|
© KROHNE 08/2003 |
DIN A4: 7.02145.33.00 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||
|
US size: 7.02145.73.00 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Handbook
IFC 110 F V2.0
IFC 110 F-EEx V2.0
Signal converters for electromagnetic flowmeters
How to use these Instructions
Flowmeters are delivered ready for operation.
The flow sensor must be installed in the pipeline as described in the instructions for installation inside the packing of the flow sensor.
– Connection of power supply (Sect. 1.1-1.2) |
Pages |
6- 7 |
|
– Electrical connection between IFC 110 F and primary head (Sect. 1.3) |
Pages |
8-15 |
|
– |
Electrical connection of outputs and inputs (Sect. 2) |
Pages 16-24 |
|
– |
Factory settings (Sect. 2.7) and start-up (Sect. 3) |
Pages 25-27 |
Power the flowmeter. THAT’S ALL. The system is operative.
Operator control of the IFC 110 F signal converter is described in Sect. 4 and 5.
Applicable to
Software Versions
●Display & control unit No. 3.19937.02.00
●A/D converter
No. 8.13393.02.00
●Outputs/inputs (I/O) No. 3.16230.01.00
Variable area flowmeters Vortex flowmeters
Flow controllers
Electromagnetic flowmeters
Ultrasonic flowmeters Mass flowmeters
Level measuring instruments Communications technology Engineering systems & solutions
Switches, counters, displays and recorders Heat metering
Pressure and temperature
|
Contents |
|
1 |
Electrical connection: power supply.................................................................................................... |
6 |
1.1 |
Location and important installation notes ……………………. PLEASE NOTE ! ...................................... |
6 |
1.2 |
Power supply - connection ....................................................................................................................... |
7 |
1.3 |
Electrical connection of flow sensors ....................................................................................................... |
8 |
1.3.1 |
General remarks on signal lines A and B and field current line C............................................................ |
8 |
1.3.2 |
Stripping (preparation) of signal cables.................................................................................................... |
9 |
1.3.3 |
Grounding of flow sensor ....................................................................................................................... |
10 |
1.3.4 |
Cable lengths (max. distance between signal converter and flow sensor)............................................. |
11 |
1.3.5 |
Connection diagrams for power supply and flow sensors ...................................................................... |
12 |
1.3.6 |
EEx-Connection diagrams for power supply and flow sensors .............................................................. |
14 |
2 |
Electrical connection: outputs and inputs......................................................................................... |
16 |
2.1 |
Important information for outputs and inputs …….…………. PLEASE NOTE ! ..................................... |
16 |
2.2 |
Current output I....................................................................................................................................... |
17 |
2.3 |
Pulse outputs P and A1.......................................................................................................................... |
18 |
2.3.1 |
Pulse output P for electronic totalizers (EC)........................................................................................... |
18 |
2.3.2 |
Pulse output A1 for electromechanical totalizers (EMC) ........................................................................ |
19 |
2.4 |
Status outputs A1 / A2 / D1 / D2............................................................................................................. |
20 |
2.5 |
Control inputs C1 and C2 ....................................................................................................................... |
20 |
2.6 |
Connection diagrams of outputs and inputs ........................................................................................... |
21 |
2.7 |
Standard factory settings........................................................................................................................ |
25 |
3 |
Start-up.................................................................................................................................................. |
26 |
4 |
Operating of the signal converter....................................................................................................... |
28 |
4.1 |
KROHNE operating concept................................................................................................................... |
28 |
4.2 |
Operating and control elements ............................................................................................................. |
29 |
4.3 |
Key functions.......................................................................................................................................... |
30 |
4.4 |
Table of settable functions ..................................................................................................................... |
32 |
4.5 |
Error messages in measuring mode ...................................................................................................... |
38 |
4.6 |
Resetting the totalizer and deleting error messages, RESET/QUIT menu ............................................ |
39 |
4.7 |
Examples of signal converter settings.................................................................................................... |
39 |
5 |
Description of functions ...................................................................................................................... |
40 |
5.1 |
Full-scale range Q100% ............................................................................................................................ |
40 |
5.2 |
Time constant......................................................................................................................................... |
40 |
5.3 |
Low-flow cutoff SMU............................................................................................................................... |
41 |
5.4 |
Display.................................................................................................................................................... |
41 |
5.5 |
Internal electronic totalizer ..................................................................................................................... |
42 |
5.6 |
Internal power supply (E+/E-) for connected loads ................................................................................ |
43 |
5.7 |
Current output I....................................................................................................................................... |
43 |
5.8 |
Pulse outputs P and A1.......................................................................................................................... |
44 |
5.9 |
Status outputs A1 / A2 and D1 / D2 ....................................................................................................... |
46 |
5.10 |
Control inputs C1 and C2 ....................................................................................................................... |
47 |
5.11 |
Language................................................................................................................................................ |
48 |
5.12 |
Entry code .............................................................................................................................................. |
48 |
5.13 |
Flow sensor ............................................................................................................................................ |
49 |
5.14 |
User-defined units .................................................................................................................................. |
50 |
5.15 |
F/R mode, forward/reverse flow measurement ...................................................................................... |
51 |
5.16 |
Output characteristics............................................................................................................................. |
51 |
5.17 |
Applications ............................................................................................................................................ |
52 |
5.18 |
Hardware settings................................................................................................................................... |
52 |
5.19 |
Limit switches ......................................................................................................................................... |
53 |
5.20 |
Range change ........................................................................................................................................ |
54 |
2 |
IFC 110 F |
05/2003 |
6 |
Special Applications, Functional Checks, Service and Order Numbers |
........................................ 55 |
|
6.1 |
Use in hazardous areas......................................................................................................................... |
|
55 |
6.1.1 |
General.................................................................................................................................................. |
|
55 |
6.1.2 |
Main safety features .............................................................................................................................. |
|
55 |
6.1.3 |
Installation and electrical connection..................................................................................................... |
56 |
|
6.2 |
Magnetic sensors MP (optional)............................................................................................................ |
|
57 |
6.3 |
Changing the load capacity of the output A1 for polarized DC operation.............................................. |
58 |
|
6.4 |
Interfaces............................................................................................................................................... |
|
58 |
6.4.1 |
RS 232 adapter incl. IMoCom software (optional)................................................................................. |
58 |
|
6.4.2 |
HART®- interface ................................................................................................................................... |
