Lennox LMDV-3530-CNE, LMDV-40, LMDV-4035-CPM, LMDVR-3328-CNM, LMDVT-3328-CNM User Manual

...
0 (0)

This appliance may be installed in an aftermarket permanently located, manufactured home (USA only) or mobile home, where not prohibited by local codes. This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases, unless a certified kit is used.

In the Commonwealth of Massachusetts:

Installation must be performed by a licensed plumber or gas fitter;

See Table of Contents for location of additional Commonwealth of Massachusetts requirements.

WARNING:IFTHEINFORMATIONINTHISMANUAL IS NOT FOLLOWED EXACTLY, A FIRE OR EXPLOSIONMAYRESULTCAUSINGPROPERTYDAMAGE, PERSONAL INJURY OR LOSS OF LIFE.

Do not store or use gasoline or other flammable vapors or liquids in the vicinity of this or any other appliance.

WHAT TO DO IF YOU SMELL GAS:

Do not light any appliance.

Do not touch any electrical switch; do not Use any phone in your building.

Immediately call your gas supplier from a neighbor’s phone. Follow your gas supplier's instructions.

If your gas supplier cannot be reached, call the fire department.

Installation and service must be performed by a qualified installer, service agency or the gas supplier.

OTL Report No. 116-F-31-5

US

A French manual is available upon request. Order P/N 850,029CF

Ce manuel d’installation est disponible en francais, simplement en faire la demande. Numéro de la pièce 850,029CF.

INSTALLATION

INSTRUCTIONS

DIRECT VENT MERIT

LMDV-33/35/40 SERIES

VENTED GAS FIREPLACE HEATERS - DIRECT VENT MODELS

P/N 850,029M REV. G 05/2008

MODELS

Millivolt Models

Electronic Models

LMDVT-3328-CNM LMDV-3530-CNM

LMDVT-3328-CNE

LMDVT-3328-CPM

LMDV-3530-CPM

LMDVR-3328-CNE

LMDVR-3328-CNM LMDV-4035-CNM

LMDV-3530-CNE

LMDVR-3328-CPM

LMDV-4035-CPM

LMDV-4035-CNE

INSTALLER: Leave this manual with the appliance. CONSUMER: Retain this manual for future reference.

AVERTISSEMENT: ASSUREZ-VOUS DE BIEN SUIVRE LES INSTRUCTIONS DONNÉ DANS CETTE NOTICE POUR RÉDUIRE AU MINIMUM LE RISQUE D'INCENDIE OU POUR ÉVITER TOUT DOMMAGE MATÉRIEL, TOUTE BLESSURE OU LA MORT.

POUR VOTRE SÉCURITÉ: Ne pas entreposer ni utiliser d'essence ni d'autre vapeurs ou liquides inflammables dans le voisinage de cet appareil ou

de tout autre appareil.

POUR VOTRE SÉCURITÉ: Que faire si vous sentez une odeur de gaz:

Ne pas tenter d'allumer d'appareil.

Ne touchez à aucun interrupteur. Ne pas vous servir des téléphones se trouvant dans le batiment où vous vous trouvez.

Evacuez la piéce, le bâtiment ou la zone.

Appelez immédiatement votre fournisseur de gaz depuis un voisin. Suivez les instructions du fournisseur.

Si vous ne pouvez rejoindre le fournisseur de gaz, appelez le service dos incendies.

L'installation et service doit être exécuté par un qualifié installeur, agence de service ou le fournisseur de gaz.

TABLE OF CONTENTS

 

 

Packaging..........................................

Page

2

Introduction.......................................

Page

2

General Information...........................

Page

2

New York City Approval.....................

Page

3

Requirements for the

 

 

Commonwealth of Massachusetts..Page

4

Cold Climate Insulation......................

Page

4

Location.............................................

Page

4

Manufactured Home Requirements...

Page

5

Vent Termination Clearances ............

Page

5

Appliance and Vent Clearances..........

Page

7

Detailed Installation Steps.................

Page

8

Typical Installation Sequence ............

Page

8

Step 1. Framing.................................

Page

8

Step 2. Routing Gas Line...................

Page

8

Fireplace Specifications.....................

Page

9

Step 3. Install the Venting System.....

Page

11

Vertical Termination Systems............

Page

12

Vent Section Length Chart.................

Page

12

Vertical Vent Tables and Figures........

Page

14

Horizontal Termination System..........

Page

16

Horizontal Vent Tables and Figures....

Page

19

Venting Using Flexible Vent Pipe.......

Page

22

Step 4. Field Wiring.........................

Page

23

Step 5. Optional Blower Kit Wiring..Page

23

Step 6. Connecting Gas Line............

Page

24

Step 7. Checking Unit Operation......

Page

25

Step 8. Installing Logs ....................

Page

26

Step 9. Installing Glass Door ..........

Page

29

Step 10. Burner Adjustments.............

Page

29

Step 11. Hood Installation.................

Page

30

Finishing Requirements.....................

Page

30

Installation Accessories.....................

Page

31

Gas Conversion Kits...................

Page 34

This manual is part of a set of two supporting this product. Refer to manual 875,028M for Care & Operation information.

Please read and understand these instructions before beginning your installation.

The Millivolt appliances have a millivolt gas control valve with piezo ignition system which provides safe, efficient operation. If any optional accessories that will require electrical power are to be installed, the electrical power must be provided at the time of appliance installation.

The Electronic appliances have an electronic intermittent pilot ignition system which provides safe, efficient operation. External electrical power is required to operate these appliances.

PACKAGING

The assembled vented gas fireplace heater is packaged with:

1 - One log set located in firebox area.

2- One envelope containing the literature package which consists of the homeowner's manual, installation instructions, and warranty; envelope is located in the control compartment.

3- One vent restrictor to be applied as shown on Page 11 ; restrictor is taped to the envelope.

4- One hood located behind the top panel.

5- One bag of decorative volcanic stone located in the control compartment.

6- One bag of glowing embers located in the control compartment.

7- One bag of vermiculite located in the control compartment.

Introduction

These vented gas fireplace heaters are sealed combustion, air circulating gas fireplaces designed for residential applications.

Approved Vent Components - These fireplaces are designed, tested and listed for operation and installation with, the following vent components only:

Secure Vent™ Direct Vent System Components,

Secure Flex™ Flexible Vent Components manufactured by Security Chimneys International and

Z-FLEX™ Model GA Venting Systems listed to UL1777 and ULCS635 manufactured by Flexmaster Canada Limited.

These approved vent system components are labeled for identification. DO NOT use any other manufacturer’s vent components with these appliances. Use only the correct size venting (4-1/2" inner & 7-1/2" outer).

These appliances comply with National Safety Standards and are tested and listed by OMNITest Laboratories, Inc. (Report No. 116-F-31-5) to ANSI Z21.88b (in Canada, CSA-2.33b), and CAN/CGA-2.17-M91 in both USA and Canada, as vented gas fireplace heaters.

