MODEL: T21004R
IN RAINPROOF (TYPE 3R) ENCLOSURE FOR INDOOR/OUTDOORPANEL WITHUSETIME SWITCH
60SUITABLEAMPFOR120/240SWIMMINGVOLTPOOLOR/SPA120/208APPLICATIONSVOLTANDSINGLEFOR DIRECTPHASE,CONDUIT(THREECONNECTIONWIRE)TO A ACWET-NICHE OR NO NICHE LUMINAIRE.
IMPORTANT:The short circuit rating of this panel is 10000 symmetrical amperes.
This control panel must be installed according to the National Electrical Code (including article 680) or Canadian Electrical Code (including section 68) and local code requirements. This installation is subject to the approval by the local inspection authority. The main lugs and neutral main are suitable for No. 14 to 2 AWG COPPER conductors. Use No. 14 to 6 AWG COPPER conductors for branch circuit wiring. Follow gauge selection table and corresponding terminal screw tightening torque requirements below. Install interchangeable circuit breakers with an interrupting current rating of 10000 symmetrical amperes, or higher. All circuit breakers in this control panel shall be of the same manufacturer and type. See list of suitable types below. Follow manufacturers instructions for installing and testing of ground fault circuit breakers (GFCB) and interrupters (GFCI). Install only LISTED receptacle(s) and/or wiring device(s) inside the enclosure. A LISTED wiring device may be installed in the rectangular side knockout provided. When panel is outdoors, a LISTED rainproof cover must be installed over the wiring device in the side knockouts. If this enclosure is used for direct conduit connection to a wet-niche or no niche luminaire, one of the connection kits listed below in Note 5 must be used. This control should not be connected to any equipment which would cause bodily injury or property damage should it be activated unexpectedly. After wiring, install front panel over wiring compartment and close unused breaker openings with filler plates. KEEP DOOR CLOSED AT ALL TIMES.
|
|
|
SUITABLE LISTED BREAKERS |
|
|
|
|
|||||||||
|
|
|
|
|
|
|
|
CIRCUIT BREAKER |
|
|
FILLER |
|
||||
MANUFACTURER |
|
SINGLE |
DOUBLE |
TWIN |
QUAD |
|
GFCB |
|
PLATE |
|
||||||
|
|
|
|
|
||||||||||||
CUTLER-HAMMER |
|
|
BR |
|
BR |
BRD |
BRD |
|
GFCB |
|
BRFP |
|
||||
MURRY |
|
|
MP-T |
MP-T |
MH-T |
MH-T |
|
MP-GT |
|
LX100FP |
|
|||||
SIEMENS |
|
|
|
QP |
|
QP |
QT |
QT |
|
QPF |
|
QF3 |
|
|||
SQUARE D |
|
|
HOM |
|
HOM |
HOMT |
HOMT |
|
---- |
|
HOMFP |
|
||||
THOMAS & BETTS |
|
|
TB |
|
TB |
TBBD |
TBBQ |
|
GFB |
|
FP-1C-TB |
|
||||
NOTES: |
|
|
|
|
|
|
|
|
|
|
|
|
|
|||
1. Any Intermatic T100M or ET100CM series Time Switch, PF1000M |
||||||||||||||||
Series freeze protection or RC2000M Series air switch mechanism |
||||||||||||||||
may be installed in the bracket provided or in the event an existing |
||||||||||||||||
mechanism is replaced. |
|
|
|
|
|
|
|
|
|
|||||||
2. If this control panel requires bonding, attach a LISTED bonding |
||||||||||||||||
terminal of a suitable size using the mounting hole(s) provided on the |
||||||||||||||||
bottom of the enclosure (156T11047A may be ordered). |
|
|
|
|||||||||||||
