Jackson Systems WZ1, Wireless Zone One WZ1 Installation And Operation Manual

Wireless
ZONE NE
Made in the USA
Installation and Operation Manual
TM
Model WZ1
Application
SYSTEM
FAN
The WZ1-T is a battery powered, auto-changeover thermostat that communicates via an RF wireless data link to a damper control module located on the Zone One™ damper. The system is designed to prevent overheating and overcooling of individual zones. can be used in the same location
Up to 8 WZ1 thermostat controlled dampers
.
Sequence of operation
An automatic changeover duct sensor located on the damper senses whether there is warm air or cool air in the branch supply duct. If the Zone One™ thermostat is calling for cooling and the duct sensor determines there is cool air in the duct, the damper will power open; otherwise, the damper will remain closed. If the Zone One™ thermostat is calling for heating and the duct sensor determines there is warm air in the duct, the damper will power open; otherwise, the damper will remain closed. The relay control module has LED indication to confirm mode of operation and damper position.
Specifications
Damper Actuator Type
Communications Indicator
Damper Position Indicator
Communications
Range
Control Module Power
Control Module Housing
Control Module Dimensions
Thermostat Dimensions
24 Volt, 10 VA, 2-wire, powered open / spring return close
Multi-color LED indicates mode of operation
Green LED indicates when damper is open
Wireless, 915MHz, proprietary protocol
Up to 100 feet
24VAC, 40VA
Molded plastic
3.25 x 5.50 x 1.125 inches (WHD)
5.00 x 4.50 x 1.00 inches (WHD)
Wireless Zone One™ Module
1
Installation
The Wireless Zone One™ damper control module comes installed on the zone damper and is completely factory wired. The damper control module is powered by a separate 24 Volt, 40 VA transformer.
DAMPER
ON WHEN DAMPER
IS POWERED OPEN
LED
24 VAC
LED
ACTUATOR
PO/SC
GREEN
PROGRAM
ENABLE BUTTON
GYWRC
Solid Red LED = Heat Call Solid Yellow LED = Cool Call Flashing Green LED = No Calls
Wireless Zone One™ Thermostat
2
Location
1 234 56 7
DUCT SENSOR
The thermostat should be located in the area being controlled by the zone damper and away from the HVAC unit thermostat. Do not install the thermostat in an area where drafts are present, near the floor, behind doors or on an external wall. Avoid placing the thermsotat in areas where the air movement is limited, affected by direct sunlight or other areas not typical of the temperature in the space.
2
43
Removing the Subbase
Hold the subbase with one hand, press the case as shown below and pull the bottom of the thermostat from the subbase.
Press here to release
case from subbase.
4
Installing the Subbase
The thermostat should be installed approximately 5 feet above the floor. Level the subbase for appearance and use the wall anchors and screws provided.
5
Installing the Batteries
Slide the battery cover off and install two AA batteries included with the thermostat. Install the batteries with the positive terminals to the right as shown. Replace the battery cover.
3
6
Thermostat Installer Options
The installer options can be accessed by pressing and holding the key for seven seconds. The LCD displays Option 01 for setting the number.
Zone
ENTER
(See Installer Options Chart)
Press or hold the key to advance to the next option. The LCD will advance through to Option 09 and then return to
NEXT
Option 01.
Press the key to save all options in non-volatile memory.
ENTER
If only one wireless thermostat and damper control module are used in an application, the thermostat can be left with the factory default setting of Zone = 01
If multiple wireless thermostats and damper control modules are used that are less than 500 feet away from one another, each thermostat must be set to a different number. For convenience, set the Installer Options with the thermostat
Zone
off the subbase and in easy access of its damper control module.
7
Setting the Zone Number
If more than one WZ1 is used in the same application, each thermostat and module must be assigned a different communications address. Use the and keys to set the zone number for each thermostat in the system. maximum number that can be used in the same building is eight
UP DOWN The
.
Installer Options Chart
Zone
Option
CANCEL NEXT
ENTER
Press the key to advance to the next option. Press the key if no more options are to be changed.NEXT ENTER
8
Heating Setpoint Limit
Press the key to select and press the or key to
NEXT Option 08 Up Down
set maximum allowable heating setpoint.
