MGE UPS Systems 40-150kVA User Manual

0 (0)

w w w . m g e u p s . c o m

⁄ ı

CO

M

M

G

ET

E

U P S S Y S T E M S

Comet 40-150kVA

Uninterruptible Power Supply

Installation and User Manual

Installation and User Manual

Comet

40 - 150kVA

Installation and User Manual

Revision History

Comet 40-150kVA UPS Installation and User Manual

86-160310-00

Revision:

A00

Initial Release

03/1997

 

B00

ECN#: 289-91

01/1998

 

C00

ECN#: 290-30

07/1998

 

D00

ECN#: 002456

02/2002

 

E00

ECN#: 004466

08/2005

Copyright © 2005 MGE UPS SYSTEMS, INC.

All rights reserved. Printed in U.S.A.

MGE UPS SYSTEMS, INC.

1660 Scenic Avenue Costa Mesa, CA 92626 (714) 557-1636

Customer Care Center: 1-800-438-7373 (Hours: 24/7)

86-160310-00 E00

i

Comet 40-150kVA

IMPORTANT SAFETY INSTRUCTIONS

SAVE THESE INSTRUCTIONS – This manual contains important instructions for the

Comet 40-150kVA that must be followed during operation and maintenance of the equipment.

WARNING ATTENTION WARNUNG!

WARNING ATTENTION WARNUNG!

NOTE

WARNING

ATTENTION

WARNUNG!

Opening enclosures expose hazardous voltages. Always refer service to qualified personnel only.

L'ouverture des cabinets expose des tensions dangereuses. Assurez-vous toujours que le service ne soit fait que par des personnes qualifiees.

Das öffnen der Gehäuse legen gefährliche Spannungen bloss.

Service sollte immer nur von qualifizierten Personal durchgeführt werden.

As standards, specifications, and designs are subject to change, please ask for confirmation of the information given in this publication.

Comme les normes, spécifications et produits peuvent changer, veuillez demander confirmation des informations contenues dans cette publication.

Normen, Spezifizierungen und Pläne unterliegen Anderungen. Bitte verlangen Sie eine Bestätigung über alle Informationen, die in dieser Ausgabe gemacht wurden.

This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment.

This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at user's own expense.

To reduce the risk of fire or electric shock, install in a controlled indoor environment free of conductive contaminants.

This equipment is intended only for installations in a RESTRICTED ACCESS LOCATION.

Pour réduire le riske d'inccendie ou d'électrocution, installer dans une enciente intérieure contrôlée en température et humidité et sans contaminants conducteurs.

Ce matériel est destiné seulement pour des installations dans un EMPLACEMENT RESTREINT D'ACCES.

Um die Gefahr von Feuer und elektrischem Schock zu reduzieren, muss das Gerät in einem temperatur - und feuchtigkeitskontrollierten Raum, frei von leitungsfähigen Verunreinigungen, installiert werden. Dieses Gerät ist nur für die Installation an einem Ort mit qeingeschränkter Zugangserlaubnis vorgesehen.

Diese Ausrüstung ist nur für Anlagen in einem EINGESCHRäNKTEN ZUGRIFF STANDORT bestimmti.

ii

Important Safety Instructions

86-160310-00 E00

Installation and User Manual

WARNING

ATTENTION

WARNUNG!

HIGH LEAKAGE CURRENT. Earth connection essential before connecting supply.

COURANT DE FUITE ELEVE. Raccordement a la terre indispensable avant le raccordement au reseau.

Hoher Ableitstrom Vor Inbetriebnahme Schutzleiterverbindung herstellen.

Certification Standards - Three Phase UPS

IEC 1004/ANSI C62.41 Standards for Surge Withstand Ability.

FCC Part 15, Subpart J, Class A.

UL/cUL 1778, Standard for Uninterruptible Power Supply Equipment.

NEMA PE 1 - Uninterruptible Power Systems.

NFPA 70 - National Electrical Code.

ISO 9001.

Safety of Persons

The UPS has its own internal power source (the battery). Consequently, the power outlets may be energized even if the UPS is disconnected from the AC power source.

The UPS must be properly grounded.

The battery supplied with the UPS contains small amounts of toxic materials. To avoid accidents, the directives listed below must be observed:

-Never burn the battery (risk of explosion).

-Do not attempt to open the battery (the electrolyte is dangerous for the eyes and skin).

-Comply with all applicable regulations for the disposal of the battery.

