CLEA N • FRES H • AIR
OPERATION AND
INSTALLATION MANUAL
Contains
ControlAir 15
For Models:
95MAX
155MAX
200MAX MAXTOP 195DCS 300DCS
200ERV
200ERVD
IMPORTANT - PLEASE READ THIS MANUAL BEFORE INSTALLING UNIT
CAUTION
Before installation, careful consideration must be given to how this system will operate if connected to any other piece of mechanical equipment, i.e. a forced air furnace or air handler, operating at a higher static. After installation, the compatibility of the two pieces of equipment must be confirmed by measuring the airflow’s of the Heat Recovery Ventilator (HRV) or Energy Recovery Ventilator (ERV) by using the balancing procedure found in this manual.
It is always important to assess how the operation of any HRV/ERV may interact with vented combustion equipment (ie. Gas Furnaces, Oil Furnaces, Wood Stoves, etc.).
NEVER install a ventilator in a situation where its normal operation, lack of operation or partial failure may result in the backdrafting or improper functioning of vented combustion equipment!!!
TO BE COMPLETED BY CONTRACTOR AFTER INSTALLATION
Installing Contractor
Telephone / Contact
Serial Number
Installation Date |
Model |
* LEAVE FOR HOMEOWNER
NOTE: Due to ongoing research and product development, specifications, ratings and dimensions are subject to change without notice.
TI-84R-NE
0112
Table of Contents |
|
Introduction................................................................... |
2 |
Warranty ....................................................................... |
2 |
ERV Questions & Answers .......................................... |
3 |
Climate Map ................................................................. |
4 |
Technical Data - Model 95MAX ................................... |
5 |
Technical Data - Model 155MAX ................................. |
6 |
Technical Data - Model 200MAX ................................. |
7 |
Technical Data - Model MAXTOP................................ |
8 |
Technical Data - Model 195DCS ................................. |
9 |
Technical Data - Model 300DCS ............................... |
10 |
Technical Data - Model 200ERV ................................ |
11 |
Technical Data - Model 200ERVD ............................. |
12 |
Function and Control |
|
Operation of the ControlAir 15 .................................... |
13 |
Glossary of Terms ...................................................... |
13 |
To Select Mode of Operation....................................... |
14 |
Optional Remote Controls ......................................... |
15 |
Using the Dehumidistat............................................ |
16 |
Schematic Diagram - Model 95MAX ....................... |
17 |
m |
|
Installation |
|
Installation ............................................................... |
18 |
• Location |
|
• Mounting the HRV/ERV |
|
• Electrical |
|
• Installing the Drain Line and "P" Trap |
|
Installing Air Ducts .................................................. |
19 |
•Outside Weatherhoods
•Locating the Weatherhoods
•Installing Ducting from Weatherhoods to the HRV/ERV
•Warmside Ducting
Supply Air Ducting ..................................................... |
20 |
Stale Air Exhaust System .......................................... |
20 |
Dampers and Grilles .................................................. |
20 |
Installation Diagrams .......................................... |
21 - 24 |
Air Flow Balancing ..................................................... |
25 |
Maintenance |
|
Maintenance Routine For HRV .................................. |
27 |
Maintenance Routine For ERV .................................. |
28 |
Troubleshooting.......................................................... |
29 |
Wiring Diagram .......................................................... |
31 |
INTRODUCTION
HRV - Aluminum Core
A Heat Recovery Ventilator (HRV) is designed to provide fresh air into a building while exhausting an equal amount of stale air. During the winter months, the incoming cold fresh air is warmed by utilizing the heat recovered from the stale air before it is exhausted to the outdoors. During summer months when the indoor space is air conditioned, the Heat Recovery Ventilator will help in cooling the incoming fresh air with the stale air that is being exhausted.
ERV - Enthalpic Paper Core
An Energy Recovery Ventilator (ERV) is designed to provide fresh air into a building while exhausting an equal amount of stale air. An ERV is designed for use in warm humid areas with heavy air conditioning use. The ERV will transfer both sensible and latent heat from the incoming fresh air to the outgoing stale air thereby reducing the load (due to ventilation) on the air conditioning system.
ERVs are not suitable for climates where the temperature drops below -4˚C (25˚F).
WARRANTY
All Heat Recovery Ventilators carry a Lifetime Warranty on the heat recovery core and a 5 (five) year replacement parts warranty.
All Energy Recovery Ventilators carry a 5 (five) year warranty on the energy recovery core and a 5 (five) year replacement parts warranty.
