Kutai electronics ATS-33 Operation Manual

Page 1
Headquarters : No.3, Ln. 201, Qianfu St., Qianzhen Dist., Kaohsiung City 80664, Taiwan
Tel : + 886-7-8121771 Fax : + 886-7-8121775 URL : http://www.kutai.com.tw
ATS-33 Ver1.3
Automatic Transfer Switch Control Unit
Operation Manual
Page 2
TABLE OF CONTENTS
Section Page
SECTOIN 1 : INTRODUCTION
1.1 Preliminary Comments And Safety Precautions ......................................................................................... 3
1.2 Product Overview........................................................................................................................................ 3
1.3 Functions / Features ................................................................................................................................... 3
SECTOIN 2 : OPERATOR PANEL
2.1 General ....................................................................................................................................................... 4
2.2 Display Window .......................................................................................................................................... 4
2.3 Operate Touch Buttons ............................................................................................................................... 5
2.4 Panel Led Outputs ...................................................................................................................................... 5
SECTOIN 3 : OPERATION
3.1 General ....................................................................................................................................................... 7
3.2 AUTO Mode ................................................................................................................................................ 7
3.3 OFF Mode ................................................................................................................................................... 7
3.4 Bypass Mode .............................................................................................................................................. 7
3.5 Programming Instruction ............................................................................................................................. 7
3.6 Remote Communication Instruction............................................................................................................ 8
3.7 Voltage Adjustment (If Needed) .................................................................................................................. 9
3.8 Line By Line Programming Table ............................................................................................................. 11
3.9 Specification Summary ............................................................................................................................. 12
SECTOIN 4 : INSTALLATION INSTRUCTIONS
4.1 General ..................................................................................................................................................... 12
4.2 Panel Cut-Out ......................................................................................................................................... 12
4.3 Unit Dimensions ...................................................................................................................................... 13
4.4 Installation Reference ............................................................................................................................... 13
SECTOIN 5 : TYPICAL WIRING
___________________________________________________________________________________________
2 ATS-33
Page 3
WARNING
High voltage will cause severe injury or death
SECTION 1 : INTRODUCTION
1.1 Preliminary Comments and Safety Precautions
This technical document is intended to cover most aspects related with the installation, operation and maintenance of the ATS-33 Automatic Transfer Switch Controller. This manual is for authorized and qualified personnel only.
1.2 Product Overview
The ATS-33 controller represents a state-of –the-art advancement in automatic transfer switch controls, where utility power is unavailable and generators must be in a constant operational state. The ATS-33 design is specifically tailored for the dual generator power system: a two-generator system, one primary generator and its back-up or stand-by generator. The ATS-33 controller manages the automatic start-up and transfer of load between the primary and stand-by generators, whether the power-loss is an unexpected event or scheduled. Additionally, the controller can be programmed to deliver a set operation duty cycle, which enables both the primary and stand by generators to operate in relay duty.
The ATS-33 Controller provides an unmatched degree of programmed flexibility. It provides all the necessary administration to ensure that the ATS switch operates properly through a series of programmed sensing and timing functions.
Controllers features
Microprocessor based with touch screen.
Smart touch screen (touch sensor) design.
Compact size with user-friendly LED display.
Programmable for cycle-mode or fix-mode displays
for 3-phase and 1-phase voltages and frequencies.
All programming and operations are done from the front screen interface.
Monitor both primary and stand-by generator for over and under voltages.
Monitor both primary and stand-by generator for over and under frequency.
Dry-contact alarm for transfer fail and over-cranking.
Manual force-bypass.
Compatible with almost all ATS switches.
Optional USB / RS485 / Ethernet remote (mobile
proxy) communication functions.
Program on-site or from remote (mobile) device (PC, Smart Phone).
Auto-saved settings (memory preserved throughout all power disconnects and resets).
Front panel display provides source status and fail alarm indications.
1.3 Functions / Features
The primary function of ATS-33 controller is to monitor power sources and provide the necessary intelligence to operate a seamless and automatic transfer of load between two generators.
1.3.1 Operational Simplicity
From installation to programming and to usage, the ATS-33 controller is designed with operational simplicity in mind. The user-friendly front panel interface simplifies routine operation, programming and setting adjustments.
