ADEMCO VISTA SERIES
VISTA-20P / VISTA-20PSIA
VISTA-15P / VISTA-15PSIA
Security Systems
Installation and Setup Guide
K5305-1V5 10/04 Rev. A
RECOMMENDATIONS FOR PROPER PROTECTION
The Following Recommendations for the Location of Fire and Burglary Detection Devices Help Provide Proper Coverage for the Protected Premises.
Recommendations For Smoke And Heat Detectors
With regard to the number and placement of smoke/heat detectors, we subscribe to the recommendations contained in the National Fire Protection Association's (NFPA) Standard #72 noted below.
Early warning fire detection is best achieved by the installation of fire detection equipment in all rooms and areas of the household as follows: For minimum protection a smoke detector should be installed outside of each separate sleeping area, and on each additional floor of a multi-floor family living unit, including basements. The installation of smoke detectors in kitchens, attics (finished or unfinished), or in garages is not normally recommended.
For additional protection the NFPA recommends that you install heat or smoke detectors in the living room, dining room, bedroom(s), kitchen, hallway(s), attic, furnace room, utility and storage rooms, basements and attached garages.
In addition, we recommend the following:
•Install a smoke detector inside every bedroom where a smoker sleeps.
•Install a smoke detector inside every bedroom where someone sleeps with the door partly or completely closed. Smoke could be blocked by the closed door. Also, an alarm in the hallway outside may not wake up the sleeper if the door is closed.
•Install a smoke detector inside bedrooms where electrical appliances (such as
|
KITCHEN |
TV ROOM |
KITCHEN |
DINING |
BDRM |
DINING |
BEDROOM BEDROOM |
||||
|
|
|
|
|
|
|
|
|
LIVING ROOM |
BDRM |
|
|
|
|
|
LIVING ROOM |
|
|
|
BEDROOM |
BEDROOM |
||||||
|
|
|
|
|
|||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Smoke Detectors for Minimum Protection |
|
|
|
|
|
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
|
|
Smoke Detectors for Additional Protection |
|
|
|
|
|
|
|
|
|
|
|
||
|
|
|
|
|
BEDROOM |
|
|
Heat-Activated Detectors |
BEDROOM |
TO |
BEDROOM |
|
|
BR |
|
|
||
|
|
|
|
|
|
|
KTCHN |
|
GARAGE |
LVNG RM |
|
. |
CLOSED |
|
|
|
|||
|
|
|
DOOR |
|
BASEMENT |
|
|
|
|
|
|
|
|
floor_plan-001-V0 |
portable heaters, air conditioners or humidifiers) are used.
•Install a smoke detector at both ends of a hallway if the hallway is more than 40 feet (12 meters) long.
•Install smoke detectors in any room where an alarm control is located, or in any room where alarm control connections to an AC source or phone lines are made. If detectors are not so located, a fire within the room could prevent the control from reporting a fire or an intrusion.
THIS CONTROL COMPLIES WITH NFPA
REQUIREMENTS FOR TEMPORAL PULSE
SOUNDING OF FIRE NOTIFICATION
APPLIANCES.
Recommendations For Proper Intrusion Protection
For proper intrusion coverage, sensors should be located at every possible point of entry to a home or commercial premises. This would include any skylights that may be present, and the upper windows in a multi-level building.
In addition, we recommend that radio backup be used in a security system so that alarm signals can still be sent to the alarm monitoring station in the event that the telephone lines are out of order (alarm signals are normally sent over the phone lines, if connected to an alarm monitoring station).