|
58 |
6.4.3 |
KROHNE RS 485 Interface (Option) ..................................................................................................... |
60 |
|
6.5 |
Pulsating flow ........................................................................................................................................ |
|
61 |
6.6 |
Unstable display and outputs ................................................................................................................ |
|
62 |
6.7 |
Quickly changing flows .......................................................................................................................... |
|
64 |
6.8 |
Changeover of current output, active / passive mode ........................................................................... |
64 |
|
6.9 |
Empty pipe detection EPD..................................................................................................................... |
|
65 |
6.10 |
Stable signal outputs with empty measuring tube ................................................................................. |
66 |
|
7 |
Functional checks ............................................................................................................................... |
|
68 |
7.1 |
Checking the zero with IFC 110 F signal converter, Fct. 3.03............................................................... |
68 |
|
7.2 |
Checking the measuring range Q, Fct. 2.01.......................................................................................... |
68 |
|
7.3 |
Hardware information and error status, Fct. 2.02.................................................................................. |
69 |
|
7.4 |
Hardware test, Fct. 2.03 ........................................................................................................................ |
|
69 |
7.5 |
Faults and symptoms during start-up and flow measurement............................................................... |
70 |
|
7.6 |
Checking the flow sensor ...................................................................................................................... |
|
76 |
7.7 |
Checking the signal converter using a GS 8 A simulator (optional) ...................................................... |
77 |
|
8 |
Service.................................................................................................................................................. |
|
80 |
8.1 |
Replacing the power supply fuse........................................................................................................... |
80 |
|
8.2 |
Retrofitting of magnetic sensors MP (optional)...................................................................................... |
81 |
|
8.3 |
Replacing the complete electronic unit of the IFC 110 F signal converter ............................................ |
82 |
|
8.4 |
Replacing single printed circuit boards (PCBs) ..................................................................................... |
83 |
|
8.5 |
Replacing the flow sensor ..................................................................................................................... |
|
83 |
8.6 |
IFC 110 F replacements for old KROHNE signal converters ................................................................ |
83 |
|
8.7 |
Illustration printed circuit boards (PCBs) ............................................................................................... |
84 |
|
9 |
Order numbers..................................................................................................................................... |
|
87 |
10 |
Technical data...................................................................................................................................... |
|
88 |
10.1 |
Signal converter..................................................................................................................................... |
|
88 |
10.2 |
Error limits ............................................................................................................................................. |
|
90 |
10.3 |
Dimensions and weights IFC 110 F / IFC 110 F-EEx and ZD / ZD-EEx ............................................. |
91 |
|
10.4 |
Flow table .............................................................................................................................................. |
|
91 |
11 |
Measuring principle............................................................................................................................. |
|
92 |
12 |
Block diagram...................................................................................................................................... |
|
93 |
13 |
Approvals ............................................................................................................................................. |
|
94 |
13.1 |
EC-type examination certificate |
English translation ............................................................................. |
94 |
13.2 |
EC-type examination certificate |
German original ................................................................................. |
97 |
14 |
Index ................................................................................................................................................... |
|
100 |
If you need to return flowmeters for testing or repair to KROHNE........................................................... |
103 |
05/2003 |
IFC 110 F |
3 |
Signal converter versions
The operating data are factory-set to your ordered specifications.
Standard version, with local display and control elements
Same as display version, additional with magnetic sensors (MP)
Same as display version (D + MP),
for operation with flow sensors installed in hazardous areas
Same as standard version,
but additionally with different interfaces
Items included with supply
•Signal converter in the version as ordered, see above.
•Signal cable in the version and length as ordered (standard: signal cable A, length 10 m / 30 ft)
•Condensed installation and operating manual in the ordered language for installation, electrical connection, start-up and operator control of the signal converter.
•Service Manual in english language.
Please note!
In the Installation and Operating Manual there are hints with Sect. Numbers which you can find in the Handbook / Service Manual only!
Instrument nameplates
Signal converter (example)
IFC 110 F
Signal converter IFC 110F-EEx (example)
Flow sensor (example)
ALTOFLUX 4000 F
4 |
IFC 110 F |
05/2003 |
System description
Electromagnetic flowmeters are precision instruments designed for linear flow measurement of liquid products
The process liquids must be electrically conductive:, ≥ 5 µS/cm (for cold demineralized water ≥ 20 µS/cm).
The full-scale range Q100% can be set as a function of the meter size: flow velocity of 0.3 - 12 m/s or 1 - 40 ft/s (s. Section 10.4.).
Product liability and warranty
The electromagnetic flowmeters are designed solely for measuring the volumetric flowrate of electrically conductive, liquid process products.
These flowmeters are available for use in hazardous areas.
Special regulations apply in this case, which are given in the special EEx directions.
Responsibility as to suitability and intended use of these electromagnetic flowmeters rests solelywith the operator.
Improper installation and operation of the flowmeters (systems) may lead to loss of warranty.
In addition, the “General conditions of sale” forming the basis of the purchase contract are applicable.
If flowmeters need to be returned to KROHNE, please note the information given on the last-but- one page of these Instructions. KROHNE regrets that it cannot repair or check your flowmeter(s) unless accompanied by the completed form sheet.
CE / EMC / Standards / Approvals
The here described Electromagnetic flowmeters meet the NAMUR Directive NE21, the protection requirements of Directive 89/336/EEC in conjunction with EN 61326-1 (1997) and A1 (1998), as well as Directives 73/23/EEC and 93/68/EEC in conjunction with EN 61010-1, and bear the CE marking.
Software history
Display & control unit |
Amplifier (ADC) |
Inputs and outputs (I/O) |
|||
Software |
Status |
Software |
Status |
Software |
Status |
3.19937.02.00 |
current |
8.13393.02.00 |
current |
3.16230.01.00 |
current |
|
|
|
|
|
|
IMPORTANT!
In respect of EEx versions, pay regard to all directions marked with the symbol, and also the information given in Sect. 6.1 and 13.
Only the EEx flow sensor may be installed in the hazardous area. The EEx certified signal converter must be installed outside the hazardous area!
05/2003 |
IFC 110 F |
5 |
Sect. 1.1 |
Part A System installation and start-up |
1 Electrical connection: power supply
1.1Location and important installation notes ……………………. PLEASE NOTE !
•Electrical connection in accordance with VDE 0100 ”Regulations for the erection of power installations with nominal voltages up to 1000 V” or equivalent national regulations.
•Do not cross or loop cables inside the terminal compartment.
•Use separate wiring (PG screwed cable entries) for power supply, field current lines, signal lines, outputs and inputs.
•Hazardous areas are subject to special regulations, see Section 6.1 and special installation instructions for hazardous-duty versions.
•Do not expose signal converter and switchgear cabinets with built-in converters to direct sunlight. Install a sunshade if necessary.
•Signal converters installed in switchgear cabinets require adequate cooling (e.g. by fans or heat exchangers).
•Do not expose signal converters to intense vibration.
•Keep the distance between the flow sensor and signal converter as small as possible, for empty pipe detection (EPD) ≤ 20 m / ≤ 66 ft. Observe maximum lengths of signal and field current lines (see Section 1.3.4).
•Use KROHNE signal line A (type DS, standard) or signal line B (type BTS, bootstrap, optional), standard length 10 m (33 ft).
•Generally use bootstrap signal lines B (type BTS) for PROFIFLUX 5000 F and VARIFLUX 6000 F flow sensors sized at DN 2.5-15 and 1/10’’-1/2’’ and for contaminated liquids which tend to form electrically insulating deposits.
•Always calibrate flow sensor and signal converter together. During installation particular care should therefore be given to identical settings of flow sensor constant GK (see instrument nameplate of flow sensor). In case GK constants are not identical, the signal converter must be adjusted to the flow sensor GK (see Sections 4 and 8.5).
