Honeywell W7081, W7100A, W7100C Catalog Page

0 (0)
Honeywell W7081, W7100A, W7100C Catalog Page

Legacy Building Systems

W7081 Limit Controller

Used with W7080A Load Analyzer to provide cold deck low limit, hot deck high limit, and economizer/mixed air low limit functions.

• Limits the maximum and minimum temperatures of the hot and cold deck and of the mixed air by supplying modified demand signals to the W7080A Load Analyzer and to the economizer

• The positive limits stabilize deck temperatures under light load conditions providing greater comfort and reducing energy usage

• Has jumper selectable set points for each of its 3 functions

• Compact to fit easily in HVAC system control panel

• Mounts with 4 No. 8 screws (not provided) through holes in base

Application Size: Small (<20 I/O Points)

Dimensions, Approximate: 6 1/4 in. high x 4 1/8 in. wide x 2 5/16 in. deep (159 mm high x 105 mm wide x 59 mm deep)

Electrical Connections: 1/4 in. quick-connect male terminals

Power Consumption: 0.29 VA maximum

Operating Temperature Range: -40 F to +150 F (-40 C to +65 C)

Shipping Temperature Range: -40 F to +150 F (-40 C to +65 C)

Approvals

ASHRAE Guidelines: Meets ASHRAE 90-75

Canadian Standards Association: Component Recognized Department of Defense Guidelines: Meets

Underwriters Laboratories, Inc: Component Recognized

 

 

 

 

 

Product Number

Application

Control System

Compatible with:

Description

 

 

 

 

 

W7081A1015/U

Split System; Heat Pump Systems; Furnace; Packaged RTU

W7080 control system

W7080 Load analyzer

Limit Controller

 

 

 

 

 

W7100A,C Discharge Air Temperature Controller

Maintain an average discharge air temperature in variable air volume (VAV) systems, or other systems requiring discharge air control of multistage cooling or heating. Reduce kilowatt demand

and consumption by maintaining the minimum amount of heating or cooling capacity required to hold the discharge air set point. Utilize economizer for free cooling when available.

W7100 Controller maintains an average discharge air temperature in variable air volume (VAV) cooling systems by modulating an economizer and sequencing stages of mechanical cooling

The W7100 can be applied to electric makeup air and other systems requiring discharge air control of multistage heating or cooling

Staging capacity of the W7100A,C can be extended six stages using a W7101A Satellite Sequencer

When power is interrupted, the system cycles to all stages off

When power is restored, the economizer will first be modulated open (if enthalpy is suitable), then stages of mechanical cooling will be sequenced on

If enthalpy is not suitable for economizer operation, the first stage of cooling or heating is energized within five minutes

Reset signal from either space sensor or outdoor air sensor

Dimensions, Approximate: 8 5/8 in. high x 6 1/2 in. wide x 3 in. deep (219 mm high x 161 mm wide x 76 mm deep)

Contact Ratings:

NO 240 VA inrush @ 24 Vac, 60 VA running @ 24 Vac NC 75 VA inrush @ 24 Vac, 30 VA running @ 24 Vac

NO 750 VA inrush @ 120/240 Vac, 75 VA running @ 120/240 Vac NC 240 VA inrush @ 40 Vac, 30 VA running @ 24 Vac

Electrical Connections: 1/4 in. quick-connect male terminals Voltage: 20 to 30 Vac

Frequency: 50 Hz; 60 Hz

Power Consumption: 12 VA at 24 Vac, 50/60 Hz (max).

Operating Temperature Range: 40 F to 90 F (4 C to 32 C) Setpoint Temperature Range: 40 F to 90 F (4 C to 32 C) Shipping Temperature Range: -40 F to +150 F (-40 C to +65 C)

Accessories:

S963B1037-Manual Potentiometer (480 ohm) S963B1078-Manual Potentiometer (500 ohm) S963B1128-Manual Potentiometer (135 ohm)

 

 

 

 

 

 

 

 

 

Application

Control

 

 

 

Product Number

Application

Size

System

Output Type

Description

Comments

 

 

 

 

 

 

 

W7100A1053/U

Discharge Air

0 Heat / 6 Cool

W7100 family

Staged On/Off

20 to 30 Vac Discharge air

Additional stages of heating and

 

 

 

 

 

temperature controller

cooling can be achieved by adding

 

 

 

 

 

 

a W7101 Satellite Sequencer

 

 

 

 

 

 

 

W7100C1018/U

Discharge Air

2 Heat / 4 Cool

W7100 family

Staged On/Off

20 to 30 Vac Discharge air

Additional stages of heating and

 

 

 

 

 

temperature controller

cooling can be achieved by adding

 

 

 

 

 

 

a W7101 Satellite Sequencer

 

 

 

 

 

 

 

336

customer.honeywell.com

70-6910