ii
Table Of Contents
Features and Installation Highlights............................................................................................................ |
1-1 |
Capabilities and Functions................................................................................................................................................ |
1-1 |
Compatible Devices ........................................................................................................................................................... |
1-2 |
Important Installation Highlights (Installer Please Read) ............................................................................................. |
1-2 |
Mounting and Wiring the Control ................................................................................................................. |
2-1 |
Installing the Control Cabinet and PC Board .................................................................................................................. |
2-1 |
Cabinet and Lock ......................................................................................................................................................... |
2-1 |
Mounting the PC Board Alone (no RF Receiver) ........................................................................................................ |
2-1 |
Mounting Board with RF Receiver.............................................................................................................................. |
2-1 |
AUXILIARY DEVICE CURRENT DRAW WORKSHEET .............................................................................. |
2-2 |
AC Power, Battery, and Ground Connections .................................................................................................................. |
2-3 |
1321 Transformer......................................................................................................................................................... |
2-3 |
1361X10 Transformer .................................................................................................................................................. |
2-3 |
Battery Connections..................................................................................................................................................... |
2-3 |
Battery Saver Feature ................................................................................................................................................. |
2-3 |
Earth Ground ............................................................................................................................................................... |
2-3 |
Sounder (Bell) Connections ............................................................................................................................................... |
2-4 |
Basic Connections ........................................................................................................................................................ |
2-4 |
Supervised output ........................................................................................................................................................ |
2-4 |
Connecting the Keypads and Other Addressable Devices ............................................................................................... |
2-4 |
Connections .................................................................................................................................................................. |
2-4 |
Supplementary Power (optional)................................................................................................................................. |
2-4 |
Keypad Notes ............................................................................................................................................................... |
2-5 |
Long Range Radio Connections................................................................................................................................... |
2-5 |
Table of Device Addresses ................................................................................................................................................. |
2-5 |
Hardwire Zones and Zone Expansion ............................................................................................................................... |
2-6 |
Hardwire Zones ............................................................................................................................................................ |
2-6 |
Double-Balanced Zones................................................................................................................................................ |
2-6 |
Zone Doubling .............................................................................................................................................................. |
2-6 |
Smoke Detectors........................................................................................................................................................... |
2-6 |
Smoke Detector Notes.................................................................................................................................................. |
2-7 |
4219/4229 Expansion Zones ........................................................................................................................................ |
2-7 |
Installing the RF Receiver and Wireless Transmitter Zones .......................................................................................... |
2-8 |
Compatible Receivers................................................................................................................................................... |
2-8 |
Receiver Connections ................................................................................................................................................... |
2-8 |
RF Receiver Notes........................................................................................................................................................ |
2-8 |
Installing a 5800TM Module ....................................................................................................................................... |
2-9 |
Installing the Transmitters ......................................................................................................................................... |
2-9 |
Transmitter Battery Life ............................................................................................................................................. |
2-9 |
Installing a Keyswitch..................................................................................................................................................... |
2-10 |
Keyswitch Connections .............................................................................................................................................. |
2-10 |
Keyswitch Notes......................................................................................................................................................... |
2-10 |
Connecting Relay Modules, Powerline Carrier Devices and Output Triggers.............................................................. |
2-11 |
4204/4229 Relay Modules .......................................................................................................................................... |
2-11 |
Powerline Carrier Devices ......................................................................................................................................... |
2-11 |
On-Board Triggers ..................................................................................................................................................... |
2-12 |
Phone Line/Phone Module, and Audio Alarm Verification (AAV) Connections............................................................ |
2-13 |
Phone Line.................................................................................................................................................................. |
2-13 |
4285/4286 Phone Module........................................................................................................................................... |
2-13 |
Phone Module Problems ............................................................................................................................................ |
2-13 |
Audio Alarm Verification Connections...................................................................................................................... |
2-14 |
Programming Overview ................................................................................................................................... |
3-1 |
About Programming .......................................................................................................................................................... |
3-1 |
Mechanics of Programming............................................................................................................................................... |
3-1 |
Data Field Programming Procedures.......................................................................................................................... |
3-1 |
Interactive Mode Programming ( 56, *57, 58, 79, 80, 81, 82)........................................................................... |
3-2 |
Loading Factory Defaults/Initializing for Download.................................................................................................. |
3-2 |
Exiting the Programming Mode .................................................................................................................................. |
3-2 |
