Your new Comfort System™ T-32-P Universal Thermostat has been built using the highest quality
components and design currently available. As a result, when properly installed and configured by your
professional heating and air conditioning contractor, the T-32-P will provide years of trouble-free
operation.
The T-32-P has been designed to be an attractive, highly reliable and easy-to-use thermostat. By taking
the time to read and understand this operation manual, you can take advantage of the many user
features offered in this premium product.
Great care has been taken in the preparation of this manual. Jackson Systems takes no responsibility for
errors or omissions contained in this document. It is the responsiblity of the user to ensure that this
thermostat, or equipment connected to it is operating to their respective specifications and in a safe
manner.
Due to ongoing product improvements, Jackson Systems reserves the right to change the
specifications of the T-32-P thermostat (or its components) without notice.
The T-32-P can be used for both residential and commercial applications. Within these applications
the thermostat can be either programmable or non-programmable. The HVAC installer will have set
these parameters to best suit your individual needs.
For clarity, this Operation Manual is broken into the following main sections:
•
Residential Programmable Mode (4 schedules per day)
• Commercial Programmable Mode (2 schedules per day)
• Non-programmablel Mode
• Common Functions
The T-32-P can be configured for a wide range of HVAC systems and applications requiring specific
functions. Therefore, this manual may describe a function that is not active for you specific
application.
1
Residential Programmable Mode
MODE Selection
Press thekey to cycle through the modes of
MODE
operation and the LCD will display the following:
Cool
Heat
MODEO/RIDEPROG
MODE KEY
FAN
FAN KEY
Heat
Cool
Cool
Heat
E. Heat
OFF
Heat Mode
Cool Mode
Auto Changeover (Installer must
activate this mode)
Emergency heat when T-32-P is
configured for a heat pump system
Thermostat is off
FAN Selection
Press thekey to cycle through the fan selections. More details on fan functions can be found on
FAN
page 20 of this manual.
Auto
On
MODEO/RIDEPROG
The HVAC system fan will only run with a call for heating or cooling.
The HVAC system fan will run continuously.
Cool
Heat
FAN
Setting the clock
The T-32-P has a real-time clock that is used for
programming functions. It is important that the time
and day of week be set properly so that programmed
events run correctly.
To set the clock, press thekey until the hour
PROG
flashes on the LCD. Use the up ( ) or down ( ) key to
set the current hour along with the AM and PM
symbol. Press thekey again until the minutes
PROG
flash. Use the up ( ) or down ( ) key to set the
current minutes. Press thekey again until the
PROG
day flashes. Use the up ( ) or down ( ) key to set the
correct day of the week. Press theagain to
PROG
exit the clock and day of week program.
UP / DOWN
KEYS
PROG
KEY
2
Programming 4 daily events
The T-32-P can be programmed to provide 4 individual time-of-day temperature settings for each day
of the week.
Each event is noted on the LCD by numerals
1234
At the start of each event, the programmed heating and cooling temperature will be maintained until
the next event starts.
Entering the program mode
Cool
Heat
Hold thekey down for 3 seconds.
The display will show the numberand the day
MON
PROG
will flash.
11
1
Use the up ( ) or down ( ) key to set the day you
wish to start programming.
Press thekey again and the hour will flash.
PROG
Use the up ( ) or down ( ) key to set the time you
11
MODEO/RIDEPROG
FAN
wish programto start. Make sure that the AM / PM
is correct.
1
Press thekey again and the minutes will flash.
PROG
Use the up ( ) or down ( ) key to set the minutes for
1
programto start.
UP / DOWN
KEYS
Press thekey again andorwill be displayed along with the temperature value. Use
PROGHeatCool
PROG
KEY
11
the up ( ) or down ( ) key to select the desired heating or cooling temperature to be maintained for
1
1
the programtime period.
Press thekey again and the opposite mode and a temperature value will be shown on the
LCD.
Use the up ( ) or down ( ) key to select the desired temperature to be maintained for the
programtime period.
1
PROG
1
Note: There must be at least a 2 degree difference between the heating and cooling temperatures.
The heating temperature must always be lower than the cooling temperature. If you set the heating
or cooling temperature closer than the minimum value, the T-32-P will automatically move one of the
temperature settings to maintain the 2 degree difference.
3
12
Press thekey again and the same day selected will be shown along with the number,
PROG
1
which represents the second program event. The hour will flash indicating that this value can now be
programmed. Use the up ( ) or down ( ) key to advance the hour to the second event start time.
Make sure that the AM / PM is correct.
Press thekey again and the minutes will flash. Use the up ( ) or down ( ) key to set the
minutes for programto start.