-Batteries constitute a danger (electrical shock, burns). The short-circuit current may be very high. Precautions must be taken for all handling: remove watches, rings, bracelets and any other metal objects, use tools with insulated handles.

-Do not lay tools or metal parts on top of batteries.

Product Safety

A protection circuit breaker must be installed upstream and be easily accessible.

The UPS can be disconnected from the AC power source by opening the input circuit breaker.

UPS must be connected to a nearby power source that is easily accessible.

Never block the ventilation grates of the UPS.

The UPS must be installed in a controlled environment.

Special Precautions

The UPS connection instructions and operation described in the manual must be followed in the indicated order.

Check that the indications on the rating plate correspond to your AC powered system and to the actual electrical consumption of all the equipment to be connected to the UPS.

Before and after the installation, if the UPS remains de-energized for a long period, the UPS must be energized for a period of 24 hours, at least once every 3 months (for a normal storage temperature less than 25°C). This charges the battery, thus avoiding possible irreversible damage.

86-160310-00 E00

Certification Standards and Safety of Persons

iii

Comet 40-150kVA

(This page left blank intentionally)

iv

86-160310-00 E00

Contents

 

section

description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

. .page

 

 

Revision History . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

. . . . . .i

 

 

IMPORTANT SAFETY INSTRUCTIONS . . . . . . . . . . . . . . . . . .

. . . . .ii

 

 

Certification Standards - Three Phase UPS . . . . . . . . . . . . . . .

. . . . .iii

 

 

Safety of Persons . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

. . . . .iii

 

 

Product Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

. . . . .iii

 

 

Special Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

. . . . .iii

 

 

CAUTION: Record All Serial Numbers! . . . . . . . . . . . . . . . . . . .

. . .c iv

 

 

Symbol Usage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

. . .c vi

 

 

Section Descriptions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

. . .c vi

Section 1

System Description and Specifications

 

 

1.0

Scope . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

.1 — 1

 

1.1

General Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

.1 — 1

 

1.2

Major Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

.1 — 3

 

1.3

Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

.1 — 8

 

1.3.1

AC Input Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

.1 — 9

 

1.3.2

AC Output Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

.1 — 9

 

1.3.3

DC Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

.1 — 9

 

1.3.4

Mechanical Specifications (UPS Cabinet Only) . . . . . . . . . . . . .

1 — 10

 

1.3.5

Environmental Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . .

1 — 10

 

1.3.6

DB15 Connector Pinouts and Designations . . . . . . . . . . . . . . . .

1 — 10

 

1.4

Options and Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1 — 11

 

1.4.1

UPS Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1 — 11

 

1.4.2

Software and Communication Package . . . . . . . . . . . . . . . . . . .

1 — 11

Section 2

Installation

 

 

 

2.0

Scope . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

.2 — 1

 

2.1

Receiving . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

.2 — 1

 

2.2

Handling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

.2 — 1

 

2.3

Storage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

.2 — 2

 

2.4

Prerequisite to Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

.2 — 2

 

2.4.1

Environmental . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

.2 — 2

 

2.4.2

Mechanical . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

.2 — 3

 

2.4.3

Electrical . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

.2 — 3

 

2.5

Installation Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

.2 — 4

 

2.5.1

Placement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

.2 — 4

86-160310-00 E00

Contents

c i

Comet 40-150kVA

 

section

description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

. .page

Section 2

Installation (continued)

 

 

2.6

Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

.2 — 4

 

2.6.1

Main AC Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

.2 — 4

 

2.6.2

Bypass AC Input (Optional) . . . . . . . . . . . . . . . . . . . . . . . . . . . .

.2 — 4

 

2.6.3

Remote Emergency Power Off (REPO) . . . . . . . . . . . . . . . . . .

.2 — 4

 

2.6.4

AC Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

.2 — 5

 

2.6.5

Battery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

.2 — 5

Section 3

Operation

 

 

 

3.0

Scope . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

.3 — 1

 

3.1

Power Flow . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

.3 — 1

 

3.1.1

Power Flow, For Normal Operation . . . . . . . . . . . . . . . . . . . . . .

.3 — 1

 

3.1.2

Power Flow, For On Battery Operation . . . . . . . . . . . . . . . . . . .

.3 — 1

 

3.1.3

Power Flow, For Bypass Operation . . . . . . . . . . . . . . . . . . . . . .

.3 — 2

 

3.2

Graphical User Interface, Controls and Indicators . . . . . . . . . . .