Zone Type Definitions........................................................................................................................................................ |
3-2 |
iii
Table Of Contents (continued)
Data Field Programming ................................................................................................................................. |
4-1 |
About Data Field Programming........................................................................................................................................ |
4-1 |
System Setup Fields ( 20 – 29) ....................................................................................................................................... |
4-1 |
Zone Sounds & Timing ( 31– 39) ..................................................................................................................................... |
4-1 |
Dialer Programming ( 40 – 50) ....................................................................................................................................... |
4-2 |
System Status Report Codes ............................................................................................................................................. |
4-4 |
Miscellaneous System Fields ............................................................................................................................................ |
4-5 |
Pager Programming Fields................................................................................................................................................ |
4-7 |
Miscellaneous System Fields ............................................................................................................................................ |
4-8 |
Configurable Zone Type Fields ......................................................................................................................................... |
4-9 |
Touch Screen Device (AUI) Enable................................................................................................................................. |
4-11 |
Keypad Programming Fields........................................................................................................................................... |
4-11 |
Menu Mode Programming ............................................................................................................................... |
5-1 |
Zones and Partitions.......................................................................................................................................................... |
5-1 |
About Zone Programming ( 56 and 58 Menu Modes) .................................................................................................... |
5-1 |
56 Zone Programming Procedure ................................................................................................................................... |
5-1 |
Completing Zone Programming ........................................................................................................................................ |
5-4 |
58 Expert Programming Mode Procedures..................................................................................................................... |
5-4 |
Wireless Key Programming Templates ............................................................................................................................ |
5-6 |
About Output Device Programming (*79/*80 Menu Mode) ............................................................................................. |
5-8 |
Programming Output Devices........................................................................................................................................... |
5-8 |
*79 Menu Mode: Output Device Mapping ........................................................................................................................ |
5-8 |
*80 Menu Mode: Defining Output Functions ................................................................................................................. |
5-10 |
About Zone Lists (*81 Menu Mode) ................................................................................................................................ |
5-12 |
Zone List Programming................................................................................................................................................... |
5-12 |
About Function Keys (*57 Menu Mode).......................................................................................................................... |
5-13 |
Programming Function Keys .......................................................................................................................................... |
5-13 |
About Descriptor Programming (*82 Menu Mode) ........................................................................................................ |
5-14 |
Programming Zone Descriptors (Menu Mode 82)......................................................................................................... |
5-14 |
Adding Custom Words (will not be annunciated by 4285/4286 Phone Module) ........................................................... |
5-15 |
Programming Installer and User Schedules .................................................................................................................. |
5-17 |
System Communication and Operation ....................................................................................................... |
6-1 |
Panel Communication with Central Station .................................................................................................................... |
6-1 |
Report Code Formats......................................................................................................................................................... |
6-1 |
Ademco Contact ID® ......................................................................................................................................................... |
6-3 |
System Security Codes ...................................................................................................................................................... |
6-4 |
Panic Keys...................................................................................................................................................................... |
6-6 |
Setting the Real-Time Clock ............................................................................................................................................. |
6-6 |
Various System Trouble Displays..................................................................................................................................... |
6-7 |
Testing the System............................................................................................................................................. |
7-1 |
About Test Procedures....................................................................................................................................................... |
7-1 |
System Test........................................................................................................................................................................ |
7-1 |
Checking Transmitter Enrollment (Sniffer Mode)........................................................................................................... |
7-1 |
Go/No Go Test Mode .......................................................................................................................................................... |
7-2 |
Dialer Communication Test and Periodic Test Reports................................................................................................... |
7-2 |
Automatic Standby Battery Tests..................................................................................................................................... |
7-2 |
Specifications & Accessories........................................................................................................................... |
8-1 |
Security Control................................................................................................................................................................. |
8-1 |
Compatible Devices ........................................................................................................................................................... |
8-1 |
5800 Series Transmitter Input Loop Identification ......................................................................................................... |
8-3 |
Regulatory Agency Statements ...................................................................................................................... |
9-1 |
Limitations and Warranty ............................................................................................................................. |
10-7 |
iv
S E C T I O N 1
Features and Installation Highlights
This manual applies to the following Honeywell security systems:
ADEMCO VISTA-20P/ADEMCO VISTA-20PSIA/ADEMCO VISTA-20PCN (collectively referred to as VISTA-20P series), ADEMCO VISTA-15P/ADEMCO VISTA-15PSIA/ADEMCO VISTA-15PCN (collectively referred to as VISTA-15P series)
Features and procedures apply to all, except where differences are noted.
SIA Installations: The VISTA-20PSIA and VISTA-15PSIA are certified SIA-compliant controls that meet SIA specifications for False Alarm Reduction. The other controls described in this manual are not certified as SIA compliant, but can be programmed for False Alarm Reduction. To program for False Alarm Reduction, follow the SIA Guidelines noted in the applicable programming fields.
NOTE: Throughout this manual, device model numbers are ADEMCO model numbers unless otherwise noted.