•Dimensions of signal converter see Section 10.3.
IMPORTANT!
For EEx versions, also pay regard to all directions included in Sect. 6.1 and 13.
Only the EEx flow sensor may be installed in the hazardous area. The EEx certified signal converter must be installed outside the hazardous area!
6 |
IFC 110 F |
05/2003 |
Part A System installation and start-up |
Sect. 1.2 |
1.2Power supply - connection
PLEASE NOTE !
•Type of enclosure IP 65 to IEC 529 / EN 60529 equivalent to NEMA 4/4X.
•Dimensioning: the flowmeter housing protecting the electronic equipment against dust and moisture must always be kept closed. The selected clearances and creeping distances comply with VDE 0110 and/or IEC 664 regulations for contamination grade 2. Supply circuits and output circuits are designed to meet standards of overvoltage classes III and II, respectively.
•Fuse protection, disconnecting device: fuse protection for the feeding power circuit, and also a disconnecting device (switch, circuit breaker) for isolating the signal converters must be provided (see also Sect. 1.3.5 and 1.3.6).
100-230 V AC (tolerance range 85-255 V AC)
•Observe information on the instrument nameplate, power supply voltage and frequency.
•The protective conductor PE of the power supply must be connected to the separate U-clamp terminal inside the terminal compartment of the signal converter.
•CAUTION: do not remove the internal connection (line) inside the terminal compartment of the signal converter (yellow/green wire) between the U-clamp terminal and terminal 10 - protective conductor (protection class I instrument).
•Connection diagrams I - IV for the power supply and for the electrical connection between flow sensor and signal converter, see Sections 1.3.5 (Standard) and 1.3.6 (EEx).
24 V AC / DC (tolerance ranges: AC 20.4 - 26.4 V / DC 18 - 31.2 V)
•Observe information on the instrument nameplate, power supply voltage and frequency.
•For technical reasons concerning the measuring process, a functional grounding conductor FE has to be connected to the separate U-clamp terminal inside the terminal compartment of the signal converter.
•A facility providing a reliable electrical separation (PELV) has to be provided for connections to functional extra-low voltages (24 V AC / DC) - (VDE 0100 / VDE 0106 and/or IEC 364 /
IEC 536 or equivalent national regulations).
•Connection diagrams I - IV for the power supply and for the electrical connection between flow sensor and signal converter, see Sections 1.3.5 (Standard) and 1.3.6 (EEx).
IMPORTANT!
For EEx versions, also pay regard to all directions included in Sect. 6.1 and 13.
Only the EEx flow sensor may be installed in the hazardous area. The EEx certified signal converter must be installed outside the hazardous area!
Warning: Instrument must be properly grounded to avoid personnel shock hazard.
05/2003 |
IFC 110 F |
7 |
Sect. 1.3.1 |
Part A System installation and start-up |
1.3Electrical connection of flow sensors
1.3.1 General remarks on signal lines A and B and field current line C
Proper operation of the equipment is ensured when KROHNE signal lines A and B are used with foil screen and magnetic shield.
•Signal lines must be firmly installed.
•Shields are connected via stranded drain wires.
•Underwater or underground routing is possible.
•Insulating material flame-retardant to IEC 332.1 / VDE 0742.
•Low-halogen, unplasticized signal lines which remain flexible at low temperatures.
Signal line A (type DS) with double shielding
1Stranded drain wire, 1st shield, 1.5 mm² or AWG 14
2Insulation
3Stranded wire 0.5 mm² or AWG 20 (3.1 red/3.2 white)
4Special foil, 1st shield
5Insulation
6Mu-metal foil, 2nd shield
7Stranded drain wire, 2nd shield, 0.5 mm² or AWG 20
8Outer sheath
Signal line B (type BTS) with triple shielding (bootstrap line)
The bootstrap technology always controls the individual shields (3) of the signal converter exactly to the voltage which is supplied to the signal conductors (5). As this prevents voltage differences between the individual shields (3) and signal conductors (5), no current flows via the line capacitances between 3 and 5. The line capacitance seems to become ”zero”.
This allows greater cable lengths in case the electric conductivity of the liquid to be measured is low.
1Dummy glider wire
2Insulation (2.1 red/2.2 white)
3Special foil, 1st shield (3.1/3.2)
4Insulation (4.1/4.2)
5Stranded wire 0.5 mm² or AWG 20 (5.1 red/5.2 white)
6Stranded drain wire, 1st shield, 0.5 mm² or AWG 20 (6.1/6.2)
7Special foil, 2nd shield
8Stranded drain wire, 2nd shield, 1.5 mm² or AWG 14
9Insulation
10Mu-metal foil, 3rd shield
11Stranded drain wire, 3rd shield, 0.5 mm² or AWG 20
12Outer sheath
Field current line C1
Line 2 x 0.75 mm² (18 AWG) Cu or 2 x (4 x) 1.5 mm² (14 AWG) Cu (Cu = copper cross section) The cross section depends on the required cable length.
For max. permissible cable lengths please refer to Section 1.3.4
IMPORTANT!
For EEx versions, also pay regard to all directions included in Sect. 6.1 and 13.
Only the EEx flow sensor may be installed in the hazardous area. The EEx certified signal converter must be installed outside the hazardous area!
8 |
IFC 110 F |
05/2003 |
Part A System installation and start-up |
Sect. 1.3.2 |
1.3.2 Stripping (preparation) of signal cables
Please note: The numbers in the drawings designate the stranded drain wires of signalling cables A and B, see sectional drawings in Sect. 1.3.1.
Flow sensor
Length |
flow sensor |
|
|
mm |
inch |
a |
90 |
3.60 |
b |
8 |
0.30 |
c |
25 |
1.00 |
d |
8 |
0.30 |
e |
70 |
2.80 |
Signal cable A (type DS), double shielding
for flow sensor
Converter
Length |
|
Converter |
|
|
mm |
|
inch |
a |
50 |
|
2.00 |
b |
8 |
|
0.40 |
d |
8 |
|
0.40 |
e |
20 |
|
0.80 |
Signal cable A (type DS), double shielding
for IFC 110 F Converter
Signal cable A bending radius ≥ 50 mm (≥ 2”)
Signal cable A bending radius ≥ 50 mm (≥ 2”)
Signal cable B (type BTS), |
Signal cable B (type BTS), |
with triple shielding (bootstrap) |
with triple shielding (bootstrap) |
for flow sensor |
for IFC 110 F Converter |
Signal cable B bending radius ≥ 50 mm (≥ 2”)
Customer-supplied materials
WInsulation tubing (PVC), Ø 2.0-2.5 mm (Ø 1”)
XHeat-shrinkable tubing or cable sleeve
YWire end sleeve to DIN 41 228: E 1.5-8
ZWire end sleeve to DIN 41 228: E 0.5-8
Signal cable B bending radius ≥ 50 mm (≥ 2”)
05/2003 |
IFC 110 F |
9 |
Sect. 1.3.3 |
Part A System installation and start-up |
1.3.3 Grounding of flow sensor
•The flow sensor must be correctly connected to ground.
