KSB LevelControl Basic 2 Supplementary Operating Manual

Page 1
Level Control Unit
LevelControl Basic 2
Signalling Module Current Measuring Module
Supplementary Operating Manual
Page 2
Supplementary Operating Manual LevelControl Basic 2
Original operating manual
All rights reserved. The contents provided herein must neither be distributed, copied, reproduced, edited or processed for any other purpose, nor otherwise transmitted, published or made available to a third party without the manufacturer's express written consent.
Subject to technical modification without prior notice.
© KSB SE & Co. KGaA, Frankenthal 19/01/2018
Page 3
Contents
3 of 40
LevelControl Basic 2
Contents
1 General.................................................................................................................................................... 4
2 Safety...................................................................................................................................................... 5
2.1 General..............................................................................................................................................................5
3 Transport/Temporary Storage/Disposal............................................................................................... 6
3.1 Condition upon delivery ..................................................................................................................................6
3.2 Transport...........................................................................................................................................................6
3.3 Storage..............................................................................................................................................................6
4 Description ............................................................................................................................................. 7
4.1 Compatibility ....................................................................................................................................................7
4.2 General description ..........................................................................................................................................7
4.3 Technical data...................................................................................................................................................9
5 Installation at Site................................................................................................................................ 11
5.1 Connecting the signalling module ................................................................................................................11
5.2 Connecting the current measuring module..................................................................................................13
6 Commissioning/Start-up/Shutdown................................................................................................... 15
6.1 Commissioning/start-up .................................................................................................................................15
6.2 Shutdown........................................................................................................................................................15
7 Operation.............................................................................................................................................. 17
7.1 Extensions with signalling/current measuring module................................................................................17
7.1.1 Menu extension .................................................................................................................................17
7.1.2 Additional functions ..........................................................................................................................17
8 Servicing/Maintenance........................................................................................................................ 28
8.1 Maintenance/inspection measures ................................................................................................................28
9 Trouble-shooting.................................................................................................................................. 29
10 Related Documents.............................................................................................................................. 30
10.1 Wiring diagram/terminal diagram ................................................................................................................30
10.1.1 Individual signals - control board display (example) ....................................................................... 30
10.1.2 Analog output....................................................................................................................................30
10.1.3 Three-phase current measurement...................................................................................................31
10.1.4 Single-phase current measurement ..................................................................................................32
10.1.5 Field bus connection ..........................................................................................................................32
10.1.6 Redundant pneumatic level measurement ...................................................................................... 33
10.1.7 Partially redundant bubbler system..................................................................................................35
Index ..................................................................................................................................................... 37
Page 4
1 General
4 of 40
LevelControl Basic 2
1 General
This supplementary operating manual accompanies the installation/operating manual. All information contained in the installation/operating manual must be observed.
Table1: Relevant operating manuals
Type series Reference number of the installation/operating
manual
LevelControl Basic 2 4041.80
Page 5
2 Safety
5 of 40
LevelControl Basic 2
2 Safety
2.1 General
This supplementary operating manual contains additional applicable information. General installation, operating and maintenance instructions that must be observed to ensure safe operation and prevent personal injury and damage to property are given in the installation/operating manual.
The safety information in all sections of this supplementary operating manual and in the relevant installation/operating manual must be complied with.
The supplementary operating manual must be read and completely understood by the responsible specialist personnel/operators.
The contents of this supplementary operating manual must be available to the specialist personnel at the site at all times.
The operator is responsible for ensuring compliance with all local regulations which are not taken into account in this supplementary operating manual.
Page 6
3 Transport/Temporary Storage/Disposal
6 of 40
LevelControl Basic 2
3 Transport/Temporary Storage/Disposal
3.1 Condition upon delivery
NOTE
Prior to shipping, the accessories were tested to ensure full compliance with the specifications. They should, therefore, be in perfect electrical and mechanical condition upon arrival. It is recommended that the accessories be inspected for in-transit damage immediately upon receipt. If there are any complaints or objections, the recipient and carrier must jointly draw up a damage report.
3.2 Transport
CAUTION
Improper transport
Damage to the accessories!
Always transport the accessories properly and in their original packaging.
During transport, observe the transport instructions on the original packaging.
Transport the accessories as specified.
3.3 Storage
If the ambient conditions for storage are met, the accessories will give reliable service even after a prolonged period of storage.
Table2: Ambient conditions for storage
Ambient conditions Value
Relative humidity Max. 85% (no condensation)
Ambient temperature - 10°C to +70°C
Store the accessories in dry, vibration-free conditions and, if possible, in their
original packaging.
Store the accessories in a dry room in which the atmospheric humidity is
maintained at a constant level (as far as this is possible).
Prevent excessive fluctuations in atmospheric humidity (see table "Ambient
conditions for storage").
If stored properly, the accessories will be protected for a maximum of 12 months.
Page 7
4 Description
7 of 40
LevelControl Basic 2
4 Description
4.1 Compatibility
NOTE
The KSB Service Tool can be downloaded free-of-charge from the KSB web site. The web site also contains further information on how to order the additional parameterisation cable required.
Signalling module and current measuring module can be used with device firmware version 1.2 or higher. Devices with earlier firmware versions must be updated using the KSB Service Tool.