Capabilities and Functions
Feature/Function |
ADEMCO VISTA-20P Series |
ADEMCO VISTA-15P Series |
Partitions |
• 2 partitions, can protect two independent |
VISTA-15P is not a partitioned system. |
|
areas |
|
|
• Common zone option allows either |
|
|
partition to arm, while leaving a common |
|
|
area (ex. lobby or foyer) disarmed for |
|
|
access into the other partition. |
|
Zones |
Up to 48 protection zones plus 16 keyfob |
Up to 32 zones plus 8 keyfob zones (zones |
|
zones (zones 49-64) for total of 64 zones: |
49-56) for total of 40 zones: |
|
• 8 basic hardwired zones (zones 1-8) with |
• 6 basic hardwired zones (zone 1-6) |
|
optional zone-doubling feature |
• Up to 16 additional wired zones (zones 9- |
|
• Up to 40 additional wired zones (zones 9- |
24) using up to 2 4219/4229 modules |
|
48) using up to 5 4219/4229 modules |
• Up to 26 wireless transmitter zones |
|
• Up to 40 wireless transmitter zones (5800 |
(5800 series; zones 9-34) |
|
series; zones 9-48) |
• Up to 2 configurable zone types |
|
• Up to 4 configurable zone types |
|
Security Codes |
Up to 48 Security Codes, with separate |
Up to 32 Security Codes, with separate |
|
authority levels and partition access |
authority levels |
One-button arming |
Dedicated keys can arm the system. |
Dedicated keys can arm the system. |
Schedules |
Up to 32; can control devices and/or auto- |
Up to 8; can control devices and/or auto- |
|
arm/disarm |
arm/disarm |
Keypad macros |
Up to 4; activated by wired keypads |
Up to 2; activated by wired keypads |
Paging |
Up to 4 pagers; certain system conditions |
Up to 2 pagers; certain system conditions |
|
can report to pagers; can use a dedicated |
can report to pagers; can use a dedicated |
|
key on keypads to send a signal to a pager |
key on keypads to send a signal to a pager |
Event Logging |
100 events; log display is done via Ademco |
50 events; log display is done via Ademco |
|
Compass Downloader software or |
Compass Downloader software or |
|
installer/master code at Keypad |
installer/master code at Keypad |
Zone descriptors |
Can assign for all zones (for alpha display keypads and/or 4285/4286 Phone Module). |
|
Bell supervision |
Optional, detects external sounder wiring short or open; causes a trouble condition, |
|
|
keypad display, and sends a report to the central monitoring station, if enabled. |
|
RF jam detection |
Optional, for wireless systems detects a condition that may impede proper RF reception |
|
|
(i.e., jamming or other RF interference); causes keypad display, and sends a report to the |
|
|
central monitoring station (if trouble reporting is enabled). |
|
Telephone Line |
Built-in option can monitor the telephone line voltage and can cause a local display, or a |
|
Monitoring |
display and trouble/alarm sound |
|
Downloading |
Via an IBM compatible computer, Compass downloading software, and a compatible |
|
|
HAYES or CIA modem specified by Ademco. |
|
1-1
Installation and Setup Guide
Compatible Devices
Device |
VISTA-20P |
VISTA-15P |
Notes |
Addressable Keypads |
8 |
8 |
6150 Fixed-Word Keypad, 6160 Alpha Keypad, 6150V |
|
|
|
Fixed-Word Display Voice Keypad, 6160V Alpha |
|
|
|
Display Voice Keypad, 6150RF Keypad/Transceiver |
Touch Screen (AUI) |
2 |
2 |
Touch Screen (AUI) devices are in addition to the 8 |
Devices |
|
|
addressable keypads. E.g., Symphony, 6270 |
4219, 4229 Zone |
Up to 5 for |
Up to 2 for |
Zone numbers are predefined according to the device |
Expander Modules |
up to 40 |
up to 16 |
addresses used. See Expander Module Addresses table |
|
exp. zones |
exp. zones |
in Wiring section and set addresses accordingly. |
5800 Series Wireless |
Up to 40 RF |
Up to 26 RF |
Uses 5881/5883 Series Receivers/Transceivers. |
|
zones |
zones |
|
Output relays and/or |
Up to 16 |
Up to 8 |
Use any combination of 4204, 4229 and or Powerline |
Powerline Carrier |
|
|
Carrier Devices. |
Devices (X-10 type) |
|
|
Map output devices via *79 Menu mode. |
On-Board Triggers |
2 |
2 |
Can be used to reset 4-smoke detectors. |
Output functions |
