KROHNE IFC-090i User Manual

0 (0)
KROHNE IFC-090i User Manual

IFC090 FF 01/2006

7.10025.21.00

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Supplementary

Installation and

Operating Instructions

IFC 090, IFC 090 i

With FOUNDATION

FIELDBUS Communication

KROHNE Messtechnik GmbH & Co. KG

Tel.: 0203-301 309 Fax: 0203-301389

Supplementary Documentation

Page 2 of 44

IFC090, IFC090 i with FF

 

IFC090 FF 01/2006

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Contents:

1

Introduction

4

2

Installation and Operation

4

 

2.1

Technical Data IFC090 FF

4

 

2.2

Electrical Connection of Foundation Fieldbus Devices

4

 

2.3

Installation in the Hazardous Area, Bus Cable

5

 

2.4

Shielding and Grounding

6

 

2.5

IFC090 Menu Settings for Foundation Fieldbus

6

 

2.6

Foundation Fieldbus Functional Blocks

6

3

Foundation Fieldbus Principles

7

 

3.1

Resource Block

7

 

3.2

Transducer Block

8

 

3.3

Function Blocks

8

4

IFC090-FF Block Description

9

 

4.1

Resource Block

10

 

4.2

Transducer Block

14

 

4.3

Analog Input Block (Flow)

16

 

4.4

Integrator Blocks 1 and 2 (Flow(+)- and Flow(-)-Totalizer)

22

5

IFC090-FF Configuration

28

 

5.1

Resource Block Configuration

28

 

5.1.1

Resource Block Mode Handling

28

 

5.1.2

Write Protection

28

 

5.1.3

Resource State Re-Initialization

29

 

5.2

Transducer Block Configuration

29

 

5.2.1

Transducer Block Mode Handling

30

 

5.2.2

IFC090-FF Zero Point Calibration

30

 

5.3

Analog Input Block Configuration

30

 

5.3.1

Process Value Selection

31

 

5.3.2

Linearization and Scaling

31

 

5.3.3

Filtering

32

 

5.3.4

Input/Output Options

32

 

5.3.5

Output Status Options

32

 

5.3.6

Process Alarms

33

 

5.4

Integrator Blocks Configuration

34

 

5.4.1

Integrator Block Mode Handling

34

 

5.4.2

Integration Input – Rate or Accumulated Pulses

34

 

5.4.3

Adaptation of Integrator Inputs

34

 

5.4.4

Setting the Flow Direction

36

 

5.4.5

Type of Integration

36

 

5.4.6

Integrator Reset Strategies

37

 

5.4.7

Trip and Pre-trip Handling

39

 

5.4.8

Status Handling

39

 

5.4.9

Input Value Handling

39

KROHNE Messtechnik GmbH & Co. KG · Ludwig-Krohne-Str. 5 D-47058 Duisburg Tel.: 0203-301 309 Fax: 0203-301389 · E-mail: krohne@krohne.de

Supplementary Documentation

Page 3 of 44

IFC090, IFC090 i with FF

 

IFC090 FF 01/2006

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6 Troubleshooting

42

6.1

BLOCK_ERROR

42

6.1.1

Resource Block

42

6.1.2

Transducer Block

42

6.1.3

Analog Input Block

43

6.1.4

Integrator Blocks

44

6.2

Transducer Block XD_ERROR

44

6.3

Measurement Value Status

44

KROHNE Messtechnik GmbH & Co. KG · Ludwig-Krohne-Str. 5 D-47058 Duisburg Tel.: 0203-301 309 Fax: 0203-301389 · E-mail: krohne@krohne.de

Supplementary Documentation

 

Page 4 of 44

IFC090, IFC090 i with FF

 

 

IFC090 FF 01/2006

Introduction

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1 Introduction

These instructions are supplementary to the “Installation and Operating Instructions IFC 090 K / F“. The details depicted therein, in particular the Safety Information are valid and should be adhered to. The present Supplementary Instructions provide additional information for the devices when being operated and connected to a Foundation Fieldbus.

Note: Please set the controller to manual mode before changing parameters of the IFC 090.

The present Supplementary Instruction for the IFC 090 with Foundation Fieldbusinterface, plus a diskette with the DD and CCF file are included in our scope of supply, in addition to those items delivered for the standard device.