During the warranty period, if any core experiences a failure or perforation caused by normal use while owned by the original purchaser, a replacement core (FOB our plant) will be supplied at no expense.
®
2
ERV Questions & Answers
What is the difference between an HRV and an ERV?
The core in an HRV (Heat Recovery Ventilator) transfers heat from one air stream to the other. This is called sensible heat. The term ERV (Energy Recovery Ventilator) is usually used to describe a unit with an enthalpic core that transfers moisture as well as heat from one air stream to the other. This (moisture transfer) is called latent heat.
Enthalpic - what does it mean?
Enthalpy is the term used to describe the energy content of air. This energy is a combination of the sensible and latent heat. Therefore, a core which transfers energy is called an enthalpic core.
Is an ERV better than an HRV?
NOT NECESSARILY!! In cold climates such as most of North America, an HRV works better than an ERV. This is because the air inside the home during the winter months will be more humid than the outside air. An ERV would transfer the latent heat (humidity) from the exhaust air back into the incoming airstream. This will aggravate moisture problems in the home and encourage the growth of mold and mildew. If the air in the home is too dry for comfort, an ERV will not help. A humidifier should be used to increase the humidity to a comfortable level.
and damp situation. In fact, about 2/3 of the energy used by the air conditioner system is to remove moisture. Therefore, when ventilating in the summer, less moisture brought into the home means less work for the air conditioner, and energy savings for you.
During the winter, an ERV recovers some humidity from the exhaust air, reducing the need for humidification, if the required ventilation rate would make the home too dry.
What's the difference between this type of core and a rotary type?
Here's a list of characteristics of the fixed plate core.
1.No rotating parts, so maintenance is easy and the unit lasts a long time.
2.It is very flexible in terms of installation.
3.The core can easily be changed.
4.Because the supply and exhaust air streams are completely separate, there is very little cross leakage of any dust or germs.
Can the core become clogged with dust?
Because the surface of the core is a turbulent flow area, dust sticks to it easily; however, because the inside of the element is a laminar flow area, virtually no dust sticks to it.
Where do you use an ERV instead of an HRV?
An ERV is recommended for warm, humid areas with heavy air conditioning use. As there is no defrost in an ERV it is not recommended for areas where the temperature drops below -4˚C (25˚F).
Why transfer moisture in the summer (cooling season)?
The enthalpic core will allow moisture to be transferred from a humid air flow to a dry air flow. This property is useful in the cooling season if an air conditioning system is used to lower the indoor humidity. You will then have dry, cool air in the exhaust of the ERV, and warm humid air in the supply stream. With these conditions, the ERV will be able to transfer the moisture and heat of the supply air to the exhaust air. In this way, the ERV will supply to the home air which is cooler and drier than outside. Remember that an ERV is not a dehumidifier, and on its own will not take moisture out of the air.
So why use an ERV?
A properly operating air conditioner will not only lower the temperature in your house, but will also lower the humidity level. This prevents an uncomfortable cold
What is the maintenance?
About once a year you should use a vacuum cleaner to remove the dust from the core's surface. DO NOT WASH WITH WATER!!
Is an air filter needed?
To prevent clogging of the core, an air filter should always be installed on the supply and exhaust sides of the core.
How much ventilation do I need?
During seasons when your windows and doors are closed, the ERV should operate continuously when the dwelling is occupied, and either continuously or intermittently when not occupied.
For most installations the ERV will normally be set to operate continuously on low speed with the option of going to high speed as the need arises. For example; if you are entertaining and there is a large number of people present (some may be smoking), the unit should be switched to high speed.
Your ERV may be equipped with automatic or manual switches, but all ERVs will have a manual speed control override.
3
4
ENGINEERING DATA
THERMALLY CONDUCTIVE, PATENTED ALUMINUM CORE
The cross-flow heat recovery core transfers heat between the two airstreams. It is easily removed for cleaning or service.
MOTORS AND BLOWERS - Each air stream has one centrifugal blower driven by a common PSC motor. 5 speed fan operation. 120 VAC, .8 Amps.
FILTERS - Washable air filters in exhaust and supply air streams.
MOUNTING THE HRV - Four threaded inserts at corners of the cabinet designed to accept PVC reinforced polyester straps that are supplied with the unit.
DEFROST - Recirculating defrost system.
