Compact Switching Power Supply

MS2 Series

Instruction Manual

Read this manual before using the product in order to achieve maximum performance. Keep this manual in a safe place after reading it so that it can be used at any time.

Part Names and Functions

.8.8.8

Digital display window

Displays the current values of output current/voltage and other items.

Display mode selection (MODE)

Switches the display mode.

Output voltage adjustment trimmer (V.ADJ)

Adjusts the output voltage within the range of ±5%.

DC output terminal (+, –) *

A load is connected here. (24 VDC)

Protective earthing terminal ()

Connect to the protective earthing conductor in the building installation.

AC input terminal (N, L)

An input cable is connected here. (100 to 240 VAC)

*Only the MS2-H300 has DC output of 4-terminal.

Safety Precautions

Danger

Do not perform any electrical wiring while electric current is applied. Failure

 

to follow this may result in an electric shock or fire.

 

 

 

Be sure to connect the grounding cable. Failure to follow this may result

 

 

in an electric shock or fire.

 

• Do not touch this unit within 1 minute after AC input is turned off. Failure

 

 

to follow this may result in an electric shock.

 

Do not modify or repair this unit. Failure to follow this may result in an

 

 

electric shock, accident, or product failure.

 

Do not touch any terminal of this unit while electric current is applied.

 

 

Use the unit with the terminal cover installed to avoid an electric shock.

 

When this unit is used in a system that may cause a serious accident or

Warning

 

damage if the unit fails, be sure to install a safety device.

 

 

 

Pay attention to prevent foreign matter such as metal particles, dust,

 

 

paper or wood chips from entering the inside of this unit. Failure to

 

 

follow this may result in a fire or product failure.

 

Do not touch any metallic part while electric current is applied or

 

 

immediately after input is shut off. Failure to follow this may result in a

 

 

burn due to a high temperature.

 

If a failure or abnormality occurs while this unit is in use, immediately

 

 

such off AC input and stop operation of this unit . Failure to follow this

 

 

may result in a fire or accident.

 

Check that the AC input rated voltage of this unit is equal to the voltage

Caution

 

of the AC power supply.

 

 

Do not connect the AC power supply to the DC output terminals.

Do not disturb the convection of air near the vent of the casing.

Precautions for CE Markings

KEYENCE has evaluated the conformity of the MS2 Series with the requirements of the EMC Directives and Low-voltage Directives under the following condition, and confirmed that the MS2 Series meets these requirements. For the Low-voltage Directives, the MS2 Series has obtained certification from TUV Rheinland for the following standards.

<Precautions>

EMC Directives (2004/108/EC)

Applicable standard (EMI)

EN55011, Group 1, Class A

Applicable standard (EMS)

EN61000-6-2

Low-voltage Directives (2006/95/EC)

Applicable standard

EN60950-1

 

 

EN50178

Overvoltage category

II

 

Pollution degree

2

 

The MS2 Series is designed as a Class I Equipment. Be sure to connect the protective earthing terminal on the terminal block to the protective earthing conductor in the building installation.

The MS2 Series is an open-type device. Be sure to install it in an appropriate enclosure rated as IP54 or better.

Use the MS2 Series according to the derating conditions and the installation conditions described in this manual.

The MS2 Series does not include a disconnecting device. Be sure to install a disconnecting device such as a circuit breaker in the building installation wiring.

Precautions for UL Standards

The MS2 Series meets the following UL standards and has obtained UL and C-UL certification.

Applicable standard

UL508

Industrial Control Equipment

 

 

UL60950-1 Information Technology Equipment - Safety

 

 

CAN/CSA C22.2 No. 14-M95

 

 

 

Industrial Control Equipment

 

 

CAN/CSA C22.2 No. 60950-1-03

 

 

 

Information Technology Equipment - Safety

UL File No.

E195940, E242533

UL category

NMTR, NMTR7 / QQGQ2, QQGQ8

<Precautions>

 

 

Use wires that meet the following conditions for the terminal block.

 

(tightening torque : 1.2 N·m)

 

 

Wire range

 

AWG#14-22

 

Wire Material

 

Copper wire only

 

Wire type

 

Stranded wire only

 

Temperature rating

60ºC/75ºC

The MS2 Series is designed as a Class I Equipment. Be sure to connect the protective earthing terminal on the terminal block to the protective earthing conductor in the building installation.

The MS2 Series is an open-type device. Be sure to install it in an appropriate enclosure rated as IP54 or better.

Use the MS2 Series according to the derating conditions and the installation conditions described in this manual.

The MS2 Series does not include a disconnecting device. Be sure to install a disconnecting device such as a circuit breaker in the building installation wiring.

The output of the MS2-H50 is rated Class 2 output specified in NFPA70 (NEC: National Electrical Code) in the U.S.A. (UL Category: EPBU2/EPBU8)

Installation Conditions

Installation environment

Installation this unit indoors.

Do not install this unit in locations exposed to direct sunlight.

Do not install this unit in locations in which there is corrosive gas or flammable gas.

Do not install this unit in locations exposed to a lot of dust, soot, or steam.

Do not install this unit in locations in which water, oil, or chemicals may splash onto the unit.

When installing this unit in a location subject to vibration or impact, consider the vibration proof mounting.

When installing this unit in a control console

The ambient temperature for this unit should not exceed the upper temperature limit (refer to the derating characteristic). When the upper temperature limit may be exceeded, install a cooling fan or cooler so that the ambient temperature is below the upper temperature limit.

Leave a sufficient ventilation space around this unit for head dissipation.

Do not install this unit just above a device with high head generation (transformer, inverter, servo amplifier, etc.).

Installation

Space around the unit

The MS2 Series uses natural air-cooling. To ensure sufficient convection of air to dissipate heat, provide enough space between the MS2 Series and the control panel or other nearby devices as shown below.

 

MS2-H50/H75/H100/H150

 

MS2-H300

 

20mm min.

 

60mm min.

 

 

 

20mm min.

20mm min.

30mm min.

30mm

min.

 

20mm min.

 

30mm min.

Installation orientation

Install this unit with the base A down as shown below. Do not install the unit in any other orientation.

Mounting bracket (optional)

Make sure that the tightening torque for the mounting screw holes of this unit is 0.5 N•m or less.

Wiring

Terminals

Screw size

Tightening torque

 

 

M4

1.2 N•m

 

 

Crimp termianls

M4 size

M4 size

8.0 mm max.

8.0 mm max.

Cables

Select cables with a wire diameter suited to the output rated current.