HEAT CONTROLLER, INC.
Wall Mounted
Multi-Split System
Air Conditioning/Heat Pump
Indoor Unit: B-MMC09FA-1
B-MMH09FA-1
B-MMC12FA-1
B-MMH12FA-1
Outdoor Unit : A-MMH18FA-1
A-MMC24FA-1
A-MMH24FA-1
A-MMC36FA-1
A-MMH36FA-1
Before servicing the unit, read the “safety precautions” in this manual.
Only for authorized service personnel.
Multi type Air Conditioner Service Manual |
|
TABLE OF CONTENTS |
|
Combination table....................................................................................................................................... |
3 |
Safety Precautions...................................................................................................................................... |
4 |
Installation guide at the seaside.............................................................................................................. |
10 |
Dimensions................................................................................................................................................ |
11 |
Indoor Unit.............................................................................................................................................. |
11 |
Outdoor Unit ........................................................................................................................................... |
12 |
Product Specifications ............................................................................................................................. |
15 |
Indoor Unit.............................................................................................................................................. |
15 |
Outdoor Unit ........................................................................................................................................... |
16 |
Installation ................................................................................................................................................. |
19 |
Installation Parts..................................................................................................................................... |
19 |
Installation Tools..................................................................................................................................... |
19 |
Select the best location ......................................................................................................................... |
20 |
Piping length and elevation .................................................................................................................... |
21 |
Fixing Installation Plate(Standard Type)................................................................................................. |
22 |
Drill a hole in the wall ........................................................................................................................... |
22 |
Flaring Work and Connection of Piping.................................................................................................. |
23 |
Flaring work............................................................................................................................................ |
24 |
Connecting the Piping ............................................................................................................................ |
24 |
Connecting the Cable between Indoor Unit and Outdoor Unit ............................................................. |
31 |
Connect the cable to the Indoor unit. ..................................................................................................... |
31 |
Connect the cable to the Outdoor unit.................................................................................................... |
32 |
Connection method of the connecting cable(Example).......................................................................... |
33 |
Connect the cable to the indoor unit....................................................................................................... |
34 |
Checking the Drainage, Forming the Pipings and Long Pipe Setting ................................................. |
35 |
Checking the drainage............................................................................................................................ |
35 |
Forming the piping.................................................................................................................................. |
36 |
Air Purging and Evacuation ..................................................................................................................... |
37 |
Checking method ................................................................................................................................... |
37 |
Evacuation.............................................................................................................................................. |
38 |
Charging .................................................................................................................................................... |
39 |
Test Running ............................................................................................................................................. |
40 |
Operation ................................................................................................................................................... |
41 |
Function of control.................................................................................................................................. |
41 |
Function of Indoor Unit ........................................................................................................................... |
46 |
Function of Outdoor Unit ........................................................................................................................ |
47 |
Remote Control Operation ..................................................................................................................... |
48 |
Disassembly .............................................................................................................................................. |
49 |
Indoor Unit.............................................................................................................................................. |
49 |
Schematic Diagram................................................................................................................................... |
52 |
Electronic Control Device ....................................................................................................................... |
52 |
Wiring Diagram....................................................................................................................................... |
55 |
Components Locations........................................................................................................................... |
57 |
Troubleshooting Guide............................................................................................................................. |
61 |
Refrigeration Cycle Diagram .................................................................................................................. |
61 |
Self-diagnosis Function .......................................................................................................................... |
64 |
Cycle Troubleshooting Guide.................................................................................................................. |
65 |
Electronic Parts Troubleshooting Guide ................................................................................................. |
66 |
Error Code.............................................................................................................................................. |
71 |
2-way, 3-way Valve .................................................................................................................................... |
75 |
Exploded View .......................................................................................................................................... |
79 |
Indoor Unit ............................................................................................................................................. |
79 |
Outdoor Unit ........................................................................................................................................... |
81 |
Copyright ©2008 LG Electronics. Inc. All right reserved. |
- 2 - |
Only for training and service purposes |
LGE Internal Use Only |
|
|
|
|
|
|
|
|
Combination table |
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Combination table |
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
|
|
18 kBtu( 2 rooms) |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Combination |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Unit-A |
|
Unit-B |
|
Total |
|||
|
|
|
|
|
|
|
|
|
|
|
1 UNIT |
9 |
|
|
- |
9 |
|
||
|
|
|
|
|
|
|
|
|
|
|
2 UNIT |
9 |
|
|
9 |
18 |
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
24 kBtu( 2 rooms) |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Combination |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Unit-A |
|
Unit-B |
|
Total |
|||
|
|
|
|
|
|
|
|
|
|
|
1 UNIT |
9 |
|
|
- |
9 |
|
||
|
|
|
|
|
|
|
|
|
|
|
12 |
|
|
- |
12 |
|
|||
|
|
|
|
|
|||||
|
|
|
|
|
|
|
|
|
|
|
|
9 |
|
|
9 |
18 |
|
||
|
|
|
|
|
|
|
|
|
|
|
2 UNIT |
9 |
|
|
12 |
21 |
|
||
|
|
|
|
|
|
|
|
|
|
|
|
12 |
|
|
12 |
24 |
|
||
|
|
|
|
|
|
|
|
|
|
36 kBtu (3 rooms) |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Combination |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Unit-A |
|
Unit-B |
|
Unit-C |
|
Total |
|
|
|
|
|
|
|
|
|
|
|
|
1 UNIT |
9 |
|
- |
|
- |
|
9 |
|
|
|
|
|
|
|
|
|
|
|
|
12 |
|
- |
|
- |
|
12 |
|
|
|
|
|
|
|
|
||||
|
|
9 |
|
9 |
|
- |
|
18 |
|
|
|
|
|
|
|
|
|
|
|
|
2 UNIT |
9 |
|
12 |
|
- |
|
21 |
|
|
|
|
|
|
|
|
|
|
|
|
|
12 |
|
12 |
|
- |
|
24 |
|
|
|
|
|
|
|
|
|
|
|
|
|
9 |
|
9 |
|
9 |
|
27 |
|
|
|
|
|
|
|
|
|
|
|
|
3 UNIT |
9 |
|
9 |
|
12 |
|
30 |
|
|
|
|
|
|
|
|
|
|
|
|
9 |
|
12 |
|
12 |
|
33 |
|
|
|
|
|
|
|
|
||||
|
|
|
|
|
|
|
|
|
|
|
|
12 |
|
12 |
|
12 |
|
36 |
|
|
|
|
|
|
|
|
|
|
|
Notes :
1.Cooling Capacity is based on : indoor temp. 26.7°C(80.1°F)DB, 19.4°C(66.9°F)WB; outdoor temp. 35°C(95°F)DB, 23.9°C(75°F)WB
2.Heating Capacity is based on : indoor temp. 21.1°C(70°F)DB, 15.6°C(60.1°F)WB; outdoor temp. 8.3°C(46.9°F)DB, 6.1°C(43°F)WB
SymbolsUsedinthisManual
This symbol alerts you to the risk of electric shock.