•The grounding cable may not transfer interference voltages.
•Do not use the grounding cable to connect more than one device to ground.
•In hazardous areas the grounding line is also used for potential equalizing purposes. Special grounding instructions are contained in the installation instructions for hazardous-duty instruments (only supplied together with such instruments).
•The flow sensor is connected to ground by means of a functional grounding conductor FE.
•Special grounding instructions for the connection of several flow sensors are contained in the separate installation instructions of the flow sensors.
•These instructions also contain detailed descriptions on how to use grounding rings and how to install flow sensors in metal or plastic pipes or in pipes which are coated on the inside.
Warning: Instrument must be properly grounded to avoid personnel shock hazard.
IMPORTANT!
For EEx versions, also pay regard to all directions included in Sect. 6.1 and 13.
Only the EEx flow sensor may be installed in the hazardous area. The EEx certified signal converter must be installed outside the hazardous area!
10 |
IFC 110 F |
05/2003 |
Part A System installation and start-up |
Sect. 1.3.4 |
1.3.4 Cable lengths (max. distance between signal converter and flow sensor)
Abbreviations and explanations
The abbreviations used in the following tables, diagrams and connection diagrams stand for:
ASignal line A (type DS) with double shielding, max. length see diagram
BSignal line B (type BTS) with triple shielding, max. length see diagram
CField current line, minimum cross section (AF) and max. length see table
DHigh-temperature silicone line, 3x1.5 mm² (14 AWG) Cu, with single shield, max. length 5 m (16 ft)
EHigh-temperature silicone line, 2 x 1.5 mm² (14 AWG) Cu, max. length 5 m (16 ft)
AF Cross section of field current line C in Cu, see table
LCable length in m or ft
Κ Electrical conductivity of the process liquid
ZD Intermediate connection box required in connection with lines D and E for flow sensors ALTOFLUX 4000 F, PROFIFLUX 5000 F and VARIFLUX 6000 F for process temperatures exceeding 150°C (302°F).
Recommended length of signal line
for magnetic field frequencies ≤ 1/6 x power frequency
Flow |
Meter size |
|
|
|
|
Signal |
||
sensor |
DN mm |
|
|
Inch |
|
|
|
line |
VARIFLUX 6000 F |
2.5 |
- |
15 |
1/10 |
- |
|
1/2 |
B1 |
|
25 |
- |
80 |
1 |
- |
3 |
|
A1 / B3 |
PROFIFLUX 5000 F |
2.5 |
- |
|
1/10 |
- |
|
|
B1 |
|
4 |
- |
15 |
1/6 |
- |
|
1/2 |
B2 |
|
25 |
- |
100 |
1 |
- |
4 |
|
A1 / B3 |
ALTOFLUX 4000 F |
10 |
- |
150 |
3/8 |
- |
6 |
|
A1 / B3 |
|
200 |
- |
1200 |
8 |
- |
48 |
|
A2 / B4 |
ALTOFLUX 2000 F |
150 |
- |
250 |
6 |
- |
10 |
|
A2 / B4 |
ECOFLUX 1000 F |
10 |
- |
150 |
3/8 |
- |
6 |
|
A1 / B3 |
M900 |
10 |
- |
300 |
3/8 |
- |
12 |
|
A2 / B4 |
Please note!
For application with empty pipe detection (EPD) max. length < 20 m / 66 ft.
|
Max. length and minimum cross section of field current line |
|
|||
|
Length L |
|
Cross section AF (Cu), minimum |
|
|
|
0 to 150 m |
5 to 500 ft |
2 x 0.75 mm² Cu |
2 x 18 AWG |
|
|
150 to 300 m |
500 to 1000 ft |
2 x 1.50 mm² Cu |
2 x 14 AWG |
|
|
300 to 600 m |
1000 to 1900 ft |
4 x 1.50 mm² Cu |
4 x 14 AWG |
|
|
|
|
|
|
|
|
05/2003 |
|
IFC 110 F |
11 |
Sect. 1.3.5 |
Part A System installation and start-up |
1.3.5 Connection diagrams for power supply and flow sensors |
|
Important remarks for circuit diagrams |
PLEASE NOTE ! |
•The figures in brackets indicate the stranded drain wires of the shields (see cross-sectional drawings of signal lines in Section 1.3.1).
•Electrical connection to VDE 0100 ”Regulations for the erection of power installations with nominal voltages up to 1000 V”
•Power supply 24 V AC / DC: protective extra-low voltages (PELV) acc. to VDE 0100/
VDE 0106 and/or IEC 364/IEC 365, or corresponding national regulations.
•Systems to be used in hazardous areas are subject to special regulations applying to electrical connections (see Section 1.3.6) for hazardous-duty instruments.
• PE = protective conductor |
FE = functional ground conductor |
IMPORTANT!
Electrical connection of EEx flow sensors and EEx signal converters to be carried out as described in Sect. 1.3.6.
*Do not remove the internal connection (cable) inside the terminal compartment of the signal converter (yellow/green wire) between the U-clamp terminal and terminal 10 (protective conductor for protection class I instruments).
12 |
IFC 110 F |
05/2003 |
|
Part A System installation and start-up |
|
Sect. 1.3.5 |
|
|
|
|
|
|
|
|
Process temperature below 150°C (302°F) |
||
|
|
|
|
|
|
|
Signal cable A (type DS) |
|
Signal cable B (type BTS) |
|
I |
II |
||
|
|
|
|
|
|
|
IFC 110 F V 2.0 |
|
IFC 110 F V 2.0 |
Flow sensor |
Flow sensor |
||
|
|
|
|
|
|
|
|
|
Process temperature above 150°C (302°F) |
||
|
|
|
|
|
Signal cable A (type DS) |
|
Signal cable B (type BTS) |
III |
IV |
||
|
|
|
|
|
IFC 110 F V 2.0 |
|
IFC 110 F V 2.0 |
|
Flow sensor |
Flow sensor |
|
|
|
|
|
|
|
|
|
|
|
|
|
05/2003 |
IFC 110 F |
13 |
|
Sect. 1.3.6 |
Part A System installation and start-up |
1.3.6 EEx-Connection diagrams for power supply and flow sensors PLEASE NOTE!
•The figures in brackets indicate the stranded drain wires for the shields (see cross-sectional drawing of signal cable in Section 1.3.1).
•The connections for the intrinsically safe electrode circuit including the shield terminals are safety-separated up to a peak value of 375 V from the terminals for thepower supply, for the inputs/outputs and for the field circuit. They are galvanically isolated from the housing (PE/PA).
•For connection of the intrinsically safe electrode circuit including shield terminals to the primary head, please refer to Item 12 in EN 60079-14.
The non-intrinsically safe field circuit to be connected to the primary head in keeping with the requirements of Item 9 in EN 60079-14 .
•The non-intrinsically safe input and output circuits may only be routed into the hazardous area in compliance with appropriate measures as specified in EN 60079-14.
•Supply power (terminals 11,12)
In conformity with current regulations for electrical installations, an isolating facility is required to be provided for the signal converter. The housing of the IFC 110 F – EEx signal converter must be incorporated in the equipotential bonding system (via external PA connection).