4.2 General description
Signalling module
The signalling module is an extension module for LevelControl Basic 2. It features:
Six volt-free signals:
Fault at pump 1
Fault at pump 2
High water
Sensor fault
Pump 1 in operation (not available for lifting units with single-phase motor
and cutter)
– Pump 2 in operation (not available for lifting units with single-phase motor
and cutter)
Analog output (level-proportional current signal, type 4–20 mA)
ModBus RTU interface (direct connection or field bus module connection)
System bus interface (currently no function)
Connection option for one current measuring module per pump
Depending on the version, the device is fitted with a pressure sensor for
redundant pneumatic level measurement (without compressor) or for setting up a partially redundant bubbler system
NOTE
The assignment of the volt-free signals and the measured values provided via the analog output can be modified using the ServiceTool.
Page 8
4 Description
8 of 40
LevelControl Basic 2
Fig.1: Description of signalling module
1 Service interface (for production only -
parameterisation takes place via the service interface on the LevelControl Basic2 printed circuit board)
2 Power supply for PCB (optional, 9–30 V)
3 Current measuring module connection, pump 2 4 Current measuring module connection, pump 1
5 Signalling module connection to LevelControl
Basic 2
6 Analog output (4–20 mA)
7 ModBus-RTU connection 8 system bus connection (no function)
9 Volt-free signal 1 (default: Pump 1 fault) 10 Volt-free signal 2 (default: Pump 2 fault)
11 Volt-free signal 3 (default: High water) 12 Volt-free signal 4 (default: External fault)
13 Volt-free signal 5 (default: Pump 1 in operation) 14 Volt-free signal 6 (default: Pump 2 in operation)
15 Redundant pressure sensor 16 Status LED
17 Terminating resistors for ModBus RTU and system
bus connection
Current measuring module
The current measuring module measures the pump current in the motor power cable in the control unit. Up to 10 A, the pump current is measured directly, over 10 A, it is measured via an upstream current transformer. The current measuring module is connected to LevelControl Basic 2 via the signalling module.
Page 9
4 Description
9 of 40
LevelControl Basic 2
Fig.2: Description of current measuring module
1 Phase L2 2 Phase L3
3 Connection to signalling module
NOTE
The current measuring module measures the currents in phases L2 and L3 (three­phase motor) or L (single-phase motor) of the connected pumps.
(ðSection10.1,Page30)
4.3 Technical data
Signalling module
Table3: Technical data
Characteristic Value
Power supply 9–30 V DC
via LevelControl Basic 2
Enclosure BC version: IP00
BS version: IP20
Switching capacity of individual signals 30 V, 1 A
Analog output 0/4-20 mA
Housing version BC version: without housing
BS version: top hat rail housing
Page 10
4 Description
10 of 40
LevelControl Basic 2
Characteristic Value
Design variants Signalling module
Signalling module with pressure sensor, 3mlc Signalling module with pressure sensor, 10 mlc
Weight 0.3 kg
NOTE
The signalling module can be used with device firmware version 1.2 or higher.
Current measuring module
NOTE
LevelControl Basic 2 is only fitted with current measuring module(s) ex works. Current measuring modules cannot be retrofitted!
The current measuring modules are connected to LevelControl Basic 2 via the signalling module. This means that the current measuring module can be used only in combination with the signalling module!
Table4: Technical data
Characteristic Value
Power supply Supply via signalling module
Enclosure IP20
Maximum supply voltage 500 V AC
Measuring range 10 (15) A
1)
Measuring ranges for indirect measurement via transformer
10 to 20 A (30 A) 20 to 40 A (60 A) 40 to 75 A (110 A)
2)
Weight 0.2 kg
NOTE
The current measuring module can be used with device firmware version 1.2 or higher.
NOTE
One current measuring module is required for each pump. For dual-pump control, the signalling module offers connection options for two current measuring modules.
1) Larger currents can be measured via upstream transformers
2) Measurement of larger currents possible on request
Page 11
5 Installation at Site
11 of 40
LevelControl Basic 2
5 Installation at Site
5.1 Connecting the signalling module
DANGER
Exposed live parts
Danger of death from electric shock!
Separate the control unit from the power supply before installing the signalling
module.
CAUTION
Improper handling of the control unit and its built-in components
Defective control unit!
Handle the control unit and its built-in components carefully.
CAUTION
Incorrect handling of the rechargeable battery
Electrical damage to the control unit!
If the battery installation option is used, disconnect one of the battery's
connectors before connecting the signalling module. This ensures that the control unit is completely de-energised.
Do not re-connect the battery connector until the connection has been made.
BC version
Fig.3: Position of signalling module in BC version
ü The place of installation conforms to the requirements.
1. Separate the control unit from the power supply and verify that it is de-
energised.
2. Open the control unit using a suitable tool.
3. Carefully detach the BC PCB cover plate from the spacers.
4. Connect the signalling module to the BC PCB using the connection cable
supplied. Make sure the connector is correctly positioned! When attaching the connection cable, observe the mechanical coding on the connectors!