CASE - Twenty gauge prepainted galvanized steel (G60) for superior corrosion resistance. Insulated to prevent exterior condensation. Drain connections 2 - 1/2" (12 mm) OD.
CONTROLS - ControlAir 15
WEIGHT 52 lbs. (23.6 kg) SHIPPING WEIGHT 56 lbs. (25.4 kg)
Model 95MAX
PERFORMANCE
HVI CERTIFIED
Net supply airflow in cfm (L/s) against external static pressure
E.S.P |
|
cfm |
L/s |
|
@ 0.1” (25 |
Pa) |
89 |
(42) |
|
@ 0.2” (50 |
Pa) |
78 |
(37) |
|
@ 0.3” |
(75 |
Pa) |
64 |
(30) |
@ 0.4” |
(100 Pa) |
36 |
(17) |
Maximum Temperature Recovery |
74% |
|
|
|
|
Sensible Effectiveness |
80% |
|
@ 64 cfm (30 L/s) (CSA C439M) |
||
Sensible Efficiency |
|
|
@ 64 cfm (30 L/s) |
32˚F (0˚C) |
75% |
Sensible Efficiency |
|
|
@ 64 cfm (30 L/s) |
-13˚F (-25˚C) |
75% |
|
|
|
VAC @ 60HZ |
|
120 |
WATTS / Low speed |
35 |
|
WATTS / High speed |
136 |
|
Amp rating |
|
0.8 |
|
|
|
DIMENSIONS 95MAX |
inches (mm) |
|
|
|
|
|
|
|
|
|
|
18.5" |
|
|
Hanging |
|
|
|
(470 mm) |
|
|
|
|
|
|
|
|
straps (4) |
|
|
|
|
|
|
knockout for |
|
|
|
|
|
|
|
Threaded |
|
|
|
|
|
side mounting of |
|
|
|
|
|
|
|
inserts (4) |
|
|
|
|
|
EXHAUST return port |
|
|
|
|
|
|
|
at corners |
|
|
|
|
|
6" round collar |
|
|
|
|
|
|
|
|
|
|
|
|
|
converted to oval |
|
|
18.5" |
|
|
|
|
|
|
|
|
|
|
|
|
|
(470 mm) |
|
|
|
|
|
|
EXHAUST |
|
mm)(622 |
|
|
|
SUPPLY |
Stale Air |
|
|
|
|
to outside |
||
24.5" |
|
|
|
Fresh air |
||
Core |
|
|
EXHAUST |
|||
|
|
Removably |
|
|
from outside |
5" round collar |
|
|
Heat Recovery |
|
|
5" round collar |
|
|
|
|
|
|
|
Return air |
|
|
|
|
|
SUPPLY |
from building |
|
|
|
minimum |
|
Fresh air |
Choice of port location |
|
|
|
|
to building |
||
|
|
|
18 inches (459 mm) |
|
||
|
|
|
|
6" round |
Knockouts on top and |
|
|
|
|
required for |
|
||
|
|
|
|
(conv. to oval) |
side of unit (use 1 only) |
|
|
|
|
service access |
|
||
|
|
Drain Pan |
|
collar |
6" round (conv. to oval) |
|
|
|
|
|
|||
|
|
|
|
|
|
collar supplied |
|
|
Drain spout |
|
16" |
|
|
|
|
|
|
|
|
|
|
FRONT |
|
SIDE |
(406 mm) |
|
TOP |
|
|
|
|
|||
OPTIONS |
|
|
|
|
|
99-104 Digital Electronic Timer - 20/40/60 min.
99-105 Programmable Ventilation Control (PVC)
includes Programmable Time Clock, Dehumidistat
and Air Sentry™
99-109 Air Sentry™ Air Quality Monitor designed to accept remotely mounted Control Pad
99-250 Ventilation Dehumidistat - Dehumidistat designed to accept remotely mounted Control Pad
DATE: __________________________
99-163 Duct Heater w/ Electronic SCR Thermostat, 1 Kw,
6” (150 mm)
99-186 Weatherhoods, Two - 5” (125 mm) c/w 1/4” (6 mm) mesh screen
All units conform to CSA and UL standards.
