Defrost-

 

 

 

 

 

 

 

 

(SV1)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OFF

 

ON

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ing time

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(*1)

(4-minute)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(4-minute)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(2-minute)

 

 

 

 

 

 

 

 

(3-minute)

- 26 -

Loading...
+ 66 hidden pages