Page 12
5 Installation at Site
12 of 40
LevelControl Basic 2
(The connector has a pin that has to engage in the hole in the PCB next to the PCB-side connector.)
5. Snap the signalling module for the BC version onto the spacers and check that it
is firmly seated.
6. Close the control unit again properly.
7. Reconnect the power supply.
When the device is switched on, the green status LED on the signalling module lights up continuously. This means that the signalling module is functioning correctly. If the green status LED on the signalling module does not illuminate, the correct seating of the cable connecting the signalling module and the LevelControl Basic 2 PCB must be checked again. If the green status LED on the signalling module flashes, the signalling module has not been detected by LevelControl Basic 2. In this case, check the firmware version of the control unit, which is displayed at parameter 4-1-1. Firmware version 1.2 or higher is required.
NOTE
To set up a redundant pneumatic level measurement system, observe (ðSection10.1.6,Page33) .
To set up a partially redundant bubbler system, observe (ðSection10.1.7,Page35) .
Page 13
5 Installation at Site
13 of 40
LevelControl Basic 2
BS version
Fig.4: Position of signalling module in BS version
ü The place of installation conforms to the requirements.
1. Separate the control unit from the power supply and verify that it is de-
energised.
2. Open the control unit.
3. Snap the signalling module for the BS version onto a free top hat rail slot and
check that it is firmly seated.
4. Connect the signalling module to the BS PCB using the connection cable
supplied. Make sure the connector is correctly positioned! When attaching the connection cable, observe the mechanical coding on the connectors! (The connector has a pin that has to engage in the hole in the PCB next to the PCB-side connector.)
5. Close the control unit again properly.
6. Reconnect the power supply.
When the device is switched on, the green status LED on the signalling module lights up continuously. This means the signalling module is functioning correctly. If the green status LED on the signalling module does not illuminate, the correct seating of the cable connecting the signalling module and the LevelControl Basic 2 PCB must be checked again. If the green status LED on the signalling module flashes, the signalling module has not been detected by LevelControl Basic 2. In this case, check the firmware version of the control unit, which is displayed at parameter 4-1-1. Firmware version 1.2 or higher is required.
NOTE
To set up a redundant pneumatic level measurement system, observe (ðSection10.1.6,Page33) .
To set up a partially redundant bubbler system, observe (ðSection10.1.7,Page35) .
5.2 Connecting the current measuring module
NOTE
LevelControl Basic 2 is only fitted with current measuring module(s) ex works. Current measuring modules cannot be retrofitted!
Page 14
5 Installation at Site
14 of 40
LevelControl Basic 2
Connect the current measuring module in accordance with the wiring diagram. (ðSection10.1.3,Page31) / (ðSection10.1.4,Page32)
Page 15
6 Commissioning/Start-up/Shutdown
15 of 40
LevelControl Basic 2
6 Commissioning/Start-up/Shutdown
6.1 Commissioning/start-up
ü The supplementary operating manual and the installation/operating manual
have been read.
ü The device variant conforms to the requirements.
ü The control unit has been assembled as per operating instructions and connected
to the power supply in accordance with the wiring diagram.
ü The signalling module has been installed as per operating instructions
Section5.1,Page11) and connected in accordance with the terminal diagram.
ü The current measuring module has been installed as per operating instructions
and connected in accordance with the terminal diagram.
1. Re-tighten the connection terminals (individual signals, analog output, field bus
connection and current measuring modules).
2. Connect the power cable.
3. Connect the sensors.
4. Insert the motor protection device and fuses.
5. Set the manual-0-automatic switches for both pumps to "0".
6. Switch on the power supply.
7. Check that the green status LED is continuously ON.
8. Check that the parameters are set as required and adapt if necessary.
9. Carry out test run for several start/stop cycles.
10. Check alarm devices, including the individual signals, for proper function.
11. Set the manual-0-automatic switches for both pumps to "Automatic".
ð Both pumps can now be started/stopped by the control unit as required.
12. Provide support and/or training for operating personnel.
13. File a copy of the supplementary operating manual with the installation/
operating manual.
6.2 Shutdown
Short-term shutdown
1. Set the manual-0-automatic switches for both pumps to "0".
ð Both pumps are switched off.
ð The control unit remains operational.
Short-term shutdown for work on the pump
1. Set the manual-0-automatic switches for both pumps to "0".
ð Both pumps are switched off.
ð The control unit remains operational.
2. Open the control unit.
3. For 400V variants:
Switch off motor protection switch for both pumps and secure to prevent restart. For 230V variants: Pull pump mains plug. If the pumps are connected directly to the terminals in the device, the device must be disconnected from the power supply.
4. Close the control unit again.
Long-term shutdown
1. Set the manual-0-automatic switches for both pumps to "0".
2. Switch off the power supply.
Page 16
6 Commissioning/Start-up/Shutdown
16 of 40
LevelControl Basic 2
ð This disables all control and signalling functions.
Page 17
7 Operation
17 of 40
LevelControl Basic 2
7 Operation
7.1 Extensions with signalling/current measuring module
NOTE
Additional parameters available are documented on the enclosed parameter label.
If signalling module and, where applicable, current measuring module are installed, additional parameters appear in the display. These can be selected as usual using the arrow keys. The selectable parameters depend on the operating mode and measurement method. Only parameters that are relevant to the current operating mode and measurement method are displayed.