Both millivolt and electronic versions of these appliances are listed by OMNI-Test Laboratories for installation in bedrooms and Manufactured Homes.

Manufactured Homes -

See Manufactured Home Requirements on

Page 5 for additional information.

WARNING

Improper installation, adjustment, alteration, service or maintenance can cause injury or property damage. Refer to this manual. For assistance or additional information consult a qualified installer, service agency or the gas supplier.

NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.

This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases, unless a certified kit is used.

Cet appareil doit être utilisé uniquement avec les types de gaz indiqués sur la plaque signalétique. Ne pas l'utiliser avec d'autres gaz sauf si un kit de conversion certifié est installé.

Misc. Codes / Standards -

Installation must conform to local codes. In the absence of local codes, installation must comply with the current National Fuel Gas Code, ANSI Z223.1. (In Canada, the current CAN-1 B149 installation code).

The appliance, when installed, must be electrically grounded & wired in accordance with local codes or, in the absence of local codes, with the National Electrical Code, ANSI / NFPA 70-latest edition, or the Canadian Electrical Code, CSA C22.1 - latest edition.

General Information

Note: Installation and repair should be performed by a qualified service person. The appliance should be inspected annually by a qualified professional service technician. More frequent inspections and cleanings may be required due to excessive lint from carpeting, bedding material, etc.

S'assurer que le brùleur et le compartiment des commandes sont propres. Voir les instructions d'installation et d'utilisation qui accompagnent l'appareil.

Provide adequate clearances around air openings and adequate accessibility clearance for service and proper operation. Never obstruct the front openings of the appliance.

These appliances are designed to operate on natural or propane gas only. The use of other fuels or combination of fuels will degrade the performance of this system and may be dangerous.

These fireplaces are designed as supplemental heaters. Therefore, it is advisable to have an alternate heat source when installed in a dwelling.

Millivolt Models - The millivolt appliances are manually controlled and feature a spark igniter (piezo) that allows the appliance's pilot gas to be lit without the use of matches or batteries. This system provides continued service in the event of a power outage.

Millivolt models come standard with a manu- ally-modulated gas valve; flame appearance and heat output can be controlled at the gas valve. The BTU Input for these appliances is shown in Tables 1 & 2.

Lennox LMDV-3530-CNE, LMDV-40, LMDV-4035-CPM, LMDVR-3328-CNM, LMDVT-3328-CNM User Manual

Input (BTU) Manually-Modulated Gas

Valves (millivolt models)

NATURAL GAS

Models

Input Rate (BTU / HR)

 

 

LMDVT-3328CNM

17,500 high

LMDVR-3328CNM

11,700 low

 

 

LMDV-3530CNM

20,000 high

12,800 low

 

LMDV-4035CNM

27,000 high

18,500 low

 

Table 1

 

Input (BTU) Manually-Modulated Gas

Valves (millivolt models)

PROPANE GAS

Models

Input Rate (BTU / HR)

LMDVT-3328CPM

17,500 high

LMDVR-3328CPM

14,000 low

 

 

LMDV-3530CPM

20,000 high

15,200 low

 

LMDV-4035CPM

27,000 high

21,500 low

 

Table 2

Electronic Models -

Electronic models have a fixed rate gas valve. Input of electronic models is shown in Table 3.

Electronic Models with Fixed Rate Gas Valve

Natural and Propane Gas

Model Series

Input Rate

 

(BTU / HR)

 

 

LMDVT-3328

17,500

LMDVR-3328

 

 

 

LMDV-3530

20,000

LMDV-4035

27,000

 

 

Table 3

Gas Pressure - All Models

Tables 4, 5 and 6 show the appliances' gas pressure requirements:

Inlet Gas Supply Pressure

(all models)

Fuel #

Minimum

Maximum

 

 

 

Natural Gas

5.0" WC

10.5" WC

(1.24 kPa)

(2.61 kPa)

 

 

 

 

Propane

11.0" WC

13.0" WC

(2.74 kPa)

(3.23 kPa)

 

Table 4

Manifold Gas Supply Pressure

(millivolt models)

Fuel #

Low

High

 

 

 

Natural

(Lo) 2.2" WC

(Hi) 3.5" WC

Gas

(.55 kPa)

(.87 kPa)

 

 

 

Propane

(Lo) 6.3" WC

(Hi) 10.0" WC

(1.57 kPa)

(2.49 kPa)

 

 

 

 

Table 5

Manifold Gas Supply Pressure

(electronic models)

Fuel #

Maximum Manifold Pressure

Natural Gas

(Hi) 3.5" WC (.87 kPa)

 

 

Propane

(Hi) 10.0" WC (2.49 kPa)

 

 

Table 6

Test gauge connections are provided on the front of the millivolt gas control valve, identified IN for the inlet and OUT for the manifold side. A 1/8" NPT Test gauge connection is provided at the inlet and outlet side of the electronic gas control valve.

These appliances must be isolated from the gas supply piping system (by closing their individual manual shut-off valve) during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 psig (3.5 kPa).

These appliances and their individual shut-off valves must be disconnected from the gas supply piping system during any pressure testing of that system at pressures greater than 1/2 psig (3.5 kPa).

Orifice Sizes - Sea Level to High Altitude

(All Models)

These appliances are tested and approved for installation at elevations of 0-4500 feet (0-1372 meters)abovesealevelusingthestandardburner orifice sizes (marked with an "*" in Table 7). For elevations above 4500 feet, contact your gas supplier or qualified service technician .

Burner Orifice Sizes Elevation 0-4500 feet ( 0-1372 meters)

Model

Nat.Gas

Propane

Series

drill size (inches)

drill size (inches)

 

 

 

LMDVT-3328

#45 (.082") *

(.048") *

LMDVR-3328

39L66 •

99K780

LMDV-3530

#44 (.086") *

#55 (.052") *

60J8001 •

19L5201

 

 

 

 

LMDV-4035

#37 (.104") *

1/16" (.062")*

24M1001 •

21L0101 •

Table 7

* Standard size installed at factory

• Part /Cat. Number

 

NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.

Install the appliance according to the regulations of the local authorities having jurisdiction and, in the USA, the National Fuel Gas Code NFPA 54 / ANSI Z223.1 - latest edition or, in Canada, the CAN1-B149.1 and .2 codes - latest edition.

Gas Valve Diagrams

See Figures 1 & 2 for Millivolt models and Figure 3 For Electronic Models.