1.3.2 Standard Features
All logic settings for different ATS’s are
preprogrammed and stored in its non-volatile random-access memory (NVRAM), this memory retains its information when power is turned off. Some features and set points are user adjustable.
___________________________________________________________________________________________
ATS-33 3
Page 4
Feature 1 : Generator Duty Cycle – start attempts settings
You can program the ATS-33 to switch the lead generator duty by time or start-run attempts. When the working generator times out, or runs a number of times the ATS-33 starts the next generator and makes this one the lead generator. (See lines 3 & 4)
Adjustable duty time range01 999 Hours.
Feature 2 : Transferring Time Delay
The ATS-33 control unit provides a time delay when transferring the switch from the primary to standby generator. Countdown begins when the standby source becomes available. (Refer to program line 5 & 6)
Adjustable time delay range00 250 sec
Feature 3 : Time Delay Engine Cool-down
Controller permits the generator to continue to run unloaded after retransfer to the other generator is complete. Countdown begins when the transferring is complete. (Refer to program line 7)
Adjustable time delay range00 250 sec
Feature 4 : Time Delay OFF Position
Time Delay on OFF keeps the switch in the center neutral OFF position (completely disengaged) before transferring to the other side. (Refer to program line 8)
Adjustable time delay range00 99 sec
Feature 5 : Under / Over voltage Sensing
The controller monitors the voltage of each phase of both generators’ power source. User adjustable settings are provided. (Refer to program line 9, 10, 11, 15, 16 & 17)
Adjustable over voltage range110 500 Vac Adjustable under voltage range80 470 Vac
Feature 6 : Under / Over frequency Sensing
The controller monitors the frequency of the normal and standby power source. User adjustable settings are provided. (Refer to program line 12, 13, 14, 18, 19 &
20) Adjustable over frequency range51 70 Hz
Adjustable under frequency range45 59 Hz
Feature 7 : Fail Alarm Output
There are three different abnormal statuses whereby the controller will setoff the dry contact alarm output. The auxiliary contact may be wired to a highly audible alarm panel to indicate a malfunction with the ATS system. The three abnormal statuses are
Send start signal failure / generator fails to start.
Transfer failure occurred.
Abnormal voltage and frequency during generator
duty time period.
SECTION 2 : OPERATOR PANEL
2.1 General
Get acquainted with the ATS-33
Front Display Window
Operate Touch Buttons
Panel LEDs Display
2.2 Display Window
The ATS-33 controller has a four-digit, seven-segment displayer to monitor all parameters, setting and messages.
The screen display’s
Dual generators voltage / Duty time / Parameter
display
Time delay countdown display
Program setting parameter display
___________________________________________________________________________________________
4 ATS-33
Page 5
ICON
DESCRIPTION
Increase / Selection Touch Button
Press to increase value
Press to select phase voltage
AUTO Touch Button
Press to engage AUTO
Press to reset alarm output
OFF Touch Button
Press to into OFF mode
Press to enter program mode
Bypass Touch Button
Press to force a transfer
Decrease / Selection Touch Button
Press to decrease value
Press for Volt / Duty / Freq display
WARNING
When any failure occurs at its duty time, the controller will shut down the engine, sound an alarm output and switch to the other generator. The failed engine will not start again unless the user manually resets the alarm output by touching the AUTO key.
LEDs status under Bypass mode
2.3 Operate Touch Buttons
The front panel employs five sensitive capacitive touch and release buttons.
Touch Buttons Reference Table
2.3.1 Increase (▲) Button
In AUTO, each touch of the up arrow (▲) changes the display to the next phase voltage reading.
However, when programming every touch of the up (▲) button increases the displayed parameter by a single unit. If held, the up (▲) button continues to scroll.
2.3.2 Decrease (▼) Button
Under AUTO operate status, each touch of the decrease (▼) button will change the real parameter display between voltage, duty time and frequency.
However, when programming every touch of the down
(▼) button decreases the displayed parameter by a single unit. If held, the down (▼) button continues to
scroll.
