OPERATION

Both green indicator lights will be ON when power is present and the IG1240RC is operating properly. If one of the indicator lights is OFF, check the breakers to make sure that both are on and not tripped. If one or both of the green indicators are OFF, and the red indicator is on, the IG1240RC is no longer protecting. Replace the unit.

FIVE YEAR PRODUCT WARRANTY

SURGE PROTECTION DEVICES

If within five (5) years from the date of purchase, this surge protection device fails due to defect in material or workmanship, Intermatic Incorporated will repair or replace it free of charge. The warranty does not apply to: (a) damage caused by accident, abuse, mishandling, dropping; (b) units which have been subject to unauthorized repair, opened, taken apart; (c) units not used in accordance with directions; (d) damages exceeding the cost of the product. Some states do not allow a limitation of damages, so the foregoing limitations may not apply to you. This warranty gives you specific legal rights and you may also have other rights which vary from state to state. This warranty service is available by either (a) returning the product to the dealer from whom the unit was purchased, or

(b) by contacting Intermatic at 1-800-270-7227.

For complete information regarding the Warranty on this product, refer to the enclosed form, “FIVE YEAR LIMITED PRODUCT and CONNECTED EQUIPMENT WARRANTY for INTERMATIC Panel Guard Residential SURGE PROTECTION DEVICE”.

INTERMATIC INCORPORATED

SPRING GROVE, ILLINOIS 60081-9698

HTTP: WWW.INTERMATIC.COM

158IG11162

MODEL IG1240RC

INSTALLATION INSTRUCTIONS

(FIG.1)

CAUTION

Electricity is dangerous; follow safety rules. Never work on equipment with the electricity turned “ON”. Be absolutely certain the power is turned “OFF” to the circuit or device you are installing. Be sure you read and understand all of these installation steps before you begin to install this Surge Protection Device. For your protection, check and follow your local electrical codes. Do not touch electric circuits or devices when you are wet or standing on a wet surface. Use

a circuit tester or AC voltmeter to be sure the electricity is “OFF” before you touch wires or devices. This device is suitable for use on a circuit capable of delivering not more than 25,000 rms symmetrical ampers, 240 volts maximum.

NOTE:

ELECTRICAL GROUND IS REQUIRED FOR THIS UNIT TO

FUNCTION PROPERLY AND SAFELY!

STEP 1

Select a mounting location for the Surge Protection Device (SPD) which will allow convenient connection to the panel while keeping the lead wires as short as possible. Use an AC voltmeter or circuit tester across two breaker outputs to confirm that there is 240 volts between them. If the voltage is 0, select a different breaker of equal amperage.