SIT Millivolt

Gas Valve

HI/LO Variable

 

 

Inlet Pressure Tap

Flame Height

 

 

 

 

 

 

Adjustment

Manifold Pressure Tap

 

HTPT

 

 

OUT

IN

 

 

 

 

PT

 

IH

OFF

 

 

 

 

P

 

 

 

 

 

 

 

 

I

 

 

LOW

it

L

HT

 

O

 

 

 

 

T

 

 

 

NO

 

P

 

 

 

 

I

 

 

 

 

TOL

 

 

 

 

Pilot Adjustment

Main Gas

 

Screw

 

Control Knob

 

 

 

OFF/PILOT/ON

 

Figure 1

 

 

 

 

Honeywell Millivolt

Gas Valve

 

 

PIEZO

 

PILOT

 

IGNITER

CONVERTIBLE

 

 

 

 

HI/LO REGULATOR

ADJUSTMENT

GAS CONTROL

(adjusts flame height

SCREW

KNOB

 

and heat output)

 

 

TP/TH

 

O

 

 

 

NI

 

 

 

 

L

 

 

P

O

TP

 

H

L

I

 

 

FFO TO

 

 

TH

 

 

 

WIRING

INLET

OUTLET

TERM-

PRESSURE

PRESSURE

INALS

TAP

TAP

Figure 2

 

 

 

Honeywell Electronic Gas Valve

Manifold Pressure

ON / OFF Switch

Port

 

 

Inlet

 

 

 

C

 

 

Pressure

LORTNO

FFO NO

N

Port

 

 

I

 

ERTINGI

 

 

Electronic

 

 

 

 

 

ISP

Gas

 

 

 

Control

 

 

 

Valve

Figure 3

Massachusetts And New York City, NY Requirements

These appliances are approved for installation in the following USA locations listed in the following:

Massachusetts:

These fireplaces are approved for installation in the US state of Massachusetts if the following additional requirements are met-

Installation and repair must be done by a plumber or gas fitter licensed in the Commonwealth of Massachusetts.

The flexible gas line connector used shall not exceed 36 inches (92 centimeters) in length.

The individual manual shut-off must be a T-handle type valve.

Massachusetts Horizontal Vent Requirements

In the Commonwealth of Massachusetts, horizontal terminations installed less than seven

(7) feet above the finished grade must comply with the following additional requirements:

A hard wired carbon monoxide detector with an alarm and battery back-up must be installed on the floor level where the gas fireplace is installed. The carbon monoxide detector must comply with NFPA 720, be ANSI/UL 2034 listed and be ISA certified.

A metal or plastic identification plate must be permanently mounted to the exterior of the building at a minimum height of eight (8) feet above grade and be directly in line with the horizontal termination. The sign must read, in print size no less than one-half (1/2) inch in size, GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS.

New York City, NY:

These fireplaces are approved for installation in New York City in the US state of New York.

Cold Climate Insulation

For cold climate installations, seal all cracks around the appliance with noncombustible material and wherever cold air could enter the room. It is especially important to insulate outside chase cavity between studs and under floor on which the appliance rests, if floor is above ground level. Gas line holes and other openings should be caulked or stuffed with unfaced fiberglass insulation. If the fireplace is being installed on a cement slab, in cold climates, a sheet of plywood or other raised platform can be placed underneath to prevent conducting cold up into the room. It also helps to sheetrock inside surfaces and tape for maximum air tightness and caulk firestops.

 

 

 

 

 

 

 

 

REAR VENT APPLICATION

 

R

 

 

 

 

 

 

 

 

 

 

 

 

A E

 

 

 

 

 

 

 

 

T

 

 

P A

 

 

 

 

 

 

 

N

 

P R

 

 

 

 

 

 

N

 

 

L

V

 

 

 

 

E

 

IO

 

I

 

 

 

 

 

 

C

E

 

 

V

 

 

T

 

 

 

P

 

 

 

 

 

A

N

 

 

 

A

 

 

T

 

T

O

 

C

 

 

 

 

I

 

 

I

 

 

 

 

 

O

 

T

 

 

L

 

 

 

 

 

N

 

 

P

 

 

 

 

 

 

 

 

 

 

P

 

 

 

 

 

 

 

 

 

 

A

 

 

 

 

 

 

 

 

 

APPLICATION

 

APPLICATION

TOP VENT

APPLICATION

TOP VENT

 

TOP VENT

 

 

 

 

APPLICATION

 

 

 

 

 

 

 

RECESSED

 

TOP VENT

 

 

 

 

 

INSTALLATION

 

 

 

 

 

 

 

 

 

 

 

TOP VENT

 

 

 

 

 

 

 

 

 

 

 

 

 

APPLICATION

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HORIZONTAL VENT

 

 

VERTICAL VENT

 

 

 

 

(Rear Vent

(Rear Vent Application

 

 

Application)

without a chase)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HORIZONTAL VENT (Rear Vent Application With a chase)

 

 

 

VERTICAL VENT

HORIZONTAL VENT

(Top Vent

(Top Vent

Application)

Application)

Figure 4 - Typical Locations

Location

In selecting the location, the aesthetic and functional use of the appliance are primary concerns. However, vent system routing to the exterior and access to the fuel supply are also important. Consideration should be given to traffic ways, furniture, draperies, etc., due to elevated surface temperatures (Figure 4). The location should also be free of electrical, plumbing or other heating/air conditioning ducting.

These direct vent appliances are uniquely suited for installations requiring a utility shelf positioned directly above the fireplace. Utility shelves like these are commonly used for locating television sets and decorative plants. Be aware that this is a heat producing appliance. Objects placed above the unit are exposed to elevated temperatures.

To provide for the lowest possible shelf surface use the alternate rear vent outlet with attached venting routed in a way to minimize obstructions to the use of the space above the appliance. Do not insulate the space between the appliance and the area above it. See Figure 9. The minimum height from the base of the appliance to the underside of combustible materials used to construct a utility shelf in this fashion is shown in the Table in Figure 9.

The appliance should be mounted on a fully supported base extending the full width and depth of the unit. The appliance may be located on or near conventional construction materials. However, if installed on combustible materials, such as carpeting, vinyl tile, etc., a metal or wood barrier covering the entire bottom surface must be used.

NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.

MANUFACTURED HOME

REQUIREMENTS

This appliance may be installed in an aftermarket permanently located, manufactured home (USA only) or mobile home, where not prohibited by local codes.

Cet appareil peut être installé dans un maison préfabriquée (É.-U. seulement) ou mobile déjà installée à demeure si les réglements locaux le permettent.

Manufactured Home installations must be installed in accordance with these instructions and the following standards / codes:

Manufactured Home Construction and Safety Standard Title 24 CFR, Part 3280, or the current Standard for Fire Safety Criteria for Manufactured Home Installations, Sites and Communities ANSI / NFPA 501A in the USA, and CAN / CSA Z240 MH Mobile Home Standard in Canada

(when applicable) The American National Standardfor Manufactured Homes (NCSBCS / ANSI A225.1 - latest edition).