2 Installation and Operation

2.1Technical Data IFC090 FF

Hardware

 

Physical

to IEC 61158-2 and the FISCO model

Bus characteristics:

9... 30 V; 0.3 A max.; 4.2 W max.

Base current

10 mA

FDE

bus with separate fault detection electronics

Fault current

6 mA; (fault current = max. continuous current – base current)

Starting current

lower than the base current

“Ex“ approval

EEx ia IIC T6 or EEx ib IIC/IIB T6 in conformity with the FISCO model

Connection

independent of polarity

Software

 

DD, CFF File

supplied on diskette, available also in the KROHNE Downlaod Center

Functional blocks

flow [m3/s], integrator 1 [m3], integrator 2 [m3]; units are default units

Operator control

local display and operator interface at device

2.2Electrical Connection of Foundation Fieldbus Devices

Connect the bus cable as shown in the figure.

Connect the cable cores to terminals D and DI.. Polarity reversal will not have any effect.

The cable shield should be connected with minimum length to the FE functional ground.

The equipotential bonding conductor must be connected to the device by connecting it to FE functional ground.

KROHNE Messtechnik GmbH & Co. KG · Ludwig-Krohne-Str. 5 D-47058 Duisburg Tel.: 0203-301 309 Fax: 0203-301389 · E-mail: krohne@krohne.de

Supplementary Documentation

 

 

Page 5 of 44

IFC090, IFC090 i with FF

 

 

 

IFC090 FF 01/2006

Installation and Operation

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Foundation Fieldbus with Current Output (passive) Non Ex Version

 

current

power-

FE

fieldbus

output

supply

D

 

D

 

 

 

 

I

 

 

 

I

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

U min

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FE

4-20mA

= 8V

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

bus-

 

 

 

 

 

 

 

 

 

 

 

 

connection

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

U max = 30V

Outputs intrinsically safe

current

fieldbus

power

output

supply

I

 

 

 

I

D

D

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

U min

 

4-20mA

= 8V

 

 

 

busconnection

U max = 30V

Foundation Fieldbus with Binary Output (passive) Non Ex Version

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

switching

 

power-

FE

 

fieldbus

 

output

 

supply

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

D

D

 

 

 

 

 

 

 

 

 

B1

B1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

bus-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

connection

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Outputs intrinsically safe

 

 

 

 

 

 

 

 

 

switching

 

 

 

 

 

 

 

 

 

 

power

 

 

 

 

 

 

 

 

 

output

 

fieldbus

 

supply

 

 

 

 

 

 

 

 

B1

B1

 

 

 

D

D

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

busconnection

1

2.3Installation in the Hazardous Area, Bus Cable

We recommend that a Foundation Fieldbus network in the hazardous area should be projected in accordance with PTB’s FISCO model. The FISCO-Model is based on the following conditions:

all electrical components which should be connected to the bus must be approved according to the FISCO model (even the termination)

the maximum cable length should not exceed 1000 m,

the values of the cable are within the following ranges: R´=15...150Ω/km; L´=0,4...1mH/km; C´=80...200nF/km, other limitations for the cable than the FISCO limitations are not existent. Nevertheless, a twisted pair and shielded cable is strongly recommended. Example: a good quality cable could have the following data: 44Ω/km, <90nF/km, <3dB attenuation at 39 kHz and 100 Ohm impedance at 31,25kHz.

the approved input values of the field devices (Uo, Io, Po) comply to the output values of the power supply (e.g. segment coupler) according to UI ≤ Uo, II ≤ Io und PI ≤ Po.

KROHNE Messtechnik GmbH & Co. KG · Ludwig-Krohne-Str. 5 D-47058 Duisburg Tel.: 0203-301 309 Fax: 0203-301389 · E-mail: krohne@krohne.de

Supplementary Documentation

 

 

Page 6 of 44

IFC090, IFC090 i with FF

 

 

 

IFC090 FF 01/2006

Installation and Operation

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2.4Shielding and Grounding

For optimum electromagnetic compatibility of systems it is extremely important that the system components, and particularly the bus cables connecting the components, are shielded and that such shields - if possible - form an unbroken cover.