Up to 48 |
Up to 24 |
Program output functions via *80 Menu mode. |
4285/4286 Phone |
Partition 1 |
yes |
Provides access to the system via on premises or off- |
Module |
only |
|
premises phones for arming, disarming, etc., plus |
|
|
|
control of relay outputs and Powerline Carrier devices. |
Audio Alarm |
Using AAV |
Using AAV |
Use ADEMCO UVS or Eagle Model 1250; can be used |
Verification |
module |
module |
in conjunction with an output trigger to permit voice |
|
|
|
dialog between an operator at the central station and |
|
|
|
a person at the premises. |
Alarm output |
12VDC, 2 |
12VDC, 2 |
Can drive the compatible sounders; steady output for |
|
AMP output |
AMP output |
burglary/panic, or temporal pulse (3 pulses – pause – |
|
|
|
3 pulses – pause – 3 pulses. . .) for fire. Uses current |
|
|
|
limiting circuitry for protection. |
Auxiliary Power Output |
See note. |
See note |
12VDC, 600 mA maximum; uses fuse for protection. |
Backup Battery |
See note. |
See note. |
Rechargeable (sealed lead-acid type) 12VDC, 4AH |
|
|
|
minimum. |
Long Range Radio |
See note. |
See note. |
Primary telephone number messages can be reported |
|
|
|
via ECP connection to various Long Range Radios |
|
|
|
(check compatibility/availability of specific models) |
AC Power Supply |
See note. |
See note. |
Plug-in 120VAC transformer, ADEMCO 1321 |
|
|
|
(1321CN in Canada) or, if using Powerline Carrier |
|
|
|
devices, ADEMCO 1361X10 Transformer Module |
NOTE: All devices and accessories used in a Canadian installation must be Listed for use in Canada.
Important Installation Highlights (Installer Please Read)
•This system uses addressable keypads and Zone Expander Modules (see Table of Addresses in
Section 2. Mounting and Wiring – Wiring the Keypads and Other Addressable Devices).
•Keypads must be set for addresses 16-23 (first keypad is address 16, which is different from previous controls) and programmed in data fields *190-*196.
•Zone Expander Modules must be set for specific addresses (07-11), based on the zone numbers used.
•4204 Relay Modules must be set for specific addresses (12-15).
•This control will not power-up unless AC power is connected (will not power-up on battery alone). However, once the system is powered up, it will operate on battery power in the event of AC loss.
•Relays have two programming menu modes: Use *79 Menu mode to map module addresses and device (output) numbers. Use *80 Menu mode to define the output functions.
•This system supports programmable function keys. Use *57 Menu mode to define the function keys.
•This system provides various paging features. Refer to the Programming Overview section for a summary on pager programming.
1-2
S E C T I O N 2
Mounting and Wiring the Control
Installing the Control Cabinet and PC Board
Cabinet and Lock |
1. |
Mount the control cabinet to a |
|
|
sturdy wall in a clean, dry area, |
|
|
which is not readily accessible to |
|
|
the general public, using fasteners |
|
|
or anchors (not supplied) with the |
|
|
four cabinet mounting holes. |
|
2. |
Remove cabinet door, then remove |
|
|
the lock knockout from the door. |
|
|
Insert the key into the lock. |
CHECK |
SNAP |
|
POSITION |
||
TAB |
||
LOCKED |
PUSH |
|
|
||
|
ADEMCO |
|
|
SNAP |
|
UNLOCKED |
TAB |
|
CABINET DOOR |
STEP 1 |
|
BOTTOM |
|
PUSH |
|
ON LOCK |
|
UNTIL IT |
IS SEATED |
|
SECURELY |
|
ADEMCO |
|
STEP 2 |
lock snap-001-V0 |
|
cab |
Figure 1. Installing the Cabinet Lock
3.Position the lock in the hole, making certain that the latch will make contact with the latch bracket when the door is closed. When correctly positioned, push the lock until the snap tabs hold it securely.
The cabinet can be secured without a lock by using 2 screws in the cover's edge.
Mounting the PC Board |
Before installing the cabinet's contents, remove the metal cabinet knockouts required for |
Alone (no RF Receiver) |
wiring entry. Do not remove the knockouts after the circuit board has been installed. |
1.Hang two short mounting clips (provided) on the raised cabinet tabs (see Detail B).