.3 — 2

 

3.3

Startup Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

.3 — 5

 

3.3.1

Preliminary Checks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

.3 — 5

 

3.3.2

Powering Up the Comet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

.3 — 5

 

3.4

Inverter Manual Startup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

.3 — 5

 

3.5

Operating Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

.3 — 6

 

3.5.1

Normal Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

.3 — 6

 

3.5.2

Operation on Battery Power . . . . . . . . . . . . . . . . . . . . . . . . . . . .

.3 — 6

 

3.5.3

Battery Duration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

.3 — 6

 

 

3.5.3.1 Return to AC Power . . . . . . . . . . . . . . . . . . . . . . . . . . .

.3 — 6

 

3.5.4

Overload . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

.3 — 7

 

3.6

Emergency Shutdown Using EPO/REPO . . . . . . . . . . . . . . . . .

.3 — 8

 

3.7

Forced Transfer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

.3 — 8

 

3.8

Maintenance Bypass . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

.3 — 8

 

3.8.1

From Normal Maintenance Bypass Mode . . . . . . . . . . . . . . . . .

.3 — 8

 

3.8.2

From Maintenance Bypass to Normal Mode . . . . . . . . . . . . . . .

.3 — 9

 

3.9

Shutdown Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3 — 10

 

3.9.1

Inverter Shutdown . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3 — 10

 

3.9.2

Powering Down . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3 — 10

 

3.10

Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3 — 10

Section 4

Maintenance

 

 

4.0

Scope . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

.4 — 1

 

4.1

Battery Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

.4 — 1

 

4.2

Preventive Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

.4 — 1

 

4.3

Replacement Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

.4 — 2

c ii

Contents

86-160310-00 E00

Installation and User Manual

Figures

figure description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page

1-1: Comet 40-80kVA. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1-2: Comet 100-150kVA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 — 1 1-3: Single Line Diagram for the Comet 40-80kVA . . . . . . . . . . . . . . . . . . . . .1 — 2 1-4: Single Line Diagram for the Comet 100-150kVA . . . . . . . . . . . . . . . . . . .1 — 2

1-5: Front View of the Comet 40-80kVA . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 — 4 1-6: Rear View of the Comet 40-80kVA . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 — 5 1-7: Front View of the Comet 100-150kVA . . . . . . . . . . . . . . . . . . . . . . . . . . .1 — 6 1-8: Front View of Communications Components for

the Comet 100-150kVA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 — 7 1-9: Pinouts on the DB15 Connector . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 — 10

2-1: The Comet 100-150kVA on Pallet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2 — 2

3-1: Power Flow, For Normal Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 — 1 3-2: Power Flow, For On Battery Operation . . . . . . . . . . . . . . . . . . . . . . . . . .3 — 1 3-3: Power Flow, For Bypass Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 — 2 3-4: Comet Front Panel GUI, Controls and Indicators . . . . . . . . . . . . . . . . . .3 — 3 3-5: Output Current Overload Curve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 — 7 3-6: Output Power Overload Curve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 — 7

Tables

table description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page

1-1: Comet 40-150kVA Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 — 8 1-2: UPS Manager Dry Contact Interface . . . . . . . . . . . . . . . . . . . . . . . . . . .1 — 10

2-1: Recommended upstream protective device sizing * . . . . . . . . . . . . . . . .

2 — 3

MGE Warranty & Proprietary Rights for Three Phase Products

MGE Standard Three Phase Warranty

Proprietary Rights Statement

Warranty and Product Registration

User Information

Product Information

Warranty Extension (Warranty+)

Customer Care Center - Three Phase Products

Technical Support and Product Services

Who to Contact

Scheduling Field Service Engineer Support

Return Policy for Repair of Three Phase Products (RGA)

Glossary

Reorder Form

86-160310-00 E00

Contents

c iii

Comet 40-150kVA

CAUTION: Record All Serial Numbers!

RECORD ALL SERIAL NUMBERS FOR THE COMET UPS AND ACCESSORIES. THESE SERIAL NUMBERS WILL BE REQUIRED IF YOUR SYSTEM NEEDS SERVICE. KEEP THIS MANUAL IN A PLACE WHERE YOU CAN REFERENCE THE SERIAL NUMBERS IF SERVICE IS REQUIRED!

UPS SERIAL NUMBER: _______________________________________________________

BATTERY SERIAL NUMBER: ___________________________________________________

ADDITIONAL MODULES SERIAL NUMBERS:

____________________________ ______________________________

____________________________ ______________________________

____________________________ ______________________________

____________________________ ______________________________

____________________________ ______________________________

____________________________ ______________________________

NOTES:

c iv

CAUTION: Record All Serial Numbers!