Hence, it follows that, for use in non-hazardous duty systems, the cable shield should be grounded as often as possible.

In “Ex“ systems an adequate equipotential bonding in the hazardous and non-hazardous location along the entire fieldbus installation is strongly recommended. Multiple grounding of the shield is of advantage.

Note: The use of twisted and shielded cables is strongly recommended, otherwise EMC protection of the IFC 090 cannot be assured.

2.5IFC090 Menu Settings for Foundation Fieldbus

(see also Section 4 in the Installation and Operating Instructions for the IFC090)

The following settings need to be made for operation of the IFC 090 on a Foundation Fieldbus network. Note that the address can be set by the service “set slave address” as well.

Function (Fct.)

Description

 

 

 

 

3.9 COM

Select function for the communication port

 

♦ OFF

♦ HART

♦ PROFI PA *

 

 

 

 

• Note: * indicates Foundation Fieldbus Communication when selected

2.6Foundation Fieldbus Functional Blocks

The IFC090 supports the H1 Foundation Fieldbus Communication Standard FF-003-2.2-1-1, Version 1.4. Additionally, all relevant parameters in the device are offered via the FF interface. The IFC 090 defines the following functional blocks:

Three Function Blocks (FB): One Analog Input-FB for flow and two integrator-FBs for integration. Reset function is possible.

One Transducer Block for electromagnetic flow measurement.

One standard Resource Block.

KROHNE Messtechnik GmbH & Co. KG · Ludwig-Krohne-Str. 5 D-47058 Duisburg Tel.: 0203-301 309 Fax: 0203-301389 · E-mail: krohne@krohne.de

Supplementary Documentation

 

 

Page 7 of 44

IFC090, IFC090 i with FF

 

 

 

IFC090 FF 01/2006

Foundation Fieldbus Principles

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3 Foundation Fieldbus Principles

The Foundation Fieldbus is a Local Area Network (LAN) for connecting field devices like sensors and actuators. One of the main benefits of Foundation Fieldbus is line saving in comparison to the traditional 4 ... 20 mA technology.

The different device functions are implemented in a block-based scheme within a User Application. In this block scheme, a distinction is made between the following kinds of blocks (see Figure 1):

Resource Block,

Transducer Block(s) and

Function Block(s).

Figure 1: Foundation Fieldbus block scheme

3.1Resource Block

Each FF device possesses exactly one Resource Block describing the specific features of the fieldbus device. The Resource Block is not related to any functional process of the device, but contains data that are specific for the device (e.g. device name, serial number, supported features, etc).

In addition, the Resource Block provides dynamic diagnostic data giving information on the current state of the hardware.

A basic set of Resource Block parameters is specified by Fieldbus Foundation (see FF-891, 3.1). This set can be extended by additional manufacturer specific parameters (the IFC090-FF possesses the Foundation specified parameters only).

KROHNE Messtechnik GmbH & Co. KG · Ludwig-Krohne-Str. 5 D-47058 Duisburg Tel.: 0203-301 309 Fax: 0203-301389 · E-mail: krohne@krohne.de

Supplementary Documentation

 

 

Page 8 of 44

IFC090, IFC090 i with FF

 

 

 

IFC090 FF 01/2006

Foundation Fieldbus Principles

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3.2Transducer Block

Transducer Blocks represent the interface between the device specific hardware (i.e. input/output functions) and the FF specified Function Block model. Since there might be multiple functions in a device (measurement values, positioning functions, etc), an FF device can have several Transducer Blocks1.

They provide device specific information in terms of sensor/actuator functions (e.g. type of sensor, range of process value, etc) and they make available the process values to the function blocks or provide the actuator input values obtained from function blocks to the hardware respectively.

3.3Function Blocks

The main functional behavior of the FF device is implemented in one or several Function Blocks. Depending on the device type there are Input Blocks (e.g. flow device → Analog Input Block, Discrete Input, etc), Output Blocks (e.g. valve → Discrete Input, etc), or Control Blocks (PID, etc). These blocks have input and/or output parameters to be linked to other devices and to control systems by the Fieldbus.