Option Description
Zone number
01
Range Default
Program damper module to Zone address
03
Default 01
Maximum allowable heating setpoint
08
Range Default
Minimum allowable cooling setpoint
09
Range Default
01 to 08 01
60 to 85F 76F
55 to 80F 68F
Heat
Set To
The maximum heating setpoint range is 60 to 85F.
Option
CANCEL NEXT
ENTER
4
9
Cooling Setpoint Limit
Cool
Set To
Press the key to select and press the or key to
NEXT Option 09 Up Down
set the minimum allowable cooling setpoint.
The minimum cooling setpoint range is 55 to 80F.
Option
10
CANCEL NEXT
Programming the Module
ENTER
If there is only one WZ-1 installed, it is not necessary to program the address as the thermostat and damper control module default address is Zone 01.
After selecting the Zone number for the thermostat, the same address must be programmed into the damper control module. Remove the cover on the module and apply 24 Volts power. Press the button. The
PROGRAM ENABLE
module will accept a new address for thirty seconds. The LED on the module will alternately blink red and green while it is waiting for a new address. When the module accepts the address, the LED will begin to flash green confirming communications with the thermostat.
24 VAC
ACTUATOR
PO/SC
ON WHEN DAMPER IS POWERED OPEN
PROGRAM
ENABLE
LED
BUTTON
GREEN
LED
1 234 56 7
FLASHING LED
GYWRC
The multi-colored LED indicator normally flashes green when no calls are active. The LED is continuously yellow during cooling calls and red during heating calls.
While the module LED is alternately blinking red and green, press and hold
ENTER
the key for seven second until the zone number is displayed. Press
NEXT Option 03 (Pr)
until and the zone number are displayed. Send the
zone address to the damper control module by pressing the key.
ENTER
Zone
When the module LED begins to flash green, communications with the thermostat has be enabled.
Option
CANCEL NEXT
ENTER
5
Thermostat Operation
Temperature Setting
Up and Down keys used when adjusting temperature, time of day, day of the week, and other options
Space temperature
Menu key used to set time of day and day of week
Cancel key used to cancel changes
CANCEL
MENU
Next key used when setting time of day and changing from heating and cooling setpoint
Heat
Inside
Set To
AUTO
SYSTEM
SYSTEM key selects
Mo
AM
NEXT
ENTER
FAN
Auto and Off
Fan key (Not used)
Battery compartment, 2 AA batteries.
Enter key used to access Installer Setup and save settings
6
11
Setting the Time and Weekday
To set the time of day and the day of the week, press the key and the LCD will display the hour. Use the and keys to set the hour. Make sure that the AM or PM is correct.
Press the key to set the minute. Use the and keys to set the minute.
Press the key to set the current day of the week. Use the and
Down ENTER
11
Press the hold the Up or Down key to change the heating or cooling temperature. Press the Next key to switch between the heating and cooling temperature.
NEXT Up Down
NEXT Up
keys to select the day of the week and press the key.
Setting the Heating and Cooling Temperature
Up Down
MENU
MENU
Th
CANCEL NEXT
Inside
Th
AM
ENTER
Heat
Set To
HEAT
AUTO
AM
12
If the battery voltage drops to where it could interfere with reliable operation, the LCD will alternately display in place of the Inside temperature. .
Low Battery Indication
Lo
Replace batteries immediately
MENU
MENU
NEXT
Inside
Day
NEXT
ENTER
Heat
Set To
AUTO
Th
AM
ENTER
7
9
Resetting Factory Defaults
To reset the factory defaults, remove the batteries and re-install them while holding down the key. All prior changes will default to the factory settings. This will require resetting the time and day. Refer to the Installer Options Chart default settings to make any additional changes.
Hold down key
SYSTEM
SYSTEM
while replacing batteries
Although great care has been taken in preparation of this manual, Jackson Systems takes no responsibility for errors or omissions contained herein. It is the responsibility of the installer to ensure that the Wireless Zone One™ thermostat, control module and damper are installed and wired properly to provide safe and efficient operation.
Due to ongoing product improvements, Jackson Systems reserves the right to change the specifications of the Wireless Zone One™ system and its components without notice.
All rights reserved.
©
Jackson Systems, LLC 2010
Intellectual rights apply.
This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference and (2) this device must accept any interference received, including interference
5418 Elmwood Avenue, Indianapolis, IN 46203-6025 Toll Free: 888.652.9663 Fax: 317.227.1034 www.jacksonsystems.com
8
06-1059-012611
Loading...