Mitsubishi Electronics PMFY-P08NBMU-E1, PMFY-P12NBMU-E1, PMFY-P08NBMU-E, PMFY-P06NBMU-E1, PMFY-P06NBMU-E User Manual

...
0 (0)

SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS

July 2007

No. OC341

REVISED EDITION-B

TECHNICAL & SERVICE MANUAL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Indoor unit

 

 

 

 

 

[Model names]

 

[Service Ref.]

PMFY-P06NBMU-E

 

PMFY-P06NBMU-E

 

 

 

 

PMFY-P06NBMU-E1

PMFY-P08NBMU-E

 

PMFY-P08NBMU-E

 

 

 

 

PMFY-P08NBMU-E1

PMFY-P12NBMU-E

 

PMFY-P12NBMU-E

 

 

 

 

PMFY-P12NBMU-E1

PMFY-P15NBMU-E

 

PMFY-P15NBMU-E

 

 

 

 

PMFY-P15NBMU-E1

R410A / R22

Revision:

PMFY-P06/08/12/15NBMU-E1 are added in REVISED EDITION-B.

Some descriptions have been modified.

Please void OC341 REVISED EDITION-A.

NOTE:

This manual describes only service data of the indoor units.

RoHS compliant products have <G> mark on the spec name plate.

For servicing RoHS compliant products, refer to the RoHS PARTS LIST.

CONTENTS

1.TECHNICAL CHANGES··········

2.FEATURES ················

3.PART NAMES AND FUNCTIONS ······

4.SPECIFICATION ··············

5.OUTLINES AND DIMENSIONS·······

6.WIRING DIAGRAM·············

7.REFRIGERANT SYSTEM DIAGRAM ···12

8.MICROPROCESSOR CONTROL······

9.TROUBLESHOOTING ···········

10.DISASSEMBLY PROCEDURE········

11.PARTS LIST················

12.RoHS PARTS LIST·············

INDOOR UNIT

1 TECHNICAL CHANGES

PMFY-P06NBMU-E PMFY-P08NBMU-E PMFY-P12NBMU-E PMFY-P15NBMU-E

PMFY-P06NBMU-E1

PMFY-P08NBMU-E1

PMFY-P12NBMU-E1

PMFY-P15NBMU-E1

1.FAN MOTOR(MF) has been changed.

2.CONTROLLER BOARD(I.B) has been changed.

2 FEATURES

Models

Cooling capacity / Heating capacity

PMFY-P06NBMU-E

6,000 /

6,700 Btu/h

PMFY-P08NBMU-E

8,000 /

9,000 Btu/h

PMFY-P12NBMU-E

12,000 / 13,500 Btu/h

PMFY-P15NBMU-E

15,000 / 17,000 Btu/h

1. Fresh Air Intake

Air recycled indefinitely can become stale and stagnant with air quality suffering significantly. Fresh air is the answer and it is for this reason that the PMFYseries takes in air directly from outdoors. This fresh air intake allows you to enjoy the comfort of crisp, refreshing air in the confines of your living or working space.

2. Light and Compact

The main unit weighs only 31 lb. and the panel merely 7 lb. This makes the PMFYseries one of the lightest in the industry. The unit size is also quite small, having been standardised to a strikingly compact 33-5/8 inch. All of this make the chore of installation and maintenance that much simpler and easier.

2

3 PART NAMES AND FUNCTIONS

Indoor Unit

Auto Air Swing Vane

 

 

 

Guide vane

 

Disperses airflow up and

 

 

down and adjusts the angle

 

Air flow can be

changed to horizontal

of airflow direction.

by moving the guide vane to the left or right.

 

 

 

 

 

 

 

 

Horizontal Air Outlet

Filters

Air intake

Remove dust and pollutants

Returns air from room.

from return air.

 

Wired remote controller

Once the controllers are set, the same operation mode can be repeated by simply pressing the ON/OFF button.

Temperature setting buttons

 

 

 

Down

 

 

 

Up

 

 

 

Timer Menu button

 

 

 

(Monitor/Set button)

 

 

 

Mode button (Return button)

 

 

 

 

 

TEMP.

 

Set Time buttons

 

 

 

Back

 

MENU

ON/OFF

Ahead

BACK

MONITOR/SET

DAY

 

Timer On/Off button

PAR-21MAA

CLOCK

(Set Day button)

 

 

 

Opening the

 

 

 

lid

 

 

 

 

ON/OFF

 

 

FILTER

 

CHECK

TEST

OPERATION

CLEAR

 

Built-in temperature sensor

ON/OFF button

Fan Speed button

Filter button (<Enter> button)

Test Run button

Check button (Clear button)

Airflow Up/Down button

Louver button

( Operation button)

To return operation number

Ventilation button

(Operation button)

To go to next operation number

3

Wired remote controller

Display Section

For purposes of this explanation,

Day-of-Week

all parts of the display are shown

Shows the current day of the week.

as lit. During actual operation, only

 

the relevant items will be lit.