___________________________________________________________________________________________
ATS-33 5
2.3.3 Auto Button
When selecting the AUTO key, the ATS-33 runs in automatic mode lighting the corresponding LED to indicate the selection. The controller automatically starts the generator, transfer and retransfers from source to source as commanded by the features supplied and the preprogrammed setting.
In AUTO, all anomaly are accompanied by its matching alarm output make sure all failures are corrected before touching the auto key to reset the alarm signal.
2.3.4 Bypass Function Button
The Bypass button provides for a manual override of pre-programmed functions. When the ATS-33 is in AUTO, touching the Bypass key ignores the current timers and setting, and the controller will force-start the second generator and transfer the switch from the current working generator to the second generator. The Bypass function can be activated only in AUTO.
2.3.5 OFF Button
Touching the OFF key, turns the ATS-33 OFF engaging a flashing red LED instantly disabling all functions.
When in program mode, touching the off button allows the user to change the program line table and set the
desire parameter using decrease (▼) or increase (▲)
button.
2.4 Panel LED Outputs
Eight individual red and blue LEDs light bars perform or indicating each function.
Page 6
Power available display for G1 and G2
Generator-1 Over Voltage
Generator-1 Under Voltage
Generator-1 Over Frequency
Generator-1 Under Frequency
Generator-2 Over Voltage
Generator-2 Under Voltage
Generator-2 Over Frequency
Generator-2 Under Frequency
Generator-1 Transfer Failure
Generator-2 Transfer Failure
Generator-1 Fail to Start
Generator-2 Fail to Start
Information concerning the LEDs output
___________________________________________________________________________________________
6 ATS-33
Page 7
SECTION 3 : OPERATION
3.1 General
The five functions of the ATS-33
Automatic mode
OFF mode
Bypass mode
Programming mode
KCU-XX Remote Communication
The practical use of each operation under each category will be explained in this section. It is assumed that prior sections are understood, and the operator has a basic understanding of the hardware.
3.2 AUTO Mode
The AUTO mode of the ATS-33 controller provides for automatic start, transfer and retransfers from source to source as dictated by the programmed values.
The ATS-33 controller constantly monitors the condition of both generators’ power sources thus providing the required intelligence for transfer operations.
For example, the ATS-33 control unit automatically initiates a start and transfer of power when the working generator duty time countdown to zero or when power fails or voltage level drops below a preset value at its duty time. Exactly what the ATS-33 controller will initiate in response to a given system condition depends upon the combination of standard and selected optional features.
3.3 OFF Mode
In OFF the ATS-33 disables all the transfers and protection functions, the display window and all the LEDs are turned off.
Both remote start signals are also disabled in OFF and
the ATS can’t transfer the load to any source
automatically. However, when programming, the OFF button allows
you to move to the next program line and then change
the values for that line using down (▼) and up (▲)
buttons.
Controller Panel Lighting Test
This checks the LED lights. Press the OFF button, all panel LEDs must light up.
3.4 Bypass Mode
If the ATS-33 is running in AUTO, pressing the bypass button ignores its current duties and force starts the next generator, and transfer’s power from this generator to the other. If the second generator fail to start or its voltage and frequency does not become available, the controller keeps the load connected to the working generator and triggers an alarm.
Activate the Bypass only when in AUTO.
3.5 Programming Instruction
You program the ATS-33 from the front faceplate. To start, set the controller to OFF and press & hold the
OFF button for 4 seconds. The word “Vr1.0” appears
on the display for 2 seconds, showing the software version.
You are now ready to start the line-by-line programming sequence. Always press the OFF key to move to the next line. To change the parameter, on
each line use the up (▲) and down (▼) arrows. Repeatedly pressing the up (▲) or down (▼) key,
changes the displayed by one. To change faster, hold the buttons down.
Remember to always press the “OFF” button to move
to the next line or until the “End” appears on the screen. Note : To end and exit at any time, hold the “OFF” key down for 4 seconds.
If you make an error or need to return to factory settings, stay or reenter programming and then hold the AUTO keys down for 4 seconds, until the word
“Au.Po” appears on the screen verifying that all
programming lines are factory reset back like in the manual. (See line-by-line programming table for ATS-33 factory settings).