CAUTIONS

Ensure that the cross members are not cut or weakened during installation. The structural integrity of the manufactured home floor, wall, and ceiling / roof must be maintained.

Thisappliancemustbe grounded to the chassis of the manufactured home in accordance with local codes or in the absence of local codes, with the National Electrical Code ANSI / NFPA 70 - latest edition or the Canadian ElectricalCodeCSAC22.1-latest edition.

Vent Termination Clearances

These instructions should be used as a guideline and do not supersede local codes in any way. Install vent according to local codes, these instructions, the current National Fuel Gas Code (ANSI-Z223.1) in the USA or the current standards of CAN/CGA-B149.1 and -B149.2 in Canada.

Terminate multiple vent terminations according to the installation codes listed above.

Terminate single vent caps relative to building components according to Figure 5.

Vertical Vent Termination Clearances

TERMINATION HEIGHTS FOR VENTS ABOVE FLAT OR SLOPED ROOFS

Horizontal Overhang

2 FT MIN.

Vent

Termination

Storm Collar

Flashing

Concentric

Vent Pipe

2 FT

 

Vertical

MIN.

 

Wall

 

 

Lowest

Discharge

Opening

H*

X

12

Roof Pitch is X/12

1 inch (25.4 mm) Minimum Clearance to Combustibles

*H = MINIMUM HEIGHT FROM ROOF TO LOWEST DISCHARGE OPENING OF VENT

The vent / air intake termination clearances above the high side of an angled roof is as shown in the following chart:

Figure 5

Termination Heights For Vents Above Flat Or Sloped Roofs Ref. NFPA 54 / ANSI Z223.1, 7.6

Roof Pitch

* Feet

*Meters

 

 

 

Flat to 6/12

1.0

0.3

 

 

 

6/12 to 7/12

1.25

0.38

 

 

 

7/12 to 8/12

1.5

0.46

 

 

 

8/12 to 9/12

2.0

0.61

9/12 to 10/12

2.5

0.76

 

 

 

10/12 to 11/12

3.25

0.99

 

 

 

11/12 to 12/12

4.0

1.22

12/12 to 14/12

5.0

1.52

 

 

 

14/12 to 16/12

6.0

1.83

16/12 to 18/12

7.0

2.13

 

 

 

18/12 to 20/12

7.5

2.29

20/12 to 21/12

8.0

2.44

 

 

 

Horizontal Vent Termination Clearances

Combustible Projection 2-1/2 inches or less in length

Combustible Projection greater than 2-1/2 inches in length

Ventilated

Soffit Unventilated

Soffit

 

 

 

 

 

 

 

3"

 

18"

12"

 

 

 

 

(76 mm)

 

 

(457 mm)

(305 mm)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Side Elevation View

Termination Kit

All horizontal terminations

 

may be located as close as

 

6” (152mm) to any

 

(non-combustible and

 

combustible) exterior

 

sidewall. This distance

 

may be decreased to 2”

 

(51mm) for non-

 

combustible exterior

 

sidewalls only, if the

 

SV4.5HT-2 termination

 

is used.

Termination Kit

 

Figure 6

Note - See Figure 35 on Page 20 for the exterior wall recess

allowances of the square horizontal termination.

Horizontal Vent Termination Clearances

The horizontal vent termination must have a minimum of 3" (76 mm) clearance to any overhead combustible projection of 2 1/2" (64 mm) or less. See Figure 6. For projections exceeding 2 1/2" (64 mm), see Figure 6. For additional vent location restrictions refer to Figure 7 on Page 8.

NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.

Exterior HORIZONTAL Vent TERMINATION Clearance Requirements

V L

 

 

 

 

 

 

 

 

 

 

NOTE: Local Codes Or Regulations

 

 

 

 

* See Item D in the Text Below.

 

 

 

 

 

May Require Different Clearances.

 

 

P

 

 

 

 

 

 

NOTE: Location Of The Vent Termination

N

 

N

Exterior Wall

Center Line

 

 

Inside

 

 

 

 

 

 

 

 

 

 

 

 

 

of Termination

 

 

Corner Detail

 

Must Not Interfere With Access To The

 

 

 

O

*18”

 

 

 

 

 

 

 

Electrical Service.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

V

 

Horizontal

V

 

 

 

 

 

G

 

 

 

 

 

Q

 

 

 

 

 

 

 

 

 

 

 

 

 

Termination

 

 

 

 

 

 

V

 

 

 

 

 

 

 

 

 

18”

Ventilated Soffit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Inside Corner

 

 

 

 

 

 

= 9” in U.S.

 

 

 

 

 

 

 

 

 

 

 

 

A

 

 

 

 

 

Detail D

 

 

 

 

 

= 12” in Canada

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

H

 

 

 

 

 

 

 

 

 

 

 

 

 

3 ft.

 

 

 

 

 

B

 

 

 

 

C

B

 

 

 

X

 

 

 

 

D

 

 

 

V

 

 

 

 

A

A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

V

 

 

 

Fixed

 

V

Operable

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Closed

 

 

Window

 

 

3 ft.

 

 

 

 

 

 

F

V

 

Window

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C

B

 

 

J

 

 

M

 

 

 

 

V

 

 

 

 

 

 

 

 

 

 

 

 

 

C

C

 

B

B

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

V

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A

 

 

 

 

 

 

 

 

 

 

I

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

X = Air Supply Inlet

V = Vent Terminal

= Area where Terminal is not Permitted

 

 

 

 

 

Canadian Installation*

US Installation**

 

 

 

A = Clearance above grade, veranda, porch, deck, or balcony.

12 inches (30cm)*

12 inches (30cm)**

B = Clearance to window or door that may be opened.

6 inches (15cm) for appliances

6 inches (15cm) for appliances

 

< 10,000 Btuh (3kW), 12 inches (30cm)

< 10,000 Btuh (3kW), 9 inches (23cm)

 

for appliances > 10,000 Btuh (3kW)

for appliances > 10,000 Btuh (3kW) and

 

 

< 50,000 Btuh (15kW), 12 inches (30cm)

 

 

for appliances > 50,000 Btuh (15kW)**

 

 

 

C = Clearance to permanently closed window

12 inches (305mm) recommended to

9 inches (229mm) recommended to

 

prevent window condensation

prevent window condensation

D = Vertical clearance to ventilated soffit located above the

18 inches (458mm)

18 inches (458mm)

terminal within a horizontal distance of 18 inches (458mm)

 

 

from the center line of the terminal

 

 

E = Clearance to unventilated soffit***

12 inches (305mm)

12 inches (305mm)

F = Clearance to outside corner

5 inches (12.7cm) minimum

5 inches (12.7cm) minimum

G = Clearance to inside corner

6 inches (15.2cm) minimum

6 inches (15.2cm) minimum

 

 

 