WARRANTY
Units carry a LIFETIME warranty on the heat recovery core and a 5 year replacement parts warranty.
|
511 McCormick Blvd. |
|
PROJECT: ________________________________________ |
London, Ontario N5W 4C8 |
|
Ph: (519) 457-1904 |
||
|
||
|
Fx: (519) 457-1676 |
|
MECHANICAL CONTRACTOR: ________________________________ |
Email: nutech@lifebreath.com |
|
Website: www.lifebreath.com |
||
5 |
TI-113-NE |
|
|
0103 |
Model 155MAX
ENGINEERING DATA
THERMALLY CONDUCTIVE, PATENTED ALUMINUM CORE
The cross-flow heat recovery core transfers heat between the two airstreams. It is easily removed for cleaning or service.
MOTORS AND BLOWERS - Each air stream has one centrifugal blower driven by a common PSC motor. 5 speed fan operation. 120 VAC, 1.0 Amps.
FILTERS - Washable air filters in exhaust and supply air streams.
MOUNTING THE HRV - Four threaded inserts at corners of case designed to accept four reinforced polyester straps that are supplied with the unit.
DEFROST - Recirculating damper defrost system.
DEHUMIDISTAT - Adjustable Internal Dehumidistat.
CASE - Twenty gauge prepainted galvanized steel (G60) for superior corrosion resistance. Insulated to prevent exterior condensation. Drain connections 2 - 1/2" (12 mm) OD.
CONTROLS - ControlAir 15
WEIGHT 71 lbs. (32.5 kg) SHIPPING WEIGHT 73 lbs. (33.5 kg)
PERFORMANCE
HVI CERTIFIED
Net supply airflow in cfm (L/s) against external static pressure
E.S.P |
cfm |
L/s |
@ 0.1” (25 Pa) |
169 |
(80) |
@ 0.2” (50 Pa) |
161 |
(76) |
@ 0.3” (75 Pa) |
150 |
(71) |
@ 0.4” (100 Pa) |
130 |
(61) |
@ 0.5” (125 Pa) |
56 |
(26) |
Maximum Temperature Recovery |
83% |
||
|
|
||
Sensible Effectiveness |
76% |
||
@ 64 cfm (30 L/s) (CSA C439M) |
|||
|
|||
Sensible Efficiency |
32°F (0OC) |
70% |
|
@ 64 cfm (30 L/s) |
|||
Sensible Efficiency |
-13°F (-25OC) |
70% |
|
@ 64 cfm (30 L/s) |
|
||
|
|
|
|
VAC @ 60HZ |
|
120 |
|
|
|
|
|
WATTS / Low speed |
|
49 |
|
|
|
||
WATTS / High speed |
120 |
||
|
|
|
|
Amp rating |
|
1.0 |
DIMENSIONS 155MAX inches (mm)
FRESH AIR |
STALE AIR |
FROM OUTSIDE |
FROM INSIDE |
RECIRCULATING |
FILTERS |
|
|
|
|
DEFROST |
|
|
DAMPER |
|
|
CORE |
BLOWERS |
|
MOTOR |
|
|
|
(483) |
|
|
19" |
|
STALE AIR |
FRESH AIR |
|
TO OUTSIDE |
TO INSIDE |
|
*NOTE: Front clearance of 25 inches (635 mm) is recommended
for servicing unit.
32 5/8"
CONDENSATE DRAINS (828) 14 3/4" (375)
*All Duct Connections 6" (150mm)
OPTIONS
99-104 Digital Electronic Timer - 20/40/60 min.
99-105 Programmable Ventilation Control (PVC)
includes Programmable Time Clock, Dehumidistat
and Air Sentry™
99-109 Air Sentry™ Air Quality Monitor designed to accept remotely mounted Control Pad
99-250 Ventilation Dehumidistat - Dehumidistat designed to accept remotely mounted Control Pad.
99-163 Duct Heater w/ Electronic SCR Thermostat, 1 Kw,
6” (150 mm)
99-164 Duct Heater w/ Electronic SCR Thermostat, 2 Kw,
6” (150 mm)
99-186 Weatherhoods, Two - 6” (150 mm) c/w 1/4” (6 mm) mesh screen
All units conform to CSA and UL standards.
WARRANTY
Units carry a LIFETIME warranty on the heat recovery core and a 5 year replacement parts warranty.
DATE: __________________________
|
511 McCormick Blvd. |
|
PROJECT: __________________________________________ |
London, Ontario N5W 4C8 |
|
Ph: (519) 457-1904 |
||
|
Fx: (519) 457-1676 |
|
MECHANICAL CONTRACTOR: _____________________________ |
Email: nutech@lifebreath.com |
|
Website: www.lifebreath.com |
||
6 |
TI-92-NE |
|
0103 |
||
|
Model 200MAX
ENGINEERING DATA
THERMALLY CONDUCTIVE, PATENTED ALUMINUM CORE
The cross-flow heat recovery core transfers heat between the two airstreams. It is easily removed for cleaning or service.