___________________________________________________________________________________________
ATS-33 7
Page 8
WARNING
A remote start signal can activate the ATS-33 and the engines can start at anytime without warning. Place a “Danger” warning sign next to the generator, stating that this generator can start at anytime! also install a warning buzzer or a flash light. Unexpected engine starts can result in serious injury or death. When performing service or maintenance, always disconnect the remote start signal input.
NOTE
ATS-33 with KCU-02 module constitutes a closed LAN network. Each controller address can be set from 1 to 99 and not to be repeated. Same transmission rate is a must !!
3.6 Remote Communication Instruction
You can monitor and control the two gen-set on a remote PC using the optional USB / RS485 / Ethernet remote communication modules.
If you have an Ethernet module installed on your ATS-33 you can remotely monitor and operate the ATS and generator using the IPhone and Android mobile phones. Free App software currently available for Apple iOS5.1 system or above and android operating system. Free software can be downloaded from App Store or Google Play by simply key in “Kutai” and hit search.
Free software can be downloaded from App Store or Google Play by simply key in “Kutai” and hit search.
You have the option of using one of these communications modules.
KCU-01 – USB communication module KCU-02 – RS-485 communications module KCU-03 – Ethernet communications module
The corresponding program settings for ATS-33 installed with KCU-XX module includes item (23), (24), (25) Programming item (23) is a must. When Item (23) is set to "00", then the remote monitoring software is restricted to read information only whereas remote command is strictly forbidden.
If KCU-02 - RS485 communication module is installed, additional program setting on lines (24) and (25) are needed.
For more detail, information refers to the KCU-XX manual.
The installation for the KCU-XX communication module on the ATS-33 controller is fairly simple.
Step 1Remove cover on the back of the ATS-33.
Step 2Plug in tighten the screw on the KCU-XX module to the ATS-33 PCB.
___________________________________________________________________________________________
8 ATS-33
Page 9
EX. Generator-1 Phase L12 Calibration
EX. Generator-2 Phase L23 Calibration
End Programming Display
Calibration Failure
3.7 Voltage Adjustment (If Needed)
The ATS-33 voltage readings are factory set and calibrated. However, if you need to modify any voltage reading, follow these steps.
Step 1 Manually start the primary and standby generators.
Step 2Enter Program mode and set the program item (22) to (01). “VAdJ” will appear on the display window.
Step 3Select the phase you wish to re-calibrate by pressing the OFF key.
Step 6Press the “OFF” button to move to the next
phase or until the word “End” appears on the screen.
To exit hold the “OFF” key at any time for 4 sec.
Step 7If you get “FAIL”, the calibration is null. Touch OFF to reset and repeat Step 1.
Step 4Use a good quality voltmeter as a reference to calibrate the ATS-33 voltage reading to the desired
phase. Step 5With the up (▲) and down (▼) buttons reset the
voltage reading on the ATS-33.
___________________________________________________________________________________________
ATS-33 9
Page 10
___________________________________________________________________________________________
10 ATS-33
Page 11
LINE
DESCRIPTION
VALUE
FACTORY
SETTING
1
Is this ATS operating in 1 phase or 3 phase?
00  1 Phase 01  3 Phase
01
2
Selected the Switch type of ATS
00) MCCB type ATS (Single motor)
01) Mot type ATS (Dual motors)
02) Air circuit breaker (ACB)
03) Double throw type (Single coil)
04) Double throw type (Dual coils)
05) Kutai TS-XXX type ATS
06) Magnetic contact type
00
3
Generator-1 duty time
01 999 Hours
12 Hr
4
Generator-2 duty time
01 999 Hours
12 Hr
5
Time delay Generator-1 to Generator-2
00 250 sec
5 sec
6
Time delay Generator-2 to Generator-1
00 250 sec
5 sec
7
Time delay engine cool-down
00 250 sec
15 sec
8
Time delay OFF position
00 99 sec
5 sec
9
Generator-1 over voltage setting
11 55 ( 110 550V )
25 (250V)
10
Generator-1 under voltage setting
08 47 ( 80 470V )
18 (180V)
11
Time delay if there is a problem with Generator-1 voltage output
00 99 sec ( 00 = Without voltage monitor function )
10 sec
12
Generator-1 over frequency setting
51 75 Hz
65 Hz
13
Generator-1 under frequency setting
45 59 Hz
55 Hz
14
Time delay if there is a problem with Generator-1 frequency output
00 99 sec ( 00 = Without frequency monitor function )
10 sec
15
Generator-2 over voltage setting
11 55 ( 110 550V )
25 (250V)
16
Generator-2 under voltage setting
8 47 ( 80 470V )
18 (180V)
17
Time delay if there is a problem with Generator-2 voltage output
00 99 sec ( 00 = Without voltage monitor function )
10 sec
18
Generator-2 over frequency setting
51 75 Hz
65 Hz
19
Generator-2 under frequency setting
45 59 Hz
55 Hz
20
Time delay if there is a problem with Generator-2 frequency output
00 99 sec ( 00 = Without frequency monitor function )
10 sec
21
Display mode setting
00 Cyclic mode 01 Fix mode
00
22
Do you want to adjust system voltage reading?