Time/Timer Display

Shows the current time, unless the simple or Auto Off timer is set.

If the simple or Auto Off timer is set, the time to be switched off is shown.

Identifies the current operation

Shows the operating mode, etc. *Multilanguage display is available.

 

TIME SUN MON TUE WED THU FRI SAT

 

TIMER

Hr

ON

 

AFTER

AFTER

OFF

 

ERROR CODE

 

FUNCTION

 

˚F˚C

 

FILTER

“Centrally Controlled” indicator

˚F˚C

 

 

WEEKLY

Indicates that operation from the

ONLY1Hr.

 

SIMPLE

 

AUTO OFF

remote controller has been prohib-

 

 

 

ited by a master controller.

 

 

 

 

 

Up/Down Air Direction indica-

 

Room Temperature display

“Timer is Off” indicator

 

 

 

 

tor

 

Shows the room temperature. The room

 

 

 

 

Shows the direction of the

 

temperature display range is 46~102°F.

Indicates that the timer is off.

 

 

 

 

outcoming airflow.

 

The display blinks if the temperature

 

 

 

 

 

 

 

is less than 46°F or 102°F or more.

 

 

 

 

 

“One Hour Only” indicator

 

Louver display

 

 

 

 

 

 

 

 

 

 

 

 

Displayed if the airflow is set to

 

 

 

 

 

 

 

 

 

 

 

 

 

Indicates the action of the swing louver.

Temperature Setting

 

 

 

 

low or downward during COOL

 

 

 

 

 

or DRY mode. (Operation varies

 

Does not appear if the louver is not

Shows the target temperature.

 

 

 

 

according to model.)

 

running.

 

 

 

 

 

The indicator goes off in one hour,

 

(Power On indicator)

 

 

 

 

 

when the airflow direction also

 

 

 

 

 

 

changes.

 

Indicates that the power is on.

“Sensor” indication

Displayed when the remote controller sensor is used.

“Locked” indicator

Indicates that remote controller buttons have been locked.

“Clean The Filter” indicator

To be displayed on when it is time to clean the filter.

Timer indicators

The indicator comes on if the corresponding timer is set.

Fan Speed indicator

Shows the selected fan speed.

Ventilation indicator

Appears when the unit is running in Ventilation mode.

Note:

“PLEASE WAIT” message

This message is displayed for approximately 3 minutes when power is supplied to the indoor unit or when the unit is recovering from a power failure.

“NOT AVAILABLE” message

This message is displayed if an invalid button is pressed (to operate a function that the indoor unit does not have).

If a single remote controller is used to operate multiple indoor units simultaneously that are different types, this message will not be displayed as far as any of the indoor units is equipped with the function.

4

4 SPECIFICATION

4-1. SPECIFICATIONS

Item

 

 

Power

V·Hz

Cooling capacity

Btu/h

Heating capacity

Btu/h

characteristic

 

Input

 

Cooling

kW

 

 

 

 

 

 

 

 

Heating

 

 

 

 

 

 

kW

Electric

 

Current

 

Cooling

A

 

 

Heating

A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Exterior

(munsell symbol)

 

 

 

 

 

Height

in.

 

 

 

 

 

Dimensions

 

Width

in.

 

 

 

 

 

Depth

in.

Heat exchanger

n

 

Fan No

 

 

Air flow W3

CFM

a

 

 

External

 

 

 

in W.G.

F

 

static pressure

 

 

Fan motor

kW

 

 

output

 

 

Insulator

 

 

Air filter

 

 

 

 

 

 

 

Pipe

 

 

Gas

[in.

 

 

 

 

 

 

side

dimensions

 

 

Liquid

[in.

 

 

 

 

 

side

Field drain pipe size

[in.

Noise level W3

dB

Product weight

lb.

PMFY-P06NBMU-E

PMFY-P08NBMU-E

PMFY-P12NBMU-E

 

PMFY-P15NBMU-E

PMFY-P06NBMU-E1

PMFY-P08NBMU-E1

PMFY-P12NBMU-E1

 

PMFY-P15NBMU-E1

 

 

 

 

 

 

Single phase 208-230V 60Hz

 

 

6,000

 

12,000

 

15,000

8,000

 

6,700

9,000

13,500

 

17,000

0.042

0.042

0.044

 

0.054

0.042

0.042

0.044

 

0.054

0.20

0.20

0.21

 

0.26

0.20

0.20

0.21

 

0.26

 

 

 

 

 

Unit : Galvanized sheets · Standard grilles : ABS resin acrylic coating

Munsell<6.4Y 8.9/0.4>

 

9-1/16<1-3/16>

 

 

 

31-15/16<39-3/8>

 

 

 

15-9/16<18-1/2>

 

 

 

Cross fin

 

 

 

Line flow fan 1

 

 

230-250-280-300

 

 

250-280-300-320

 

270-300-340-370

 

 

 

 

 

0

 

 

0.028

Polyethylene sheet

PP honey comb fabric

1/2"

1/4"

1" O.D. (PVC pipe VP-20 connectable)

27-30-33-35

32-34-36-37

33-35-37-39

 

 

 

31<7>

Note 1.

