LG L1006R, LWHD1006RY6, L1006RY6, LWHD1006R, HBLG1003R Service Manual

...
0 (0)

LG

LG Room

Air Conditioner

SERVICE MANUAL

MODEL: HBLG8003R,LB8000ER,LW8000ER,HBLG1003R,LWHD1006R,L1006R LWHD1006RY6,L1006RY6

CAUTION

BEFORE SERVICING THE UNIT, READ THE SAFETY PRECAUTIONS IN THIS MANUAL.

ONLY FOR AUTHORIZED SERVICE PERSONNEL.

Air Conditioner Service Manual

 

TABLE OF CONTENTS

 

Safety Precautions..........................................................................................................................................

3

Dimensions .....................................................................................................................................................

5

Outside Dimensions ...................................................................................................................................

5

Product Specifications ..................................................................................................................................

6

Installation .......................................................................................................................................................

7

Select the Best Location ............................................................................................................................

7

Installation Check.......................................................................................................................................

7

How to Secure the Drain Pipe....................................................................................................................

7

How to Install..............................................................................................................................................

8

Operation ......................................................................................................................................................

12

Function of Controls .................................................................................................................................

12

Disassembly ..................................................................................................................................................

14

Mechanical Parts......................................................................................................................................

14

Air handling Parts.....................................................................................................................................

15

Electrical Parts .........................................................................................................................................

16

Refrigerating Cycle...................................................................................................................................

18

Schematic Diagram.......................................................................................................................................

21

Wiring Diagram.........................................................................................................................................

21

Electronic Control Device.........................................................................................................................

22

Components Location ..............................................................................................................................

23

Troubleshooting Guide .................................................................................................................................

24

Pipeing System ........................................................................................................................................

24

Troubleshooting Guide .............................................................................................................................

25

Electrical Parts Troubleshooting Guide......................................................................................................

27

Electrical Parts ........................................................................................................................................

31

Exploded View ..............................................................................................................................................

37

Replacement Parts List ................................................................................................................................

38

2 Room Air Conditioner

Safety Precautions

Safety

Precautions

Precautions

To prevent injury and property damage, follow these instructions.

Incorrect operation due to ignoring instructions might cause harm or damage, the seriousness of which is indicated by the following symbols.

WARNING This symbol shows the possibility of death or serious injury.

CAUTION This symbol indicates the possibility of injury or damage to property.

Never Do This

Always Do This

■ The following items are classified by these symbols.

WARNINGI

Plug in the power plug properly.

Doing so may cause electric shock or fire due to heat generation.

Do not modify power cord length or share the outlet with other appliances.

Doing so may cause electric shock or fire due to heat generation.

Do not allow water to run into electric parts.

Doing so may cause failure of machine or electric shock.

Do not use the socket if it is loose or damaged.

Doing so may cause fire or electric shock.

Do not operate or stop the unit by inserting or pulling out the power plug.

Doing so may cause electric shock or fire due to heat generation.

Do not operate with wet hands or in damp environment.

Doing so may cause electric shock.

Always install air leakage breaker and a dedicated switching board.

Failure to install these may cause fire or electric shock accident.

Do not open the entrance during operation.

• It may cause electric shock.

Do not damage or use an unspecified power cord.

Doing so may cause electric shock or fire.

If the supply cord is damaged, it must be replaced by the manufacturer, the manufacturer's service agent, or a similarly qualified person in order to avoid a hazard. (Y attachment)

Always plug into a grounded outlet.

No grounding may cause electric shock (See Installation Manual).

Unplug the unit if strange sounds, odors, or smoke comes from it.

Such a unit may pose a risk of fire or electric shock accident.

Keep firearms away.

Do not use the power cord close to heating tools.

• Doing so may cause fire or electric shock.

Do not use the power cord near flammable gas or combustibles such as gasoline, benzene, thinner, etc.

• Doing so may lead to an explosion or fire.

Service Manual 3

LG L1006R, LWHD1006RY6, L1006RY6, LWHD1006R, HBLG1003R Service Manual

Safety Precautions

WARNINGI

Ventilate before operating air conditioner when gas goes out.

Operating the air conditioner in the presence of gas vapors can lead to explosions and fire.

Do not disassemble or modify products randomly.

• Doing so may cause failure or electric shock.

Never touch the metal parts of the unit when removing the filter.

They are sharp and may cause injury.

When cleaning the unit, first make sure the is off and the cord is unplugged.

CAUTIONI

Do not clean the air conditioner with water.

Water may enter the unit and degrade the insulation. It also may cause an electric shock.

Do not put a pet or house plant where it will be exposed to direct air flow.

Since the fan rotates at high speed during operation, it may cause injury if activated while cleaning.

Stop operation in storm or hurricanes.

• This could injure the pet or plant.