7.1.1 Menu extension
7.1.1.1 Measured values menu
If the signalling module and current measuring module are used, parameters indicating the current values for each pump are added to the measured values menu.
Table5: Additional parameters in measured values menu
Parameter Description Single-
pump
station
Dual-
pump
station
1-2-3 Current, pump 1 Current of pump 1 in ampere x -
1-3-3 Current, pump 2 Current of pump 2 in ampere x x
7.1.1.2 Settings menu
If a signalling module with redundant pressure measurement is used, the parameter indicating the installation height of the second open or closed pressure bell is added to the settings menu. (ðSection10.1.6,Page33)
Table6: Additional parameter in settings menu
Parameter Description Values
3-4-5-1 Level of bell 2 Distance of the second pressure bell (lower
edge) from the bottom of the tank (offset). Factory setting: 200 mm
200 mm (factory setting)
7.1.1.3 Signalling module fault
If a fault occurs at the signalling module during operation, this is indicated by fault ­A17 - in the display.
Table7: Signalling module fault message
Message Description
- A17 - Signalling module fault
7.1.2 Additional functions
7.1.2.1 Volt-free signals
If the signalling module is used, six volt-free signals are provided:
Switching capacity: 30 V, 1 A
Type: Change-over contact.
Page 18
7 Operation
18 of 40
LevelControl Basic 2
The signal relays are energised in the good or idle state and de-energise in the event of a signal.
Table8: Volt-free signals
Volt-free signal Standard assignment Description Signal status
Signal relay 1 Fault pump 1 Pump 1 is blocked due to a fault and
cannot be started upon demand.
de-energised
Signal relay 2 Fault pump 2 Pump 2 is blocked due to a fault and
cannot be started upon demand.
de-energised
Signal relay 3 High water (A9) The high water switching point has been
reached
de-energised
Signal relay 4 Sensor fault (A11) Fault of the level measurement sensors
used
de-energised
Signal relay 5 Pump 1 in operation Pump 1 running energised
Signal relay 6 Pump 2 in operation Pump 2 running energised
The state of the signal relays is also indicated by the yellow LEDs positioned above the relays on the PCB. An illuminated LED indicates an energised relay.
NOTE
In the case of lifting units with single-phase motor and cutter, signal relays 5 and 6 are used to control the start capacitors required for operation and are not available for volt-free signals.
NOTE
For single-pump systems, the signal relays normally assigned with signals for pump 2 do not carry any standard settings. These can be assigned using the ServiceTool.
The signal relays can be assigned with the following functions using the ServiceTool:
Table9: Assignment of the signal relay
Signal Description Signal status
Message A1 Motor protection pump 1 (winding protection or motor
protection switch tripped)
de-energised
Message A2 Motor protection pump 2 (winding protection or motor
protection switch tripped)
de-energised
Message A3 Motor 1 temperature too high de-energised
Message A4 Motor 2 temperature too high de-energised
Message A5 Power failure de-energised
Message A6 Phase error (phase failure) de-energised
Message A7 Leakage at motor 1 de-energised
Message A8 Leakage at motor 2 de-energised
Message A9 High water alert de-energised
Message A10 External alarm de-energised
Message A11 Sensor fault de-energised
Message A12 Incorrect rotary field of mains supply (phase sequence) de-energised
Message A13 Undervoltage (-15 % of rated voltage) de-energised
Message A14 Overvoltage (+15 % of rated voltage) de-energised
Message A15 Flat battery de-energised
Message A16 Service interval (activation via parameter 3-7-1) de-energised
Fault pump 1 Pump 1 is blocked due to a fault and cannot be started upon
demand.
de-energised
Fault pump 2 Pump 2 is blocked due to a fault and cannot be started upon
demand.