1 Note: This does not imply that an FF device has to have several Transducer Blocks if it provides several functions.

KROHNE Messtechnik GmbH & Co. KG · Ludwig-Krohne-Str. 5 D-47058 Duisburg Tel.: 0203-301 309 Fax: 0203-301389 · E-mail: krohne@krohne.de

Supplementary Documentation

 

 

Page 9 of 44

IFC090, IFC090 i with FF

 

 

 

IFC090 FF 01/2006

IFC090-FF Block Description

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4 IFC090-FF Block Description

The IFC090-FF consists of the following blocks (see figure 2):

1 Resource Block,

1 Transducer Block (standard flow),

1 Analog Input Block (flow value) and

2 Integrator Blocks (1 for positiveand 1 for negative flow integration)

Figure 2: IFC090-FF block scheme

In the following, the different block parameters are described in detail.

KROHNE Messtechnik GmbH & Co. KG · Ludwig-Krohne-Str. 5 D-47058 Duisburg Tel.: 0203-301 309 Fax: 0203-301389 · E-mail: krohne@krohne.de

Supplementary Documentation

 

 

Page 10 of 44

IFC090, IFC090 i with FF

 

 

 

IFC090 FF 01/2006

IFC090-FF Block Description

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4.1Resource Block

Table 1 lists the Resource Block parameters in alphabetical order (this list provides a description of the various parameters only; for a more detailed description of how to configure these parameters: see chapter below.

Parameter

Access

ACK_OPTION

R/W

ALARM_SUM Mix

ALERT_KEY

R/W

 

 

BLOCK_ALM

R

BLOCK_ERR R

CLR_FSTATE R/W

CONFIRM_TIME R/W

Description

Allows to enable automatic acknowledge of Resource Block alarms. The following settings are valid for Resource Block:

Unack Alarm 1

(Discrete Alarm)

clearing of soft write lock

Unack Alarm 8

(Block Alarm)

block mode switches to Out of Service

If set, the respective alarm doesn’t have to be acknowledged when occurring.

see also: ALARM_SUM, WRITE_LOCK, WRITE_ALM

Display of process alarms. The current alarm is displayed in the current field and can have the following values:

Discrete Alarm the soft write lock was cleared

Block Alarm block mode switches to Out of Service

The additional fields unacknowledged and unreported give respective information about the current alarm state. The field disabled, which is the only writable field of this parameter, can be used to disable these alarms.

see also: ACK_OPTION

ALERT_KEY parameter contains the identification number of the plant unit. It helps to identify the location (plant unit) of an event. The handling of this parameter is up to the control system or control person, respectively.

Display of current block state. Field subcode gives information about the state current errors. The following errors can occur:

Configuration Error

Change in Simulation Jumper Local Override

Device Fault State Memory Failure Lost Static Data Lost NV Data Power-up

Block was put Out of Service

The remaining fields give information about the state and the occurence of this alarm. Display of active block errors. The following errors are possible:

Out of Service

block is in Out of Service mode

Power-up

power supply of IFC090-FF was interrupted

Device needs Maintenance now

fatal error of IFC090-FF hardware

Memory Failure

memory of device has errors

Input Failure

measurement value not o.k.

Other

any other hardware problem

Writing a Clear to this parameter will clear the device fault state if the field condition, if any, has cleared.

NOTE:

This parameter is not supported! see also: FAULT_STATE

Time the resource waits for receipt confirmation of an earlier sent report, before trying to send a new one. If zero (0), no retry will be performed.

KROHNE Messtechnik GmbH & Co. KG · Ludwig-Krohne-Str. 5 D-47058 Duisburg Tel.: 0203-301 309 Fax: 0203-301389 · E-mail: krohne@krohne.de

Supplementary Documentation

 

 

Page 11 of 44

IFC090, IFC090 i with FF

 

 

 

IFC090 FF 01/2006

IFC090-FF Block Description

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Parameter

Access

CYCLE_SEL

R/W

CYCLE_TYPE R

DD_RESOURCE R

DD_REV R

DEV_REV R

DEV_TYPE R

FAULT_STATE R

FEATURES R

FEATURE_SEL R/W

FREE_TIME R

FREE_SPACE R

GRANT_DENY R/W

HARD_TYPES R

ITK_VER R

LIM_NOTIFY R/W

Description

Used to select the block execution method for this resource. The following methods are available:

Scheduled

Completion of block execution

see also: CYCLE_TYPE

Identifies the block execution methods available for this resource.