Hold the plug by the head when taking it out.

Operate only in a well ventilated area when using in the presence of a stove, etc.

An oxygen shortage may otherwise occur.

Do not use appliance for special purpose such as climate control for animals or vegetables, precision machine, or conservation of art articles.

It may cause damage of animals or vegetables or loss of property.

Turn off the main power switch when not using it for a long time.

Operation with windows opened may cause wetting of indoor and soaking of household furniture.

Do not place obstacles around the absorption inlet or output.

Doing so may cause failure of appliance or accident.

• Improper handling may cause

• Doing so can prolong the life of

electric shock or damage.

the product.

Ensure that an installation console of the outdoor appliance is not damaged due to extened use.

If the previous air conditioner damaged the console, there is a risk of the new unit falling.

Always insert filters securely. Clean them every two weeks.

Operation without filters will cause failure.

Do not use abrasives or strong detergent such as wax or thinner. Always use a soft cloth.

Otherwise, the products appearance may be damaged due to change of product color or scratching of its surface.

Do not place heavy object on the power cord and take care so that the cord is not pinched.

Treating the power cord carelessly poses a danger of fire or electric shock.

Do not drink water drained from air conditioner.

It contains contaminants that would make you sick.

If water enters the product, turn off the the power switch of the main body of appliance. Contact service center after taking the powerplug out from the socket.

Do not direct airflow at room occupants only.

• This could damage your health.

4 Room Air Conditioner

Dimensions

Dimensions

SymbolsUsedin this Manual

This symbol alerts you to the risk of electric shock.

This symbol alerts you to hazards that could cause harm to the air conditioner.

NOTICE This symbol indicates special notes.

OutsideDimensions

 

 

 

 

 

 

 

unit: mm(inch)

490(19 3/8")

 

 

 

 

 

 

 

 

29(1

5/

) 126.5(431/32"

)

 

 

510 20 3 32

 

 

 

 

32"

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FAN

")32/29354(13

18(23/32")

Service Manual 5

Specfications

PrProduct Specifications

ITEMS

MODELS

 

POWER SUPPLY

 

COOLING CAPACITY

(Btu/h)

INPUT

(W)

RUNNING CURRENT

(A)

E.E.R

(BTU/W .h)

OPERATING

INDOOR (°C)

 

CONDITION

OUTDOOR (°C)

 

REFRIGERANT (R-22) CHARGE

EVAPORATOR

CONDENSER

FAN, INDOOR

FAN, OUTDOOR

FAN SPEEDS, FAN/COOLING

FAN MOTOR

OPERATION CONTROL

ROOM TEMP. CONTROL

AIR DIRECTION CONTROL

CONSTRUCTION

PROTECTOR

COMPRESSOR

FAN MOTOR

 

POWER CORD

 

 

DRAIN SYSTEM

 

 

NET WEIGHT

 

(lbs/kg)

OUTSIDE DIMENSION

(inch)

(W x H x D)

 

(mm)

* DB:Dry Bulb ** WB:Wet Bulb

HBLG8003R

LB8000ER

LW8000ER

 

1ø, 115, 60Hz

8,000

 

8,200

820

 

750

7.4

 

7.0

9.8

 

10 . 9

 

26.7(DB)*

19.4(WB)**

 

35(DB)*

23.9(WB)**

300g(10.6oz)

 

400g(14.1oz)

2 ROW 11STACKS

 

3 ROW 11STACKS

2 ROW 16STACKS TURBO FAN

PROPELLER TYPE FAN WITH SLINGER RING 3/3

6 POLES REMOTE CONTROLLER

THERMISTOR

VERTICAL LOUVER (RIGHT & LEFT)

HORIZONTAL LOUVER (UP & DOWN)

SLIDE IN-OUT CHASSIS

OVERLOAD PROTECTOR

INTERNAL THERMAL PROTECTOR

(3 WIRE WITH GROUDING) ATTACHMENT PLUG (CORD-CONNECTED TYPE)

DRAIN PIPE OR SPLASHED BY FAN SLINGER 62/28

203/32 x 13 7/8 x 193/8 510 x 353 x 490

HBLG1003R LWHD1006R(Y6) L1006R(Y6)

10, 000

1,020

9.2

9 .8

420g(14.6oz)

71/32

6 Room Air Conditioner

Installation

Installation

SelecttheBest Location

1.To prevent vibration and noise, make sure the unit is installed securely and firmly.

2.Install the unit where the sunlight does not shine directly on the unit.

3.The outside of the cabinet must extend outward for at least 12" and there should be no obstacles, such as a fence or wall, within 20" from the back of the cabinet because it will prevent heat radiation of the condenser.

Restriction of outside air will greatly reduce the cooling efficiency of the air conditioner.

COOLED AIR

30"~60"

Figure 1

CAUTION: All side louvers of the cabinet must remain exposed on the outdside of the structure.