Note! A PE safety conductor is not connected if a functional extra-low voltage with safety separation (PELV) is used. Grounding is then carried out by way of the equipotential bonding conductor.
•Electrode circuit (terminals 1, 20, 2, 3, 30 and shield terminal S)
In conformity with the requirements for separation of intrinsically safe circuits, Category ib to EN 50 020, the cable for the intrinsically safe electrode circuit must, up to the terminals, be separated from all non-intrinsically safe circuits.
Terminals 20 and 30 are optionally provided for connecting cables with single shielding. The terminal for the outer shield (S) is capacitance grounded in the signal converter. The outer overall shield to be connected by the shortest possible wire to the shield terminal. Shields to be carefully insulated from ground and from each other.
•Field circuit FSV (terminals 7, 8)
The field circuit is all-pole protected on the FSV circuit board with an internal fusible link
160mA / 250V.
•Input/output circuits
The connection is made to functional extra-low voltage circuits with safety separation (PELV). The I/O functions and technical data are described in the Standard Installation and Operating Instructions.
IMPORTANT!
For EEx versions, also pay regard to all directions included in Sect. 6.1 and 13.
Only the EEx flow sensor may be installed in the hazardous area. The EEx certified signal converter must be installed outside the hazardous area!
*Do not remove the internal connection (cable) inside the terminal compartment of the signal converter (yellow/green wire) between the U-clamp terminal and terminal 10 (protective conductor for protection class I instruments).
14 |
IFC 110 F |
05/2003 |
|
Part A System installation and start-up |
|
Sect. 1.3.6 |
|
|
|
|
|
|
|
|
Process temperature below 150°C (302°F) |
||
|
|
|
|
|
|
|
Signal cable A (type DS) |
|
Signal cable B (type BTS) |
|
I |
II |
||
|
|
|
|
|
|
|
IFC 110 F V 2.0 |
|
IFC 110 F V 2.0 |
Hazardous area |
|
Hazardous area |
|
|
|
|
|
|
|
Flow sensor |
|
Flow sensor |
|
|
|
|
|
|
|
|
|
Process temperature above 150°C (302°F) |
||
|
|
|
|
|
Signal cable A (type DS) |
|
Signal cable B (type BTS) |
III |
IV |
||
|
|
|
|
|
IFC 110 F V 2.0 |
|
IFC 110 F V 2.0 |
Hazardous area |
|
Hazardous area |
|
|
|
Flow sensor |
Flow sensor |
05/2003 |
IFC 110 F |
15 |
Sect. 2.1 |
Part A System installation and start-up |
2 Electrical connection: outputs and inputs
IMPORTANT!
For EEx versions, also pay regard to all directions included in Sect. 6.1 and 13.
Only the EEx flow sensor may be installed in the hazardous area. The EEx certified signal converter must be installed outside the hazardous area!
2.1Important information for outputs and inputs …….…………. PLEASE NOTE !
•The signal converter has the following outputs and inputs:
Output and |
Symbol |
Terminals |
Remarks |
|
input group |
|
|
|
|
Power output |
I |
IS / I |
|
active / passive selectable |
Current output |
P |
P / P |
for electronic totalizers |
|
Pulse output |
A1* (P2) |
A1* |
/ A |
for electromechanical totalizers |
Status outputs |
A1* and A2 |
A1* |
/ A / A2 |
A common centre grounding contact |
Status outputs |
D1 and D2 |
D1 / D / D2 |
D common centre grounding contact |
|
Control inputs |
C1 and C2 |
C1 / C / C2 |
C common centre grounding contact |
|
Internal power supply |
E |
E+ / E- |
for active mode of outputs and inputs |
*Output A1 can be used as a 2nd pulse output P2 for electromechanical totalizers or as a 4th status output, see Section 4.4, Fct. 3.07 HARDWARE.
•The output and input groups are electrically isolated from each other and from all other input and output circuits.
• Please note: |
A common centre grounding contact for outputs A1 and A2 |
|
D common centre grounding contact for outputs D1 and D2 |
|
C common centre grounding contact for control inputs C1 and C2 |
•Active mode: the signal converter supplies the power for the operation (selection) of
receiver instruments, observe max. operating data (terminals E+ and E-).
•Passive mode: the operation (selection) of receiver instruments requires an external
power supply (Uext), observe max. operating data.
•Connection diagrams of outputs and inputs are shown in Section 2.6.
•For operating data of outputs and inputs please refer to Sections 2.6 and 10.1.
16 |
IFC 110 F |
05/2003 |
Part A System installation and start-up |
Sect. 2.2 |
2.2Current output I
•The current output is electrically isolated from all other circuits.
•Setting data and functions can note down in the Table in Sect. 3.
Please also refer to Section 2.7 ”Standard factory settings”.
•All operating data and functions are adjustable (see Sections 4.4 and 5.6, Fct. 1.05).
•Max. load : active operation 15-500 Ω
passive operation ≤ 800 Ω
•Selfcheck : - interrupting the mA loop, and
-short-circuit of mA loop via test function, see Fct. 2.03 or when power supply is switched on in Fct. 3.07
Error message on display (see Fct. 1.04, Section 5.4) and/or status output (see Fct. 1.07-1.10, Section 5.8).
•Current value for error identification is adjustable, see Fct. 1.05 and Section 5.6.
•Range change-over, automatically or externally by control input, see Sections 4.4 and 5.19, Fct. 1.07-1.10 and 1.11-12.
Setting range from 5-80% of Q100%
(corresponding low to high range ratio from 1:20 to 1:1.25).
Change-over from high to low range at approx. 85% of low range and vice versa at approx. 98% of low range.
The active range is signalled via one of the four status outputs.
•Forward/reverse flow measurement (F/R mode) is possible (see Section 5.15).
•Connection diagrams see Section 2.6.
05/2003 |
IFC 110 F |
17 |
Sect. 2.3.1 |
Part A System installation and start-up |
2.3Pulse outputs P and A1
2.3.1 Pulse output P for electronic totalizers (EC)
•Pulse output P is electrically isolated from all other circuits.
•Setting data and functions can note down in the Table in Sect. 3.
Please also refer to Section 2.7 ”Standard factory settings”.
•All operating data and functions are adjustable, see Sections 4.4 and 5.7, Fct. 1.05.
•Active mode: uses the internal power supply, terminals E+/E-
Passive mode: requires external power supply, Uext ≤ 32V DC/24V AC, I ≤ 30mA
•Max. adjustable frequency 10 kHz
• Scaling |
in pulses per unit time (e.g. 1000 pulses/s at Q100% flow) or |
|
in pulses per unit volume (e.g. 100 pulses/m³ or US Gal). |
•Pulse width symmetric, pulse duty factor 1:1, independent of output frequency,
automatic, with optimum pulse width,
pulse duty factor approx. 1:1 at Q100%, or
pulse width range from 0.01 to 1 s adjustable as required for correspondingly lower output frequency.
•Forward/reverse flow measurement (F/R mode) is possible, see Section 5.15.