It is possible to deliver devices which have the DD for its resource within the device. This parameter assigns the tag where to find the DD in the resource. Since the IFC090-FF doesn't come with a 'build-in' DD, this value is blank.

Revision associated with the DD of the resource – used by interface devices to locate the DD file for the resource.

KROHNE revision number associated with this resource – used by interface devices to locate the DD file for the resource.

KROHNE model number of the IFC090-FF – used by interface devices to locate the DD file for the resource.

Condition set by loss of communication to an output block.

NOTE:

Since the IFC090-FF doesn’t have an output block, this parameter isn’t supported. Used to show supported resource block options. The following features are supported by the IFC090-FF:

Reports

Soft Write Lock

see also: FEATURE_SEL

Used to select supported features. The following features are selectable:

Reports

enable sending of alert reports

Soft Write Lock

enable soft write locking of parameters

see also: FEATURE_SEL

Available time for configuration of further blocks.

NOTE:

Since the IFC090 blocks are preconfigured, this value is always zero (0). Available memory for configuration of further blocks.

NOTE:

Since the IFC090 blocks are preconfigured, this value is always zero (0).

Options for controlling access of host computer and local control panels to operating, tuning and alarm parameters of the block.

NOTE:

This parameter is not supported by IFC090-FF

The type available input signal that is delivered by the Transducer Block and used as Analog Input Block input parameter. For the IFC090-FF this is ‘Scalar Input’ (1).

Major revision number of the interoperability test case used in certifying this device as interoperable.

NOTE:

Due to an error, this value is ‘0’, but has to be ‘4’ (since the IFC090-FF is interoperable with interoperability test case version 4).

Maximum number of unconfirmed alert notifies messages allowed. This number always has to be less than MAX_NOTIFY.

see also: MAX_NOTIFY

KROHNE Messtechnik GmbH & Co. KG · Ludwig-Krohne-Str. 5 D-47058 Duisburg Tel.: 0203-301 309 Fax: 0203-301389 · E-mail: krohne@krohne.de

 

Supplementary Documentation

 

 

Page 12 of 44

 

IFC090, IFC090 i with FF

 

 

 

 

 

 

 

IFC090 FF 01/2006

 

 

 

 

IFC090-FF Block Description

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Parameter

 

 

Access

 

 

Description

 

 

 

 

 

MANUFAC_ID

R

 

Manufacturer identification number. For KROHNE devices this is always

 

 

 

 

 

 

 

 

 

00012C16 = 30010 = KROHNE

 

 

 

 

MAX_NOTIFY

R

 

Maximum number of unconfirmed notifies messages possible.

 

 

 

 

 

 

 

 

see also: LIM_NOTIFY

 

 

 

 

 

MEMORY_SIZE

 

R

 

Available configuration memory in the empty resource.

 

 

 

 

 

 

 

 

NOTE:

 

 

 

 

 

 

 

 

 

 

 

 

This parameter is not supported by IFC090.

 

MIN_CYCLE_T

R

 

Time duration of the shortest cycle interval of which the IFC090 is capable. Within this

 

 

 

 

 

 

 

 

cycle all Function Blocks (1 Analog Input + 2 Integrators) have to be executed for one

 

 

 

 

 

 

 

 

time.

 

 

 

 

 

MODE_BLK

Mix

 

Display of the current (actual), desired (target), possible (permitted) and normal modes

 

 

 

 

 

 

 

 

of the Resource Block. By writing a permitted value to the target field, you can control

 

 

 

 

 

 

 

 

the execution modes of the block. The following block modes are allowed for the

 

 

 

 

 

 

 

 

IFC090-FF Resource Block:

 

 

 

 

 

 

 

 

 

 

 

Automatic Mode (AUTO)

 

 

 

 

 

 

 

 

 

 

 

In this mode, the complete resource is able to execute. All other blocks

 

 

 

 

 

 

 

 

(Transducer, Analog Input, Integrator) can switch to a mode different from Out of

 

 

 

 

 

 

 

 

Service)

 

 

 

 

 

 

 

 

 

 

 

 

Out of Service (OOS)

 

 

 

 

 

 

 

 

 

 

 

In this mode, the complete

resource stops its execution. For the other blocks

 

 

 

 

 

 

 

 

it is not possible to switch to AUTO mode, unless the Resource Block does.