de-energised
Pump 1 operational No fault at pump 1, the manual-0-automatic switch is in "Auto"
position
energised
Page 19
7 Operation
19 of 40
LevelControl Basic 2
Signal Description Signal status
Pump 2 operational No fault at pump 2, the manual-0-automatic switch is in "Auto"
position
energised
Pump 1 in operation Pump 1 running energised
Pump 2 in operation Pump 2 running energised
Pump 1 in automatic mode
Manual-0-automatic switch of pump 1 in "Auto" position energised
Pump 2 in automatic mode
Manual-0-automatic switch of pump 2 in "Auto" position energised
Check run pump 1 Check run of pump 1 in progress energised
Check run pump 2 Check run of pump 2 in progress energised
7.1.2.2 Analog output
The signal module offers an analog output with the following specifications:
Table10: Analog output specifications
Specification Value
Type 0/4–20 mA
External working resistance Mains operation: max. 500 Ω
Battery operation: max. 300 Ω
The analog output signals the measured fill level as standard. The analog output can optionally be assigned with the following values using the ServiceTool:
Table11: Analog output assignment
Parameter Value Display
Level
(ðSection7.1.2.2.1,Pag e19) to (ðSection7.1.2.2.4,Pag e22)
1-1-3 Mains voltage of the system 0 mA = fault
4 mA 180 V 20 mA 500 V
None System current
- single-pump: current of pump1
- dual-pump: current of pumps1+2
0 mA = fault 4 mA 0 A 20 mA 30 A
NOTE
For current measurement > 10 (15) A, please note the following transformer factors: 10–20 (40) A: 4 mA 0 A, 20 mA 40 A 20–40 (60) A: 4 mA 0 A, 20 mA 60 A 40–75 (110) A: 4 mA 0 A, 20 mA 110 A
7.1.2.2.1 Level measurement using float switches or digital sensors
When digital level measuring methods are employed (floats, digital switches), a step signal corresponding to the switching status is displayed. The allocation of the switching states is shown in the table below:
Page 20
7 Operation
20 of 40
LevelControl Basic 2
Table12: Allocation of switching states for level measurement with float switches or digital sensors
Display Level Analog signal Switching state
When draining When filling
Sensor fault 0 mA - -
Very low 4 mA Pumps OFF Peak load pump ON
Low 7 mA Peak load pump OFF
(irrelevant)
Base load pump ON
Medium 10 mA - -
High 13 mA Base load pump ON Peak load pump OFF
(irrelevant)
Page 21
7 Operation
21 of 40
LevelControl Basic 2
Display Level Analog signal Switching state
When draining When filling
Very high 16 mA Peak load pump ON Pumps OFF
High water 20 mA All pumps ON All pumps OFF
NOTE
If sensor fault and high water are present at the same time, the high water level is output in accordance with the priority of the pending faults.
7.1.2.2.2 Level measurement using an analog sensor
If a 4–20 mA analog sensor is used for level measurement, the input signal of the sensor is duplicated.
Fig.5: Level measurement with analog sensor
1 0 mA = fault
A sensor signal of between 0 and 3.6 mA indicates a broken wire, and sensor fault ­A11- is output.
7.1.2.2.3 Level measurement using a bubbler system or pneumatic measurement
If pneumatic measurement (without compressor) or a bubbler system is used for level measurement, the analog output provides a level-proportional current signal, i.e. the measured value is converted into an output current from 4 to 20 mA, depending on the measuring range of the pressure sensor used in the signalling module.
Page 22
7 Operation
22 of 40
LevelControl Basic 2
If a control unit with pressure sensor for up to 3 metres of water is used, the fill level in the range of 0–4 mlc is converted into a signal of 4 to 20 mA.
Fig.6: Pneumatic measurement up to 3 mlc
1 0 mA = fault
If a control unit with pressure sensor for up to 10 mlc is used, the fill level in the range of 0–12 mlc is converted into a signal of 4 to 20 mA.
Fig.7: Pneumatic measurement up to 10 mlc
1 0 mA = fault
If there is a sensor fault, it will always be indicated by 0 mA at the analog output.
7.1.2.2.4 Level measurement for lifting units
On control units for lifting units of the MiniCompacta/Compacta series, the analog output provides a level-proportional current signal, i.e. the values measured in the range of 0 to 1 mlc are converted into output currents from 4 to 20 mA, regardless of any settings made.
Page 23
7 Operation
23 of 40
LevelControl Basic 2
Fig.8: Level measurement for lifting units
1 0 mA = fault
If there is a sensor fault, it will always be indicated by 0 mA at the analog output.
7.1.2.2.5 Level measurement using a partially redundant bubbler system or redundant pneumatic measurement
NOTE
To set up a redundant pneumatic level measurement system or a partially redundant bubbler system, a signalling module with pressure sensor is required.
NOTE
Redundant arrangement of the sensors enables redundant minimum level monitoring as stipulated by the Atex directives.
NOTE
If the power supply fails and the unit is operated on battery power, level measurement will be non-redundant. The redundant pressure sensor is deactivated during battery operation.
NOTE
To set up a redundant pneumatic level measurement system or a redundant bubbler system, observe the wiring diagram/terminal diagram.
(ðSection10.1,Page30)
The signalling module provides the option of setting up a redundant pneumatic level measurement system or partially redundant bubbler system. If a redundant level measurement system is used, the mean value of the two measured values is used for level measurement and pump control. In the event of a fault in one of the two level measurement systems,
for non-Atex applications (3-6-1 Atex-Mode = "0", deactivated), the higher of the
measured values is used for controlling the pumps
for Atex applications (3-6-1 Atex-Mode = "1", activated), the higher of the
measured values is used as long as at least one of the two level measurement systems ensures sufficient submergence of the pump.
If a pump that represents a potential ignition source in a potentially explosive atmosphere can no longer be guaranteed to be sufficiently submerged, all running pumps will be stopped. In the event of a fault, message "A11 – Sensor fault" is output.
Page 24
7 Operation
24 of 40
LevelControl Basic 2
7.1.2.3 Field bus connection
The extension module for LevelControl Basic 2 offers a Modbus-(RTU) interface which is galvanically isolated from the control unit. The ModBus interface can be used directly for integration into a ModBus network and provides the option of connecting corresponding field bus gateways. The ModBus interface is implemented as a RS485 interface with ModBus-(RTU) protocol in accordance with Specification v1.1b.