MOTORS AND BLOWERS - Each air stream has one centrifugal blower driven by a common PSC motor. 5 speed fan operation. 120 VAC, 1.4 Amps.
FILTERS - Washable air filters in exhaust and supply air streams.
MOUNTING THE HRV - Four threaded inserts at corners of case designed to accept four reinforced polyester straps that are supplied with the unit.
DEFROST - Recirculating damper defrost system.
DEHUMIDISTAT - Adjustable Internal Dehumidistat.
CASE - Twenty gauge prepainted galvanized steel (G60) for superior corrosion resistance. Insulated to prevent exterior condensation. Drain connections 2 - 1/2" (12 mm) OD.
CONTROLS - ControlAir 15
WEIGHT 71 lbs. (32.5 kg SHIPPING WEIGHT 73 lbs. (33.5 kg)
PERFORMANCE
HVI CERTIFIED
Net supply airflow in cfm (L/s) against external static pressure
E.S.P |
cfm |
L/s |
@ 0.1” (25 Pa) |
232 |
(109) |
@ 0.2” (50 Pa) |
223 |
(105) |
@ 0.3” (75 Pa) |
215 |
(102) |
@ 0.4” (100 Pa) |
195 |
(92) |
@ 0.5” (125 Pa) |
189 |
(89) |
Maximum Temperature Recovery |
81% |
|
Sensible Effectiveness |
74% |
|
@ 117 cfm (55 L/s) (CSA C439M) |
||
Sensible Efficiency |
|
|
@ 117 cfm (55 L/s) |
32˚F (0˚C) |
65% |
Sensible Efficiency |
|
|
@ 117 cfm (55 L/s) |
-13˚F (-25˚C) |
66% |
|
|
|
VAC @ 60HZ |
|
120 |
WATTS / Low speed |
87 |
|
WATTS / High speed |
164 |
|
Amp rating |
|
1.4 |
DIMENSIONS 200MAX inches (mm)
FRESH AIR |
STALE AIR |
FROM OUTSIDE |
FROM INSIDE |
RECIRCULATING |
FILTERS |
|
|
|
|
DEFROST |
|
|
DAMPER |
|
|
CORE |
BLOWERS |
|
MOTOR |
|
|
|
(483) |
|
|
19" |
|
STALE AIR |
FRESH AIR |
|
TO OUTSIDE |
TO INSIDE |
|
*NOTE: Front clearance of 25 inches (635 mm) is recommended
for servicing unit.
32 5/8"
CONDENSATE DRAINS (828) 14 3/4" (375)
*All Duct Connections 6" (150mm)
OPTIONS
99-104 Digital Electronic Timer - 20/40/60 min.
99-105 Programmable Ventilation Control (PVC)
includes Programmable Time Clock, Dehumidistat
and Air Sentry™
99-109 Air Sentry™ Air Quality Monitor designed to accept remotely mounted Control Pad
99-250 Ventilation Dehumidistat - Dehumidistat designed to accept remotely mounted Control Pad.
99-163 Duct Heater w/ Electronic SCR Thermostat, 1 Kw,
6” (150mm)
99-164 Duct Heater w/ Electronic SCR Thermostat, 2 Kw,
6” (150mm)
99-186 Weatherhoods, Two - 6” (150mm)
c/w 1/4” (6mm) mesh screen
All units conform to CSA and UL standards.
WARRANTY
Units carry a LIFETIME warranty on the heat recovery core and a 5 year replacement parts warranty.
DATE: __________________________
|
511 McCormick Blvd. |
PROJECT: __________________________________________ |
London, Ontario N5W 4C8 |
Ph: (519) 457-1904 |
|
|
Fx: (519) 457-1676 |
MECHANICAL CONTRACTOR: _____________________________ |
Email: nutech@lifebreath.com |
Website: www.lifebreath.com |
|
7 |
TI-99-NE |
0103 |
Model MAXTOP
ENGINEERING DATA
THERMALLY CONDUCTIVE, PATENTED ALUMINUM CORE
The cross-flow heat recovery core transfers heat between the two airstreams. It is easily removed for cleaning or service.
MOTORS AND BLOWERS - Each air stream has one centrifugal blower driven by a common PSC motor. 5 speed fan operation. 120 VAC, 1.4 Amps.