•Connection diagrams see Section 2.6
•Schematic wiring diagram for pulse output P for electronic totalizers EC
Similar to a relay contact, this pulse output switches direct and alternating voltages.
18 |
IFC 110 F |
05/2003 |
Part A System installation and start-up Sect. 2.3.2
2.3.2 Pulse output A1 for electromechanical totalizers (EMC) PLEASE NOTE:
The output terminal A1 can be used as status output A1 or as a 2nd pulse output A1 for electromechanical totalizers.
Setting is as described in Fct. 3.07 HARDWARE, see Sections 4.4 and 5.18.
•Pulse output A1 is electrically connected to status output A2 (common centre grounding contact A ) but electrically isolated from all other circuits.
•Setting data and functions can note down in the Table in Sect. 3.
Please also refer to Section 2.7 ”Standard factory settings”.
•All operating data and functions are adjustable, see Sections 4.4 and 5.7, Fct. 1.07.
•Active mode: uses the internal power supply, terminals E+/E-
•Passive mode: requires external power supply, Uext ≤ 32V DC/24V AC, I ≤ 100mA
(I ≤ 200mA for polarized DC operation, see Section 6.3)
•Max. adjustable frequency 50 kHz
• Scaling |
in pulses per unit of time (e.g. 10 pulses/s at Q100% flow) or |
|
in pulses per unit of volume (e.g. 10 pulses/m³ or US Gal). |
•Pulse width symmetric, pulse duty factor 1:1, independent of output frequency,
automatic, with optimum pulse width,
pulse duty factor approx. 1:1 at Q100%, or
pulse width range from 0.01 to 1 s adjustable as required for correspondingly lower output frequency.
•Forward/reverse flow measurement (F/R mode) is possible, see Section 5.15.
•Connection diagrams see Section 2.6
•Schematic wiring diagram for pulse output A1 for electromechanical totalizers EMC. This pulse output has a MOSFET switch as output which switches direct and alternating voltages similar to a relay contact.
05/2003 |
IFC 110 F |
19 |
Sect. 2.4 |
Part A System installation and start-up |
2.4Status outputs A1 / A2 / D1 / D2
PLEASE NOTE:
The output terminal A1 can be used as status output A1 or as a 2nd pulse output A1 for electromechanical totalizers.
Setting is as described in Fct. 3.07 HARDWARE, see Sections 4.4 and 5.18.
•Status outputs A1/A2 and D1/D2 with the common centre grounding contacts A and B are electrically isolated from each other and from all other circuits.
•Setting data and functions can note down in the Table in Sect. 3.
Please also refer to Section 2.7 ”Standard factory settings”.
•All operating data and functions are adjustable, see Sections 4.4 and 5.8, Fct. 1.07-1.10.
•Active mode: uses the internal power supply, terminals E+/E-
Passive mode: requires external power supply, Uext ≤ 32V DC/24V AC, I ≤ 100mA
(I ≤ 200mA for A1 in case of polarized DC operation, see Section 6.3)
•The following operating conditions can be signalled using the status outputs:
-flow direction (F/R mode)
-limits
-error messages
-active range in case of range change-over
-inverse operation of A1 and A2 or D1 and D2,
i.e. used as change-over switch with common centre grounding contact A or D .
•Connection diagrams see Section 2.6
•Schematic wiring diagram for status outputs A1/A2 and D1/D2.
This status outputs have MOSFET switches as outputs which switch direct and alternating voltages similar to relay contacts.
2.5Control inputs C1 and C2
•Control inputs C1 and C2 are electrically connected (common centre grounding contact C ) but electrically isolated from all other circuits.
•Setting data and functions can note down in the Table in Sect. 3.
Please also refer to Section 2.7 ”Standard factory settings”.
•All operating data and functions are adjustable, see Sections 4.4 and 5.9, Fct. 1.11-1.12.
•Active mode: uses the internal power supply, terminals E+/E-
Passive mode: requires external power supply, Uext ≤ 32V DC/24V AC, I ≤ 10mA
•The following operating conditions can be initiated using the control inputs:
-external range change
-holding of output values
-zeroing the outputs
-resetting the internal totalizer
-resetting (deleting) the error messages
•Connection diagrams see Section 2.6
20 |
IFC 110 F |
05/2003 |
Part A System installation and start-up |
Sect. 2.6 |
2.6Connection diagrams of outputs and inputs
IMPORTANT!
For EEx versions, also pay regard to all directions included in Sect. 6.1 and 13.
Only the EEx flow sensor may be installed in the hazardous area. The EEx certified signal converter must be installed outside the hazardous area!
I |
Current output (included HART®) |
P, A1* Pulse output
A1*, A2, Status outputs
D1, D2
C1, C2 Control inputs
Totalizer
-electromechanical (EMC) - electronic (EC)
milliampmeter
0-20 mA or 4-20 mA and other
Key, N/O contact
External voltage source (Uext), DC or AC voltage, connection polarity arbitrary
DC voltage,
external power source (Uext), note connection polarity
Please note ! Unwired contacts or terminals may not have any conductive connection with other electrically conducting parts.
Interface operation with HART® or RS 485 (Option) see Sect. 6.4.
*selectable as status output A1 or pulse output A1
Active mode: the IFC 110 F supplies the power required for operating (driving) the receiver instruments. Observe the max. operating data (terminals E+ and E-).
Passive mode: an external power supply source (Uext) is required for operating (driving) the receiver instruments.
Groups A / C / D / E / I / P are electrically isolated from each other and from all other input and output circuits.
Please note: common reference potential
A for A1 and A2
C for C1 and C2
D for D1 and D2
05/2003 |
IFC 110 F |
21 |
|
Sect. 2.6 |
|
Part A System installation and start-up |
|
|
{ Current output Iactive |
|
Current output Iactive with automatic |
|
|
| |
|
||
|
|
|
range change BA |
|
|
|
|
without external change-over relay |
|
|
|
|
low range |
|
|
|
|
high range |
|
|
|
|
Ri 15 - 500 Ω |
|
|
Ri 15 - 500 Ω |
|
|
|
|
|
|
|
|
}Current output Ipassive
(see Sect. 6.8 passive/active operation
selectable with internal power supply E or external power supply Uext.
Uext. |
15 - 22 V DC |
22 - 32 V DC |
Ri |
0 - 500 Ω |
0 - 800 Ω |
|
|
|
Forward/reverse flow meausrement (F/R mode)
for pulse and current outputs (P and Iactive) without external change-over relay
reverse |
reverse |
flow |
flow |
forward |
forward |
flow |
flow |
|
Ri 15 - 500 Ω |
Electronic totalizers must be connected as shown in the connection diagrams for pulse output P on the following page.