This symbol alerts you to hazards that could cause harm to the air conditioner.
|
NOTICE |
This symbol indicates special notes. |
|
|
|
|
|
Copyright ©2008 LG Electronics. Inc. All right reserved. |
- 3 - |
||
Only for training and service purposes |
LGE Internal Use Only |
||
|
Safety Precautions
Safety Precautions
To prevent injury to the user or other people and property damage, the following instructions must be followed.
■Incorrect operation due to ignoring instruction will cause harm or damage. The seriousness is classified by the following indications.
WARNING This symbol indicates the possibility of death or serious injury.
CAUTION This symbol indicates the possibility of injury or damage to properties only.
■ Meanings of symbols used in this manual are as shown below.
Be sure not to do.
Be sure to follow the instruction.
WARNING
Do not use a defective or underrated circuit breaker. Use this appliance on a dedicated circuit.
•There is risk of fire or electric shock.
For electrical work, contact the |
Always ground the product. |
|||
dealer, seller, a qualified electrician, |
|
|
|
|
or an Authorized Service Center. |
|
|
|
|
• Do not disassemble or repair the |
• There is risk of fire or electric |
|||
product. There is risk of fire or |
shock. |
|||
electric shock. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Install the panel and the cover |
Always install a dedicated cir- |
of control box securely. |
cuit and breaker. |
• There is risk of fire or electric |
• Improper wiring or installation may |
shock. |
cause fire or electric shock |
Use the correctly rated breaker or fuse.
•There is risk of fire or electric shock.
Copyright ©2008 LG Electronics. Inc. All right reserved. |
- 4 - |
Only for training and service purposes |
LGE Internal Use Only |
|
Safety Precautions
Do not install, remove, or re- |
Be cautious when unpacking |
install the unit by yourself |
and installing the product. |
(customer). |
|
• There is risk of fire, electric shock, |
• Sharp edges could cause injury. |
|
Be especially careful of the case |
|
edges and the fins on the con- |
|
denser and evaporator. |
Do not install the product on a |
Be sure the installation area |
defective installation stand. |
does not deteriorate with age. |
For installation, always contact the dealer or an Authorized Service Center.
•There is risk of fire, electric shock, explosion, or injury.
Do not let the air conditioner run for a long time when the humidity is very high and a door or a window is left open.
• It may cause injury, accident, or |
• If the base collapses, the air condi- |
|
tioner could fall with it, causing |
|
property damage, product failure, |
|
and personal injury. |
•Moisture may condense and wet or damage furniture.
Do not allow water to run into electric parts.
•It may cause There is risk of fire, failure of the product, or electric shock.
Do not store or use flammable |
Do not use the product in a |
gas or combustibles near the |
tightly closed space for a long |
product. |
time. |
• There is risk of fire or failure of |
• Oxygen deficiency could occur. |
product. |
|
Gasolin
Copyright ©2008 LG Electronics. Inc. All right reserved. |
- 5 - |
Only for training and service purposes |
LGE Internal Use Only |
|
Safety Precautions
When flammable gas leaks, turn off the gas and open a window for ventilation before turn the product on.
•Do not use the telephone or turn switches on or off. There is risk of explosion or fire
If strange sounds, or smoke |
Stop operation and close the |
comes from product. Turn the |
window in storm or hurricane. |
breaker off. |
If possible, remove the prod- |
|
uct from the window before |
|
the hurricane arrives. |
• There is risk of electric shock or |
• There is risk of property damage, |
fire. |
failure of product, or electric shock. |
When the product is soaked |
Be cautious that water could |
(flooded or submerged), contact |
not enter the product. |
an Authorized Service Center. |
|
• There is risk of fire or electric |
• There is risk of fire, electric shock, |
|
or product damage. |
to time when |
Turn the main power off when cleaning or |
etc. |
maintaining the product. |
|
• There is risk of electric shock. |
Copyright ©2008 LG Electronics. Inc. All right reserved. |
- 6 - |
Only for training and service purposes |
LGE Internal Use Only |
|
Safety Precautions
When the product is not to be used for a long time, disconnect the power by turning off the breaker.
Take care to ensure that nobody could step on or fall onto the outdoor unit.
• There is risk of product damage or failure, or unintend- • This could result in personal injury and product damage.
CAUTION
■ Installation
Always check for gas (refrigerant) leakage after installation or repair of product.
• Low refrigerant levels may cause |
• |
Do not install the product where the noise or hot air from the outdoor unit could oftend neighbors.
• It may cause a problem for your |
• |
neighbors. |
|
Keep level even when installing the product.
•To avoid vibration or water leakage.
90°
Do not install the product where it will be exposed to sea wind (salt spray) directly.
•It may cause corrosion on the product. Corrosion, particularly on the condenser and evaporator fins, could cause product malfunction or inefficient operation.
Copyright ©2008 LG Electronics. Inc. All right reserved. |
- 7 - |
Only for training and service purposes |
LGE Internal Use Only |
|
Safety Precautions
■ Operational
Do not expose the skin directly to cool air for long periods of time.
(Don't sit in the draft.)
Do not use the product for special purposes, such as preserving foods, works of art, etc. It is a consumer air conditioner, not a precision refrigeration system.
Do not block the inlet or outlet of air flow.
• There is risk of damage or loss of • It may cause product failure. property.
Use a soft cloth to clean. Do not use harsh detergents, solvents, etc.
•There is risk of fire, electric shock, or damage to the plastic parts of
Do not touch the metal parts of |
Do not step on or put anyting |
the product when removing the |
on the product. (outdoor |
air filter. They are very sharp! |
units) |
• There is risk of personal injury. |
• There is risk of personal injury and |
|
failure of product. |
Wax
Thinner
Always insert the filter secure- |
Do not insert hands or other |
ly. Clean the filter every two |
objects through the air inlet or |
weeks or more often if neces- |
outlet while the product is |
sary. |
operated. |
• A dirty filter reduces the efficiency of |
• There are sharp and moving parts |
the air conditioner and could cause |
that could cause personal injury. |
product malfunction or damage. |
|
Do not drink the water drained from the product.
•It is not sanitary and could cause serious health issues.
Copyright ©2008 LG Electronics. Inc. All right reserved. |
- 8 - |
Only for training and service purposes |
LGE Internal Use Only |
|
Safety Precautions
Use a firm stool or ladder when cleaning or maintaining the product.
• Be careful and avoid personal injury.
If you eat the liquid from the batteries, brush your teeth and see doctor. Do not use the remote if the batteries have leaked.
•The chemicals in batteries could cause burns or other health hazards.
Replace the all batteries in the remote control with new ones of the same type. Do not mix old and new batteries or different types of batteries.
• There is risk of fire or explosion
If the liquid from the batteries gets onto your skin or clothes, wash it well with clean water. Do not use the remote if the batteries have leaked.
