Sensor Amplifier
Communication Manual
Read this manual before use.
Keep this manual in a safe place for future reference.
This manual contains information about communicating data by connecting either of the network units listed below and sensor amplifiers.
Compatible network units
CC-Link compatible network unit, NU-CL1 DeviceNet compatible network unit, NU-DN1
For specific communication procedures, refer to the manual of each network unit. For the functions of sensor amplifiers, refer to the manual of each sensor amplifier.
96063E |
1 |
The table below summarizes how many ID numbers are occupied by each model of sensor amplifier.
Model |
Number of ID numbers occupied |
|
|
FS-N10 |
1 |
|
|
FS-N12* |
1 |
|
|
FS-N14* |
2 |
|
|
Connection example:
ID number
FS-N14*
FS-N12*
FS-N10
CH1 CH2
Network unit
Each ID number is assigned an output, setting value, current value, and external input.
Model |
Item |
Ch1 (1st ID number) |
Ch2 (2nd ID number) |
|
|
|
|
|
|
|
Output |
Output |
|
|
FS-N10 |
|
|
|
|
Setting value |
Setting value of output |
- |
||
FS-N12* |
|
|
||
Current value |
Received light intensity |
|||
|
||||
|
|
|
|
|
|
External input |
External input |
|
|
|
|
|
|
|
|
Output |
Output 1 |
Output 2 |
|
|
|
|
|
|
FS-N14* |
Setting value |
Setting value of output 1 |
Setting value of output 2 |
|
|
|
|
||
Current value |
Received light intensity |
(Not used) |
||
|
||||
|
|
|
|
|
|
External input |
External input |
(Not used) |
|
|
|
|
|
The external input can be used after configuring the "Control Input"parameter
Point
of each sensor. (By default, "Control Input" is set to "0: Not use.") The models FS-N10/N12* do not have an external input wire, but they can utilize external input via network by using a network unit.
2 |
- Sensor Amplifier Network Manual - |
1 FS-N Series
For the FS-N series, the data parameters that can be communicated via a network unit are specified as follows:
Parameter |
Available settings |
||
|
|
|
|
Current Value |
|
0 to 9999 |
|
|
|
|
|
Setting Value |
|
0 to 9999 |
|
|
|
|
|
Current Value Prop- |
Over Range |
(Not used with FS-N) |
|
|
|
||
Under Range |
(Not used with FS-N) |
||
erty |
|||
|
|
||
Invalid |
(Not used with FS-N) |
||
|
|||
|
|
|
|
|
|
0: No Error |
|
|
|
1: Overcurrent Error |
|
|
|
2: Not used |
|
Sensor Error |
|
3: EEPROM Error |
|
|
4: Not used |
||
|
|
||
|
|
5: Not used |
|
|
|
6: DATUM Correction Error |
|
|
|
7: APC Error |
|
|
|
|
|
Sensor Warning |
|
0: No Warning |
|
|
1: Limit Output ON |
||
|
|
||
|
|
|
|
|
|
0: Unlock |
|
Key Lock |
|
1: Key Lock |
|
|
2: PIN Code Lock |
||
|
|
||
|
|
3: Communication Lock |
|
|
|
|
|
|
|
FS-N10: 2000 |
|
Product Code |
|
FS-N12: 2000 |
|
|
|
FS-N14: 2001 |
|
|
|
|
|
Head Code |
|
(Not used with FS-N) |
|
|
|
|
|
|
|
0: OUT1: L-on / OUT2: L-on |
|
L-on/D-on (N.O./N.C.) |
|
1: OUT1: D-on / OUT2: L-on |
|
|
2: OUT1: L-on / OUT2: D-on |
||
|
|
||
|
|
3: OUT1: D-on / OUT2: D-on |
|
|
|
|
- Sensor Amplifier Network Manual - |
3 |