Pulse output A1 active |
Pulse output A1 passive |
for electromechanical totalizers (EMC) |
for electromechanical totalizers (EMC) |
Ri ≥ 160 Ω |
Uext. ≤ 32 V DC / ≤ 24 V AC |
I ≤ 10 mA |
I ≤ 100 mA |
oder umschaltbar auf |
|
|
Uext.2 ≤ 32 V DC I ≤ 200 mA |
|
22 |
IFC 110 F |
05/2003 |
Part A System installation and start-up |
Sect. 2.6 |
Pulse output Pactive |
Pulse output Pactive |
for electronic totalizers (EC) |
for electronic totalizers (EC) |
for frequencies ≤ 1 kHz |
for frequencies > 1 kHz |
R1 |
= 1 kΩ/0.5 W I ≤ 20 mA |
Ri EC > 100 kΩ R = 1 kΩ/0.35 W I ≤ 30 mA |
|||
|
|
|
|
|
|
R2 |
/ 0.2 W |
10 kΩ |
1 kΩ |
270 Ω |
|
UEC max |
22 V |
12 V |
5 V |
|
Pulse output Ppassive
for electronic totalizers (EC)
for frequencies ≤ 1 kHz
Uext
I
R
PR
≤≤ 32 V DC / ≤ 24 V AC
≤≤ 30 mA
=1 - 10 kΩ
≥Uext 2
R
for frequences > 1 kHz
|
Uext |
= ≤ 24 V DC / AC |
|
|
|
Ri EC |
≥ 100 kΩ |
|
|
|
|
|
|
|
|
I |
~ 30 mA |
~ 18 mA |
|
|
R |
560 Ω |
1 kΩ |
|
|
PR |
0.5 W |
0.35 W |
|
|
UEC |
16 V |
18 V |
|
|
|
|
|
|
*Shielded cables
must be used to prevent radio interference at pulse output frequencies > 100 Hz
05/2003 |
IFC 110 F |
23 |
Sect. 2.6 |
Part A System installation and start-up |
Status outputs D1 / D2 / A1 / A2 active |
Status outputs D1 / D2 / A1 / A2 passive |
I ≤ 100 mA |
Uext. ≤ 32 V DC / ≤ 24 V AC |
|
|
I ≤ 100 mA |
|
9 e.g. message display |
9 |
e.g. message display |
|
|
|
|
|
|
Control inputs C1 / C2 active |
|
Control inputs C1 / C2 passive |
Contacts 24 V, 10 mA |
Uext. ≤ 32 V DC / ≤ 24 V AC |
I ≤ 7 mA |
I ≤ 10 mA |
24 |
IFC 110 F |
05/2003 |
Part A System installation and start-up |
Sect. 2.7 |
2.7Standard factory settings
•All operating data are set at the factory in accordance with the specifications contained in the order.
•If no specifications are made in the order, instruments will be delivered with the standard parameters and functions indicated in the table below.
•To facilitate the start-up of the instrument, current and pulse outputs are set to handle measurements in ”two flow directions” so that the current flow rates and volumes are displayed and/or counted independent of the direction of flow. The figures displayed may have a preceding sign.
•Such factory setting of current and pulse outputs may lead to measuring errors, particularly when volumes are metered and totalized.
•If e.g. pumps are switched off and ”backflows” occur which are not within the low-flow cutoff (SMU) range, or if separate displays and counts are required for both flow directions.
•To avoid faulty measurements, it may therefore be necessary to change the setting of the
following functions: |
|
- SMU low-flow cutoff |
Fct. 1.03, Section 5.3 |
- display |
Fct. 1.04, Section 5.5 |
- current output I |
Fct. 1.05, Section 5.6 |
- pulse output P |
Fct. 1.06, Section 5.7 |
•For special applications, such as pulsating flows, see Sections 6.5 to 6.10
Standard factory settings
Fct. No. |
Function |
Setting |
1.01 |
Full-scale range |
See instr. nameplate |
|
|
of flow sensor |
1.02 |
Time constant |
3 Sec. for display, |
|
|
pulse, current and |
|
|
status ouputs |
1.03 |
Low-flow cutoff |
ON: 1% |
|
|
OFF: 2% |
1.04 |
Display |
|
|
flow rate |
m³/h |
|
totalizer |
m³ |
1.05 |
Current output |
Iactive |
|
function |
2 directions |
|
range |
4-20 mA |
|
error detection |
22 mA |
1.06 |
Pulse output P |
|
|
function |
2 directions |
|
pulse value |
1000 pulses/Sec. |
|
pulse width |
symmetric |
1.07 |
Pulse output 2, A1 |
|
|
function |
2 directions |
|
pulse value |
1 pulse/s |
|
pulse width |
50 ms |
Fct. No. |
Function |
Setting |
1.08 |
Status output A2 |
ON |
1.09 |
Status output D1 |
All error |
1.10 |
Status output D2 |
Indication F/R |
1.11 |
Control input C1 |
Totalizer reset |
1.12 |
Control input C2 |
OFF |
3.01 |
Language |
German |
3.02 |
Flow sensor |
|
|
meter size |
See instr. nameplate |
|
direction of flow |
+ direction, |
|
|
see arrow on |
|
|
flow sensor |
3.04 |
Entry code |
NO |
3.05 |
User unit |
Liter/h |
3.06 |
Application |
|
|
flow |
steady |
|
empty pipe |
NO |
|
ADC gain |
automatic |
|
special filter |
OFF |
3.07 |
Hardware |
|
|
terminal A1 |
pulse output A1 |
|
selfcheck |
NO |
05/2003 |
IFC 110 F |
25 |
Sect. 3 |
Part A System installation and start-up |
3 Start-up
•Before connecting to power, check that the instrument is correctly installed as described in Sections 1 and 2.
•The flowmeter, flow sensor and signal converter are delivered ready for operation. All operating data are set at the factory in accordance with your specifications.
Please also refer to Section 2.7 ”Standard factory settings”.
•Switch on the power supply. The flowmeter immediately begins to measure the flow.
•When the power supply is switched on, the display successively shows START UP and READY. Then the current flow rate and/or the current totalizer count are displayed. Displays are either steady or cyclic depending on the setting described for Fct. 1.04.
•2 light-emitting diodes (LED) in the ”diagnostics” field on the front panel of the signal converter indicate the status of measurement.
LED displays |
Status of measurement |
Green ”normal” LED |
Everything O.K. |
is flashing |
|
Green ”normal” LED |
Momentary overload of outputs and/or A/D converter. |
and red ”error” LED |
Detailed error messages by setting Fct. 1.04 DISPLAY, |
are flashing alternately |
subfunction ”MESSAGES” to ”YES”, see Sections 4.4 and 5.5. |
Red ”error” LED is |
Fatal Error, see Sections 7.3 and 7.4 |
flashing |
|
IMPORTANT!
For EEx versions, also pay regard to all directions included in Sect. 6.1 and 13.
Only the EEx flow sensor may be installed in the hazardous area. The EEx certified signal converter must be installed outside the hazardous area!