•The chemicals in batteries could cause burns or other health hazards.
Copyright ©2008 LG Electronics. Inc. All right reserved. |
- 9 - |
Only for training and service purposes |
LGE Internal Use Only |
|
Installation guide at the seaside
Installation guide at the seaside
1.Air conditioners should not be installed in areas where corrosive gases, such as acid or alkaline gas, are produced.
2.Do not install the product where it could be exposed to sea wind (salty wind) directly. It can result corrosion on the product. Corrosion, particularly on the condenser and evaporator fins, could cause product malfunction or inefficient performance.
3.If outdoor unit is installed close to the seaside, it should avoid direct exposure to the sea wind. Otherwise it needs additional anticorrosion treatment on the heat exchanger.
Selecting the location(Outdoor Unit)
1)If the outdoor unit is to be installed close to the seaside, direct exposure to the sea wind should be avoided. Install the outdoor unit on the opposite side of the sea wind direction.
Sea wind |
Sea wind |
2) In case, to install the outdoor unit on the seaside, set up a windbreak not to be exposed to the sea wind.
Windbreak
Sea wind
•It should be strong enough like concrete to prevent the sea wind from the sea.
•The height and width should be more than 150% of the outdoor unit.
•It should be keep more than 70 cm of space between outdoor unit and the windbreak for easy air flow.
3)Select a well-drained place.
1.If you can’t meet above guide line in the seaside installation, please contact LG Electronics for the additional anticorrosion treatment.
2.Periodic ( more than once/year ) cleaning of the dust or salt particles stuck on the heat exchanger by using water
Copyright ©2008 LG Electronics. Inc. All right reserved. |
- 10 - |
Only for training and service purposes |
LGE Internal Use Only |
|
Dimensions
Dimensions
IndoorUnit
Split Type Indoor
H
D
W
Installation plate
|
Model |
|
Split Type |
|
S4 |
SE |
|
Dimension |
|
||
|
9 kBtu/h |
12 kBtu/h |
|
|
|
||
W |
mm(in) |
840(33) |
895(35.2) |
H |
mm(in) |
270(10.6) |
282(11.1) |
D |
mm(in) |
153(6) |
165(6.5) |
Copyright ©2008 LG Electronics. Inc. All right reserved. |
- 11 - |
Only for training and service purposes |
LGE Internal Use Only |
|
Dimensions
OutdoorUnit
W
|
|
|
|
|
|
|
|
D |
|
L1 |
|
|
|
|
|
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
L2 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
L3
H
L4
L6 |
|
L5 |
|
L7 |
|
|
|
|
|||
|
|
|
|
|
|
|
|
|
|
UE |
|
|
MODEL |
|
|
|
DIM |
|
|
18kBtu/h |
|
|
|
|
|
|
|
|
|
|
|
W |
mm(in) |
870(34.3) |
|
|
|
|
|
|
|
H |
mm(in) |
655(25.8) |
|
|
|
|
|
|
|
D |
mm(in) |
320(12.6) |
|
|
|
|
|
|
|
L1 |
mm(in) |
370(14.6) |
|
|
|
|
|
|
|
L2 |
mm(in) |
25(1.0) |
|
|
|
|
|
|
|
L3 |
mm(in) |
775(30.5) |
|
|
|
|
|
|
|
L4 |
mm(in) |
25(1.0) |
|
|
|
|
|
|
|
L5 |
mm(in) |
546(21.5) |
|
|
|
|
|
|
|
L6 |
mm(in) |
160(6.3) |
|
|
|
|
|
|
|
L7 |
mm(in) |
160(6.3) |
|
|
|
|
|
|
Copyright ©2008 LG Electronics. Inc. All right reserved. |
- 12 - |
Only for training and service purposes |
LGE Internal Use Only |
|
W
|
|
|
|
|
|
|
|
D |
|
L1 |
|
|
|
|
|
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
L2 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
H L3
L4
L6 |
|
L5 |
|
L7 |
|
|
|
|
|||
|
|
|
|
|
|
|
|
|
|
UE 1 |
|
|
MODEL |
|
|
|
DIM |
|
|
24kBtu/h |
|
|
|
|
|
|
|
|
|
|
|
W |
mm(in) |
870(34.3) |
|
|
|
|
|
|
|
H |
mm(in) |
808(31.8) |
|
|
|
|
|
|
|
D |
mm(in) |
320(12.6) |
|
|
|
|
|
|
|
L1 |
mm(in) |
370(14.6) |
|
|
|
|
|
|
|
L2 |
mm(in) |
25(1.0) |
|
|
|
|
|
|
|
L3 |
mm(in) |
775(30.5) |
|
|
|
|
|
|
|
L4 |
mm(in) |
25(1.0) |
|
|
|
|
|
|
|
L5 |
mm(in) |
546(21.5) |
|
|
|
|
|
|
|
L6 |
mm(in) |
160(6.3) |
|
|
|
|
|
|
|
L7 |
mm(in) |
160(6.3) |
|
|
|
|
|
|
Copyright ©2008 LG Electronics. Inc. All right reserved. |