Rating conditions

 

 

 

Cooling: Indoor:

D.B. 80°F

W.B. 67°F

 

outdoor: D.B. 95°F

W.B. 75°F

 

Heating: Indoor:

D.B. 70°F

 

 

outdoor: D.B. 47°F

W.B. 43°F

Note 2.

The number indicated in < > is for the grille.

W 3. Air flow and the noise level are indicated as Low - Medium2 - Medium1 - High.

5

4-2. ELECTRICAL PARTS SPECIFICATIONS

Service Ref.

PMFY-P06NBMU-E PMFY-P08NBMU-E PMFY-P12NBMU-E PMFY-P15NBMU-E Symbol PMFY-P06NBMU-E1 PMFY-P08NBMU-E1 PMFY-P12NBMU-E1 PMFY-P15NBMU-E1

Parts name

Room temperature thermistor

Liquid pipe thermistor

Gas pipe thermistor

Fuse

(Indoor controller board)

Fan motor

Vane motor

Drain pump

Drain sensor

Linear expansion valve

Power supply terminal block

Transmission terminal block

MA-remote controller terminal block

TH21

TH22

TH23

FUSE

MF

MV

DP

DS

LEV

TB2

TB5

TB15

Resistance 30˚F/15.8k", 50˚F/9.6k", 70˚F/6.0k", 80˚F/4.8k", 90˚F/3.9k", 100˚F/3.2k"

Resistance 30˚F/15.8k", 50˚F/9.6k", 70˚F/6.0k", 80˚F/4.8k", 90˚F/3.9k", 100˚F/3.2k"

Resistance 30˚F/15.8k", 50˚F/9.6k", 70˚F/6.0k", 80˚F/4.8k", 90˚F/3.9k", 100˚F/3.2k"

250V 6A

DC Brushless Motor

8-pole OUTPUT 28W

PN0H28-MB

MSFJC 20M23 12V/380"

PJV-1063 208-240V 50/60Hz

Thermistor resistance 30_F/6.3k", 50_F/3.9k", 70_F/2.5k", 80_F/2.0k", 90_F/1.6k", 100_F/1.3k"

DC12V Stepping motor drive port dimension [3.2 (0~2000pulse)

EDM-40YGME

(L1, L2, GR) Rated to 330V 30A w

(M1, M2, S) Rated to 250V 20A w

(1,2) Rated to 250V 10A w

wNote : Refer to WIRING DIAGRAM for the supplied voltage.

6

4-3. AIR CAPACITY TAKEN FROM OUTSIDE

PMFY-P·NBMU-E series are capable of taking air from outside. When taking air from outside, the duct fan is used. The air capacity should be 20% or less of the airflow SPEC(Hi).

9-13/16

11-3/8

90-

 

 

 

 

 

 

4-{1/8

 

 

 

 

15/16

 

 

 

3-

 

 

 

{

 

 

 

4-1/4

 

 

 

 

 

{

 

 

 

 

4

 

 

 

 

-

 

 

 

 

13/16

 

Fresh air intake hole

Fresh air intake hole

 

(Unit:inch)

 

(Knockout)

(Knockout)

 

Service Ref.

Air flow (Hi)

Air capacity taken from outside

 

 

 

PMFY-P06NBMU-E

300 CFM

60 CFM

PMFY-P06NBMU-E1

 

 

PMFY-P08NBMU-E

320 CFM

64 CFM

PMFY-P08NBMU-E1

 

 

PMFY-P12NBMU-E

320 CFM

64 CFM

PMFY-P12NBMU-E1

 

 

PMFY-P15NBMU-E

370 CFM

74 CFM

PMFY-P15NBMU-E1

 

 

Operation in conjunction with duct fan (Booster fan)

●Whenever the indoor unit is operating, the duct fan operates.

(1)Connect the optional multiple remote controller adaptor (PAC-SA88HA-E) to the connector CN51 on the indoor controller board.

(2)Drive the relay after connecting the 12V DC relay between the Yellow and Orange connector lines.

(w)Use a relay of 1W or smaller.