 

 

 

 

 

 

 

 

NOTE:

 

 

 

 

 

 

 

 

 

 

 

 

Under certain conditions (e.g. RS_STATE = ONLINE_LINKING) the Resource Block is

 

 

 

 

 

 

 

 

not capable of switching to AUTO mode.

 

 

 

 

 

 

 

 

see also: RS_STATE

 

 

 

 

 

NV_CYCLE_T

R

 

Minimum time interval between two cycles of writing non-volatile parameters OUT, PV

 

 

 

 

 

 

 

 

and FIELD_VAL. Since these values are not saved, this value is always zero (0) which

 

 

 

 

 

 

 

 

means don’t save these parameters.

 

RESTART

 

R/W

 

Allows a manual restart to be initiated. Several degrees of restart are possible:

 

 

 

 

 

 

 

 

RUN

 

Setting for normal operation.

 

 

 

 

 

 

 

 

RESTART RESOURCE

Warm start of the IFC090-FF.

 

 

 

 

 

 

 

 

RESTART WITH DEFAULTS

Sets all FF parameters to their default values.

 

 

 

 

 

 

 

 

 

 

 

To be used with caution!

 

 

 

 

 

 

 

 

RESTART PROCESSOR

Cold start of IFC090 measurement electronics

 

 

 

 

 

 

 

 

 

 

 

and warm start of FF process.

 

RS_STATE

R

 

State of the function block application state machine. The following states are possible:

 

 

 

 

 

 

 

 

ONLINE

Normal operation state: All defined links are established.

 

 

 

 

 

 

 

 

INITIALIZATION

Initialization state: All alarms will be confirmed and

 

 

 

 

 

 

 

 

 

 

acknowledged.

 

 

 

 

 

 

 

 

ONLINE-LINKING Link evaluation state: Wait until all links are established

 

 

 

 

 

 

 

 

STANDBY

Out of Service state: Entered if mode of Resource Block is

 

 

 

 

 

 

 

 

 

 

OOS.

 

 

 

 

SET_FSTATE

 

R/W

 

Allows the Fault State conditions for output function blocks to be manually initiated by

 

 

 

 

 

 

 

 

setting to ‘Set’.

 

 

 

 

 

 

 

 

 

 

 

 

NOTE:

 

 

 

 

 

 

 

 

 

 

 

 

Since the IFC090-FF doesn’t have an output block, this parameter is not supported.

 

SHED_RCAS

 

R/W

 

Time duration for the monitoring-cycle in which a function block in mode RCAS has to

 

 

 

 

 

 

 

 

answer on control system requests.

 

 

 

 

 

 

 

 

NOTE:

 

 

 

 

 

 

 

 

 

 

 

 

Since the IFC090-FF has no function block capable of switching to mode RCas, this

 

 

 

 

 

 

 

 

parameter is not supported.

 

 

 

KROHNE Messtechnik GmbH & Co. KG · Ludwig-Krohne-Str. 5 D-47058 Duisburg Tel.: 0203-301 309 Fax: 0203-301389 · E-mail: krohne@krohne.de

Supplementary Documentation

 

 

Page 13 of 44

IFC090, IFC090 i with FF

 

 

 

IFC090 FF 01/2006

IFC090-FF Block Description

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Parameter

Access

SHED_ROUT

R/W

 

 

STRATEGY

R/W

 

 

ST_REV

R

 

 

TAG_DESC

R/W

 

 

TEST_RW

R/W

 

 

UPDATE_EVT

R

 

 

WRITE_ALM

R

 

 

WRITE_LOCK

R/W

 

 

WRITE_PRI

R/W

 

 

Description

Time duration for the monitoring-cycle in which a function block in mode Rout has to answer on control system requests.

NOTE:

Since the IFC090-FF has no function block capable of switching to mode Rout, this parameter is not supported.

Parameter used to group a set of blocks. This is done by assigning the same STRATEGY numerical value to all blocks belonging to one group.