- 13 - |
Only for training and service purposes |
LGE Internal Use Only |
|
Dimensions
W
L2 |
D |
L1 |
|
L3 |
|
H |
|
|
|
|
L4 |
|
|
L11 |
|
|
|
|
L10 L11 L11 L11 L11 |
|
L5 |
|
|
L9 |
|
L7 |
L6 |
L8 |
||
|
Gas side
3-way valve
Liquid side 2-way valve
|
|
|
|
UE2 |
|
|
|
|
MODEL |
|
|
||
|
DIM |
|
|
36kBtu/h |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
W |
mm(in) |
|
870(34.3) |
|
|
|
|
|
|
|
|
|
|
H |
mm(in) |
|
1038(40.7) |
|
|
|
|
|
|
|
|
|
|
D |
mm(in) |
|
320(12.6) |
|
|
|
|
|
|
|
|
|
|
L1 |
mm(in) |
|
360(14.2) |
|
|
|
|
|
|
|
|
|
|
L2 |
mm(in) |
|
340(13.4) |
|
|
|
|
|
|
|
|
|
|
L3 |
mm(in) |
|
25(1.0) |
|
|
|
|
|
|
|
|
|
|
L4 |
mm(in) |
|
1035(40.8) |
|
|
|
|
|
|
|
|
|
|
L5 |
mm(in) |
|
25(1.0) |
|
|
|
|
|
|
|
|
|
|
L6 |
mm(in) |
|
546(21.5) |
|
|
|
|
|
|
|
|
|
|
L7 |
mm(in) |
|
160(6.3) |
|
|
|
|
|
|
|
|
|
|
L8 |
mm(in) |
|
160(6.3) |
|
|
|
|
|
|
|
|
|
|
L9 |
mm(in) |
|
44(11.7) |
|
|
|
|
|
|
|
|
|
|
L10 |
mm(in) |
|
64.5(2.5) |
|
|
|
|
|
|
|
|
|
|
L11 |
mm(in) |
|
50(2.0) |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Copyright ©2008 LG Electronics. Inc. All right reserved. |
- 14 - |
Only for training and service purposes |
LGE Internal Use Only |
|
Product Specifications
Product Specifications
Indoor Unit
Indoor Unit Type |
|
|
Wall Mounted |
|
|||
|
Model |
|
B-MMC09FA-1 |
B-MMH09FA-1 |
B-MMC12FA-1 |
B-MMH12FA-1 |
|
|
|
|
|
|
|
||
Nominal Cooling Capacity |
kcal/h(W) |
2,267(2,637) |
2,267(2,637) |
3,023(3,516) |
3,023(3,516) |
||
|
|
|
Btu/h |
9,000 |
9,000 |
12,000 |
12,000 |
|
|
|
|
|
|
|
|
Nominal Heating Capacity |
|
kcal/h(W) |
- |
2,267(2,637) |
- |
3,023(3,516) |
|
|
|||||||
|
|
|
|
|
|
|
|
|
|
|
Btu/h |
- |
9,000 |
- |
12,000 |
|
|
|
|
|
|
|
|
Air Circulation |
H/M/L |
|
CMM(CFM) |
8.2(289) |
8.2(289) |
9.4(332) |
9.4(332) |
|
|
|
|
|
|
|
|
Setting temperature range(cool/heat) |
°C |
18~30 |
18~30 |
18~30 |
18~30 |
||
|
|
|
|
|
|
|
|
Fan motor |
Output |
|
W |
15 |
15 |
15 |
15 |
|
|
|
|
|
|
|
|
|
Model |
|
|
DL-88430LGIF |
DL-88430LGIF |
DL-88430LGIF |
DL-88430LGIF |
|
|
|
|
|
|
|
|
|
Input |
|
V |
DC36 |
DC36 |
DC36 |
DC36 |
|
|
|
|
|
|
|
|
|
Running Current |
A |
0.15 |
0.15 |
0.15 |
0.15 |
|
|
|
|
|
|
|
|
|
Fan |
Type |
|
|
Cross Flow Fan |
Cross Flow Fan |
Cross Flow Fan |
Cross Flow Fan |
|
|
|
|
|
|
|
|
|
No. Used / Diameter |
EA/inch(mm) |
1/3.74(95) |
1/3.74(95) |
1/3.74(95) |
1/3.74(95) |
|
|
|
|
|
|
|
|
|
Noise Level (Sound Press,1m) H/M/L |
dBA |
31 / 29 / 22 |
31 / 29 / 22 |
36 / 32 / 29 |
36 / 32 / 29 |
||
|
|
|
|
|
|
|
|
Temperature controller |
|
|
Thermistor |
Thermistor |
Thermistor |
Thermistor |
|
|
|
|
|
|
|
|
|
Coil |
Tube Size (OD) |
inch(mm) |
0.197(5.0) |
0.197(5.0) |
0.197(5.0) |
0.197(5.0) |
|
|
|
|
|
|
|
|
|
|
Fins per inch |
|
20 |
20 |
18 |
18 |
|
|
|
|
|
|
|
|
|
|
No. of Rows & Column |
|
2R,15C |
2R,15C |
2R,15C |
2R,15C |
|
|
|
|
|
|
|
|
|
Dehumidification Rate |
|
l/h |
- |
1.1 |
- |
1.2 |
|
|
|
|
|
|
|
|
|
Dimensions (W*H*D) |
|
inch(mm) |
33.0*10.6*6.0(840*270*153) |
33.0*10.6*6.0(840*270*153) |
35.2*11.1*6.5(895*282*165) |
35.2*11.1*6.5(895*282*165) |
|
|
|
|
|
|
|
|
|
Net Weight |
|
|
kg(lbs) |
7(15.4) |
7(15.4) |
9.5(20.9) |
9.5(20.9) |
|
|
|
|
|
|
|
|
Piping Connection |
Liquid |
|
inch(mm) |
1/4 (6.35) |
1/4 (6.35) |
1/4 (6.35) |
1/4 (6.35) |
|
|
|
|
|
|
|
|
|
Gas |
|
inch(mm) |
3/8 (9.52) |
3/8 (9.52) |
3/8 (9.52) |
3/8 (9.52) |
|
|
|
|
|
|
|
|
|
Drain hose (ID Ø) |
mm |
20 |
20 |
20 |
20 |
|
|
|
|
|
|
|
|
|
Packing Dimension (W*H*D) |
|
inch(mm) |
35.7*13.1*8.8(906*332*223) |
35.7*13.1*8.8(906*332*223) |
38.3*9.1*14.6(973*231*372) |
38.3*9.1*14.6(973*231*372) |
|
|
|
|
|
|
|
|
|
Stuffing Quantity |
With(Without) S/Parts |
20/40ft(hi-c) |
440/910 (1091) |
440/910 (1091) |
353/719 (792) |
353/719 (792) |
|
|
|
|
|
|
|
|
|
Note : 1. See the page "Combination Table"