86-160310-00 E00

Installation and User Manual

(This page left blank intentionally)

86-160310-00 E00

c v

Comet 40-150kVA

Symbol Usage

This manual uses five icon symbols with text to convey important information and tips.

WARNING

Information provided to protect the user and service personnel against safety

 

 

hazards and/or possible equipment damage.

 

 

 

 

 

 

 

 

 

CAUTION

Information provided to protect the user and service personnel against possible

 

 

equipment damage.

 

 

 

 

 

 

 

 

 

ELECTRICAL

Information provided to protect the user and service personnel against possible

 

 

electrical hazard and equipment damage.

 

 

 

 

 

 

 

 

 

IMPORTANT

Information provided as an operating instruction, or as an operating tip.

 

NOTE

 

 

 

 

 

 

Information provided as an operating tip or an equipment feature.

 

 

 

 

 

Section Descriptions

1System Description and Specifications

Provides a general description of the Comet 40-150kVA Uninterruptible Power Systems major components, available options, and system specifications.

2Installation

Installation of the Comet 40-150kVA UPS, which include receiving, handling, and storage procedures; prerequisites to installation; installation procedures; and startup procedures.

3Operation

Important information on the Comet 40-150kVA systems’ operation procedure sequences; for normal, on battery, and bypass operation, with descriptions of the control and display indicators.

NOTE

For details on the Graphical User Interface (GUI) display, please refer to

 

manual 86-160316-00.

 

 

4Maintenance

Preventive maintenance and battery safety instructions for Comet 40-150kVA UPS, and information about replacement parts, and customer service.

A Glossary provides definitions of abbreviations and terms used in this manual.

NOTE

This manual provides technical information required for operation and

 

maintenance of the Comet 40-150kVA Uninterruptible Power System (UPS).

 

Please read this manual before operating the Comet 40-150kVA equipment.

 

Please retain this manual for future reference.

 

 

c vi

Symbol Usage and Section Descriptions

86-160310-00 E00

System Description and Specifications

1.0Scope

Provides a general description of the Comet 40-150kVA Uninterruptible Power Systems major components, available options, and system specifications.

1.1General Description

The Comet family consists of compact, high-efficiency Uninterruptible Power Systems which are available in power ratings from 40-150kVA, and are optimized for compatibility with nonlinear computer-type loads. Computer-aided UPS diagnostics and modular construction assure that any required service can be identified and completed rapidly. Remote system monitoring, remote annunciation of UPS performance signals and communication capabilities allow total control of the UPS by its user. See Figures 1-1 and 1-2.

The Comet UPS and its auxiliary equipment are designed for installation in a room where humidity and temperature can be controlled. The recommended and maximum environmental parameters are listed in the Specifications section of this document.

Figure 1-1: Comet 40-80kVA.

Figure 1-2: Comet 100-150kVA.

 

 

 

 

⁄ ı

COMET

M G E

U P S S Y S T E M S

⁄ ı

COMET

M G E

U P S S Y S T E M S

86-160310-00 E00

System Description and Specifications

1 — 1

Comet 40-150kVA

Figure 1-3, and 1-4 show single-line diagrams of a typical UPS system installation. During normal operation, utility power (Main Input) is supplied to the UPS Rectifier where it is converted to DC voltage. The Inverter converts the DC voltage from the Rectifier to three-phase regulated AC voltage, which supplies the critical load. During power failure conditions, the Inverter is supplied by the stored energy in the batteries, and the load is powered continuously with no disruption.

Figure 1-3: Single Line Diagram for the Comet 40-80kVA.

UPS CABINET

 

STATIC SWITCH

 

BYPASS

KA2

 

 

 

 

 

AC INPUT

 

 

SR1

(OPTIONAL)

 

 

 

 

 

MAIN

KA1

K3N

TO

 

 

 

CRITICAL

AC INPUT

 

 

INPUT

OUTPUT

LOAD

 

 

FUSES RECTIFIER

INVERTER FUSES

 

 

BATTERY

QF1

 

 

CABINET

 

 

BATTERY

 

Figure 1-4: Single Line Diagram for the Comet 100-150kVA.