FILTERS - Washable air filters in exhaust and supply air streams.
MOUNTING THE HRV - Four threaded inserts at corners of case designed to accept four reinforced polyester straps that are supplied with the unit.
DEFROST - Recirculating damper defrost system.
DEHUMIDISTAT - Adjustable Internal Dehumidistat.
CASE - Twenty gauge prepainted galvanized steel (G60) for superior corrosion resistance. Insulated to prevent exterior condensation. Drain connections 2 - 1/2" (12 mm) OD.
CONTROLS - ControlAir 15
WEIGHT 87 lbs. (39.5 kg) SHIPPING WEIGHT 89 lbs. (40.5 kg)
PERFORMANCE
HVI CERTIFIED
Net supply airflow in cfm (L/s) against external static pressure
E.S.P |
cfm |
L/s |
@ 0.1” (25 Pa) |
196 |
(93) |
@ 0.2” (50 Pa) |
188 |
(89) |
@ 0.3” (75 Pa) |
178 |
(84) |
@ 0.4” (100 Pa) |
165 |
(78) |
@ 0.5” (125 Pa) |
149 |
(71) |
Maximum Temperature Recovery |
80% |
||
Sensible Effectiveness |
72% |
||
@ 117 cfm (55 L/s ) (CSA C439M) |
|||
|
|||
Sensible Efficiency |
32OF (0°C) |
64% |
|
@ 117 cfm (55 L/s) |
|||
Sensible Efficiency |
-13OF (-25°C) |
70% |
|
@ 67 cfm (31 L/s) |
|
||
VAC @ 60HZ |
|
120 |
|
|
|
|
|
WATTS / Low speed |
|
74 |
|
|
|
||
WATTS / High speed |
164 |
||
|
|
|
|
Amp rating |
|
1.4 |
|
DIMENSIONS MAXTOP |
inches (mm) |
|
|
|
|
|
|
|
|
|
|
|
ALL DUCT CONNECTIONS |
|
|
|
|
ARE 6" (150 mm) |
|
CONTROLS |
|
|
|
|
7 1/2" |
|
STALE AIR |
|
|
(191 mm) |
|
FRESH AIR |
|
|
|
EXHAUST |
||
|
|
|
SUPPLY |
|
|
|
|
|
|
|
|
|
|
TO BUILDING |
25 1/2 " |
|
|
|
|
(648 mm) |
|
|
SUPPLY OF |
STALE AIR |
|
|
|
||
|
18" |
|
FRESH AIR |
RETURN FROM |
|
(457 mm) |
|
|
BUILDING |
|
|
|
|
|
|
¤ |
|
|
|
22 1/2" |
DRAIN |
26 1/2" |
|
*Service Clearance |
(572 mm) |
CONNECTION |
(673 mm) |
|
25" (635 mm) |
FRONT VIEW |
|
SIDE VIEW |
|
TOP VIEW |
OPTIONS
99-104 Digital Electronic Timer - 20/40/60 min.
99-105 Programmable Ventilation Control (PVC)
includes Programmable Time Clock, Dehumidistat
and Air Sentry™
99-109 Air Sentry™ Air Quality Monitor designed to accept remotely mounted Control Pad
99-250 Ventilation Dehumidistat - Dehumidistat designed to accept remotely mounted Control Pad
99-163 Duct Heater w/ Electronic SCR Thermostat, 1 Kw,
6” (150mm)
99-164 Duct Heater w/ Electronic SCR Thermostat, 2 Kw,
6” (150mm)
99-186 Weatherhoods, Two - 6” (150mm)
c/w 1/4” (6mm) mesh screen
All units conform to CSA and UL standards.
WARRANTY
Units carry a LIFETIME warranty on the heat recovery core and a 5 year replacement parts warranty.
DATE: __________________________
|
511 McCormick Blvd. |
PROJECT: __________________________________________ |
London, Ontario N5W 4C8 |
Ph: (519) 457-1904 |
|
|
Fx: (519) 457-1676 |
MECHANICAL CONTRACTOR: _____________________________ |
Email: nutech@lifebreath.com |
Website: www.lifebreath.com |
|
8 |
TI-100-NE |
|
0103 |
Model 195DCS
ENGINEERING DATA
THERMALLY CONDUCTIVE, PATENTED ALUMINUM CORE
The cross-flow heat recovery core transfers heat between the two airstreams. The two cores are arranged for highly efficient counter current airflow.