00  No 01  Yes
00
23
Enable remote control by KCU-XX Module
00  No 01  Yes
00
24
KCU-02 module address setting
00  None 01 99
00
25
KCU-02 Baud rate setting
01  115200 04  19200 07  4800 02  57600 05  14400 08  2400 03  38400 06  9600 09  1200
03
3.8 Line By Line Programming Table
___________________________________________________________________________________________
ATS-33 11
Page 12
DESCRIPTION
SPECIFICATION
DC Power Supply Voltage
8 60 Vdc
AC Voltage Measurement Range
50 510 Vac 50/60 Hz
Frequency Measurement Range
45 70 Hz
Remote Start Contact
7A @ 250 Vac Max
Generator-1 ON Contact
7A @ 250 Vac Max
Generator-2 ON Contact
7A @ 250 Vac Max
Alarm Output Contact
7A @ 250 Vac Max
Operating Temperature
-20 to +60 C
Storage Temperature
-30 to +80 C
Operating Humidity
Max. 90%
Weight
495 g +/- 2%
3.9 Specification Summary
SECTION 4: INSTALLATION INSTRUCTIONS
4.1 General
The ATS-33 controller has been designed for front panel mounting.
4.2 Panel Cut-Out ( All Dimensions in mm. )
___________________________________________________________________________________________
12 ATS-33
Page 13
Silicon waterproof seal
Panel Cut-out
A T S
Metal door
Fix bracket
Screw
Screw
Fix bracket
4.3 Unit Dimensions ( All Dimensions in mm. )
4.4 Installation Reference
___________________________________________________________________________________________
ATS-33 13
Page 14
#ELS>>Generator-2 Auxiliary Switch
#NLS>>Generator-1 Auxiliary Switch
ATS-33 Control Unit
L2
L1
N
L3
Genset-2
L3 NL1
LOAD
L2
MCCB TYPE BTS
L2
L1
N
L3
Genset-1
SECTION 5 : TYPICAL WIRING
5.1 MCCB Type ATS Wiring Diagram (3P/4P 220 Vac)
___________________________________________________________________________________________
14 ATS-33
Page 15
Genset-1
L1
L2
MCCB TYPE BTS
L2
LOAD
L1
Genset-2
L1
L2
ATS-33 Control Unit
#NLS>>Generator-1 Auxiliary Switch
#ELS>>Generator-2 Auxiliary Switch
5.2 MCCB Type ATS Wiring Diagram (2P 220 Vac)
___________________________________________________________________________________________
ATS-33 15
Page 16
#ELS>>Generator-2 Auxiliary Switch
#NLS>>Generator-1 Auxiliary Switch
ATS-33 Control Unit
MOT TYPE BTS
C(P1)
E-MOTOR UNIT
L1
NL2L3
A(On)B(Off)C(P1)
D(P2)
N-MOTOR UNIT
B(Off)
D(P2)
A(On)
L1
L3
L2
N
Genset-2Genset-1
L3 NL1
LOAD
L2
5.3 MOT Type ATS Wiring Diagram (3P/4P 220 Vac)
___________________________________________________________________________________________
16 ATS-33
Page 17
L2
LOAD
L1
Genset-1 Genset-2
L2
L1
A(On)
D(P2)
B(Off)
N-MOTOR UNIT
D(P2)
C(P1) B(Off) A(On)
L2
L1
E-MOTOR UNIT
C(P1)
MOT TYPE BTS
ATS-33 Control Unit
#NLS>>Generator-1 Auxiliary Switch
#ELS>>Generator-2 Auxiliary Switch
5.4 MOT Type ATS Wiring Diagram (2P 220 Vac)
___________________________________________________________________________________________
ATS-33 17
Page 18