Press thekey again and the wordorwill be displayed along with the temperature
PROG
12
1
PROGHeatCool
value. Use the up ( ) or down ( ) key to select the desired temperature to be maintained for the
12
programtime period.
Press thekey again and the opposite mode and a temperature value will be displayed. Use
the up ( ) or down ( ) key to select the desired temperature to be maintained for the programtime
1
PROG
12
1
period.
13
Continue to press thekey to advance through each programming step for program events
14
1
and. Once you have completed programming the numberevent, press thekey again and
the LCD will display the word. You now have two options.
PROG
COPY
14
1
PROG
1
Option 1 - Copy Program
To copy all the values you have programmed to other days of the week, press the
up ( ) or down ( ) key and select each additional day you wish to duplicate the program. Press the
PROGCOPY
key again and the wordwill flash briefly to confirm the copy process. Normal
programming steps will resume showing the next day to be programmed.
Option 2 - Different Daily Program
If you chose to have the next day represent a different program, simply press thekey after
the wordappears and the
COPY
PROG
T-32-P will advance to the next day. Follow the same programming steps as the prior day. This
allows you to have a different schedule for each day of the week.
Temporary Temperature Override
The T-32-P has a temporary program override function
that permits you to change the current event set
temperatures for a fixed period of time. The HVAC
installer will have set the override period from 1 to 12
hours. If during the override period another scheduled
COPY
event takes place, the override will be canceled.
To place the T-32-P in the temporary temperature
override mode, press the up ( ) or down ( ) key. The
LCD will show the wordand the current mode.
HeatCool
(or) Press the up ( ) or down ( ) key to
SET
change the current temperature setting.
If the thermostat has been configured for auto-
MODEO/RIDEPROG
FAN
changeover, wait 3 seconds after adjusting the first
mode (or) and the display will show the
HeatCool
next mode which can also be changed after which the
T-32-P will exit the override program.
4
The LCD will now flash the current program number to remind you that an override is in progress. The
override temperature settings will remain in effect until the override time expires or until the next
scheduled event (whichever comes first). You can return to the programmed schedule at any time by
pressing thekey and then pressing it again. The program number will stop flashing
O/RIDE
confirming that the T-32-P is now running the programmed schedule.
Permanent Temperature Hold
Press thekey. The LCD will show the word. The current programmed heating and
O/RIDE
HOLD
cooling temperatures will be held permanently or can be adjusted by pressing the up ( ) or down ( )
key which will display the current program temperature along with the word. Press the up ( ) or
SET
down ( ) key to change the temperature.
To return to the programmed schedule, press thekey until the wordis no longer
O/RIDE
HOLD
displayed.
Reviewing Set Temperatures
Your can review the set temperatures at any time by simply pressing the up ( ) or down ( ) key.
Auto Changeover (Installer must
activate this mode)
Emergency heat when T-32-P is
configured for a heat pump system
Thermostat is off
5
FAN Selection
Press thekey to cycle through the fan selections. More details on fan functions can be found on
FAN
page 20 of this manual.
Auto
On
The HVAC system fan will only run with a call for heating or cooling.
The HVAC system fan will run continuously.
Setting the clock
The T-32-P has a real-time clock that is used for
programming functions. It is important that the time
Start
and day of week be set properly so that programmed
events run correctly.
Cool
Heat
To set the clock, press thekey until the hour
PROG
flashes on the LCD. Use the up ( ) or down ( ) key to
set the current hour along with the AM and PM
symbol. Press thekey again until the minutes
PROG
flash. Use the up ( ) or down ( ) key to set the
PROG
PROG
MODEO/RIDEPROG
FAN
current minutes. Press thekey again until the
day flashes. Use the up ( ) or down ( ) key to set the
correct day of the week. Press theagain to
exit the clock and day of week program.
UP / DOWN
KEYS
PROG
KEY
Programming 2 daily events
The commercial programmable mode provides 2 schedules per day using a separate heating and
cooling setpoint. The schedule is shown on the LCD asand.represents the
occupied mode andrepresents the unoccupied mode. Programming steps are the same as a
Stop
StartStop Start
residential program other than there are only two events per day rather than four.
Entering the program mode
Start
Cool
Heat
Hold thekey down for 3 seconds.
The display will show(occupied) and the day
MON
PROG
Start
will flash.
Use the up ( ) or down ( ) key to set the day you
wish to start programming.
Press thekey again and the hour will flash.
PROG
Use the up ( ) or down ( ) key to set the hour you
MODEO/RIDEPROG
FAN
wish the program to start. Make sure that the AM /
PM is correct.
UP / DOWN
KEYS
PROG
KEY
Press thekey again and the minutes will flash.