NOTE:

This parameter is neither checked nor used by the function block application! It can be used by control system to group blocks!

Static data revision counter. ST_REV will be incremented if a static Resource Block parameter has changed. By checking this parameter, control systems are able to realize if a static parameter has changed its value without checking all static parameters all the time.

User description of the intended application of the block. The user is free in setting this value. The only limitation is the length of 32 characters at maximum. It is not checked by the application, but has informational character only.

Read/write test parameter. It is only used during Fieldbus Foundation interoperability testing and has no meaning for normal operation!

Alert generated by a change to static data. The subfields of this parameter give detailed information about the changed static parameter, time of change and state of the update event.

Alarm generated, if the parameter write lock is cleared.

see also: ACK_OPTION, WRITE_LOCK, WRITE_PRI

If this parameter is set to ‘Locked’ (2) all writable parameters in all blocks are write protected, with the exception of WRITE_LOCK itself. Dynamic data will continue to be updated.

To disable the write protection, set this parameter to ‘Not Locked’ (1).

see also: ACK_OPTION, WRITE_ALM, WRITE_PRI

Priority of the alarm generated by clearing the WRITE_LOCK:

0alarm isn't be evaluated

1no notification to the control system in case of an write protection alarm

2reserved for block alarms

3-7 write protection is send as user/operator note to the control system, according to the given priority (3 = low and 7 = high)

8-15 write protection alarm is sent with the appropriate priority (15 = high and 8 = low).

Table 1: Resource Block parameters

KROHNE Messtechnik GmbH & Co. KG · Ludwig-Krohne-Str. 5 D-47058 Duisburg Tel.: 0203-301 309 Fax: 0203-301389 · E-mail: krohne@krohne.de

Supplementary Documentation

 

 

Page 14 of 44

IFC090, IFC090 i with FF

 

 

 

IFC090 FF 01/2006

IFC090-FF Block Description

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4.2Transducer Block

Table 2 lists the Transducer Block parameters in alphabetical order (this list gives a description of the various parameters only; see chapter below. for a detailed description depicting how to configure these parameters):

Parameter

Access

ALERT_KEY

R/W

 

 

BLOCK_ALM

R

 

 

BLOCK_ERR

R

 

 

CAL_MIN_SPAN

R

CAL_POINT_HI

R/W

 

 

CAL_POINT_LO

R/W

 

 

CAL_UNIT

R/W

 

 

CAL_ZEROPOINT

R/W

 

 

COLLECTION_DIRECTORY

R

 

 

CYCLES_ZEROPOINT_CAL

R/W

 

 

LIN_TYPE

R/W

 

 

Description

Identification number of the plant unit. It helps to identify the location (plant unit) of an event. The handling of this parameter is up to the control system or control person, respectively.

Display of current block state. Field subcode gives information about the state current errors. The following errors can occur:

Configuration Error

Block was put Out of Service

The remaining fields give information about the state and the occurrence of this alarm.

Display of active block errors. The following errors are possible:

Out of Service

block is in Out of Service mode

Device needs Maintenance now

fatal error of IFC090-FF hardware

Minimum calibrated span value allowed.

 

Highest calibrated value. This value depends on the IFC090-FF pipe diameter.

Lowers calibrated value. This is the absolute value of the lowest positive and negative value, the device is capable of measuring, and it is constant to ‘0’. Engineering units code index for the calibration values. This is always m3/s (cubic meter per second).

Start zero point calibration by writing a value different from ‘0’.

NOTE:

Handle this parameter with caution, since a correct zero point calibration is based some important conditions.

Directory that specifies the number, starting index, and DD2 item IDs of the transducer block’s data collections. The first entry specifies the number of data collections, and the remaining specifies the data collections.

Number of cycles to perform if a zero point calibration is started. Valid values are in between 0 and 2000.

Linearization type used to describe the behavior of the sensor output. The IFC090-FF has a linearization type of ‘linear with input’.

2 DD = Device Description

KROHNE Messtechnik GmbH & Co. KG · Ludwig-Krohne-Str. 5 D-47058 Duisburg Tel.: 0203-301 309 Fax: 0203-301389 · E-mail: krohne@krohne.de

Loading...
+ 30 hidden pages