ATS-33 Control Unit
L1
L2
N
L3
ACB TYPE BTS
L1
L3NL2
Genset-1
Genset-2
L3 NL1
LOAD
L2
MCH: Charging Alternator
MX1: Trip coil
XF : ON Coil
5.5 Air Circuit Breaker Type ATS Wiring Diagram (3P/4P 220 Vac)
___________________________________________________________________________________________
18 ATS-33
Page 19
XF : ON Coil
MX1: Trip coil
MCH: Charging Alternator
L2
LOAD
L1
Genset-2
Genset-1
L2
L1
ACB TYPE BTS
L2
L1
ATS-33 Control Unit
5.6 Air Circuit Breaker Type ATS Wiring Diagram (2P 220 Vac)
___________________________________________________________________________________________
ATS-33 19
Page 20
CS2
CS2
CS2
CS2
CS1
CS1
CS1
CS1
#ELS>>Generator-2 Auxiliary Switch
#NLS>>Generator-1 Auxiliary Switch
ATS-33 Control Unit
1 COIL DOUBLE THROW TYPE
L2L3L1
N
L3
N
L1
L2
L2
LOAD
L1 NL3
Genset-1
Genset-2
5.7 Single Coil Double Throw Type ATS Wiring Diagram (3P/4P 220 Vac)
___________________________________________________________________________________________
20 ATS-33
Page 21
CS2
CS2
CS1
CS1
Genset-2
Genset-1
L1
LOAD
L2
L2
L1L1
L2
1 COIL DOUBLE THROW TYPE
ATS-33 Control Unit
#NLS>>Generator-1 Auxiliary Switch
#ELS>>Generator-2 Auxiliary Switch
5.8 Single Coil Double Throw Type ATS Wiring Diagram (2P 220 Vac)
___________________________________________________________________________________________
ATS-33 21
Page 22
CS2
CS2
CS2
CS2
CS1
CS1
CS1
CS1
#ELS>>Generator-2 Auxiliary Switch
#NLS>>Generator-1 Auxiliary Switch
ATS-33 Control Unit
2 COILS DOUBLE THROW TYPE
L3
L2
L1
N
L2
L1
N
L3
L3 NL1
LOAD
L2
Genset-2
Genset-1
5.9 Dual Coil Double Throw Type ATS Wiring Diagram (3P/4P 220 Vac)
___________________________________________________________________________________________
22 ATS-33
Page 23
CS2
CS2CS1
CS1
Genset-1
Genset-2
L2
LOAD
L1
L1
L2
L1
L2
2 COILS DOUBLE THROW TYPE
ATS-33 Control Unit
#NLS>>Generator-1 Auxiliary Switch
#ELS>>Generator-2 Auxiliary Switch
5.10 Dual Coil Double Throw Type ATS Wiring Diagram (2P 220 Vac)
___________________________________________________________________________________________
ATS-33 23
Page 24
Genset-2
Genset-1
ATS-33 Control Unit
#NLS>>Generator-1 Auxiliary Switch
#ELS>>Generator-2 Auxiliary Switch
GREENCN1-5
BROWNCN1-1
N1
N3
N2
BLUE
PINK
WHITE
BLACK
NLS
CN1-9
ELS
CN1-11
CN1-6
CN1-10
RED
COIL
220V
CN1-2
CS1
CS1
CS1
CS2
CS2
CS2
GRAY
RED/WHITE
ORANGE
YELLOW
CN1-3
CN1-8
CN1-12
CN1-4
KUTAI TS3P125
E1
E3
E2
L2
LOAD
L1 L3
5.11 KUTAI TS-XXX Type ATS Wiring Diagram (3P/4P 220 Vac)
___________________________________________________________________________________________
24 ATS-33
Page 25
RED/WHITECN1-12
WHITECN1-9
Genset-2
Genset-1
CN1-4 YELLOW
L1
LOAD
L2
E2
E1
KUTAI TS2P125
CN1-3 ORANGE
CS2
CS2
CS1
CS1
CN1-2
220V
COIL
RED
CN1-10
CN1-6
CN1-11
ELSNLS
BLACK
PINK
BLUE
N2
N1
CN1-1 BROWN
#ELS>>Generator-2 Auxiliary Switch