H = Clearance to each inside of center line extended above

3 feet (91cm) within a height of 15 feet

3 feet (91cm) within a height of 15 feet

meter/regulator assembly

above the meter/regulator assembly*

above the meter/regulator assembly**

I = Clearance to service regulator vent outlet

3 feet (91cm)*

3 feet (91cm)**

 

 

 

J = Clearance to nonmechanical air supply inlet to building or

6 inches (15cm) for appliances

6 inches (15cm) for appliances

the combustion air inlet to any other appliance

< 10,000 Btuh (3kW), 12 inches (30cm)

< 10,000 Btuh (3kW), 9 inches (23cm)

 

for appliances > 10,000 Btuh (3kW)

for appliances > 10,000 Btuh (3kW) and

 

 

< 50,000 Btuh (15kW), 12 inches (30cm)

 

 

for appliances > 50,000 Btuh (15kW)**

K = Clearance to a mechanical air supply inlet

6 feet (1.83m)*

3 feet (91cm) above if within 10 feet

 

 

(3m) horizontally**

L = Clearance above paved sidewalk or paved diveway located

7 feet (2.13m)‡

7 feet (2.13m)‡

on public property

 

 

M = Clearance under veranda, porch, deck or balcony

12 inches (30cm)*‡

12 inches (30cm)‡

 

 

 

N = Depth of Alcove (Maximum)

6 feet (1.83m)*

6 feet (1.83m)**

O = Clearance to Termination (Alcove)

6 inches (15.2mm)*

6 inches (15.2mm)**

P = Width of Alcove (Minimum)

3 feet (91cm)*

3 feet (91cm)*

Q = Clearance to Combustible Above (Alcove)

18 inches (457mm)*

18 inches (457mm)**

* In accordance with the current CSA-B149.1 National Gas And Propane Installation Code. ** In accordance with the curent ANSI SZ223.1/NFPA 54 National Fuel Gas Codes.

*** Clearance required to vinyl soffit material - 30 inches (76cm) minimum.

‡ A vent shall not terminate directly above a sidewalk or paved driveway which is located between two single family dwellings and serves both dwellings.

*‡ Only permitted if veranda, porch, deck or balcony is fully open on a minimum 2 sides beneath the floor:

Figure 7

NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.

Minimum Clearances to Combustibles

Hearth Extension A hearth extension is not required with this appliance. If a hearth extension is

Appliance and Vent Clearances

used, do not block the lower control compartment door. Any hearth extension used is for appearance

The appliance is approved with zero clearance to

only and does not have to conform to standard hearth extension installation requirements.

combustible materials on all sides (as detailed in

 

 

 

 

 

 

 

 

 

 

Wall Finishes / Surrounds / Mantels

 

 

 

 

 

 

Table 8), with the following exception: When the

Note: Combustible wall finish materials and/or surround materials must not be allowed to encroach

unit is installed with one side flush with a wall, the

the area defined by the appliance front face (black sheet metal). Never allow combustible materials

wall on the other side of the unit must not extend

to be positioned in front of or overlapping the appliance front face. See Figure 61 on Page 30.

beyondthefrontedgeoftheunit.Inaddition,when

Non-combustible materials, such as surrounds and other appliance trim, may be installed on the

the unit is recessed, the side walls surrounding

the unit must not extend beyond the front edge

appliance front face with these exceptions: they must not cover any portion of the removable glass

of the unit. See Figure 4.

panel or louvers.

 

 

 

 

 

 

 

 

 

Vertical installation clearances to combustible mantels vary according to the depth of the mantel.

 

 

MINIMUM CLEARANCES Inches (millimeters)

See Figure 8. Mantels constructed of non-combustible materials may be installed at any height

 

 

 

Back

 

1/2 (13)

above the appliance opening; however, do not allow anything to hang below the hood.

 

 

 

 

 

 

 

 

 

 

 

 

 

0 (0) Spacers

 

 

 

 

 

 

 

 

 

 

Sides

 

1/2 (13)

 

 

 

 

 

 

 

 

 

 

 

 

 

Mantel Depth

 

 

 

inches (millimeters)

 

 

0 (0) Spacers

 

 

 

 

 

 

 

 

 

 

 

14 (356)

 

 

 

 

 

 

 

 

 

Top Spacers

 

0 (0)

 

 

 

 

 

 

 

 

 

 

 

 

 

12 (305)

 

 

 

 

 

 

 

 

 

Floor

 

0 (0)

 

 

 

 

 

 

 

 

 

 

 

 

10 (254)

 

 

 

 

 

 

 

 

 

Bottom of Appliance

 

64 (1626)

 

 

 

 

 

 

 

 

 

To Ceiling

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

8 (203)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Top of

Vent

 

3 (76) Top *

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1 (25.4) Sides & Bottom

6 (152)

 

 

 

 

 

Appliance

 

 

4 (102)

 

 

 

 

 

 

 

 

 

SERVICE CLEARANCES Feet (meters)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Front

 

3 ft. (0.9 m)

 

 

 

 

 

 

 

 

 

 

 

 

 

12

10

8

6

4

2

 

 

 

 

Table 8

 

(305)

(254)

(203)

(152)

(102)

(51)

 

 

 

 

 

 

 

 

 

 

 

*Note: 3 in. (75 mm) above any horizontal/in-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

clined vent component.

 

Note - Hood shown as positioned with louvered panels.

**Note: See Page 8, Step 1 for clearance Figure 8 - Minimum Mantel Clearances requirements to the nailing flange located at each side of the unit and any screw heads

adjacent to it.

Model No.

Combustible Shelf Height - Inches (millimeters)

Minimum Distance to Unprotected Side Wall

Top Vent - with One 90 Degree Elbow

Rear Vent - Straight Out the Back

Combustible materials may project beyond the sides of the fire-

 

 

 

 

 

 

 

Secure Vent

Secure Flex

Secure Vent

Secure Flex

place opening as long as they are kept within the shaded areas

 

 

(flex elbow)

 

 

illustrated here.

 

 

LMDVT-3328

*44-1/2 (1130)

*46-1/4 (1175)

N/A

N/A

At 14" minimum

 

 

 

 

 

 

 

 

 

LMDVR-3328

N/A

N/A

33-1/4 (845)

33-1/4 (845)

side wall clearance, At 8-1/4" side

 

 

 

 

 

 

a combustible wall

wall clearance, a

Top View of

LMDV-3530

*46-1/2 (1181)

*48-1/4 (1226)

35-1/4 (895)

35-1/4 (895)

can project to any

combustible wall

Fireplace

can project 12"

LMDV-4035

*51-1/2 (1308)

*53-1/4 (1349)

40-1/4 (1022)

40-1/4 (1022)

length.