 

UPS CABINET

 

 

 

 

 

KA2

STATIC SWITCH

 

 

BYPASS

 

 

 

 

 

 

 

 

 

AC INPUT

 

 

 

 

SR1

 

 

 

 

 

MAIN

KA1

 

 

K3N

TO

 

 

 

 

 

 

 

CRITICAL

AC INPUT

 

 

 

 

INPUT

 

 

OUTPUT

LOAD

 

 

 

 

FUSES

RECTIFIER

INVERTER

FUSES

 

 

 

BATTERY

QF1

 

 

 

 

CABINET

 

 

 

 

 

 

 

 

 

BATTERY

 

 

1 — 2

System Description and Specifications

86-160310-00 E00

Installation and User Manual

1.2Major Components

The following is a description of the cabinets and major components. Refer to Figures 1-5 to 1-8.

UPS Cabinet

Converts the input AC power to direct current and charges the battery. DC power

 

is converted back to clean AC power by the inverter for the critical load. Section

 

3 describes the operation in detail.

Auxiliary Cabinet

Performs the voltage conversion for the input AC and/or bypass AC using step-

 

up and/or step-down transformers.

Battery Cabinet

The battery cabinet stores energy for use by the Inverter. The stored energy is

 

utilized in the event that the AC input power from the utility source fails, or falls

 

outside of acceptable tolerances. The internal Battery Charger maintains the

 

charge of the battery system. The DC output voltage of the charger is tempera-

 

ture regulated to ensure an optimal charge voltage. If a customer supplied battery

 

system is to be used, an external battery charger may be necessary.

 

The standard battery system is housed in a separate enclosure. For systems where

 

additional back-up time is required, up to two (2) additional battery cabinets are

 

available.

 

A standard battery cabinet is available in an adjacent configuration or a stand-

 

alone configuration. Adjacent battery cabinets are attached to the right side of the

 

UPS using c-brackets provided with the cabinet. Stand-alone battery cabinets

 

are remote from the UPS. Refer to the battery cabinet installation drawing for

 

more details. An external battery system can also be supplied by the customer.

Rectifier

Converts the AC input voltage from the utility source into a DC voltage, supplying

 

the Inverter.

Inverter

Converts the DC voltage supplied from either the Rectifier or the battery system into

 

a three-phase AC voltage. An AC output filter is used to achieve a computer-grade

 

sinewave output voltage waveform, with a total harmonic distortion of less than 2%

 

under linear-load conditions.

Static Switch

Transfers the load between the Inverter output and the bypass AC source without

 

interrupting the supply of power to the load, allowing the load to continue

 

operation in the event of a UPS fault. The Static Switch circuit assures that

 

voltage from the UPS output cannot be fed back to the utility input lines.

Battery System

Stores energy for use by the Inverter. The stored energy is utilized in the event

 

that the AC input power from the utility source fails, or falls outside of acceptable

 

tolerances. The internal Battery Charger maintains the charge of the battery

 

system. The DC output voltage of the charger is temperature regulated to ensure

 

an optimal charge voltage. If a customer supplied battery system is to be used,

 

an external battery charger may be necessary.

86-160310-00 E00

System Description and Specifications

1 — 3

MGE UPS Systems 40-150kVA User Manual

Comet 40-150kVA

Figure 1-5: Front View of the Comet 40-80kVA.

1 (KA1) Input Contactor

(K3N) Output Contactor

(KA2) Bypass Input Contactor (Optional)

(F1, F2, F3) Input Fuses

(F4, F5, F6) Output Fuses

(SR1) Rotary Switch

Rectifier/Static Switch Assembly

Inverter Assembly

Feedback PCA

DC Power Supply PCA

Interconnect PCA

High-Frequency Power Supply PCA

(FU1-FU6) Power Supply Fuses

Teleservice Receptacles (J1-J2) & Fuse (FU13)

Heatsink Cooling Fans

(TB3) Separate Bypass Input Terminal Block

Battery Connections

(TB1) Main Input Terminal Block

(TB2) Output Terminal Block

(SR2) Fan Control Switch

DETAIL BEHIND ITEM 25

A

01

04

05

02

(FU7-FU12) Fan and Teleservice Fuses

Ground Busbar

Neutral Busbar

Bottom of Top-Entry Channel

1 — 4

System Description and Specifications

86-160310-00 E00

Installation and User Manual

Figure 1-6: Rear View of the Comet 40-80kVA.

TOP ENTRY

CONDUIT LANDING

TOP ENTRY

CHANNEL

T1 INPUT TRANSFORMER (OPTIONAL)

T2 OUTPUT TRANSFORMER (OPTIONAL)

86-160310-00 E00

System Description and Specifications

1 — 5