#NLS>>Generator-1 Auxiliary Switch
ATS-33 Control Unit
5.12 KUTAI TS-XXX Type ATS Wiring Diagram (2P 220 Vac)
___________________________________________________________________________________________
ATS-33 25
Page 26
CS2
CS2
CS2
CS2
CS1
CS1
CS1
CS1
#ELS>>Generator-2 Auxiliary Switch
#NLS>>Generator-1 Auxiliary Switch
ATS-33 Control Unit
L1
L2
N
L3
L1
L3
L2
AICHI WN-TYS TYPE BTS
KME WN TYPE BTS
N
L2
LOAD
L1 NL3
Genset-1
Genset-2
5.13 KME WN Type and AICHI WN type ATS Wiring Diagram (3P/4P 220 Vac)
___________________________________________________________________________________________
26 ATS-33
Page 27
CS2
CS2CS1
CS1
#ELS>>Generator-2 Auxiliary Switch
#NLS>>Generator-1 Auxiliary Switch
L2
L1
Genset-2
L1
LOAD
L2
L2
L1
Genset-1
KME WN TYPE BTS
AICHI WN-TYS TYPE BTS
ATS-33 Control Unit
5.14 KME WN Type and AICHI WN type ATS Wiring Diagram (2P 220 Vac)
___________________________________________________________________________________________
ATS-33 27
Page 28
CS2
CS2
CS2
CS2
CS1
CS1
CS1
CS1
ATS-33 Control Unit
SOCOMEC ATyS-3S TYPE BTS
N
L2
L1
L3
L2
L1
L3
N
Genset-1
Genset-2
L3 NL1
LOAD
L2
5.15 SOCOMEC ATyS-3S type ATS Wiring Diagram (3P/4P 220 Vac)
___________________________________________________________________________________________
28 ATS-33
Page 29
CS2
CS2CS1
CS1
L2
LOAD
L1
Genset-2
Genset-1
L1
L2
L1
L2
SOCOMEC ATyS-3S TYPE BTS
ATS-33 Control Unit
5.16 SOCOMEC ATyS-3S type ATS Wiring Diagram (2P 220 Vac)
___________________________________________________________________________________________
ATS-33 29
Page 30
CS2
CS2
CS2
CS2CS1
CS1
CS1
CS1
ATS-33 Control Unit
L3
L2
L1
N
L3L1L2
N
Genset-1
Genset-2
L3 NL1
LOAD
L2
SOCOMEC ATyS-3e TYPE BTS
5.17 SOCOMEC ATyS-3e type ATS Wiring Diagram (3P/4P 220 Vac)
___________________________________________________________________________________________
30 ATS-33
Page 31
CS2
CS2CS1
CS1
SOCOMEC ATyS-3e TYPE BTS
L2
LOAD
L1
Genset-2
Genset-1
L2
L1
L1
L2
ATS-33 Control Unit
5.18 SOCOMEC ATyS-3e type ATS Wiring Diagram (2P 220 Vac)
___________________________________________________________________________________________
ATS-33 31
Page 32
CS2
CS2
CS2
CS2CS1
CS1
CS1
CS1
ATS-33 Control Unit
SOCOMEC ATyS-6 TYPE BTS
NL2L3
L1
L2
L3
N
L1
Genset-1
Genset-2
L3 NL1
LOAD
L2
5.19 SOCOMEC ATyS-6 type ATS Wiring Diagram (3P/4P 220 Vac)
___________________________________________________________________________________________
32 ATS-33
Page 33
CS2
CS2CS1
CS1
L2
LOAD
L1
Genset-2
Genset-1
L1
L2
L1
L2
SOCOMEC ATyS-6 TYPE BTS
ATS-33 Control Unit
5.20 SOCOMEC ATyS-6 type ATS Wiring Diagram (2P 220 Vac)
___________________________________________________________________________________________
ATS-33 33
Page 34
CS2
CS2
CS2
CS2CS1
CS1
CS1
CS1
ATS-33 Control Unit
SOCOMEC ATyS-6e TYPE BTS
L3
L2NL1
L2
N
L3
L1
Genset-1
Genset-2