MB: Electromagnetic switch power relay for duct fan. X: Auxiliary relay (12V DC LY-1F)

 

How to read curves

 

 

 

 

Curve in the

Duct characteristics

 

 

 

1

at site

 

 

 

 

 

right graphs

 

 

 

 

 

0

 

A

C

Q…Designed amount

of

fresh air

 

 

 

 

 

 

intake

 

<CFM>

 

Q

B

 

A…Static pressure loss

of fresh air

 

 

 

 

 

 

intake duct system with air flow

 

 

 

 

 

 

 

 

amount Q

 

<in. W.G>

2

 

 

 

B…Forced static pressure at air condi-

 

 

 

tioner inlet with air flow amount Q

 

 

 

 

 

 

C A

 

 

 

<in. W.G>

 

 

 

 

C…Static pressure of booster fan with

 

 

E

 

air flow amount Q

 

<in. W.G>

 

Q

 

 

D…Static pressure loss

increase

 

 

 

amount of fresh air intake duct

 

 

 

 

 

 

 

 

system for air flow amount Q

3

 

 

 

 

 

<in. W.G>

 

 

 

E…Static pressure of indoor unit with

 

 

D

 

 

 

 

air flow amount Q

 

<in. W.G>

 

 

 

 

 

 

 

 

 

Qa…Estimated amount of fresh air

 

 

A

 

intake without D

 

<CFM>

 

Q

 

 

 

 

 

 

Qa

 

 

 

 

 

 

 

 

Be sure to secure insulation

~

 

 

 

 

 

 

 

material by tape, etc.

 

CN51

5

Green

 

 

on

 

 

Yellow

 

 

indoor unit

 

 

 

 

1

 

Orange

 

MB

board

 

 

 

Connector (5P)

Red

 

 

 

 

 

 

 

 

Indoor unit side

Brown

Installation at site

 

Multiple remote

 

 

 

 

 

 

 

 

 

 

 

controller adapter

Be sure to secure insulation

 

 

 

PAC-SA88HA-E

material by tape, etc.

Indoor controller board

Distance between indoor controller board and relay must be within 33 feet.

Multiple remote controller adapter PAC-SA88HA-E

CN51

Characteristic diagram of air capacity taken from outside of PMFY-P·NBMU-E

 

0.2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(in.W.G.)

0.1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

00

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

pressure

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2 intake

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

-0.1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1 intake

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Static

-0.2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

-0.3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

-0.4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0

10

20

30

40

50

60

70

80

Air flow (CFM)

7

Mitsubishi Electronics PMFY-P08NBMU-E1, PMFY-P12NBMU-E1, PMFY-P08NBMU-E, PMFY-P06NBMU-E1, PMFY-P06NBMU-E User Manual

4-4. NOISE CRITERION CURVES

PMFY-P06NBMU-E

 

NOTCH

SPL(dB)

LINE

PMFY-P06NBMU-E1

 

High

35

 

 

Medium1

33

 

 

 

 

 

 

 

 

 

 

 

 

Medium2

30

 

 

 

 

 

 

Low

27

 

bar)

90

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

dB = 0.0002

80

 

 

 

 

 

 

 

70

 

 

 

 

 

 

NC-70

dB (0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LEVEL,

60

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NC-60

 

 

 

 

 

 

 

 

PRESSURE

50

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NC-50

40

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NC-40

SOUND

 

 

 

 

 

 

 

30

 

 

 

 

 

 

 

BAND

 

 

 

 

 

 

 

NC-30

20

 

 

 

 

 

 

 

OCTAVE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NC-20

APPROXIMATE THRESHOLD OF HEARING

 

 

 

 

FOR CONTINUOUS NOISE

 

 

 

 

 

 

10

125

250

500

1000

2000

4000

8000

 

 

63

BAND CENTER FREQUENCIES, Hz

PMFY-P15NBMU-E

 

NOTCH

SPL(dB)

LINE

PMFY-P15NBMU-E1

 

High

39

 

 

Medium1

37

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Medium2

35

 

 

 

 

 

 

 

Low

33

 

bar)

90

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

dB = 0.0002

80

 

 

 

 

 

 

 

 

70

 

 

 

 

 

 

 

NC-70

dB (0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LEVEL,

60

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NC-60

 

 

 

 

 

 

 

 

 

PRESSURE

50

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NC-50

40

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NC-40

SOUND

 

 

 

 

 

 

 

 

30

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NC-30

BAND

 

 

 

 

 

 

 

 

20

APPROXIMATE

 

 

 

 

 

 

OCTAVE

 

 

 

 

 

 

 

THRESHOLD OF

 

 

 

 

 

 

 

HEARING FOR

 

 

 

 

 

NC-20

 

CONTINUOUS

 

 

 

 

 

 

10

NOISE

 

 

 

 

 

 

 

63

125

250

500

1000

2000

4000

8000

 

 

 

BAND CENTER FREQUENCIES, Hz

PMFY-P08NBMU-E

 

NOTCH

SPL(dB)

LINE

PMFY-P12NBMU-E

 

High

37

 

 

Medium1

36

 