2. Due to our policy of innovation some specifications may be changed without notification.
Copyright ©2008 LG Electronics. Inc. All right reserved. |
- 15 - |
Only for training and service purposes |
LGE Internal Use Only |
|
Product Specifications
OutdoorUnit-Multiplepipingmodels
|
Model |
|
A-MMH18FA-1 |
|
|
|
|
|
|
Cooling Capacity |
|
|
Btu/hr |
9,000~18,000 |
|
|
|
|
|
|
|
|
W |
2637~5275 |
|
|
|
kcal/hr |
2267~4536 |
Heating Capacity |
|
|
Btu/hr |
9,000~18,000 |
|
|
|
|
|
|
|
|
W |
2637~5275 |
|
|
|
kcal/hr |
2267~4536 |
Input |
Cooling |
|
W |
1070~1980 |
|
|
|
|
|
|
Heating |
|
W |
1040~1960 |
Running Current (208/230V) |
Cooling |
|
A |
4.9~8.8 |
|
|
|
|
|
|
Heating |
|
A |
4.6~8.6 |
Power Supply |
|
|
Ø,V,Hz |
1,208/230,60 |
|
|
|
|
|
Max. Number of Connectable Indoor Units |
|
2 |
||
|
|
|
|
|
Compressor |
Type |
|
Rotary |
|
(Constant) |
Model |
|
GK094K |
|
|
Motor Type |
|
|
Hermetic |
|
|
|
|
|
|
Quantity |
|
Ea |
1 |
|
Motor Input |
|
W |
955 |
|
Oil Charge |
cc |
330±10 |
|
|
Oil Type |
|
FVC68D |
|
|
|
|
|
|
|
Capacitor |
|
µF/Vac |
30 / 370 |
|
O.L.P Type(model name) |
|
External Type(MRA98996-12026) |
|
Compressor |
Type |
|
Rotary |
|
(Constant) |
Model |
|
GK113K |
|
|
|
|
|
|
|
Motor Type |
|
Hermetic |
|
|
Quantity |
|
Ea |
1 |
|
Motor Input |
|
W |
1,120 |
|
|
|
|
|
|
Oil Charge |
|
cc |
330±10 |
|
|
|
|
|
|
Oil Type |
|
FVC68D |
|
|
Capacitor |
|
µF/Vac |
35 / 370 |
|
O.L.P Type(model name) |
|
External Type(MRA12124-12026) |
|
|
|
|
|
|
Refrigerant charge |
Charge |
|
g(oz) |
1400(49) |
|
Type |
|
R410A |
|
|
Control |
|
EEV |
|
Coil |
Tube Size (OD) |
|
inch(mm) |
0.276(7.0) |
|
|
|
|
|
|
Fins per inch |
|
18 |
|
|
No. of Rows & Column/No. |
|
2R,28C |
|
Fan motor |
Model |
|
IC-1640LG GE |
|
|
Output |
|
W |
90 |
|
|
|
|
|
|
Capacitor |
|
µF/Vac |
6/370 |
Fan |
Type |
|
Propeller |
|
|
No. Used / Diameter |
|
EA/inch(mm) |
1 / 460 |
|
|
|
|
|
|
Discharge |
|
Side / Top |
Side |
|
|
|
|
|
Air Circulation |
Outdoor |
|
CMM(CFM) |
50(1765.7) |
Noise Level(H/L) at 230V |
Sound Press,1m |
|
dB(A) 1 |
51 |
Defrosting |
|
|
|
Invertion Cycle |
|
|
|
|
|
SVC Valve |
Liquid |
|
inch(mm) |
1/4 (6.35) * 2EA |
|
Gas |
|
|
3/8 (9.52) * 2EA |
Dimensions |
W*H*D |
|
inch(mm) |
34.3*25.8*12.6 (870*655*320) |
Net Weight |
Outdoor |
|
kg(lbs) |
57(125.7) |
|
|
|
|
|
Max. Interunit Piping Length |
Total of Each Room |
|
m |
30 |
|
For One Room |
|
m |
15 |
Max. Installation |
Indoor Unit~Outdoor Unit |
|
m |
7.5 |
Height Difference |
Indoor Unit~Indoor Unit |
|
m |
7.5 |
|
|
|
|
|
Packing Dimension |
W*H*D |
|
inch(mm) |
40.2*28.2*17.2 (1020*716*437) |
Testing Combinations |
|
|
|
S4 9k + S4 9k |
Stuffing Quantity |
|
|
20/40ft |
81/171 |
Note:
1. Capacities are based on the following conditions:
Cooling: |
- Indoor Temperature 26.7˚C(80˚F) DB/19.4˚C(67˚F) WB |
|
- Outdoor Temperature 35˚C(95˚F) DB/23.9˚C(75˚F) WB |
Heating: |
- Indoor Temperature 21.1˚C(70˚F) DB/15.6˚C(60˚F) WB |
|
- Outdoor Temperature 8.3˚C(47˚F) DB/6.1˚C(43˚F) WB |
Piping Length |
- Interconnecting Piping Length 7.5m |
|
- Level Difference of Zero |
2.Wiring cable size must comply with the applicable local and national code.
3.Capacities are Net Capacities.
4.: See the page "Combination Table"
5.The specification may be subject to change without prior notice for purpose of improvement.
Copyright ©2008 LG Electronics. Inc. All right reserved. |
- 16 - |
Only for training and service purposes |
LGE Internal Use Only |
|
Product Specifications
|
Model |
|
A-MMC24FA-1 |
A-MMH24FA-1 |
|
|
|
|
|
|
|
Cooling Capacity |
|
|
Btu/hr |
9,000~24,000 |
9,000~24,000 |
|
|
|
|
|
|
|
|
|
W |
2637~7033 |
2637~7033 |
|
|
|
kcal/hr |
2267~6037 |
2267~6037 |
Heating Capacity |
|
|
Btu/hr |
- |
9,000~24,000 |
|
|
|
|
|
|
|
|
|
W |
- |
2637~7033 |
|
|
|
kcal/hr |
- |
2267~6037 |
Input |
Cooling |
|
W |
1170~2390 |
1170~2390 |
|
|
|
|
|
|
|
Heating |
|
W |
- |
1220~2440 |
Running Current (208/230V) |
Cooling |
|
A |
7.7~10.1 |
7.7~10.1 |
|
|
|
|
|
|
|
Heating |
|
A |
- |
7.4~9.8 |
Power Supply |
|
|
Ø,V,Hz |
1,208/230,60 |
1,208/230,60 |
Max. Number of Connectable Indoor Units |
|
2 |
2 |
||
|
|
|
|
|
|
Compressor |
Type |
|
Rotary |
Rotary |
|
(Constant) |
Model |
|
GK094K |
GK094K |
|
|
Motor Type |
|
|
Hermetic |
Hermetic |
|
Quantity |
|
Ea |
1 |
1 |
|
|
|
|
|
|
|
Motor Input |
|
W |
955 |
955 |
|
Oil Charge |
cc |
330±10 |
330±10 |
|
|
Oil Type |
|
FVC68D |
FVC68D |
|
|
|
|
|
|
|
|
Capacitor |
|
µF/Vac |
30 / 370 |
30 / 370 |
|
|
|
|
|
|
|
O.L.P Type(model name) |
|
External Type(MRA98996-12026) |
External Type(MRA98996-12026) |
|
Compressor |
Type |
|
Rotary |
Rotary |
|
(Constant) |
Model |
|
GK141K |
GK141K |
|
|
|
|
|
|
|
|
Motor Type |
|
Hermetic |
Hermetic |
|
|
|
|
|
|
|
|
Quantity |
|
Ea |
1 |
1 |
|
Motor Input |
|
W |
1430 |
1,430 |
|
Oil Charge |
|
cc |
350±10 |
350±10 |
|
|
|
|
|
|
|
Oil Type |
|
FVE |
FVE |
|
|
Capacitor |
|
µF/Vac |
35 / 370 |
35 / 370 |
|
O.L.P Type(model name) |
|
External Type(MRA12105-12026) |
External Type(MRA12105-12026) |
|
Refrigerant charge |
Charge |
|
g(oz) |
1600 |
1600 |
|
|
|
|
|
|
|
Type |
|
R410A |
R410A |
|
|
Control |
|
EEV |
EEV |
|
Coil |
Tube Size (OD) |
|
inch(mm) |
0.276(7.0) |
0.276(7.0) |
|
|
|
|
|
|
|
Fins per inch |
|
18 |
18 |
|
|
|
|
|
|
|
|
No. of Rows & Column/No. |
|
2R,36C |
2R,36C |
|
Fan motor |
Model |
|
IC-1640LG GE |
IC-1640LG GE |
|
|
Output |
|
W |
90 |
90 |
|
|
|
|
|