MOTORS AND BLOWERS - Each air stream has one centrifugal blower driven by a common PSC motor. 5 speed fan operation. 120 VAC, 1.5 Amps.
FILTERS - Washable air filters in exhaust and supply air streams.
MOUNTING THE HRV - Four threaded inserts at corners of case designed to accept four reinforced polyester straps that are supplied with the unit.
DEFROST - Damper defrost system.
DEHUMIDISTAT - Adjustable Internal Dehumidistat.
CASE - Twenty gauge prepainted galvanized steel (G60) for superior corrosion resistance. Insulated to prevent exterior condensation. Drain connections 2 - 1/2" (12 mm) OD.
CONTROLS - ControlAir 15
WEIGHT 106 lbs. (48 kg) SHIPPING WEIGHT 108 lbs. (49 kg)
PERFORMANCE
HVI CERTIFIED
Net supply airflow in cfm (L/s) against external static pressure
E.S.P |
cfm |
L/s |
@ 0.1” (25 Pa) |
203 |
(96) |
@ 0.2” (50 Pa) |
191 |
(90) |
@ 0.3” (75 Pa) |
182 |
(86) |
@ 0.4” (100 Pa) |
167 |
(79) |
@ 0.5” (125 Pa) |
155 |
(73) |
Maximum Temperature Recovery |
88% |
||
|
|
||
Sensible Effectiveness |
88% |
||
@ 117 cfm (55 L/s) (CSA C439M) |
|||
|
|||
Sensible Efficiency |
32OF (0°C) |
80% |
|
@ 117 cfm (55 L/s) |
|||
Sensible Efficiency |
-13°F (-25OC) |
77% |
|
@ 117 cfm (55 L/s) |
|
||
VAC @ 60HZ |
|
120 |
|
|
|
|
|
WATTS / Low speed |
|
100 |
|
WATTS / High speed |
|
173 |
|
|
|
|
|
Amp rating |
|
1.5 |
TO OUTSIDE |
DIMENSIONS 195DCS |
FROM INSIDE |
|
|
||
|
|
|
|
inches (mm) |
|
|
METAL CLASPS |
FILTER |
MOTOR |
|
|
|
|
STALE AIR |
|
|
|
STALE AIR |
|
|
Ports |
|
|
|
Ports |
19" |
(483) |
6" (150 mm) |
|
|
|
7" (178 mm) |
||
|
|
|
|
|
||
FILTER |
|
|
|
BLOWERS |
|
|
|
|
|
|
|
|
*NOTE: |
FRESH AIR |
|
|
|
FRESH AIR |
|
Front clearance |
|
|
|
|
of 25 inches (635 mm) |
||
FROM OUTSIDE |
|
|
|
TO INSIDE |
|
is recommended |
|
|
|
|
|
|
for servicing unit. |
DEFROST |
|
49 " |
|
|
|
14 3/4" |
DAMPER |
CONDENSATE |
(1245) |
|
|
|
|
|
|
|
|
(375) |
||
DEFROST AIR |
DRAINS |
|
|
|
|
|
|
|
|
|
|
||
FROM INSIDE |
|
|
|
|
|
|
OPTIONS
99-104 Digital Electronic Timer - 20/40/60 min.
99-105 Programmable Ventilation Control (PVC)
includes Programmable Time Clock, Dehumidistat
and Air Sentry™
99-109 Air Sentry™ Air Quality Monitor designed to accept remotely mounted Control Pad
99-250 Ventilation Dehumidistat - Dehumidistat designed to accept remotely mounted Control Pad.
DATE: __________________________
99-160 Duct Heater w/ Electronic SCR Thermostat,
1 Kw, 7” (178 mm)
99-161 Duct Heater w/ Electronic SCR Thermostat,
2 Kw, 7” (178 mm)
99-186 Weatherhoods, Two - 6” (150 mm) c/w 1/4” (6mm) mesh screen
All units conform to CSA and UL standards.
WARRANTY
Units carry a LIFETIME warranty on the heat recovery core and a 5 year replacement parts warranty.
|
511 McCormick Blvd. |
PROJECT: __________________________________________ |
London, Ontario N5W 4C8 |
Ph: (519) 457-1904 |
|
|
Fx: (519) 457-1676 |
MECHANICAL CONTRACTOR: _____________________________ |
Email: nutech@lifebreath.com |
Website: www.lifebreath.com |
|
9 |
TI-101-NE |
0112 |
ENGINEERING DATA
THERMALLY CONDUCTIVE, PATENTED ALUMINUM CORE
The cross-flow heat recovery core transfers heat between the two airstreams The two cores are arranged for highly efficient counter current airflow.