Table13: Characteristics of the field bus connection
Characteristic Description/value
Communication protocol Modbus-RTU
Bus terminator 220 Ω (fixed, implemented internally, switchable)
Interface EIA-485 (RS485)
Transmission rate 38400 bit/s (adjustable)
Data bits 8
Parity Even
Stop bits 1
Device type Slave
Bus access Polling between master and slave
Pre-set device address 0xF7 (247)
7.1.2.3.1 Measured values and parameters
Various measured values and parameters are provided as device information via the field bus system. They can be accessed with function code 03 (read holding registers). Modbus-RTU only uses 16-bit coils. For values logged as 32-bit numbers, two coils therefore need to be read out. To show numerals after the decimal point, the read value is to be moved to the right by the number of decimal places illustrated under "Type/Format". Function code, coil and length are shown as hexadecimals and can be transferred directly to the Modbus-RTU protocol in this format.
Table14: Measured values and parameters
Function
code
Coil Length Type/Format Parameter Designation Description
03 00 01 00 01 16 Bit
"signed"
#
1-1-1 Level
(analog)
Displays the level in mm (analog level measurement)
03 00 02 00 01 16 Bit
"signed"
#
1-1-2 Level
(digital)
Displays the level as status diagram (digital measurement)
03 00 03 00 01 16 Bit
"signed"
#
1-1-3 Line Voltage Displays the mains voltage in
volts
03 00 04 00 01 16 Bit
"signed"
# ,#
1-1-4 Battery Voltage Displays the battery voltage
in volts
03 00 05 00 02 32 Bit
"unsigned"
#
1-1-5 System Operating
Hours
Operating hours of the
system
03 00 07 00 02 32 Bit
"unsigned"
#
1-2-1 Operating Hours
Pump 1
Operating hours of pump 1
03 00 09 00 02 32 Bit
"unsigned"
#
1-2-2 Start Count Pump 1 Number of start-ups of pump
1
03 00 0b 00 02 32 Bit
"unsigned"
# ,0
1-2-3 Current Pump 1 Current of pump 1
Page 25
7 Operation
25 of 40
LevelControl Basic 2
Function
code
Coil Length Type/Format Parameter Designation Description
03 00 0d 00 02 32 Bit
"unsigned"
# ,###
1-2-4 Effective Power
Pump 1
Effective power of pump 1 in kW
03 00 0f 00 02 32 Bit
"unsigned"
# ,##
1-2-5 Power Factor Pump 1 Power factor cos φ of pump 1
03 00 11 00 02 32 Bit
"unsigned"
#
1-3-1 Operating Hours
Pump 2
Operating hours of pump 2
03 00 13 00 02 32 Bit
"unsigned"
#
1-3-2 Start Count Pump 2 Number of start-ups of pump
2
03 00 15 00 02 32 Bit
"unsigned"
# ,#
1-3-3 Current Pump 2 Current of pump 2
03 00 17 00 02 32 Bit
"unsigned"
# ,###
1-3-4 Effective Power
Pump 2
Effective power of pump 2 in kW
03 00 19 00 02 32 Bit
"unsigned"
# ,##
1-3-5 Power Factor Pump 2 Power factor cos φ of pump 2
03 00 1b 00 02 32 bit
bit mask
(ðSection7.
1.2.3.2,Page25 )
2-1-1 Pending Messages Displays all active messages
03 00 1d 00 01 32 bit
bit mask
(ðSection7.
1.2.3.2,Page25 )
Further messages
7.1.2.3.2 Message transfer
Device messages and other messages are transferred as bit masks with a width of 32 bits. Bit 31 is the highest-value bit (left), bit 0 is the lowest-value bit (right). Device messages are read out via coil "52 1c", all other messages via coil "52 1e".
Table15: Device messages, coil 52 1c
Bit Code Designation Description
Bit 0 - A1 - Motor protection pump 1 Thermal circuit breaker or motor protection switch
of pump 1 has triggered
Bit 1 - A2 - Motor protection pump 2 Thermal circuit breaker or motor protection switch
of pump 2 has triggered
Bit 2 - A3 - Motor 1 temperature too
high
Motor 1 temperature too high, thermal circuit breaker has triggered alert
Bit 3 - A4 - Motor 2 temperature too
high
Motor 2 temperature too high, thermal circuit breaker has triggered alert
Bit 4 - A5 - Power failure Power supply has been interrupted
Bit 5 - A6 - Phase error Phase error (phase failure)
Bit 6 - A7 - Leakage at motor 1 Leakage at motor 1 — Leakage sensor has triggered
Bit 7 - A8 - Leakage at motor 2 Leakage at motor 2 — Leakage sensor has triggered
Bit 8 - A9 - High water alert High water alert — tank is full
Bit 9 - A10 - External alarm External alarm – Device at the external input has
been triggered
Bit 10 - A11 - Sensor fault Sensor fault (float switch fault, broken wire, short
circuit)
Page 26
7 Operation
26 of 40
LevelControl Basic 2
Bit Code Designation Description
Bit 11 - A12 - Incorrect rotary field Incorrect rotary field of mains supply (phase
sequence)
Bit 12 - A13 - Undervoltage Undervoltage (-15 % of rated voltage)
Bit 13 - A14 - Overvoltage Overvoltage (+15 % of rated voltage)
Bit 14 - A15 - Flat battery Flat battery – Device will go into sleep mode soon
Bit 15 - A16 - Service interval system Service interval system, the service interval has
expired, servicing required
Bit 16 - A17 - Signalling module fault A fault has occurred at the signalling module
Table16: Device messages, coil 52 1e
Bit Code Designation Description
Bit 0 # 0 General fault message General fault message relay has switched
Bit 1 # 1 Fault pump 1 Pump 1 is blocked due to a fault and cannot be
started upon demand.