 

 

 

 

 

 

* Includes 3” clearance to combustibles (required above vent components)

 

 

 

Combustible Materials

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Allowed In Shaded Area

 

 

 

Do not insulate the

 

 

45o

“Safe Zone”

 

 

 

 

 

Combustible Walls

Do not insulate the

 

space between the

 

 

5 (127)

 

 

 

 

shown in dark gray

space between the

 

appliance and the

 

 

 

 

 

 

 

 

appliance and the

 

area above it.

 

 

 

When the unit is

area above it.

 

 

 

 

 

 

 

 

 

 

 

 

installed with one side

 

 

 

 

 

 

12 (305)

flush with a wall, the

 

 

 

 

 

 

wall on the other side

 

 

 

*Shelf Height

 

 

 

of the unit must not

 

 

 

 

 

 

extend beyond the front

Shelf Height

 

(see table)

 

 

 

edge of the unit.

(see table)

 

 

 

 

 

 

 

 

 

 

 

 

19 (483)

 

 

 

 

 

 

14

8-1/4 Protected wall shown in white

Shelf Above Fireplace With Rear Venting

Shelf Above Fireplace With Top Venting

(356)

(209)

 

Inches (millimeters)

Figure 10

Figure 9 - Shelf Height Minimum Clearances

 

 

 

 

 

 

 

NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.

 

 

Detailed Installation Steps

Theapplianceisshippedwithallgascontrolsand components installed and pre-wired. Remove the shipping carton, exposing the front glass door. Remove the top and bottom louvered control panel per instructions on Page 25 (see

Control Compartment Access / Louver Panel Instructions). Remove the cardboard from underneath the pressure relief plates (in area behind top louver panel, See Figure 11). Open the two latches (located under the firebox floor) securing the glass door. Remove the door by tilting it outward at the bottom and lifting it up. Set the door aside protecting it from inadvertent damage. See Figure 57 on Page 29.

Pressure Relief Plates

 

REMOVE

REMOVE

CARDBOARD

CARDBOARD

BEFOREUSING

BEFOREUSING

 

Remove Cardboard Before

Using Appliance

 

Note: See-Through Model Shown

Figure 11

 

TYPICAL INSTALLATION SEQUENCE

The typical sequence of installation follows, however, each installation is unique resulting in variations to those described.

See the Page numbers references in the following steps for detailed procedures.

Step 1. (Page 8) Construct the appliance framing. Position the appliance within the framing and secure with nailing brackets.

Step 2. (Page 8) Route gas supply line to appliance location.

Step 3. (Page 11) Install the vent system and exterior termination.

Step 4. (Page 23) Field Wiring

a.Millivolt Appliances – Install the operating control switch (not factory provided) and bring in electrical service line for forced air circulating blower (optional equipment).

b.Electronic Appliances – Field wire and install operating control switch.

Step 5. (Page 23) Install blower kit (optional equipment).

Step 6. (Page 24) Make connection to gas supply.

Step 7. (Page 25) Install the logs, decorative volcanic stone and glowing embers.

Step 8. (Page 26) Checkout appliance operation.

Step 9. (Page 29) Install glass door frame assembly.

Step 10. (Page 29) Adjust burner to ensure proper flame appearance.

Step 11. (Page 30) Install the hoods.

Step 1. Framing

Frame these appliances as illustrated in Figures 14 & 15 on Pages 9 & 10 (Figure 15 applies to corner framing installations only). All framing details must allow for a minimum clearance to combustible framing members as shown in

Table 8 on Page 7.

If the appliance is to be elevated above floor level, a solid continuous platform must be constructed.

Headers may be in direct contact with the appliance top spacers but must not be supported by them or notched to fit around them. All construction above the appliance must be self supporting. DO NOT use the appliance for structural support.

The fireplace should be secured to the side framing members using the unit's nailing flanges - one top and bottom on each side of the fireplace front. See Figure 12. Use 8d nails or their equivalent.

NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.

Side

Unit Nailing Flange

(No clearance to

Framing

combustible

 

framing is required)

Left Side Front Corner of Fireplace Shown

(Right Side Requirements the Same)

Unit Being Secured By Its Nailing Flanges

 

To The Framing

Note: The nailing flanges, combustible members

and screw heads located in areas directly adjacent

to the nailing flanges, are EXEMPT from the 1/2”

clearance to combustible requirements for the

firebox outer wrapper. Combustible framing may be

in direct contact with the nailing flanges and may

be located closer than 1/2” from screw heads and

the firebox wrapper in areas adjacent to the nailing

flanges. Frame the opening to the exact dimensions

specified in the framing details of this manual.

Figure 12

Step 2. Routing Gas Line

Route a 1/2" (13 mm) gas line along the inside of the right side framing as shown in Figure 13. Gas lines must be routed, constructed and made of materials that are in strict accordance with local codes and regulations. All appliances are factory-equipped with a flexible gas line connector and 1/2 inch shutoff valve. (See

Step 6 on Page 24 ).

Right Side Front Corner of Fireplace Framing

3"

6 1/2" (76 mm)

(152 mm) Also see Figure 14.

Figure 13 - ROUTE GAS LINE

Continued on Page 10.

fireplace specifications

 

 

 

 

 

 

 

 

 

 

 

 

 

Framing

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

**FRAMING WITH SQUARE HORIZONTAL TERMINATIONS (SV4.5HT-2)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Framing Dimensions

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

VENT FRAMING -

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

** Framing should be constructed

 

Model No.

 

 

 

 

 

 

 

 

A

 

 

 

 

 

 

 

B

 

 

C

 

D

 

 

 

 

E

 

 

 

 

 

TOP VENT WITH ONE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

of 2x4 or larger lumber

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

90ϒELBOW

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10-1/2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

in.

 

33-1/4

 

 

 

 

 

33-1/4

 

 

 

 

------

 

 

37-3/4

 

12-7/8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LMDVT-3328

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(267)

 

 

 

 

 

 

 

 

 

 

 

 

 

mm

 

845

 

 

 

 

 

845

 

 

 

 

 

------

 

 

959

 

327

 

 

 

 

VENT FRAMING -

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LMDVR-3328

 

 

in.

 

33-1/4

 

 

 

 

 

33-1/4

 

 

 

 

19-5/8

 

------

 

12-7/8

 

 

 

 

REAR VENT WITH

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

mm

 

845

 

 

 

 

 

845

 

 

 

 

 

498

 

 

------

 

327

 

 

 

 

NO ELBOWS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

7

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

in.

 

35-1/4

 

 

 

 

 

35-1/4

 

 

 

 

21-11/16

39-3/4

 

16

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LMDV-3530

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5-1/8

(178)

 

 

 

 

 

 

 

 

mm

 

895

 

 

 

 

 

895

 

 

 

 

 

551

 

 

1010

 

406

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

12-1/8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(130)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(308)

 

 

 

LMDV-4035

 

 

in.