4.Install the unit a little slanted so the back is slightly lower than the front (about 1/2"). This will help force con-densed water to the outside.

5.Install the unit from the bottom about 30"~60" above the floor level.

Installation Check

The setting conditions must be checked prior to initial starting.

The undermentioned items are especially important checking points when the installation is finished.

1.Grounding wire (Green or Green and Yellow) is provided in the power cord. The green wire must be grounded.

2.Connect to a single-outlet 15A circuit. (or 20A circuit for Electric Heater Model)

3.To avoid vibration or noise, make sure the air conditioner is installed securely.

4 Avoid placing furniture or draperies in front of the air inlet and outlet.

BASE PAN

Figure 2

HowtoSecure theDrainPipe

The air conditioner must be installed horizontally or tilted slightly to the outside for proper water drainage.

On exceptionally hot and humid days the air conditioner may overflow condensed water.

If the air conditioner is used in hot and a high humidity zone, exchange the HOLE RUBBER for the DRAIN PIPE.(See figure 2, figure 3.)

BASE PAN

Figure 3

AWNING FENCE

HEAT

RADIATION

ABOUT 1/2"

Over 20"

BOTTOM 1 HOLE RUBBER

BOTTOM 2 HOLE RUBBER

Service Manual 7

Installation

HowtoInstall

1. WHEN USING GASKET

A

1

A

2

 

 

 

2

 

G

 

 

 

 

 

 

 

 

 

RIGHT SIDE

B

 

 

C

B

 

 

 

 

 

 

 

J H

HORIZONTAL

 

 

 

 

 

 

 

 

LINE

4

D

E

3

 

 

 

 

F

 

1. WINDOW (WIDTH-A, HEIGHT-B)

 

4. DETAILS 5.1 x 30 ROUND HEAD WOOD

 

2. GASKET

 

 

 

SCREWS

 

 

 

3. WALL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A

B

C

D

E

F

H

J

K

 

 

 

 

 

 

 

 

 

535mm

366mm

250mm

30mm

0~25mm

OVER 420mm

32

5~10mm

0~5mm

(211/2")

(147/16")

(10")

(11/16")

(0~1")

(OVER 1617/32")

(11/4")

(3/16"~3/8")

(0~3/16")

2. WHEN USING INSTALLATION KITS

A. WINDOW REQUIREMENTS

This unit is designed for installation in

standard double hung windows with actual opening widths from 25" to 36".

The top and bottom window sash must open sufficiently to allow a clear vertical opening of 16" from the bottom of the upper sash to the window stool.

B. INSTALLATION KITS CONTENTS

1

2

3

4

 

5

6

7

8

9

13

 

 

 

 

11

12

10

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

25" to 36"

 

 

 

 

 

 

 

 

 

 

 

 

 

15" min

Stool

 

 

 

Offset

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1/2" to 11/4"

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Sill

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Interior wall

 

 

Exterior

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

203/32" min

 

 

 

 

 

 

 

 

 

 

 

 

(Without frame curtain)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NO.

NAME OF PARTS

 

Q'TY

 

1

FRAME CURTAIN

 

2

 

2

SILL SUPPORT

 

2

 

3

BOLT

 

2

 

4

NUT

 

2

 

5

SCREW(TYPE A)

 

16

 

6

SCREW(TYPE B)

 

3

 

7

SCREW(TYPE C)

 

5

 

8

FOAM-STRIP

 

1

 

9

FOAM-PE

 

1

 

10

UPPER GUIDE

 

1

 

11

FOAM-PE

 

1

 

12

FRAME GUIDE

 

2

 

13

WINDOW LOCKING BRACKET

1

8 Room Air Conditioner

Installation

BEFORE INSTALLATION

1.Remove the screws which fasten the cabinet at both sides and at the back.

2.Slide the unit out from the cabinet by gripping the base pan handle and pulling forward while bracing the cabinet.

3.Cut the window sash seal to the proper length. Peel

off the backing and attach the Foam-Pe to the underside of the window sash.

4.Remove the backing from the top upper guide

Foam PE and attach it to the bottom of the Upper Guide .

5.Attach the upper guide onto the top of the cabinet with 3 type A screws.

6.Insert the Frame Guides into the bottom of the cabinet.

7.Insert the Frame Curtain into the upper guide and Frame Guides .

8.Fasten the curtains to the unit with 4 Type A screws at the both sides.

Shipping

Screws

EPS Material

9

13 10

NOW START INSTALLATION

1.Open the window. Mark a line on center of the window stool (or desired air conditioner location). Carefully place the cabinet on the window stool and align the center mark on the front angle with the center line marked in the window stool.

2.Pull the bottom window sash down behind the upper guide until it meets.

