HUMIDIFIER
|
© 2003 Lennox Industries, Inc. |
|
504,882M |
HEALTHY CLIMATE® HUMIDIFIERS |
|
|||
|
Dallas, Texas USA |
|
||||||
|
12/2003 |
|||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
INSTALLATION INSTRUCTIONS FOR LENNOX MODEL WB2-17 & WB2-17A |
|||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
ATTENTION INSTALLER: |
|
|
Specifications |
This product must be installed by a qualified heating and air conditioning contractor. This product must be installed in compliance with all local, state and federal codes.
! WARNING
Electrical Shock Hazard.
Can cause injury or death.
Disconnect all electrical power supplies before servicing.
! WARNING
Risk of Property Damage, Injury or Death.
Installation, adjustments, alterations, service and maintenance must be performed by your Lennox dealer.
! WARNING
Risk of Scalding.
Water temperature over 125ºF can cause severe burns and scalding instantly.
Shut off the hot water supply before disconnecting or tapping into any hot water supply line.
BYPASS HUMIDIFIER
Model WB2-17 & WB2-17A
•Unit dimensions
131/8"W x 151/2"H x 91/8"D, 6" dia. round opening
•Plenum Opening 93/4"W x 121/2"H
•Water Feed Rate 6 gph
•Electrical Data 24V-60Hz, 0.5 AMP
! CAUTION
Risk Of Sharp Edges Hazard.
Equipment sharp edges can cause injuries.
Avoid grasping equipment edges without protective gloves.
! CAUTION
Risk of Property and Equipment Damage.
Water heating system can be damaged if water supply remains off.
After humidifier installation is completed, turn hot water supply back on.
Water heating system must be de-energized if the main water supply remains shut off.
Do not set humidity level above recommended or to recommended level if condensation exists on inside windows of any unheated space, as condensation damage may result. Excess humidity can cause moisture accumulation which can allow the possibility for mold growth in your home.
Do not install unit in location where freezing temperatures may occur. The water line could freeze and crack causing water damage to the home.
Do not install humidifier or bypass connection on furnace jacket.
Do not install humidifier or bypass connection on blanked off end of cooling coil where airflow will be restricted.
Do not connect the transformer to multi-speed furnace blower motors or blower motors other than 120 VAC.
Do not install humidifier where water pressures exceed 125 psi, since humidifier damage may result. Follow codes in effect concerning pressure reduction.
Do not install power humidifier on supply plenum where static pressure exceeds 0.3” w.c.
WB2-17A
For detailed humidifier control installation and wiring instructions see form Publication No. 504,879M included with humidifier.
TEMPLATE MUST BE LEVEL