Intermatic T173 Owner's Manual

0 (0)
Intermatic T173 Owner's Manual

MODEL: T173

LR3730

24 HR DIAL TIME SWITCH WITH “SKIPPER®

DOUBLE POLE SINGLE THROW (DPST)

40 AMP. RESISTIVE, INDUCTIVE, TUNGSTEN OR

1000 VA. PILOT DUTY PER POLE - 120/208/277 VOLT AC; 2 HP (24 FLA) - 120V AC; 5 HP (28 FLA ) - 240V AC.

CLOCK MOTOR: 110-125 VOLTS - 60 HZ.

CLOCK MOTOR VOLTAGE AND CYCLE MUST BE AS SPECIFIED. TO ORDER REPLACEMENT, INDICATE PART NO. (WG--) ON MOTOR COVER.

 

ON/CUTOUT

 

WIRING

 

 

 

CLOCK

TIME

DIAGRAM

 

 

 

TRIPPER

 

 

 

 

 

 

 

MOTOR

POINTER

DAY

 

 

 

 

 

 

 

 

 

TIME

ARROW

 

 

 

A

1

2

3

4

 

DIAL

SKIPPER

 

 

 

 

OFF

 

 

 

NEUT.

 

 

 

 

 

WHEEL

 

 

 

LINE 1

 

 

 

 

 

TRIPPER

 

 

 

 

 

 

 

TO

 

 

 

 

 

 

 

 

MANUAL

 

 

 

 

LINE 2

 

 

 

 

SKIPPING

 

 

 

 

 

 

GROUND

LOAD(S)

LEVER

SCREW

 

 

 

 

 

 

 

 

 

 

 

 

 

120/240 VOLT 3 WIRE SUPPLY

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

WIRING INSTRUCTIONS: To wire switch follow diagram above. Use solid or stranded COPPER only wire with insulation to suit installation. See gauge selection table for normal service applications. To make power connections remove 1/2 inch of insulation from wire ends. Insert bare ends of wire under the pressure plate of terminals. Use 3/16 or larger screwdriver to tighten terminal screws firmly. (25 lb-in minimum).

REPLACE INSULATOR BEFORE TURNING ON ELECTRICITY.

MINIMUM

MAX.

MIN.

75°C INSULATION MAX. MOTOR

PRESSURE PLATE

COPPER

LOAD

INSUL-

 

LOAD (HP)

 

WIRE SIZE

(AMP)

ATION

SINGLE PHASE

3 PHASE

 

(AWG)

 

TEMP(°C)

TERMINAL SCREW

 

 

 

120 V.

240 V.

208 V.

240 V.

14

15

60

1/2

2

 

 

MAKE SURE WIRE

12

20

60

1

2 1/2

N/A

N/A

INSULATION CLEARS

10

30

60

2

3

 

 

PRESSURE PLATE

8

40

75

-

5

 

 

 

 

 

 

 

 

 

 

PROGRAMMING INSTRUCTIONS

1. TO SET “ON” AND “OFF” TIMES: Hold trippers against edge of CLOCK-DIAL, pointing to time (AM or PM) when ON and OFF operations are desired, tighten tripper screws firmly. For additional tripper pairs on CLOCK-DIAL order 156T1948A.

2. TO SET TIME-OF-DAY: Pull CLOCK-DIAL outward. Turn in either direction and align the exact time-of-day on the CLOCK-DIAL (the time now, when switch is being put into operation) to the pointer.

DO NOT MOVE POINTER.

3. TO SKIP OPERATION(S) ON SELECTED DAY(S): Insert SKIPPING SCREW(S) in SKIPPER WHEEL for day(s) automatic operation(s) is/are NOT required. Tighten screws firmly. Move MANUAL LEVER to

“OFF” and rotate SKIPPER WHEEL to locate correct day-of-week opposite DAY ARROW--”YESTERDAY” if ON/CUTOUT TRIPPER has not yet advanced wheel “TODAY” if it has.

OPERATING INSTRUCTIONS

• TO OPERATE SWITCH MANUALLY: Move MANUAL LEVER below

CLOCK-DIAL left or right as indicated by arrows. This will not effect next operation.

CAUTION: TO AVOID SLOW SWITCH ACTION FAILURE, DO NOT OPERATE SWITCH MANUALLY NOR PLACE A TRIPPER 4 HOURS PRIOR TO ON/CUTOUT TRIPPER SWITCHING.

• IN CASE OF POWER FAILURE, reset CLOCK-DIAL to proper time- of-day. See programming instructions.