PMFY-P08NBMU-E1

 

 

 

Medium2

34

 

PMFY-P12NBMU-E1

 

Low

32

 

 

 

 

 

 

bar)

90

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

dB = 0.0002

80

 

 

 

 

 

 

 

 

70

 

 

 

 

 

 

 

NC-70

dB (0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LEVEL,

60

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NC-60

 

 

 

 

 

 

 

 

 

PRESSURE

50

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NC-50

40

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NC-40

SOUND

 

 

 

 

 

 

 

 

30

 

 

 

 

 

 

 

 

BAND

 

 

 

 

 

 

 

 

NC-30

20

APPROXIMATE

 

 

 

 

 

 

OCTAVE

 

 

 

 

 

 

 

THRESHOLD OF

 

 

 

 

 

 

 

HEARING FOR

 

 

 

 

 

NC-20

 

CONTINUOUS

 

 

 

 

 

 

10

NOISE

 

 

 

 

 

 

 

63

125

250

500

1000

2000

4000

8000

 

 

 

BAND CENTER FREQUENCIES, Hz

UNIT

CEILING

5ft

MICROPHONE

8

5 OUTLINES AND DIMENSIONS

PMFY-P06NBMU-E PMFY-P06NBMU-E1 PMFY-P08NBMU-E PMFY-P08NBMU-E1 PMFY-P12NBMU-E PMFY-P12NBMU-E1 PMFY-P15NBMU-E PMFY-P15NBMU-E1

coverPipe O.D.{1-11/16({43) Refrigerant

piping

pipingDrainagePVC pipe:VP-20[I.D.{31/32"({25)]

ofDetailsfresh air intake hole

90-

4-{1/8(2.8) Burring hole

 

 

Knockout

9-13/16(250) 11-3/8(288.5) supplypowerforblockTerminal

{ { 6.35) 1/4"( O.D.

{ { 12.7) 1/2"( O.D.

 

 

 

 

100)

 

 

 

 

 

 

 

 

 

15/16(

 

-13/6(122)

 

 

 

 

 

 

 

-

 

 

 

 

 

 

 

 

 

3

 

 

 

 

 

 

 

 

 

{

4

 

 

 

 

 

 

 

 

{

 

 

Liquidpipe

Gaspipe

 

 

 

 

 

 

 

 

(108) 4-1/4

Fresh air intake hole

Right side

Terminal block for transmission

Unit : in. (mm)

unit

 

 

plate

 

(110)

Mounting

 

 

4-5/16

 

indoor

(235)ormore

 

 

9-1/2

 

 

 

 

 

 

9-1/16(230)

 

 

Installation space required around

(110)

4-5/16

 

Suspension bolt(M10 or W 3/8)

Panel(grille):PMP-16BMU

 

13/16(20)

2-15/18(74.5)

1-1/32(26)

 

 

9-3/8(247)

 

Outerline of grille

lineof unit

 

 

 

Electricalbox

ofside3/8(1000)outer-39grille openingceiling16(960)-13-37

boltsuspension15/18(811)-31 pitch

 

13/16(20)13/16(20)

 

2-11/16(69)

 

 

 

15/16(812)-31

 

7/8(759)-29

2-1/16(53)

 

 

outlet(lower)Air

Center

 

 

7/8(759)-29

 

15/18(74.5)-2

 

 

.11/16(175).11/16(175)

 

 

 

 

 

pipeDrainage

pipe:PVC 20[O.D.-VP {1"(26)]

Top

1/32(26)-1

 

13/18(46)-1

11/16(43)-1

 

 

 

 

 

13/16(20)

 

1-25/32(45)

 

1-25/32(45)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13/16(20)

 

 

 

13/16(20)

 

 

 

 

 

 

 

 

Suspensionboltpitch

13-3/8(340)

 

 

 

 

 

 

 

 

Ceilingopening

 

16-15/16(430)

11-7/8(302)

10(254)

5-9/16(141)

 

 

 

 

Outersideofgrille

 

 

pipe(gas)Refrigerant

{1/2"(12.7)O.D. 15-9/16(395)

 

 

 

 

 

18-1/2(470)

 

 

 

 

 

 

Terminal block for

remote controller

 

 

{1-31/32(50)

 

 

 

1-9/16(40)

3/16(56)

Front

 

outer3/8(1000)- side of grille

5/8(600)-23 7-7/8(200)

 

 

drainpan

 

 

 

 

2-

 

 

39

7/8(200)-7

9-1/16(230)

13/16(20)

 

 

 

7-13/16(198)

13/32(10)

 

 

 

 

 

 

3-3/8(96)

 

 

6-15/16(176)

 

Refrigerant

pipe(liquid) O.D.{1/4"(6.35)

Ceilingpanel

Leftside

3-3/8(96)

 

 

 

 

 

 

1-3/16(30)