MOTORS AND BLOWERS - Each air stream has one centrifugal blower driven by a common PSC motor. 5 speed fan operation. 120 VAC, 2.9 Amps.
FILTERS - Washable air filters in exhaust and supply air streams.
MOUNTING THE HRV - Four threaded inserts at corners of case designed to accept four reinforced polyester straps that are supplied with the unit.
DEFROST - Damper defrost system.
DEHUMIDISTAT - Adjustable Internal Dehumidistat.
CASE - Twenty gauge prepainted galvanized steel (G60) for superior corrosion resistance. Insulated to prevent exterior condensation. Drain connections 2 - 1/2" (12 mm) OD.
CONTROLS - ControlAir 15
WEIGHT 106 lbs. (48 kg) SHIPPING WEIGHT 108 lbs. (49 kg )
Model 300DCS
PERFORMANCE
HVI CERTIFIED
Net supply airflow in cfm (L/s) against external static pressure
E.S.P |
cfm |
L/s |
@ 0.1” (25 Pa) |
265 |
(125) |
@ 0.2” (50 Pa) |
260 |
(123) |
@ 0.3” (75 Pa) |
250 |
(118) |
@ 0.4” (100 Pa) |
235 |
(111) |
@ 0.5” (125 Pa) |
220 |
(104) |
Maximum Temperature Recovery |
90% |
||
|
|
||
Sensible Effectiveness |
90% |
||
@ 117 cfm (55 L/s) (CSA C439M) |
|||
|
|||
Sensible Efficiency |
32°F (0OC) |
79% |
|
@ 117 cfm (55 L/s) |
|||
Sensible Efficiency |
-13°F (-25OC) |
75% |
|
@ 117 cfm (55 L/s) |
|
||
VAC @ 60HZ |
|
120 |
|
|
|
|
|
WATTS / Low speed |
|
150 |
|
|
|
|
|
WATTS / High speed |
|
333 |
|
|
|
|
|
Amp rating |
|
2.9 |
TO OUTSIDE |
|
DIMENSIONS 300DCS FROM INSIDE |
||
|
|
|
|
inches (mm) |
METAL CLASPS |
|
FILTER |
MOTOR |
|
STALE AIR |
|
|
|
STALE AIR |
Ports |
|
|
|
Ports |
6" (150 mm) |
|
|
|
7" (178 mm) |
FILTER |
|
|
|
BLOWERS |
FRESH AIR |
|
|
|
FRESH AIR |
FROM OUTSIDE |
|
|
|
TO INSIDE |
DEFROST |
|
|
49 " |
|
DAMPER |
CONDENSATE |
(1245) |
|
|
|
|
|||
DEFROST AIR |
DRAINS |
|
|
|
FROM INSIDE |
|
|
|
|
19" |
(483) |
14 3/4"
(375)
*NOTE:
Front clearance
of 25 inches (635 mm) is recommended
for servicing unit.
OPTIONS
99-104 Digital Electronic Timer - 20/40/60 min.
99-105 Programmable Ventilation Control (PVC)
includes Programmable Time Clock, Dehumidistat
and Air Sentry™
99-109 Air Sentry™ Air Quality Monitor designed to accept remotely mounted Control Pad.
99-250 Ventilation Dehumidistat - Dehumidistat designed to accept remotely mounted Control Pad.
DATE: __________________________
99-160 Duct Heater w/ Electronic SCR Thermostat,
1 Kw, 7” (178 mm)
99-161 Duct Heater w/ Electronic SCR Thermostat,
2 Kw, 7” (178 mm)
99-186 Weatherhoods, Two - 6” (150mm)
c/w 1/4” (6mm) mesh screen
All units conform to CSA and UL standards.
WARRANTY
Units carry a LIFETIME warranty on the heat recovery core and a 5 year replacement parts warranty.
|
511 McCormick Blvd. |
|
PROJECT: __________________________________________ |
London, Ontario N5W 4C8 |
|
Ph: (519) 457-1904 |
||
|
Fx: (519) 457-1676 |
|
MECHANICAL CONTRACTOR: _____________________________ |
Email: nutech@lifebreath.com |
|
Website: www.lifebreath.com |
||
10 |
TI-102-NE |
|
0112 |
||
|