 

40-1/4

 

 

 

 

 

40-1/4

 

 

 

 

26-11/16

44-3/4

 

16

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

mm

 

1022

 

 

 

 

 

1022

 

 

 

 

678

 

 

1137

 

406

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

7

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Efficiencies %

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Natural Gas

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Propane

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5-1/8

(178)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

D

 

 

 

 

 

 

 

 

 

12-1/8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(130)

 

 

 

 

 

 

 

 

Models

 

 

P4

 

 

Steady

 

 

AFUE

 

 

P4

 

Steady

 

 

AFUE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(308)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

State

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

State

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LMDVT-3328

 

 

 

 

 

 

45

 

 

64

 

 

 

 

 

 

62

 

 

 

 

 

 

49

 

 

 

66

 

64

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LMDVR-3328

 

 

 

 

 

 

53

 

 

63

 

 

 

 

 

 

61

 

 

 

 

 

 

55

 

 

 

66

 

64

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LMDV-3530

 

 

 

 

 

 

53

 

 

64

 

 

 

 

 

 

62

 

 

 

 

 

 

55

 

 

 

62

 

60

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

E

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LMDV-4035

 

 

 

 

 

 

59

 

 

69

 

 

 

 

 

 

67

 

 

 

 

 

 

60

 

 

 

69

 

67

 

 

 

 

 

 

1/2 A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Notes

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Input (BTU) - MV & Electronic

 

 

Inches (mm)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

* The Steady State Efficiency numbers based on

 

 

 

 

 

 

 

 

 

 

 

Natural & Propane Gas

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

maximum vent configuration.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

E is the required framing depth dimension when the

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Models

 

 

 

 

Input Rate (BTU / HR)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Due to Lennox' ongoing commitment to quality, all

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

finish material (drywall) thickness is 1/2 in. (13mm).

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

specifications, ratings and dimensions are subject

 

 

 

 

 

LMDVT-3328CPM

 

 

17,500

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

to change without notice.

 

 

 

 

 

 

 

 

 

 

 

 

 

LMDVR-3328CPM

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LMDV-3530CPM

 

 

20,000

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Vent Size

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Vertical Venting Through the Ceiling:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LMDV-4035CPM

 

 

27,000

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Co-axial DV

 

4-1/2" Inner

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Frame ceiling opening - Use a plumb line

 

Vent Size

/ 7-1/2" Outer

 

 

 

FRAMING SPACERS (Top & Sides & Rear)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

from the

ceiling above

the appliance to

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(Louvered Front Model Shown)

 

 

 

 

 

 

 

 

locate center of the vertical run. Cut and/or

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

G

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

**See Note 1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

frame an opening, 10-1/2" x 10-1/2" (267

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

H

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

mm x 267 mm) inside dimensions, about

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*CONCENTRIC FLUE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FLUE - 4-1/2 (114)

 

 

 

 

 

 

 

 

this center mark (see Figure 25).

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

COMBUSTION AIR - 7-1/2 (190)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

* LMDV models have a top and rear vent

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LMDVR models have only a rear vent

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LMDVT models have only a top vent

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

J

 

 

**Note 1 - Collars protrude one inch on LMDVR-3328 model.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Top View

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOTE - Eyebrow

 

 

 

 

 

 

N

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3 (76)

 

 

 

 

 

 

hood shown as positioned

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1/2 (13)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

E

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

in louvered front model.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ELECTRICAL INLET

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2-3/4 x 2 (70 x 51)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

COVER PLATE with

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

** See Note 1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

KNOCKOUT)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GAS INLET

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(Either Side

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6 (152)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

and bottom)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C

 

 

 

 

 

B

OPTIONAL ELECTRICAL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

L

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

INLET KNOCKOUT,

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1-5/8

 

F**

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

D

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

REQUIRING A FIELD

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PROVIDED JUNCTION BOX

1-3/8 (35)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(42)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(Either Side)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

M

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

K

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Front View

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Right Side View

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Model No.

 

 

 

 

 

 

 

 

A

 

B

 

C

 

D

 

 

E

 

**F

 

 

 

 

G

 

 

H

 

 

 

 

 

J

 

K

 

 

 

 

L

 

 

M

N

 

 

 

 

 

 

 

 

 

LMDVT-3328

in.

 

33 1/8

 

 

 

30 1/8

17

27 1/2

33 1/8

 

19 5/8

 

21 1/2

10 3/4

 

6 13/16

3

 

8 11/32

 

2 3/4

13

 

 

 

 

 

 

 

 

 

LMDVR-3328

 

mm

 

841

 

 

 

765

 

 

432

699

841

 

 

498

 

546

 

273

 

 

 

173

 

76

 

212

 

70

330

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LMDV-3530

 

in.

 

35 1/8

 

 

 

32 1/8

19

29 1/2

35 1/8

 

21 11/16

 

24 7/8

12 7/16

 

9

 

 

 

3

 

9

 

3

16

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

mm

 

892

 

 

 

816

 

 

483

749

892

 

 

551

 

632

 

316

 

 

 

220

 

76

 

220

 

76

406

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LMDV-4035

 

in.

 

40 1/8

 

 

 

37 1/8

24

34 1/2

40 1/8

 

26 11/16

 

29 7/8

14 15/16

 

9

 

 

 

3

 

9

 

3

16

 

Figure 14

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

mm

 

1019

 

 

 

943

 

 

610

876

1019

 

 

678

 

759

 

379

 

 

 

220

 

76

 

220

 

76

406

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

fireplace FRAMING specifications

Note-

Venting requirments for rear vent applications in corner installations -

• The horizontal vent length "a" to "b" must not exceed 28 inches (711 mm).

LMDVT-3328 and LMDVR-3328 Models -

Dimension A to F occur when one 45 degree elbow is connected directly to the appliance collar.

LMDVT-3530 and LMDVR-4035 Models -

Dimension D and F occur when one 45 degree elbow is connected directly to the appliance collar.

Model No.

 

 

A

B

C

 

D

E

 

F

 

 

 

 

 

 

 

 

 

 

 

LMDVT-3328

in.

33

1/8

48 1/2

34 5/16

17

3/16

241/4

 

5

LMDVR-3328

mm

841

1232

872

437

616

127

LMDV-3530

in.

35

1/8

57 1/2

40 5/8

19

3/16

28 3/4

6

1/8

 

 

 

 

 

 

 

mm

892

1461

1032

487

730

156

 

 

 

 

 

 

 

 

 

 

 

LMDV-4035

in.

40

1/8

6 13/16

43 11/32

19

3/16

30 11/16

7

7/8

 

 

 

 

 

 

 

mm

1019

1554

1101

487

779

200

b

LMDV and LMDVR units

F

7 1/4 (184)

 

 

LMDV and LMDVT units

 

Inches

 

 

(millimeters)

C

E

 

 

D

a

A

B

Back wall of chase/enclosure (including any finishing materials)

Figure 15 - Corner Framing with Square Termination (SV4.5HT-2)

Proper Sizing of Gas Line

Properly size and route the gas supply line from the supply regulator to the area where the appliance is to be installed per requirements outlined in the National Fuel Gas Code, NFPA 54 - latest edition (USA) or B149 - latest edition (Canada).