Outersideofgrille

18-1/2(470)

2-3/8(60)

Panel(grille):PMP-16BMU

 

 

Lower view

Ceiling panel

 

pan

Same line

Drain

 

9

10

[Legend]

Symbol

 

Name

Symbol

 

Name

Symbol

 

Name

I.B

Indoor controller board

 

X1

Aux.relay

Drain pump

TH21

Thermistor

Room temp. detection

 

CN25

Connector

Humidifier

 

T

Transformer

 

 

 

 

(32°F/15k", 77°F/5.4k")

 

CN27

 

Damper

 

LED1

Power supply (I.B)

TH22

 

Pipe temp. detection / Liquid

 

CN32

 

Remote switch

 

LED2

Power supply (I.B)

 

 

 

(32°F/15k", 77°F/5.4k")

 

CN51

 

Centrally control

MF

Fan motor (with inner thermo)

TH23

 

Pipe temp. detection / Gas

 

CN52

 

Remote Indication

MV

Vane motor

 

 

 

 

(32°F1/15k", 77°F/5.4k")

 

SW2

Switch

Capacity code

DP

Drain water lifting-up mech.

A.B

Address board

 

 

SW3

 

Mode selection

DS

Drain sensor

 

 

SW1

Switch

Mode selection

 

SW4

 

Model selection

LEV

Linear expansion valve

 

SW5

 

Voltage selection

 

ZNR

Varistor

 

TB2

Terminal

Power supply

 

SW11

 

Address setting 1st digit

 

FUSE

Fuse (6A / 250V)

TB5

block

Transmission

 

SW12

 

Address setting 2nd digit

 

 

 

 

TB15

 

MA-Remote Controller

 

SW14

 

Connection No.

Note

1.At servicing for outdoor unit, always follow the wiring diagram of outdoor unit.

2.In case of using MA-Remote controller, please connect to TB15. (Remote controller wire is non-polar.) 3.In case of using M-NET, please connect to TB5. (Transmission wire is non-polar.)

4.Symbol [S] of TB5 is the shield wire connection.

5.Symbols used in wiring diagram above are, : terminal block, :connecter.

6.The setting of the SW2, SW3 dip switches differs in the capacity for the detail, refer to the fig : w1. 7.Please set the switch SW5 according to the power supply voltage.

LED on indoor board for service

Mark

Meaning

Function

LED1

Main power supply

Main power supply (Indoor unit:208-230V)

Power on Lamp is lit.

 

 

LED2

Power supply for

Power supply for MA-Remote controller

MA-Remote controller

on Lamp is lit.

<fig : w1>

Models

 

SW2

 

SW3

P06

ON

 

 

 

 

 

ON

 

 

 

 

 

 

 

 

OFF

 

 

 

 

 

OFF

 

 

 

 

 

 

 

 

 

1 2 3 4 5 6

 

1 2 3 4 5 6 7 8 910

P08

ON

 

 

ON

 

 

 

 

 

 

 

 

OFF

 

 

 

 

 

OFF

 

 

 

 

 

 

 

 

 

1 2 3 4 5 6

 

1 2 3 4 5 6 7 8 910

 

 

 

 

 

 

 

 

 

 

 

 

P12

ON

 

 

 

 

 

ON

 

 

 

 

 

 

 

 

OFF

 

 

 

 

 

OFF

 

 

 

 

 

 

 

 

 

1 2 3 4 5 6

 

1 2 3 4 5 6 7 8 910

 

 

 

 

 

 

 

 

 

 

 

 

P15

ON

 

 

 

 

 

ON

 

 

 

 

 

 

 

 

OFF

 

 

 

 

 

OFF

 

 

 

 

 

 

 

 

 

1 2 3 4 5 6

 

1 2 3 4 5 6 7 8 910

(w2)Use copper supply wire.

TO MA-REMOTE

TB15

1

CONTROLLER

2

DC8.7-13V

 

 

 

 

DS

 

I.B

 

 

 

 

3 2 1

ORN

1

 

(WHT)

 

CN3A

DRAIN

ORN

2

(BLU)

CN31

3

 

 

 

 

 

TO OUTDOOR UNIT

S(SHIELD)

TB5

M2

BLU

BC CONTROLLER

M1

BLU

REMOTE CONTROLLER

DC24-30V

 

 

POWER SUPPLY

5

MF

~ / N 208—230V 60Hz

BREAKER (15A)

LED2

1

(BLU)

(M-NET)

2

CN2M

6

 

5

 

4

FAN

3

(WHT)

2

1

FUSE(15A)

 

LED1

 

 

<w2>

L1 TB2

RED

PULL BOX

L2

BLU

 

 

G

GRN / YLW

 

 

TO NEXT INDOOR UNIT

 

 