NOTICE Do not pull the window sash down so tightly

that the movement of Frame Curtainis restricted.

(Type 9

5

5

11

11

(Type A)

5

Upper Guide

 

 

 

Window stool

 

Front Angle

Figure 4

Window Sash

Upper guide 9

 

Foam-pe 13

Cabinet

Frame Curtain 1

Foam-pe 10

Figure 5

Service Manual 9

Installation

3.Loosely assemble the sill support using the parts in Figure 6.

4.Select the position that will place the sill support near the outer most point on sill (See Figure 6)

NOTICE Be careful when you install the cabinet (frame guides are broken so easily).

5.Attach the sill support to the cabinet track hole in relation to the selected position using

2 Type A screws in each support (See Figure 7).

INDOOR

OUTDOOR

 

Sill Support

2

Bolt 3

Nut 4

 

Figure 6

12 Frame Guide

5 Screw(Type A)

 

 

Cabinet

About 1/2"

 

 

INDOOR

OUTDOOR

 

 

Figure 7

6.The cabinet should be installed with a very slight tilt (about 1/2") downward toward the outside (See Figure 8).

Adjust the bolt and the nut of Sill Support

for

balancing the cabinet.

 

7.Attach the cabinet to the window stool by

driving the screws (Type B: Length sixteen millimeters and below.) through the front angle into window stool (5/8").

8.Pull each Frame Curtain properly to each window sash track, and repeat step 2.

Screw(Type B) 6

Screw(Type A) 5

About 1/2"

 

 

 

 

 

 

 

Sill support

2

 

 

 

Sash track

 

 

 

Front Angle

Sill support

2

Screw(Type B) 6

 

 

 

Figure 8

 

 

 

 

9. Attach each Frame Curtain to the window sash by using screws (Type C).

(See Figure 9)

Type C

7

Figure 9

10 Room Air Conditioner

Installation

10. Slide the unit into the cabinet.(See Fig. 10)

CAUTION: For security purpose, reinstall screws (Type A) at cabinet's sides.

11. Cut the Foam-Strip to the proper length and insert between the upper and lower window sash.

(See Fig. 11)

12.Attach the window Locking Bracket with a type C screw. (See Fig. 12)

13.Attach the front grille to the cabinet by inserting the tabs on the grille into the tabs on the front of the cabinet. Push the grille in until it snaps into place.(See Fig. 13)

14.Lift the inlet grille and secure it with a type A screw through the front grille.(See Fig. 14)

Power cord

Screw(Type A)

Screw(Type

Figure 10

Foam-Strip 8

Figure 11

13

Figure 12

Figure 13

Figure 14

Figure 15

Service Manual 11

Installation

Operation

Designed for COOLING ONLY.

Powerful and quiet cooling.

Slide-in and slide-out chassis for the simple installation and service.

Low air-intake, top cooled-air discharge.

Built-in adjustable Thermistor

Washable one-touch filter

Compact size

Reliable and efficient rotary compressor is equipped.

RemoteControlOperations

CAUTION: The Remote Controller will not function properly if strong light strikes the sensor window of the air conditioner or if there are obstacles between the

Remote Controller and the air conditioner.

The controls look like this:

Controls

Cool

F1 LOW

'F

Energy

F2 MED

6

F3 HIGH

Saver

 

 

Fan

 

 

Dry

Timer

2

MODE

TIMER

FAN

POWER

SPEED

 

 

 

3

5

4

1

Power

Temp

Fan Speed

Timer Mode

5

1

2

4

3

12 Room Air Conditioner

Operation

1POWER

Operation starts when this button is pressed and stops when you press the button again.

2TEMPERATURE CONTROL

The thermostat monitors room temperature to maintain the desired temperature. The thermostat can be set between 60°F~86°F (16°C~30°C).

The unit takes an average of 30 minutes to adjust the room temperature by 1°F.

3OPERATION MODE SELECTOR

Select cooling mode to cool the room.

Select energy saver mode for energy saving operation. Select fan mode for basic ventilating fan operation. Select dry mode for dry operation.

4FAN SPEED SELECTOR

For increased power while cooling, select a higher fan speed. 3 steps: High Low Med

5ON/OFF TIMER

The timer can be set to start and stop the unit in hourly increments (up to 12 hours).

6 REMOTE CONTROL SENSOR

How to Insert Batteries

1 Push out the cover on the back of the remote control with your thumb

2 Pay attention to polarity and insert two new AAA 1.5V batteries.

3 Reattach the cover.

NOTICE : Do not use rechargeable batteries. Make sure that both batteries are new.

In order to prevent discharge, remove the batteries from the remote control if the air conditioner is not going to be used for an extended period of time

Keep the remote control away from extremely hot or humid places.

To maintain optimal operation of the remote control, the remote sensor should not be exposed to direct sunlight.

Service Manual 13