|
|
Capacitor |
|
µF/Vac |
6/370 |
6/370 |
|
|
|
|
|
|
Fan |
Type |
|
Propeller |
Propeller |
|
|
No. Used / Diameter |
|
EA/inch(mm) |
1 / 460 |
1 / 460 |
|
Discharge |
|
Side / Top |
Side |
Side |
|
|
|
|
|
|
Air Circulation |
Outdoor |
|
CMM(CFM) |
53(1872) |
53(1872) |
Noise Level(H/L) at 230V |
Sound Press,1m |
|
dB(A) 1 |
54 |
54 |
Defrosting |
|
|
|
- |
Invertion Cycle |
SVC Valve |
Liquid |
|
inch(mm) |
1/4 (6.35) * 2EA |
1/4 (6.35) * 2EA |
|
|
|
|
|
|
|
Gas |
|
|
3/8 (9.52) * 2EA |
3/8 (9.52) * 2EA |
Dimensions |
W*H*D |
|
inch(mm) |
34.3*31.8*12.6 (870*808*320) |
34.3*31.8*12.6 (870*808*320) |
Net Weight |
Outdoor |
|
kg(lbs) |
64(141.1) |
64(141.1) |
|
|
|
|
|
|
Max. Interunit Piping Length |
Total of Each Room |
|
m |
30 |
30 |
|
|
|
|
|
|
|
For One Room |
|
m |
15 |
15 |
Max. Installation |
Indoor Unit~Outdoor Unit |
|
m |
7.5 |
7.5 |
Height Difference |
Indoor Unit~Indoor Unit |
|
m |
7.5 |
7.5 |
|
|
|
|
|
|
Packing Dimension |
W*H*D |
|
inch(mm) |
40.2*34.3*17.2 (1022*870*437) |
40.2*34.3*17.2 (1022*870*437) |
|
|
|
|
|
|
Testing Combinations |
|
|
|
SE 12K +SE 12K |
SE 12K +SE 12K |
Stuffing Quantity |
|
|
20/40ft |
54/114 |
54/114 |
Note:
1. Capacities are based on the following conditions:
Cooling: |
- Indoor Temperature 26.7˚C(80˚F) DB/19.4˚C(67˚F) WB |
|
- Outdoor Temperature 35˚C(95˚F) DB/23.9˚C(75˚F) WB |
Heating: |
- Indoor Temperature 21.1˚C(70˚F) DB/15.6˚C(60˚F) WB |
|
- Outdoor Temperature 8.3˚C(47˚F) DB/6.1˚C(43˚F) WB |
Piping Length |
- Interconnecting Piping Length 7.5m |
|
- Level Difference of Zero |
2.Wiring cable size must comply with the applicable local and national code.
3.Capacities are Net Capacities.
4.: See the page "Combination Table"
5.The specification may be subject to change without prior notice for purpose of improvement.
Copyright ©2008 LG Electronics. Inc. All right reserved. |
- 17 - |
Only for training and service purposes |
LGE Internal Use Only |
|
Product Specifications
|
Model |
|
A-MMC36FA-1 |
A-MMH36FA-1 |
|
|
|
|
|
|
|
Cooling Capacity |
|
|
Btu/hr |
9,000~36,000 |
9,000~36,000 |
|
|
|
|
|
|
|
|
|
W |
2637~10,550 |
2637~10,550 |
|
|
|
kcal/hr |
2267~9071 |
2267~9071 |
|
|
|
|
|
|
Heating Capacity |
|
|
Btu/hr |
- |
9,000~36,000 |
|
|
|
|
|
|
|
|
|
W |
- |
2637~10,550 |
|
|
|
kcal/hr |
- |
2267~9071 |
Input |
Cooling |
|
W |
1320~3680 |
1320~3680 |
|
|
|
|
|
|
|
Heating |
|
W |
- |
1410~3340 |
Running Current (208/230V) |
Cooling |
|
A |
5.9~16.6 |
5.9~16.6 |
|
|
|
|
|
|
|
Heating |
|
A |
- |
6.3~15.0 |
Power Supply |
|
|
Ø,V,Hz |
1,208/230,60 |
1,208/230,60 |
Max. Number of Connectable Indoor Units |
|
3 |
3 |
||
Compressor |
Type |
|
Rotary |
Rotary |
|
(Constant) |
Model |
|
GK141K |
GK141K |
|
|
Motor Type |
|
|
2 Pole Induction(PSC) |
2 Pole Induction(PSC) |
|
Quantity |
|
Ea |
1 |
1 |
|
Motor Input |
|
W |
1430 |
1430 |
|
|
|
|
|
|
|
Oil Charge |
cc |
350Å}10 |
350Å}10 |
|
|
|
|
|
|
|
|
Oil Type |
|
FVC68D |
FVC68D |
|
|
Capacitor |
|
µF/Vac |
35 / 370 |
35 / 370 |
|
O.L.P Type(model name) |
|
External Type |
External Type |
|
|
|
|
|
|
|
Compressor |
Type |
|
Rotary |
Rotary |
|
|
|
|
|
|
|
(Constant) |
Model |
|
GJ230K |
GJ230K |
|
|
Motor Type |
|
2 Pole Induction(PSC) |
2 Pole Induction(PSC) |
|
|
Quantity |
|
Ea |
1 |
1 |
|
|
|
|
|
|
|
Motor Input |
|
W |
2370 |
2370 |
|
Oil Charge |
|
cc |
700±10 |
7000±10 |
|
Oil Type |
|
FVC68D |
FVC68D |
|
|
Capacitor |
|
µF/Vac |
50 / 400 |
50 / 400 |
|
|
|
|
|
|
|
O.L.P Type(model name) |
|
Internal Type |
Internal Type |
|
Refrigerant charge |
Charge |
|
g(oz) |
2400 |
2400 |
|
Type |
|
R410A |
R410A |
|
|
|
|
|
|
|
|
Control |
|
EEV |
EEV |
|
|
|
|
|
|
|
Coil |
Tube Size (OD) |
|
inch(mm) |
0.276(7.0) |
0.276(7.0) |
|
Fins per inch |
|
18 |
18 |
|
|
No. of Rows & Column/No. |
|
2R,48C |
2R,48C |
|
|
|
|
|
|
|
Fan motor |
Model |
|
ARC286B01 * 2 |
ARC286B01 * 2 |
|
|
Output |
|
W |
102 |
102 |
|
Capacitor |
|
µF/Vac |
2/370 |
2/370 |
Fan |
Type |
|
Propeller |
Propeller |
|
|
|
|
|
|
|
|
No. Used / Diameter |
|
EA/inch(mm) |
2 / 15.7(400) |
2 / 15.7(400) |
|
Discharge |
|
Side / Top |
Side |
Side |
Air Circulation |
Outdoor |
|
CMM(CFM) |
63(2225) |
63(2225) |
Noise Level(H/L) at 230V |
Sound Press,1m |
|
dB(A) 1 |
51 |
51 |
|
|
|
|
|
|
SVC Valve |
Liquid |
|
inch(mm) |
1/4 (6..35) * 3EA |
1/4 (6..35) * 3EA |
|
Gas |
|
|
3/8 (9.52) * 3EA |
3/8 (9.52) * 3EA |
Dimensions |
W*H*D |
|
inch(mm) |
34.3*40.7*12.6 (870*1038*320) |
34.3*40.7*12.6 (870*1038*320) |
|
|
|
|
|
|
Net Weight |
Outdoor |
|
kg(lbs) |
84(185.2) |
84(185.2) |
|
|
|
|
|
|
Max. Interunit Piping Length |
Total of Each Room |
|
m |
45 |
45 |
|
For One Room |
|
m |
15 |
15 |
Max. Installation |
Indoor Unit~Outdoor Unit |
|
m |
7.5 |
7.5 |
|
|
|
|
|
|
Height Difference |
Indoor Unit~Indoor Unit |
|
m |
7.5 |
7.5 |
|
|
|
|
|
|
Packing Dimension |
W*H*D |
|
inch(mm) |
41.3*44.9*17.3 (1048*1140*439) |
41.3*44.9*17.3 (1048*1140*439) |
Stuffing Quantity |
|
|
20/40ft |
53/111 |
53/111 |
Note:
1. Capacities are based on the following conditions:
Cooling: |
- Indoor Temperature 26.7˚C(80˚F) DB/19.4˚C(67˚F) WB |
|
- Outdoor Temperature 35˚C(95˚F) DB/23.9˚C(75˚F) WB |
Heating: |
- Indoor Temperature 21.1˚C(70˚F) DB/15.6˚C(60˚F) WB |
|
- Outdoor Temperature 8.3˚C(47˚F) DB/6.1˚C(43˚F) WB |
Piping Length |
- Interconnecting Piping Length 7.5m |
|
- Level Difference of Zero |
2.Wiring cable size must comply with the applicable local and national code.