TH23 TH22 TH21

2 1

2 1

2 1

(BLK) (WHT) (RED) GAS LIQUID INTAKE CN29 CN21 CN20

LEV MV

1 2 3 4 5

BLU BRN ORN YLW RED

WHT

 

BRN

RED ORN YLW GRN

6

 

 

 

 

 

 

6 5 4 3 2 1

 

6 5 4 3 2 1

(WHT)

 

 

 

(GRN)

LEV

 

 

 

VANE

CN60

 

 

 

CN6V

 

5

1

5

1

 

(WHT)

 

(GRN)

 

 

CENTRALLY

REMOTE

 

 

CONTROL

 

INDICATION

 

CN51

 

CN52

 

2 1 2 1

CN25 CN27

 

ON OFF

SW4

2 34 5

 

1

 

 

T

X1

SW3

3 45 6 7 8 910

 

 

 

 

2

 

 

 

 

 

1

 

 

 

 

SW2

6

FUSE

 

 

X1

324 5

250V

 

 

 

 

1

6A

 

 

 

 

 

 

 

 

ON OFF

CND

 

 

 

(WHT)

3 2

1

1 2 3

 

(RED)

CNP

 

 

8

 

7

(RED)

6

5

ADDRESS

CN81

4

 

3

 

2

 

1

(RED)

4

3

ADDRESS

2

CN42

1

 

(WHT) 1 REMOTE SWITCH

CN32

3

See fig : w1

DP

8

A.B

8

7 6 5 4 3 2 1

4

(RED)

 

ADDRESS

CONNECTION No.

4 3 2 1

SW14SWC

CN82

 

(RED)

ADDRESS

0

 

CN43

 

SW5

230V208V

SW1

ON

OFF

67891045312

SW11SW12

2

1

DIGITDIGITDIGIT

0

1ST2ND3RD

 

 

 

 

 

 

 

0

 

 

E-P15NBMU-PMFY E-P12NBMU-PMFY E-P08NBMU-PMFY E-P06NBMU-PMFY

DIAGRAM WIRING 6

11

[Legend]

Symbol

 

Name

Symbol

 

Name

Symbol

 

 

Name

I.B

Indoor controller board

 

X1

Aux.relay

Drain pump

TH21

Thermistor

 

Room temp. detection

 

CN25

Connector

Humidifier

 

T

Transformer

 

 

 

 

 

(32°F/15kΩ , 77°F/5.4kΩ )

 

CN27

 

Damper

 

LED1

Power supply(I.B)

TH22

 

 

Pipe temp. detection / Liquid

 

CN32

 

Remote switch

 

LED2

Power supply(I.B)

 

 

 

 

(32°F/15kΩ , 77°F/5.4kΩ )

 

CN51

 

Centrally control

MF

Fan motor

 

TH23

 

 

Pipe temp. detection / Gas

 

CN52

 

Remote Indication

MV

Vane motor

 

 

 

 

 

(32°F/15kΩ , 77°F/5.4kΩ )

 

SW2

Switch

Capacity code

DP

Drain water lifting-up mech.

A.B

Address board

 

 

SW3

 

Mode selection

DS

Drain sensor

 

 

SW1

Switch

 

Mode selection

 

SW4

 

Model selection

LEV

Linear expansion valve

 

SW5

 

 

Voltage selection

 

ZNR

Varistor

 

TB2

Terminal

Power supply

 

SW11

 

 

Address setting 1st digit

 

FUSE

Fuse (6A / 250V)

TB5

block

Transmission

 

SW12

 

 

Address setting 2nd digit

 

 

 

 

TB15

 

MA-Remote Controller

 

SW14

 

 

Connection No.

LED on indoor board for service

Mark

Meaning

 

 

 

 

Function

LED1

Main power supply

Main power supply (Indoor unit:208-230V)

Power on

 

Lamp is lit.

 

 

 

LED2

Power supply for

Power supply for MA-Remote controller

MA-Remote controller

on

 

Lamp is lit.

 

 

Note

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.At servicing for outdoor unit, always follow the wiring diagram of outdoor unit.

 

<fig:w1>

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2.In case of using MA-Remote controller, please connect to TB15. (Remote controller wire is non-polar.)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Models

 

SW2

 

 

 

SW3

3.In case of using M-NET, please connect to TB5. (Transmission line is non-polar.)

 

 

P06

ON

 

 

 

ON

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OFF

 

 

 

OFF

 

 

 

 

 

 

 

 

 

 

 

4.Symbol [S]of TB5 is the shield wire connection.

 

 

 

 

 

1 2 3 4 5 6

 

1 2 3 4 5 6 7 8 910

 

 

 

 

P08

ON

 

 

 

ON

 

 

 

 

 

 

 

 

 

 

 

5.Symbols used in wiring diagram above are,

: terminal block,

:connector.