PROG
Use the up ( ) or down ( ) key to set the minutes for
the program to start.
6
Press thekey again and the LCD will display the wordand the temperature setting for the
current mode (or). Press the ( ) or down ( ) key to change the setpoint. If Auto mode is
selected (shown by bothandon the display), wait 3 seconds after adjusting the first mode
PROGSET
HeatCool
HeatCool
setpoint and the T-32-P will change to show the next mode setpoint. Press the up ( ) or down ( ) key
to change the setpoint.
Press thekey again and the LCD will display. Follow the steps above to program the
STOPPROGCOPY
PROGSTOP
(unoccupied) time and temperature settings. Press thekey again and the word
will appear on the LCD.
Option 1 - Copy Program
To copy the start and stop times you have
programmed to other days of the week, press the
COPY
up ( ) or down ( ) key and select each additional
day you wish to duplicate the program. Press the
PROGCOPY
key again and the wordwill flash
briefly to confirm the copy process. Normal
programming steps will resume showing the next
day to be programmed.
MODEO/RIDEPROG
FAN
Option 2 - Different Daily Program
If you chose to have the next day represent a different start and stop time, simply press the
key after the wordappears and the T-32-P will advance to the next day. Follow the same
COPY
PROG
programming steps as the prior day. This allows you to have a different start and stop time for each
day of the week.
Temporary Temperature Override
To place the T-32-P in the temporary temperature override mode, press the up ( ) or down ( ) key.
The LCD will show the wordand the current mode (or). Press the up ( ) or down ( )
key to change the current temperature setting. Wait 3 second and the next mode (or) will
be displayed and can be changed. When the T-32-P will exit the override program. The word
orwill flash confirming the override event. The HVAC installer will have set the override period
STOP
SETHeatCool
HeatCool
START
from 1 to 12 hours. If during the override period another event takes place, the override will be
canceled. To manually cancel the override, press thekey twice. The thermostat will resume
O/RIDE
the programmed schedule.
Permanent Temperature Hold
Press thekey. The LCD will show the word. The current programmed heating and
O/RIDE
HOLD
cooling temperatures will be held permanently or can be adjusted by pressing the up ( ) or down ( )
key which will display the current program temperature along with the word. Press the up ( ) or
SET
down ( ) key to change the temperature.
To return to the programmed schedule, press thekey until the wordis no longer
O/RIDE
HOLD
displayed.
7
Reviewing Set Temperatures
Your can review the set temperatures at any time by simply pressing the up ( ) or down
( ) key.
Advanced Fan Operation
In many commercial applications, code requires constant ventilation during occupied periods. The
HVAC installer can configure the T-32-P to allow the fan to run continuously during the
schedule. When the thermostat changes to theschedule, the fan shuts down and only
STOP
START
operates with a heating or cooling call.
Factory Defaults
Default Schedule
Setpoint (Mon - SatSetpoint (Sat - Sun)
ScheduleStart TimeHeatingCoolingHeatingCooling
Start6:00 AM70756283
Stop6:00 PM62836283
Non-programmable Mode
Day
Cool
Heat
MODE Selection
Press thekey to cycle through the modes of
MODE
operation and the LCD will display the following:
Heat
Cool
Cool
Heat
Heat Mode
Cool Mode
Auto Changeover (Installer
must activate this mode)
MODEO/RIDEPROG
UP / DOWN
KEYS
PROG
KEY
FAN Selection
Press thekey to cycle through the fan selections. More details on fan functions can be found on
FAN
page 20 of this manual.
Auto
On
The HVAC system fan will only run with a call for heating or cooling.
The HVAC system fan will run continuously.
FAN
E. Heat
OFF
Emergency heat when T-32-P is
configured for a heat pump system
Thermostat is off
8
Setting the clock
The T-32-P has a real-time clock.
Day
Cool
Heat
To set the clock, press thekey until the hour
PROG
flashes on the LCD. Use the up ( ) or down ( ) key to
set the current hour along with the AM and PM
symbol. Press thekey again until the minutes
PROG
flash. Use the up ( ) or down ( ) key to set the
current minutes. Press thekey again until the
PROG
day flashes. Use the up ( ) or down ( ) key to set the
PROG
MODEO/RIDEPROG
UP / DOWN
KEYS
PROG
KEY
FAN
correct day of the week. Press theagain to
exit the clock and day of week program.