L3 NL1
LOAD
L2
5.21 SOCOMEC ATyS-6e type ATS Wiring Diagram (3P/4P 220 Vac)
___________________________________________________________________________________________
34 ATS-33
Page 35
CS2
CS2CS1
CS1
L2
L1
L2
L1
Genset-1
Genset-2
L1
LOAD
L2
SOCOMEC ATyS-6e TYPE BTS
ATS-33 Control Unit
5.22 SOCOMEC ATyS-6e type ATS Wiring Diagram (2P 220 Vac)
___________________________________________________________________________________________
ATS-33 35
Page 36
#EAU>>Generator-2 Auxiliary Switch
#NAU>>Generator-1 Auxiliary Switch
ATS-33 Control Unit
L3
L2
L1
N
A2
N-MOTOR UNIT
C B
A1
A2B C
E-MOTOR UNIT
A1
MITSUBISHI MD TYPE BTS
L2
L1
N
L3
Genset-1
Genset-2
L3 NL1
LOAD
L2
5.23 MITSUBISHI MD type ATS Wiring Diagram (3P/4P 220 Vac)
___________________________________________________________________________________________
36 ATS-33
Page 37
L2
LOAD
L1
Genset-2
Genset-1
L1
L2
MITSUBISHI MD TYPE BTS
A1
E-MOTOR UNIT
CB A2
A1
BC
N-MOTOR UNIT
A2
L1
L2
ATS-33 Control Unit
#NAU>>Generator-1 Auxiliary Switch
#EAU>>Generator-2 Auxiliary Switch
5.24 MITSUBISHI MD type ATS Wiring Diagram (2P 220 Vac)
___________________________________________________________________________________________
ATS-33 37
Page 38
ATS-33 Control Unit
L1
N
L3
L2
MX1: Trip coil
XF : ON Coil
MG MCB TYPE BTS
MCH: Charging Alternator
L1
L2
L3
N
Genset-1
Genset-2
L3 NL1
LOAD
L2
5.25 MERLIN GERIN MCB type ATS Wiring Diagram (3P/4P 220 Vac)
___________________________________________________________________________________________
38 ATS-33
Page 39
L2
LOAD
L1
Genset-2
Genset-1
L2
L1
MCH: Charging Alternator
MG MCB TYPE BTS
XF : ON Coil
MX1: Trip coil
L2
L1
ATS-33 Control Unit
5.26 MERLIN GERIN MCB type ATS Wiring Diagram (2P 220 Vac)
___________________________________________________________________________________________
ATS-33 39
Page 40
MAGNETIC CONTACTOR TYPE
#ELS>>Generator-2 Auxiliary Switch
#NLS>>Generator-1 Auxiliary Switch
Genset-2
Genset-1
L3
L2
L1
N
L2
L1
N
L3
L3 NL1 L2
MC1
MC1
MC1
MC1
MC2
MC2
MC2
MC2
Note:Line-2 set to (06)
ATS-33 Control Unit
5.27 Magnetic Contact type ATS Wiring Diagram (3P/4P 220 Vac)
___________________________________________________________________________________________
40 ATS-33
Page 41
Genset-2
Genset-1
#NLS>>Generator-1 Auxiliary Switch
#ELS>>Generator-2 Auxiliary Switch
ATS-33 Control Unit
Note:Line-2 set to (06)
MC2
MC2
MC1
MC1
L2L1
L1
L2
L1
L2
MAGNETIC CONTACTOR TYPE
LOAD
5.28 Magnetic Contact type ATS Wiring Diagram (2P 220 Vac)
___________________________________________________________________________________________
ATS-33 41
Page 42
For AC380/440/480V SystemFor AC220V System
220V
380/440/480V
5.29 System Voltage different From AC220V wiring Diagram
___________________________________________________________________________________________
42 ATS-33