3.Capacities are Net Capacities.
4.: See the page "Combination Table"
5.The specification may be subject to change without prior notice for purpose of improvement.
Copyright ©2008 LG Electronics. Inc. All right reserved. |
- 18 - |
Only for training and service purposes |
LGE Internal Use Only |
|
Installation
Installation
Read carefully, and then follow step by step.
InstallationParts
Installation plate |
Type "A" screw and plastic anchor |
Type "B" screw |
Remote Control Holder |
InstallationTools
Figure |
Name |
Figure |
Name |
|
Screw driver |
|
Ohmmeter |
Electric Drill |
Hexagonal wrench |
Measuring Tape, Knife |
Ammeter |
Hole Core Drill |
Gas Leak Detector |
Spanner |
Thermometer, |
|
Level |
||
|
Torque wrench |
Flaring Tool Set |
Copyright ©2008 LG Electronics. Inc. All right reserved. |
- 19 - |
Only for training and service purposes |
LGE Internal Use Only |
|
Installation
Select the best location
Indoor unit
1.Do not have any heat or steam near the unit.
2.Select a place where there are no obstacles in front of the unit.
3.Make sure that condensation drainage can be conveniently routed away.
4.Do not install near a doorway.
5.Ensure the spaces indicated by arrows from the wall, ceiling, fence or other obstacles.
6.Use a Metal Detector or Metal Scanner to locate studs to prevent unnecessary damage to the wall.
More than 10 cm |
|
(3.9 inch) |
cm |
|
More than 2.4m
(8 ft)
More than 10 cm (3.9 inch)
CAUTION: Install the indoor unit on the wall where the height from the floors more than 2.4 m (8 ft).
Outdoor unit
1.If an awning is built over the unit to prevent direct sunlight or rain exposure, make sure that heat radiation from the condenser is not restricted.
2.Ensure that the spaces indicated by arrows around front, back and side of the unit.
3.Do not place animals and plants in the path of the warm air.
4.Take the air conditioner weight into account and select a place where noise and vibration are minimum.
5.Select a place so that the warm air and sound from the air conditioner do not disturb neighbors.
Rooftop Installations:
If the outdoor unit is installed on a roof structure, be sure to level the unit. Ensure the roof structure and anchoring method are adequate for the unit location. Consult local codes regarding rooftop mounting.
18 / 24 kBtu |
more than 30 cm |
|
(11.8 inch) |
more than 30 cm |
|
(11.8 inch) |
|
more than 70 cm
(27.6 inch)
more than 60 cm (23.6 inch)
36 kBtu |
more than 30 cm |
|
|
|
(11.8 inch) |
more than 30 cm |
|
(11.8 inch) |
|
more than 70 cm (27.6 inch)
more than 60 cm (23.6 inch)
Copyright ©2008 LG Electronics. Inc. All right reserved. |
- 20 - |
Only for training and service purposes |
LGE Internal Use Only |
|
Installation
Piping length and elevation
Multi Piping Type
|
Max total length |
Max length of |
Min length of |
Max Elevation |
Max elevation |
||||
|
between each |
||||||||
Capacity |
of all pipes |
each pipe |
|
each pipe |
|
between indoor |
|||
|
|
indoor unit and |
|||||||
|
(A+B/A+B+C) |
|
(A/B/C) |
|
(A/B/C) |
|
outdoor unit (h1) |
units (h2) |
|
|
|
|
|
|
|
|
|
||
18 kBtu |
30 m (100 ft) |
15 m (50 ft) |
|
3 m (10 ft) |
|
7.5 m (25 ft) |
|
7.5 m (25 ft) |
|
24 kBtu |
30 m (100 ft) |
15 m (50 ft) |
|
3 m (10 ft) |
|
7.5 m (25 ft) |
|
7.5 m (25 ft) |
|
36 kBtu |
45 m (150 ft) |
15 m (50 ft) |
|
3 m (10 ft) |
|
7.5 m (25 ft) |
|
7.5 m (25 ft) |
|
|
|
|
|
|
Pipe Size |
|
|
|
|
Indoor Capacity |
|
Liquid |
Standard Length |
|
Additional |
||||
|
Gas |
|
|
Refrigerant |
|||||
|
|
|
|
|
|
|
|
|
|
9 kBtu |
9.52 mm (3/8") |
6.35 mm (1/4") |
7.5 m (25 ft) |
20 g/m (0.22 oz/ft) |
|||||
12 kBtu |
9.52 mm (3/8") |
6.35 mm (1/4") |
7.5 m (25 ft) |
20 g/m (0.22 oz/ft) |
|||||
18 / 24 kBtu |
A |
|
|
|
36 kBtu |
A |
|
|
|
|
|
|
|
|
|
|
h2 |
h2 |
B |
B |
|
h2 |
h1 |
h1 |
|
C |
h1 |
h1 |
|
|
|
h1 |
B
CAUTION: Capacity is based on standard length and maximum allowance length is on the basis of reliability.