Setting the temperatures
Press the up ( ) or down ( ) key for 3 seconds. The T-32-P will display the wordand the
temperature setting for the current mode (or). Press the up ( ) or down ( ) key to change
the setting. If Auto mode is selected (Shown by bothandon the display), after adjusting
HeatCool
HeatCool
SET
the heating temperature wait without touching a key for 3 seconds. The T-32-P will change to show
CoolSET.
andPress the up ( ) or down ( ) key to change the temperature setting for cooling. Wait 3
seconds and the
T-32-P will automatically exit the menu. The new temperature settings will be maintained in memory.
Switching between day and night temperature settings
If the HVAC installer has set thefunction, the T-32-P will keep two heat and two cool
temperature settings. This provides a convenient method to manually select(occupied) or
(unoccupied) settings. To toggle between theandsettings, press thekey. Set the
DayNight
andtemperature settings as previously described.
Day / Night
DayNight
DayNightPROG
Reviewing Set Temperatures
You can review the set temperatures at any time by simply pressing the up ( ) or down ( ) key.
Common Functions
MODE Key
MODE
Thekey is used to cycle through the available modes.
OFF
Heat
Cool
Heat / Cool
E. Heat
(Auto)
(emergency heat for heat pump systems only)
9
O/RIDE KeyResidential Programmable Mode
Thekey is used to override the programmed schedule and to hold the current set
O/RIDE
temperature indefinitely or until thebutton is pressed again. The word
HOLD
will be displayed on the LCD to confirm this function is active.
(Override)
O/RIDE
O/RIDE KeyCommercial Programmable Mode
Thekey is used as an after hours run timer for a programmed period established by the
O/RIDE
(Override)
HVAC installer (0.5 - 12 hours) or Off which will hold the override until the next scheduled event.
When thekey is pressed, the LCD will display the flashing wordand the
O/RIDETIMERStart
(occupied) temperatures will be initiated. The override can be canceled at any time by simply
pressing thekey and the flashing wordwill disappear on the display.
O/RIDETIMER
Up Key ( )
This key is used to increase a desired temperature or value in programming.
Down Key ( )
This key is used to decrease a desired temperature or value in programming.
PROG KeyResidential or Commercial Programmable Mode
(Program)
This key is used to set the clock and program daily events.
PROG KeyManual Mode
(Program)
This key is used to set the clock and switch betweenandmodes.
DayNight
FAN Key
This key is used to select continuous fan () or intermittent fan ().
Fan ONAuto Fan
Advanced Fan Function
The T-32-P has an Advanced Fan function that will run the fan continuously during occupied mode and
only run with a call for heating or cooling in the unoccupied mode. If this function has been enabled by
the installer, the fan key must be set to. To disable the function, simply set the fan key to. If
ONAuto
the thermostat is configured for 4 schedules per day, the fan will run continuously in schedules 1, 2
and 3 and in Auto in schedule 4. If the thermostat is configured for 2 schedules per day, the fan will run
continuously in the Start mode and in Auto in the Stop mode.
Heating Call
When the T-32-P is in themode and there is a call for heating, the LCD will display the word
HeatingHeat
. If the wordflashes, this confirms that the T-32-P is initiating a time delay before the
Heat
heating call takes place.
E. Heat Call
(emergency heat)
When the T-32-P is used with a heat pump system, and themode is selected, the LCD will
display the wordwhenever there is a call for emergency heat.
E. Heating
E. Heat
10
Cooling Call
When the T-32-P is in themode and there is a call for cooling, the LCD will display the word
CoolingCool
cooling call takes place.
LCD Symbols
. If the wordflashes, this confirms that the T-32-P is initiating a time delay before the
Cool
Program hold
active
Current
running
Day
Clock
program
System
mode
Fan
status
Modbus
communications
active
TIMER
Keyboard
or control
limit
is locked
Set or room
temperature
Outside air
temperature
Override timer
activated
Commissioning
mode
The T-32-P is capable of many advanced control options. Not all LCD symbols may appear on your
specific thermostat configuration.
11
Troubleshooting
LCD display is blank
Heating or cooling
system does not
respond
• Check HVAC circuit breaker and reset if necessary.
• Make sure power switch at HVAC system is on.
• Make sure furnace door is closed securely.
• Press MODE key to set system to Heat. Make sure the
temperature is set higher than the inside temperature.
• Press MODE key to set system to Cool. Make sure the
temperature is set lower than the inside temperature.
• Check circuit breaker and reset if necessary
•Make sure power switch at HVAC system is on.
• Make sure furnace door is closed securely.
• If Heat or Cool is flashing, the T-32-P has initiated an equipment
protection time delay. Wait 4 minutes for the system to restart.
If for any reason your T-32-P does not function properly, contact your installing HVAC contractor.
INDIANAPOLIS, IN 46203
www.jacksonsystems.com
06-1002-042210
12