26 |
IFC 110 F |
05/2003 |
|
Part B |
IFC 110 F Signal converter |
|
|
Sect. 3 |
|||
|
Setting data: Here you can note down the settings of the signal converter ! |
|||||||
|
|
|
|
|
|
|
|
|
|
Fct. No. |
|
|
Function |
|
Settings |
|
|
|
1.01 |
|
|
Full-scale range |
|
|
|
|
|
1.02 |
|
|
Time constant |
|
|
|
|
|
1.03 |
|
|
Low-flow cut-off |
|
ON: |
OFF: |
|
|
1.04 |
|
|
Display |
|
Flow |
|
|
|
|
|
|
|
|
Totalizer |
|
|
|
|
|
|
|
|
Messages |
|
|
|
|
|
|
|
|
Trend |
|
|
|
1.05 |
|
|
Current output I |
|
Function |
|
|
|
|
|
|
|
|
Reverse range |
|
|
|
|
|
|
|
|
Range I |
|
|
|
|
|
|
|
|
Error |
|
|
|
1.06 |
|
|
Pulse output P |
|
Function |
|
|
|
|
|
|
|
|
Pulswidth |
|
|
|
|
|
|
|
|
Pulse value |
|
|
|
1.07 |
|
|
Pulse output A1 or |
|
|
|
|
|
|
|
|
Status output A1 |
|
|
|
|
|
|
|
|
(for setting see below, Fct. 3.07, |
|
|
|
|
|
|
|
|
terminal A1) |
|
|
|
|
|
1.08 |
|
|
Status output A2 |
|
|
|
|
|
1.09 |
|
|
Status output A3 |
|
|
|
|
|
1.10 |
|
|
Status output A4 |
|
|
|
|
|
1.11 |
|
Control input C1 |
|
|
|
|
|
|
1.12 |
|
Control input C2 |
|
|
|
|
|
|
3.01 |
|
|
Language |
|
|
|
|
|
3.02 |
|
Flow sensor |
|
Meter size |
|
|
|
|
|
|
|
|
|
GK value |
|
|
|
|
|
|
|
|
Field frequency |
|
|
|
|
|
|
|
|
Power frequency |
|
|
|
|
|
|
|
|
Flow direction |
|
|
|
3.04 |
|
|
Entry code required ? |
|
no |
yes |
|
|
|
|
|
|
|
→ → → ↑ ↑ ↑ |
||
|
3.05 |
|
|
User-defined unit |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
3.06 |
|
|
Application |
|
Flow is |
steady |
|
|
|
|
|
|
|
|
pulsating |
|
|
|
|
|
|
|
Empty Pipe |
no |
|
|
|
|
|
|
|
Detection (EPD) |
yes |
|
|
3.07 |
|
|
Hardware-settings |
|
Terminal A1 is |
Pulse output |
|
|
|
|
|
|
|
or |
Status output |
|
|
3.08 |
|
Measuring point |
|
|
|
|
|
|
3.09 |
|
Communication |
|
of |
|
|
|
|
|
|
|
|
|
HART or |
|
|
|
|
|
|
|
|
KROHNE RS 485 |
||
|
|
|
|
|
|
Address: |
|
|
|
|
|
|
|
|
Baud rate: |
|
|
|
|
|
|
|
|
|
|
|
|
|
05/2003 |
IFC 110 F |
27 |
|
Sect. 4.1 |
Part B IFC 110 F Signal converter |
4 Operating of the signal converter
4.1KROHNE operating concept
28 |
IFC 110 F |
05/2003 |
Part B IFC 110 F Signal converter |
Sect. 4.2 |
4.2Operating and control elements
|
|
|
The instrument can be operated |
|
|
|
by means of .... |
|
|
|
… the 15 keys and accessible |
|
|
|
after removal of the glass cover, |
|
|
|
… the 3 magnetic sensors and the |
|
|
|
bar magnet without opening the |
|
|
|
housing (optional). |
{ Display, 1st line |
Displaying numerical data |
||
| Display, 2nd line |
Displaying units and texts |
||
} Display, 3rd line |
6 arrows to mark the current display |
||
flow rate |
+ |
current flow rate |
|
totalizer |
totalizer |
||
|
- |
totalizer |
|
|
Σ |
sum totalizer (+ and -) |
|
control in |
1/2 |
control input 1 or 2 active |
5 keys for operating the signal converter ← → ↑ ↓
10 keys for direct numerical setting of function values (not function numbers)
Compass field showing that a key is pressed
magnet active LED green/red, magnetic sensors active
green |
= built-in magnetic sensors (optional), see |
red |
= operation of one of the 3 magnetic sensors |
3 magnetic sensors (optional), operated by bar magnet without opening the housing, function of the sensors as described for the three keys → ↑, see .
diagnostics |
2 LEDs signalling the status of measurement |
|
|
normal |
green LED |
= correct measurement, everything O.K. |
|
error |
red LED |
= error, parameter or hardware error |
|
IMoCom |
IMoCom bus, multipoint connector for connecting external |
|
|
|
supplementary equipment, see Section 6.4, slide window to the left |
|
|
|
|
|
|
05/2003 |
|
IFC 110 F |
29 |
Sect. 4.3 |
Part B IFC 110 F Signal converter |
4.3Key functions
In the following, the cursor or flashing part of the display is shown against a grey background.
To start operator control |
|
|
|
|
|
|
|
|
Measuring mode |
|
|
|
Operator control mode |
||||
|
|
|
|
|
|
|
|
|
1 3 . 5 7 1 |
|
|
|
|
F c t . |
|
0 |
|
|
→ |
|
1. |
|||||
m 3 / h |
|
|
|
|
|
|
||
|
|
|
|
O P E R A T I O N |
||||
|
|
|
|
|
|
|
|
|
PLEASE NOTE: if ”YES” is selected in Fct. 3.04 ENTRY CODE, ”CodE 1 - - - - - - - - -” appears in the display after pressing the → key.
Enter the password for the entry code which is a sequence of 9 keys: → → → ↑ ↑ ↑
(each keystroke confirmed by ” * ”).
To terminate operator control
Press key any number of times until one of the following menus
Fct. 1.0 OPERATION, Fct. 2.0 TEST or Fct. 3.0 INSTALL is displayed.
|
|
|
|
|
|
Press key |
|||||
|
|
|
|
|
|
|
|
|
|
|
|
|
F c t . |
|
0 |
|
|
|
|
|
|
|
|
3. |
|
|
|
|
|
|
|
||||
|
|
|
|
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
|
|
||
|
I N S T A L L. |
|
|
|
S T O R E Y E S |
||||||
|
|
|
|
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
Store new parameters: acknowledge by |
|||
|
|
|
|
|
|
|
|
pressing key . Measuring mode is |
|||
|
|
|
|
|
|
|
|
continued with new parameters. |
|||
|
|
|
|
|
|
|
|
New parameters not to be stored: |
|||
|
|
|
|
|
|
|
|
press key ↑ to display |
|||
|
|
|
|
|
|
|
|
”STORE NO”. |
|||
|
|
|
|
|
|
|
|
Measuring mode is continued with the ”old” |
|||
|
|
|
|
|
|
|
|
parameters after pressing key . |
Keyboard with 10 keys
The keyboard with the 10 keys (0-9) is used for setting all flashing numbers (cursor).
Exception: the digits of the function numbers, such as Fct. 1.03, can only be changed with keys ↑ or ↓.
30 |
IFC 110 F |
05/2003 |