Copyright ©2008 LG Electronics. Inc. All right reserved. |
- 21 - |
Only for training and service purposes |
LGE Internal Use Only |
|
Installation
Fixing Installation Plate(Standard Type)
The wall you select should be strong and solid enough to prevent vibration
1.Mount the installation plate on the wall with
type "A" screws. If mounting the unit on a concrete wall, use anchor bolts.
•Mount the installation plate horizontally by aligning the centerline using a level.
2.Measure the wall and mark the centerline. It is also important to use caution concerning the location of the installation plate-routing of the wiring to power outlets is through the walls typically. Drilling the hole through the wall for piping connections must be done safely.
CHASSIS |
|
Distance (mm) |
|
||
(Grade) |
|
|
|
|
|
A |
B |
C |
D |
||
|
|||||
|
|
|
|
|
|
S4 |
50 |
105 |
59 |
105 |
|
|
|
|
|
|
|
SE |
65 |
110 |
85 |
110 |
Installation Plate
Chassis
Hook
Type "A" screw
D |
|
Installation plate |
B |
|
|
|
|
||
Ø70mm |
C |
|
A |
Ø70mm |
|
Left rear piping |
|
Right rear piping |
|
Drill a hole in the wall
•Drill the piping hole with a Ø 70 mm (Ø 2.75 inch) hole core drill. Drill the piping hole at either the right or the left with the hole slightly slanted to the outdoor side.
|
WALL |
Indoor |
Outdoor |
5-7 mm |
(0.2"~0.3") |
Copyright ©2008 LG Electronics. Inc. All right reserved. |
- 22 - |
Only for training and service purposes |
LGE Internal Use Only |
|
Flaring Work and Connection of Piping
Flaring Work and Connection of Piping
Flaringwork
Main cause for gas leakage is due to defect in flaring work. Carry out correct flaring work in the following procedure.
Cut the pipes
1.Use the piping kit accessory or the pipes purchased locally.
2.Measure the distance between the indoor and the outdoor unit.
3.Cut the pipes a little longer than measured distance.
4.Cut the cable 1.5m (5.0ft) longer than the pipe length.
Burrs removal
1.Completely remove all burrs from the cut cross section of pipe/tube.
2.Put the end of the copper tube/pipe in a downward direction as you remove burrs in order to avoid dropping burrs into the tubing.
Putting nut on
•Remove flare nuts attached to indoor and outdoor unit, then put them on pipe/tube having completed burr removal.
(not possible to put them on after flaring work)
Flaring work
•Carry out flaring work using flaring tool as shown below.
•Firmly hold copper pipe in a Bar in the dimension shown in the table Below.
Copper |
|
Slanted |
Uneven Rough |
pipe |
90° |
||
|
|
Pipe |
|
|
|
Reamer |
Point down
Flare nut
Copper tube
Outside diameter |
A |
|
|
|
|
mm |
inch |
mm |
Ø6.35 |
1/4 |
0~0.5 |
Ø9.52 |
3/8 |
0~0.5 |
|
"A" |
|
Handle |
Bar |
Bar |
|
|
|
Yoke |
||
|
|
|
|
|
|
|
Cone |
|
Copper pipe |
|
|
|
|
Clamp handle |
Red arrow mark |
|
|
|
Copyright ©2008 LG Electronics. Inc. All right reserved. |
- 23 - |
Only for training and service purposes |
LGE Internal Use Only |
|
Flaring Work and Connection of Piping
Check
1.Compare the flared work with the figure by.
2.If a flared section is defective, cut it off and do flaring work again.
Smooth all round
Inside is shiny without scratches
= Improper flaring =
Inclined Surface Cracked Uneven
damaged thickness
Even length all round
Connecting the Piping
Indoor
1. Prepare the indoor unit's piping and drain hose for installation through the wall.
2. Remove the plastic tubing retainer(see the illustration by) and pull the tubing and drain hose away from chassis.
3. Replace only the plastic tubing holder 1, not the holder 2 in the original position.
For right rear piping
1.Route the indoor tubing and the drain hose in the direction of rear right.
2.Insert the connecting cable into the indoor unit from the outdoor unit through the piping hole.
•Do not connect the cable to the indoor unit.
•Make a small loop with the cable for easy connection later.
3.Tape the tubing, drain hose, and the connecting cable. Be sure that the drain hose is located at the lowest side of the bundle. Locating at the Upper side can cause drain pan to overflow inside the unit.
If the drain hose is routed inside the room, insulate the hose with an insulation material* so that dripping from "sweating"(condensation) will not damage furniture or floors. *Foamed polyethylene or equivalent is recommended.
Drain hose
Tape
Connecting pipe
Drain hose
Connecting cable
Copyright ©2008 LG Electronics. Inc. All right reserved. |
- 24 - |
Only for training and service purposes |
LGE Internal Use Only |
|
Flaring Work and Connection of Piping
4.Indoor unit installation
Hook the indoor unit onto the upper portion of the installation plate.(Engage the two hooks of the rear top of the indoor unit with the upper edge of the installation plate.) Ensure that the hooks are properly seated on the installation plate by moving it left and right.
Press the lower left and right sides of the unit against the installation plate until the hooks engage into their slots(clicking sound).
Connecting the piping to the indoor unit and drain hose to drain pipe.
1.Align the center of the pipes and sufficiently tighten the flare nut by hand.
2.Tighten the flare nut with a wrench.
Outside diameter |
|
Torque |
||
|
|
|
|
|
mm |
inch |
kg.m |
|
lbf.in |
Ø6.35 |
1/4 |
1.8 |
|
156.2 |
Ø9.52 |
3/8 |
4.2 |
|
364.5 |
3.When extending the drain hose at the indoor unit, install the drain pipe.
Wrap the insulation material around the connecting portion.
1.Overlap the connection pipe insulation material and the indoor unit pipe insulation material. Bind them together with vinyl tape so that there may be no gap.
2.Wrap the area which accommodates the rear piping housing section with vinyl tape.
3.Bundle the piping and drain hose together by wrapping them with vinyl tape for enough to cover where they fit into the rear piping housing section.
Connecting
cable
Drain hose
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Indoor unit tubing |
Flare nut Pipes |
||||||||
|
|
|
|
|
|
|
|
|
|
Open-end wrench (fixed)
Flare nut
Wrench |
Connection pipe |
Indoor unit tubing
Drain pipe
Indoor unit drain hose
Adhesive Vinyl tape(narrow)
Plastic bands Insulation material
Connection pipe |
Indoor unit pipe |
Vinyl tape (wide) |
Wrap with vinyl tape |
Connecting cable
Pipe
Vinyl tape(narrow)
Wrap with vinyl tape
Pipe
Vinyl tape(wide)
Drain hose
Copyright ©2008 LG Electronics. Inc. All right reserved. |
- 25 - |
Only for training and service purposes |
LGE Internal Use Only |
|