Bit 2 # 2 Fault pump 2 Pump 2 is blocked due to a fault and cannot be
started upon demand.
Bit 3 # 3 Pump 1 operational No fault at Pump 1, the manual-0-automatic selector
switch for Pump 1 is in "Auto" position
Bit 4 # 4 Pump 2 operational No fault at pump 2, the manual-0-automatic selector
switch for pump 2 is in "Auto" position
Bit 5 # 5 Pump 1 in operation Pump 1 is running
Bit 6 # 6 Pump 2 in operation Pump 2 is running
Bit 7 # 7 Pump 1 in automatic mode Manual-0-automatic switch of pump 1 in "Auto"
position
Bit 8 # 8 Pump 2 in automatic mode Manual-0-automatic switch of pump 2 in "Auto"
position
Bit 9 # 9 Check run pump 1 Check run of pump 1 in progress
Bit 10 # 10 Check run pump 2 Check run of pump 2 in progress
7.1.2.3.3 Functions
Various device functions of LevelControl Basic 2 can be executed via field bus. They can be accessed using function code 05 (Write Single Coil). Function code, coil and value are shown as hexadecimals and can be transferred directly to the Modbus-RTU protocol in this format.
Table17: Field bus functions
Function
code
Coil Value Designation Description
05 f5 01 ff 00 Remote
acknowledgement
Remote acknowledgement of all current fields
05 f5 02 ff 00
00 00
External fault Set/delete the external alarm (A10)
(Standard setting: both pumps OFF)
7.1.2.3.4 Termination
NOTE
The terminating resistors for ModBus RTU and field bus connection are set at the factory. If the signalling module is not the end device, remove the terminating resistors.
If LevelControl Basic 2 is operated as the end device in the field bus system or if a point-to-point connection with a field bus gateway is made, the terminating resistors must be set on the PCB in order to guarantee correct operation. This can be achieved easily via DIL switch S1.
Page 27
7 Operation
27 of 40
LevelControl Basic 2
Fig.9: DIL switch S1
Table18: DIL switch assignment
DIL switch Connection Description Factory
setting
1 ModBus RTU RS485 termination ON
2 RS485 termination ON
3 Galvanically isolated GND (connecting
RS485 GND with common GND)
OFF
4 System bus CAN termination ON
5 CAN termination ON
6 Not used OFF
Page 28
8 Servicing/Maintenance
28 of 40
LevelControl Basic 2
8 Servicing/Maintenance
8.1 Maintenance/inspection measures
KSB recommends regular inspection/maintenance according to the following schedule:
Table19: Maintenance/inspection measures
Measure Inspection Maintenance
Read the supplementary operating manual and the installation/operating manual
x x
Check cable connection between signalling module and LevelControl Basic 2 PCB for correct installation
x x
Check cable connection between current measuring module and signalling module for correct installation
x x
Re-tighten connection terminals (individual signals, analog output, field bus connection, current measuring modules)
x x
Check that the green status LED on the signalling module is continuously ON
x x
Check parameters x
Carry out a test run for several start/stop cycles x x
Check alarm devices, including the individual signals, for proper function
x x
Determine the spare parts requirements, if any. x
Provide support and/or training for operating personnel
x x
Supply new installation/operation manual if required
x x
Page 29
9 Trouble-shooting
29 of 40
LevelControl Basic 2
9 Trouble-shooting
Table20: Trouble-shooting
Faults Causes Remedy
Control unit showing fault
-A17-
A fault has occurred at the signalling module
Check signalling module connection
Switch power supply off and then
back on again
Replace signalling module
Green status LED on signalling module not lit
Signalling module is not correctly connected to the PCB or is defective
Check signalling module connection
Replace signalling module
Green status LED on signalling module flashes
Signalling module not detected Check firmware version of the
control unit and update if necessary
Individual signals are not output as required
Setting and/or connection fault Check control unit setting
Check signalling module terminal
connection
Analog output delivering a faulty signal
Setting and/or connection fault Check control unit setting
Check signalling module terminal
connection
Analog output delivering no signal
Setting and/or connection fault Level measurement faulty (message
-A11-)
Check control unit setting
Check signalling module terminal
connection
Check level measurement
Faulty behaviour during pneumatic measurement or bubbler control
Setting and/or connection fault Tubing is leaking
Check control unit setting
Check tubing connections
Check tubing for leakage
Parameters 1-2-3, Current Pump1, and/or 1-3-3, Current Pump2, are not shown or are shown interchanged in the display
Signalling or current measuring module connection fault
Current measuring module connections to signalling module interchanged
Check connections of signalling and
current measuring module
Communication via ModBus RTU faulty
Connection fault Communication fault Communication interrupted
Check connection
Check settings
Switch power supply off and then
back on again
Reset control unit
Communication with field bus system faulty
Connection fault Communication fault Communication interrupted
Check connection
Check settings
Switch power supply off and then
back on again
Reset control unit
Incorrect parameter settings after field bus access
Undocumented parameters can also be changed via field bus
Restore parameter settings
Check script for field bus access and
correct
Page 30
10 Related Documents
30 of 40
LevelControl Basic 2
10 Related Documents
10.1 Wiring diagram/terminal diagram
10.1.1 Individual signals - control board display (example)
Fig.10: Individual signals - control board display
1 Fault pump 1 2 Fault pump 2
3 High water 4 Sensor fault
5 Pump 1 in operation 6 Pump 2 in operation
NOTE
The assignment of the signal relays can be altered using the service tool.