Never use galvanized or plastic pipe. Refer to Table 9 for proper sizing of the gas supply line, if black iron pipe is being used. Gas lines must be routed, constructed and made of materials that are in strict accordance with local codes and regulations. We recommend that a qualified individual such as a plumber or gas fitter be hired to correctly size and route the gas supply line to the appliance. Installing a gas supply line from the fuel supply to the appliance involves numerous considerations of materials, protection, sizing, locations, controls, pressure, sediment, and more. Certainly no one unfamiliar and unqualified should attempt sizing or installing gas piping.

Schedule 40

Black Iron Pipe

Inside Diameter (Inches)

Schedule 40 Pipe

Natural

Propane

Length (feet)

Gas

Gas

0-10

1/2

3/8

 

 

 

10-40

1/2

1/2

 

 

 

40-100

1/2

1/2

100-150

3/4

1/2

150-200

3/4

1/2

 

 

 

Table 9

Notes:

All appliances are factory-equipped with a flexible gas line connector and 1/2 inch shutoff valve (see Figure 48 on Page 24 ).

See Massachusetts Requirements on Page 4 for additional requirements for installations in the state of Massachusetts in the USA.

The gas supply line should Not be connected to the appliance until Step 6 (Page 24 ).

A pipe joint compound rated for gas should be used on the threaded joints. Ensure propane resistant compounds are used in propane applications. Be very careful that the pipe compound does not get inside the pipe.

It is recommended to install a sediment trap in the supply line as close as possible to the appliance (see Figure 48 ). Appliances using Propane should have a sediment trap at the base of the tank.

Check with local building official for local code requirements(i.e.arebelowgradepenetrations of the gas line allowed?, etc).

IMPORTANT: If propane is used, be aware that if tank size is too small (i.e. under 100-lbs, if this is the only gas appliance in the dwelling. Ref. NPFA 58), there may be loss of pressure, resulting in insufficient fuel delivery (which can result in sooting, severe delayed ignition or other malfunctions). Any damage resulting from an improper installation, such as this, is not covered under the limited warranty.

10

NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.

Step 3. Install the Vent System

General Information

These instructions should be used as a guideline and do not supersede local codes in any way. Install vent according to local codes, these instructions, the current National Fuel Gas Code (ANSI-Z223.1) in the USA or the current standards of CAN/CGA-B149.1 and -B149.2 in Canada.

Useonlyapprovedventingcomponents. See

Approved Vent Components on Page 2.

These fireplaces must be vented directly to the outside.

The vent system may not service multiple appliances, and must never be connected to a flue serving a solid fuel burning appliance. The vent pipe is tested to be run inside an enclosing wall (such as a chase). There is no requirement for inspection openings in the enclosing wall at any of the joints in the vent pipe.

Preparing the Appliance Vent Collar on LMDV-

3530/4035 Series (Combined Top and Rear

Vent) Models.

Each of the unit's two vent collars are sealed with a cover plate and a seal plate and gasket. The cover, and seal plate and gasket must be removed from the vent collar being used. Refer to Figure 16 for top vent usage and Figure 17 for rear, and the following steps to prepare the appropriate collar for use.

From the vent collar being used, remove the four screws securing the vent seal plate and gasket. Remove and discard the seal plate and gasket.

When the top vent collar is being used, from inside the firebox, loosen the two screws in the keyhole slots of the cover plate and remove the remaining two cover plate securing screws. Remove and discard the cover plate. Reinstall and securely tighten all four screws.

WARNING

Failure to reinstall and securely tighten cover plate screws could result in leakage of flue products into the living space. Vent cover plate and vent seal plate must remain securely installed on unused vent collar. Failure to do so could result in leakage of flue products into living space.

When the rear vent collar is being used, from inside the firebox, remove the two screws securing the lintel to the rear wall of the firebox, then remove the lintel. Remove the four cover plate securing screws.

Remove and discard the cover plate. Reinstall and securely tighten all four cover plate screws. Re-secure the lintel to the rear wall of the firebox.

On LMDV-3530/4035 Series Models (Combined Top And Rear Vent Units) Top Vent Seal & Cover Plate Removal When Using The Top Vent

(OUTSIDE of

Gasket Vent Seal Plate

Appliance)

Cabinet Top

Securing

Screws

 

 

Top Vent

Firebox Top

 

Vent Cover Plate

Cover Plate

 

Securing Screws

(Inside of Appliance)

CROSS SECTION

Figure 16

On LMDV-3530/4035 Series Models (Combined Top And Rear Vent Units)

Rear Vent Seal & Cover Plate Removal

When Using The Rear Vent

Cover Plate

Vent Seal Plate

Securing Screws

 

Gasket

(INSIDE of

 

Appliance)

Securing

 

Rear Vent

Screws

 

Lintel

 

Lintel

Cabinet

Securing

Back

Screws

(OUTSIDE of

CROSS SECTION

Appliance)

Figure 17

Installation of Vent Restrictor

A vent restrictor may be needed with this appliance, install vent restrictor (provided) in the appliance top flue outlet as shown in Figure 18

(LMDV-3328, LMDV-3530 and LMDV-4035) or rear flue outlet as shown in Figure 19 (LMDV3328, LMDV-3530 and LMDV-4035). It is held in place by friction, only.

NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.

Vent Restrictor Installation

(Top Vent)

A vent restrictor may be needed when vertically terminating the vent system above the roof (when using the appliance top vent), install vent restrictor in the top vent of the fireplace outlet on LMDV-3530/4035 and LMDVT-3328 series models. If needed, install the restrictor orientated as shown, either from inside or outside the unit,in the inner fireplace collar.

Restrictor

Inner

Fireplace

Collar Appliance Top

Vent Outlet

Figure 18

Vent Restrictor Installation

(Rear Vent)

A vent restrictor may be needed when horzontally terminating the vent system from the rear of the appliance (when using the appliance rear vent), install vent restrictor in the rear vent of the fireplace outlet on LMDV(R)-3328/3530/4035 series models, in any installation that has a vertical vent run in excess of three feet (0.914 meters).

If needed, install the restrictor orientated as shown, either from inside or outside the unit, in the inner fireplace collar

Inner Fireplace

Appliance Rear

Collar

Vent Outlet

 

 

Restrictor

Figure 19

Select Venting System - Horizontal or Vertical

With the appliance secured in framing, determine vent routing and identify the exterior termination location. The following sections describe vertical (roof) and horizontal (exterior wall) vent applications. Refer to the section relating to your installation. A list of approved venting components is shown on Pages 31 and 32.

11