3. When a back-fed breaker is used in this control panel, order |
||||||||||||||||
22T904A to comply with NEC article 384-16 (g). |
|
|
|
|
||||||||||||
4. Wiring devices may be installed in this control panel (order 21T156A |
||||||||||||||||
(4) Standoffs for mounting). |
|
|
|
|
|
|
|
|||||||||
5. The following kits are available to connect under water luminaires to this |
||||||||||||||||
enclosure: |
|
|
|
|
|
|
|
|
|
|
|
|
|
|||
|
|
1/2” non-metallic - order 156PA13713A |
|
|
|
|
||||||||||
|
|
3/4” non-metallic - order 156PA13714A |
|
|
|
|
||||||||||
|
|
1” non-metallic - order 156PA13715A |
|
|
|
|
||||||||||
|
|
1/2” metallic - order 156PA14336A |
|
|
|
|
|
|
||||||||
TIME SWITCH RATINGS: |
|
|
|
|
|
|
|
|
|
|||||||
30 AMP. RESISTIVE, INDUCTIVE, TUNGSTEN OR 1000 VA PILOT DUTY - |
||||||||||||||||
120/208/240 VOLT A.C. 2 HP |
(24 FLA)-120 VOLT A.C., |
|
|
|
|
|||||||||||
5 HP (28 FLA)-240 VOLT A.C. |
|
|
|
|
|
|
|
|||||||||
CLOCK MOTOR: 208-277 VOLTS 60 HZ. |
|
|
|
|
|
|
||||||||||
(To order clock motor replacement, specify part no. WG--on motor cover) |
|
|
|
|||||||||||||
TIME SWITCH OPERATING INSTRUCTIONS |
|
|
|
|
|
|
||||||||||
1. TO SET "ON" AND "OFF" TIMES: |
|
pointing to time (AM or PM) |
||||||||||||||
Hold TRIPPERS against edge of CLOCK-DIAL, |
||||||||||||||||
when ON and |
OFF operations are desired. Tighten tripper |
screws firmly. |
||||||||||||||
TIME |
|
2. |
TO SET TIME-OF-DAY: |
|
|
|
|
|||||||||
POINTER |
|
|
|
Pull CLOCK-DIAL outward. Turn in either direction |
||||||||||||
TIME |
ON |
|
|
and align the exact time-of-day on the CLOCK-DIAL |
||||||||||||
TRIPPER (the time now, when switch is being put into opera- |
||||||||||||||||
DIAL |
|
|
||||||||||||||
|
||||||||||||||||
|
|
|
|
|
|
tion) to the pointer. |
|
|
|
|
|
|
||||
|
|
|
|
|
|
|
|
-DO NOT MOVE POINTER- |
|
|
|
|||||
OFF |
|
|
|
• TO OPERATE SWITCH MANUALLY: Move MAN- |
||||||||||||
TRIPPER |
|
|
|
UAL-LEVER |
below |
left or right as |
indicated by |
|||||||||
|
MANUAL |
|
|
|
arrows. This will not affect the next operation. |
|||||||||||
|
LEVER |
|
|
|
ATION: • FOR MORE THAN ONE DAILY ON-OFF OPER-
Place additional tripper pairs on CLOCK-DIAL (order 156T1978A).
• IN CASE OF POWER FAILURE: Reset CLOCK-DIAL to proper time of day. See step 2 above.
WIRING INFORMATION - COPPER CONDUCTORS ONLY
|
|
TERMINAL TORQUE* |
|
|
|
GENERAL |
|
|
|
|
|
|
|
GENERAL |
PURPOSE |
|
|
|
|
MAX MOTOR |
PURPOSE |
BRANCH |
|
|
SUPPLY |
LINE AND |
|
LOAD |
BRANCH |
CIRCUIT |
|
WIRE SIZE |
CIRCUIT |
NEUTRAL |
NEUTRAL |
(CONTINUOUS |
CIRCUIT |
MAXIMUM |
|
75˚C MIN |
BREAKER |
MAIN |
AND |
DUTY) |
BREAKER |
CURRENT |
|
INSULATION |
RATING |
LUGS |
GROUND |
120V. |
240V. |
RATING |
CAPACITY |
AWG |
AMP |
LB-IN |
LB-IN |
HP |
HP |
AMP |
AMP |
14 |
15 |
35 |
20 |
1/2 |
1 |
15 |
12 |
12 |
20 |
35 |
20 |
1 |
2 |
20 |
16 |
10 |
30 |
35 |
20 |
1 1/2 |
3 |
30 |
24 |
8 |
50 |
40 |
25 |
2 |
5 |
40 |
32 |
6 |
60 |
45 |
35 |
--- |
--- |
60 |
44 |
|
|
|
|
|
|
|
|
*TORQUE CIRCUIT BREAKER LUGS TO VALUES SPECIFIED ON
CIRCUIT BREAKERS
INTERMATIC INCORPORATED
SPRING GROVE ILLINOIS 60081-9698 158TP12178