10.1.2 Analog output
Fig.11: Analog output
NOTE
The analog output provides a level-proportional 4–20 mA signal. The assignment can be altered using the service tool.
Page 31
10 Related Documents
31 of 40
LevelControl Basic 2
10.1.3 Three-phase current measurement
Fig.12: Three-phase current measurement
1 Power supply to pump 1 2 Power supply to pump 2
3 Pump 1 current measuring module 4 Pump 2 current measuring module
5 Pump 1 current measurement connection to
signalling module
6 Pump 2 current measurement connection to
signalling module
Page 32
10 Related Documents
32 of 40
LevelControl Basic 2
10.1.4 Single-phase current measurement
Fig.13: Single-phase current measurement
1 Power supply to pump 1 2 Power supply to pump 2
3 Pump 1 current measuring module 4 Pump 2 current measuring module
5 Pump 1 current measurement connection to
signalling module
6 Pump 2 current measurement connection to
signalling module
10.1.5 Field bus connection
Fig.14: Field bus connection
Page 33
10 Related Documents
33 of 40
LevelControl Basic 2
10.1.6 Redundant pneumatic level measurement
NOTE
The use of a redundant pneumatic system (without compressor) offers redundant level measurement and also, when ATEX mode is activated, redundant minimum level monitoring.
Fig.15: Redundant pneumatic level measurement
1 LevelControl Basic 2 pressure sensor 2 Redundant pressure sensor on
signalling module
3 Reducer 4 Reducer
5 Open or closed pressure bell 6 Redundant open or closed pressure
bell
Page 34
10 Related Documents
34 of 40
LevelControl Basic 2
To set up a redundant pneumatic measurement system (without compressor), two sets of closed pressure bells or two sets of open pressure bells are required.
Both closed or open measuring bells must be mounted at a distance of 200 mm (bottom edge of bell) from the tank floor. If they are installed at a different installation height, this must be configured in the control unit.
Table21: Parameter
Parameter Designation
3-4-4-1 Level of bell 1
3-4-5-1 Level of bell 2
NOTE
To relieve the strain on the plug-type connectors in the control unit, run the tubes of both closed or open measuring bells through cable glands and tighten firmly.
NOTE
To ensure the control unit is functioning correctly, the air supply tubes of both closed or open measuring bells must be routed with a continuously falling slope to prevent the formation of water pockets as a result of condensation. Tubes which are too long must be cut to length during installation.
Page 35
10 Related Documents
35 of 40
LevelControl Basic 2
10.1.7 Partially redundant bubbler system
NOTE
If the compressor fails due to a fault, both level measurement systems continue to operate as redundant pneumatic level measurement systems (without compressor).
Fig.16: Partially redundant bubbler system
1 LevelControl Basic 2 pressure sensor 2 Redundant pressure sensor on
signalling module
3 Compressor for bubbler system 4 Orifice
5 Valve 6 Reducer
7 Y-piece 8 Reducer
9 Open pressure bell 10 Redundant open pressure bell
To set up a redundant pneumatic measurement system (without compressor), two sets of closed pressure bells or two sets of open pressure bells are required.
A set of two closed or open measuring bells must be mounted at a distance of 200 mm (bottom edge of bell) from the tank floor. If they are installed at a different installation height, this must be configured in the control unit.
Page 36
10 Related Documents
36 of 40
LevelControl Basic 2
Table22: Parameter
Parameter Designation
3-4-4-1 Level of bell 1
3-4-5-1 Level of bell 2
NOTE
To relieve the strain on the plug-type connectors in the control unit, run the tubes of both closed or open measuring bells through cable glands and tighten firmly.
NOTE
To ensure the control unit is functioning correctly, the air supply tubes of both closed or open measuring bells must be routed with a continuously falling slope to prevent the formation of water pockets as a result of condensation. Tubes which are too long must be cut to length during installation.
Page 37
Index
37 of 40
LevelControl Basic 2
Index
A
Analog output19
C
Commissioning/start-up15
F
Faults29 Field bus connection24
I
Individual signals9 Inspection28 Installation11
M
Maintenance28 Measured values menu17 Menu extension17 ModBus24
R
Redundant level measurement23, 33
S
Settings menu17 Shutdown15 Storage6
T
Transport6
Page 38
Page 39
Page 40