Intermatic T21004R User Manual

4.5 (2)
Intermatic T21004R User Manual
LR3730
UL 508
UL1563
CLASS CTL DISTRIBUTION/CONTROL

MODEL: T21004R

IN RAINPROOF (TYPE 3R) ENCLOSURE FOR INDOOR/OUTDOORPANEL WITHUSETIME SWITCH

60SUITABLEAMPFOR120/240SWIMMINGVOLTPOOLOR/SPA120/208APPLICATIONSVOLTANDSINGLEFOR DIRECTPHASE,CONDUIT(THREECONNECTIONWIRE)TO A ACWET-NICHE OR NO NICHE LUMINAIRE.

IMPORTANT:The short circuit rating of this panel is 10000 symmetrical amperes.

This control panel must be installed according to the National Electrical Code (including article 680) or Canadian Electrical Code (including section 68) and local code requirements. This installation is subject to the approval by the local inspection authority. The main lugs and neutral main are suitable for No. 14 to 2 AWG COPPER conductors. Use No. 14 to 6 AWG COPPER conductors for branch circuit wiring. Follow gauge selection table and corresponding terminal screw tightening torque requirements below. Install interchangeable circuit breakers with an interrupting current rating of 10000 symmetrical amperes, or higher. All circuit breakers in this control panel shall be of the same manufacturer and type. See list of suitable types below. Follow manufacturers instructions for installing and testing of ground fault circuit breakers (GFCB) and interrupters (GFCI). Install only LISTED receptacle(s) and/or wiring device(s) inside the enclosure. A LISTED wiring device may be installed in the rectangular side knockout provided. When panel is outdoors, a LISTED rainproof cover must be installed over the wiring device in the side knockouts. If this enclosure is used for direct conduit connection to a wet-niche or no niche luminaire, one of the connection kits listed below in Note 5 must be used. This control should not be connected to any equipment which would cause bodily injury or property damage should it be activated unexpectedly. After wiring, install front panel over wiring compartment and close unused breaker openings with filler plates. KEEP DOOR CLOSED AT ALL TIMES.

 

 

 

SUITABLE LISTED BREAKERS

 

 

 

 

 

 

 

 

 

 

 

 

CIRCUIT BREAKER

 

 

FILLER

 

MANUFACTURER

 

SINGLE

DOUBLE

TWIN

QUAD

 

GFCB

 

PLATE

 

 

 

 

 

 

CUTLER-HAMMER

 

 

BR

 

BR

BRD

BRD

 

GFCB

 

BRFP

 

MURRY

 

 

MP-T

MP-T

MH-T

MH-T

 

MP-GT

 

LX100FP

 

SIEMENS

 

 

 

QP

 

QP

QT

QT

 

QPF

 

QF3

 

SQUARE D

 

 

HOM

 

HOM

HOMT

HOMT

 

----

 

HOMFP

 

THOMAS & BETTS

 

 

TB

 

TB

TBBD

TBBQ

 

GFB

 

FP-1C-TB

 

NOTES:

 

 

 

 

 

 

 

 

 

 

 

 

 

1. Any Intermatic T100M or ET100CM series Time Switch, PF1000M

Series freeze protection or RC2000M Series air switch mechanism

may be installed in the bracket provided or in the event an existing

mechanism is replaced.

 

 

 

 

 

 

 

 

 

2. If this control panel requires bonding, attach a LISTED bonding

terminal of a suitable size using the mounting hole(s) provided on the

bottom of the enclosure (156T11047A may be ordered).

 

 

 

3. When a back-fed breaker is used in this control panel, order

22T904A to comply with NEC article 384-16 (g).

 

 

 

 

4. Wiring devices may be installed in this control panel (order 21T156A

(4) Standoffs for mounting).

 

 

 

 

 

 

 

5. The following kits are available to connect under water luminaires to this

enclosure:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1/2” non-metallic - order 156PA13713A

 

 

 

 

 

 

3/4” non-metallic - order 156PA13714A

 

 

 

 

 

 

1” non-metallic - order 156PA13715A

 

 

 

 

 

 

1/2” metallic - order 156PA14336A

 

 

 

 

 

 

TIME SWITCH RATINGS:

 

 

 

 

 

 

 

 

 

30 AMP. RESISTIVE, INDUCTIVE, TUNGSTEN OR 1000 VA PILOT DUTY -

120/208/240 VOLT A.C. 2 HP

(24 FLA)-120 VOLT A.C.,

 

 

 

 

5 HP (28 FLA)-240 VOLT A.C.

 

 

 

 

 

 

 

CLOCK MOTOR: 208-277 VOLTS 60 HZ.

 

 

 

 

 

 

(To order clock motor replacement, specify part no. WG--on motor cover)

 

 

 

TIME SWITCH OPERATING INSTRUCTIONS

 

 

 

 

 

 

1. TO SET "ON" AND "OFF" TIMES:

 

pointing to time (AM or PM)

Hold TRIPPERS against edge of CLOCK-DIAL,

when ON and

OFF operations are desired. Tighten tripper

screws firmly.

TIME

 

2.

TO SET TIME-OF-DAY:

 

 

 

 

POINTER

 

 

 

Pull CLOCK-DIAL outward. Turn in either direction

TIME

ON

 

 

and align the exact time-of-day on the CLOCK-DIAL

TRIPPER (the time now, when switch is being put into opera-

DIAL

 

 

 

 

 

 

 

 

 

tion) to the pointer.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

-DO NOT MOVE POINTER-

 

 

 

OFF

 

 

 

TO OPERATE SWITCH MANUALLY: Move MAN-

TRIPPER

 

 

 

UAL-LEVER

below

left or right as

indicated by

 

MANUAL

 

 

 

arrows. This will not affect the next operation.

 

LEVER

 

 

 

ATION: FOR MORE THAN ONE DAILY ON-OFF OPER-

Place additional tripper pairs on CLOCK-DIAL (order 156T1978A).

IN CASE OF POWER FAILURE: Reset CLOCK-DIAL to proper time of day. See step 2 above.

WIRING INFORMATION - COPPER CONDUCTORS ONLY

 

 

TERMINAL TORQUE*

 

 

 

GENERAL

 

 

 

 

 

 

GENERAL

PURPOSE

 

 

 

 

MAX MOTOR

PURPOSE

BRANCH

 

SUPPLY

LINE AND

 

LOAD

BRANCH

CIRCUIT

WIRE SIZE

CIRCUIT

NEUTRAL

NEUTRAL

(CONTINUOUS

CIRCUIT

MAXIMUM

75˚C MIN

BREAKER

MAIN

AND

DUTY)

BREAKER

CURRENT

INSULATION

RATING

LUGS

GROUND

120V.

240V.

RATING

CAPACITY

AWG

AMP

LB-IN

LB-IN

HP

HP

AMP

AMP

14

15

35

20

1/2

1

15

12

12

20

35

20

1

2

20

16

10

30

35

20

1 1/2

3

30

24

8

50

40

25

2

5

40

32

6

60

45

35

---

---

60

44

 

 

 

 

 

 

 

 

*TORQUE CIRCUIT BREAKER LUGS TO VALUES SPECIFIED ON

CIRCUIT BREAKERS

INTERMATIC INCORPORATED

SPRING GROVE ILLINOIS 60081-9698 158TP12178