 

 

OFF

 

 

 

OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1 2 3 4 5 6

 

1 2 3 4 5 6 7 8 910

6.The setting of the SW2, SW3 dip switches differs in the capacity for the detail, refer to the fig :w1.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P12

ON

 

 

 

ON

 

 

 

 

 

 

 

 

 

 

 

7.Please set the switch SW5 according to the power supply voltage.

 

 

 

OFF

 

 

 

OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1 2 3 4 5 6

 

1 2 3 4 5 6 7 8 910

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P15

ON

 

 

 

ON

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OFF

 

 

 

OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1 2 3 4 5 6

 

1 2 3 4 5 6 7 8 910

 

 

LEV

MV

<w2>Use Copper Supply Wire.

 

 

 

 

TO MA-REMOTE

CONTROLLER

DC8.7-13V

TO OUTDOOR UNIT

 

BC CONTROLLER

 

REMOTE CONTROLLER

 

DC24-30V

(SHIELD)

 

POWER SUPPLY

MF

~ / N 208-230V 60Hz

BREAKER (15A)

FUSE

 

(15A)

 

<w2>

TB2

PULL BOX

L1

L2

 

 

GR

 

 

 

 

 

DS

TH23

TH22

TH21

 

 

 

M

 

 

 

 

1

 

M

5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

t°

 

 

t°

t°

t°

BRN

RED

BLU

ORN

YLW

WHT

 

 

BRN

RED

ORN YLW

GRN

 

 

I.B

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TB15

ORN

1

 

3

1

2 1

2 1

2 1

6 (WHT)LEV

1

 

 

6(GRN)VANE 1

 

CN3A

(WHT)

(BLK)

(WHT)

(RED)

 

 

CN60

 

 

 

 

CN6V

 

1

 

 

 

 

 

 

 

 

 

 

 

DRAIN

GAS

LIQUID INTAKE

 

 

 

 

 

 

 

 

 

 

 

 

ORN

 

(BLU)

 

 

 

 

 

 

 

 

 

 

 

 

 

3

 

 

 

 

 

 

 

 

 

 

 

 

2

CN31

CN29

CN21

CN20

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TB5

 

 

LED2

 

 

 

 

 

 

 

 

 

5

(WHT)

1

5

(GRN)

1

 

 

BLU

 

 

 

 

 

 

 

 

 

 

 

CENTRALLY

 

REMOTE

 

 

 

 

1

(BLU)

 

 

 

 

 

 

 

 

 

 

 

 

 

M1

 

 

 

 

 

 

 

 

 

CONTROL

 

INDICATION

 

 

BLU

 

 

 

 

 

 

 

 

 

 

 

 

M2

2

(M-NET)

 

 

 

 

 

 

 

 

 

 

CN51

 

 

CN52

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CN2M

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

S

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MS

 

3 FAN

 

 

 

 

 

 

 

 

 

 

 

 

T

 

 

 

 

3~

 

 

(WHT)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6

FUSE

U

X1

 

 

LED1

CND 3

1

1 3

 

(RED)

 

 

RED

 

 

 

BLU

 

 

 

GRN / YLW

 

 

M

 

 

 

1~

2 1

2

1

8

CN25

CN27

 

ON

OFF

(RED)

 

 

6

SW2

 

324 5

ADDRESS

 

CN81

 

 

 

 

 

1

 

 

 

8 910

1

 

 

4

SW3

 

456 7

(RED)

 

ADDRESS

 

 

2 3

CN42

 

 

1

 

 

1

 

SW4

 

234 5

(WHT)

1

 

 

1

REMOTE

 

 

ON OFF

SWITCH

 

 

 

3

 

 

CN32

 

 

 

(WHT) CNP

See fig : w1

8

4

A.B

 

 

8 (RED)ADDRESS 1

 

 

 

CN82

 

 

 

 

CONNECTION

 

4

 

1

SW14SWC

2

3

 

6

No.

 

 

 

 

 

 

45

 

7

 

 

 

(RED)

 

1

 

 

 

 

 

 

 

 

0

 

 

 

 

9

 

 

 

 

 

 

 

 

 

 

8

 

 

ADDRESS

 

FE

 

B

A

 

 

 

 

 

 

 

 

 

DC

 

 

 

 

CN43

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

 

 

1

 

 

SW5

230V208V

SW1 ON OFF 67891045312

SW11SW12

1

 

2

3

4

1ST2ND3RD

DIGITDIGITDIGIT

 

 

 

 

 

 

 

0

 

 

 

 

5

 

 

 

 

 

 

9

8

7

 

6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

 

2

3

4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0

 

 

 

 

5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

9

8

7

 

6

 

 

 

 

 

 

 

 

 

 

1E-P15NBMU-PMFY 1E-P12NBMU-PMFY 1E-P08NBMU-PMFY 1E-P06NBMU-PMFY

TO NEXT INDOOR UNIT

DP