2.a. Insert the top of the circuit board into the slots at the top of the cabinet. Make sure that the board rests on the correct row (see Detail A).
b.Swing the base of the board into the mounting clips and secure the board to the cabinet with the accompanying screws (see Detail B).
CIRCUIT |
CABINET |
|
BOARD |
||
|
CIRCUIT |
|
BOARD |
|
+ |
+ |
CABINET |
DETAIL B |
|
SIDE VIEW |
DETAIL A |
OF MOUNTING |
SIDE VIEW |
CLIPS |
OF BOARD |
|
SUPPORTING |
|
SLOTS |
|
|
MOUNTING-001-V0 |
|
Figure 2. Mounting the PC Board |
Mounting Board with RF |
• Do not mount the cabinet on or near metal objects. This will decrease RF range and/or |
Receiver |
block RF transmissions from wireless transmitters. |
•Do not locate the cabinet in an area of high RF interference (revealed by frequent or prolonged lighting of the LED in the receiver (random flicker is OK)
1.a. Remove the receiver board from its case, then insert the top of the board into the slots at the top of the cabinet, as shown in Detail A in Figure 3 on the next page. Make sure that the board rests on the correct row of tabs.
b.Swing the base of the board into the mounting clips and secure it to the cabinet with the accompanying screws.
c.Insert the top of the control's board into the slot in the clips and position two clips at the lower edge of the board.
d.Swing this board into place and secure it with two additional screws.
2.Insert grounding lugs (supplied with the receiver) through the top of the cabinet into the left-hand terminals of the antenna blocks (at the upper edge of the receiver board) and secure them to the cabinet top with the screws provided (see Detail B).
3.Insert the receiver's antennas through the top of the cabinet, into the blocks' righthand terminals, and tighten the screws.
2-1
Installation and Setup Guide
CABINET |
A |
B |
CABINET
BOARD
RECEIVER CIRCUIT BOARD SUPPORTING
SLOTS
+ |
+ |
|
CIRCUIT |
|
BOARD |
|
MOUNTING |
|
CLIP |
CONTROL
CIRCUIT
BOARD
|
DETAIL A |
MOUNTING |
SIDE VIEW |
CLIP |
OF BOARD - |
SUPPORTING SLOTS
INSTALLATION WITH RECEIVER CIRCUIT BOARD
WHITE |
BLACK |
RED |
MOUNTING |
MOUNTING |
MOUNTING |
CLIP |
CLIP |
CLIP |
NOTE
A COMBINATION OF THESE MOUNTING CLIPS HAS BEEN INCLUDED IN YOUR INSTALLATION KIT.
USE THE APPROPRIATE CLIPS FOR MOUNTING.
IF NO RF RECEIVER IS USED, MOUNT THE PC BOARD USING EITHER THE WHITE OR BLACK CLIPS, WHICHEVER ARE INCLUDED IN THE CONTROL PANEL'S HARDWARE KIT.
ANTENNA
(2)
SCREW
(2)
GROUNDING
LUG
(2)
ANTENNA
MOUNT
(2 PLACES)
DETAIL B
ANTENNA AND GROUNDING
LUG INSTALLATION
pc_mount-001-V1
Figure 3. Mounting the PC Board and RF Receiver
AUXILIARY DEVICE CURRENT DRAW WORKSHEET
|
DEVICE |
CURRENT |
No. UNITS |
TOTAL CURRENT |
6150 |
Fixed-Word Keypad |
40mA/70mA** |
|
|
6160 |
Alpha Keypad |
40mA/150mA** |
|
|
6150V Fixed-Word Display Voice Keypad |
60mA/160mA** |
|
|
|
6160V Alpha Display Voice Keypad |
60mA/190mA** |
|
|
|
8132/8142 Series AUI (Symphony) |
150mA/400mA** |
|
|
|
6270 |
Touch Screen Keypad |
180mA/280mA** |
|
|
5881/5882 RF Receiver |
60mA |
|
|
|
5883 |
Transceiver |
80mA |
|
|
4219 Zone Expander |
30mA |
|
|
|
4204 |
Relay Unit |
15/180mA‡ |
|
|
4229 |
Zone Expander/Relay Unit |
30/100mA‡ |
|
|
4285 Phone Module |
160mA |
|
|
|
4286 Phone Module |
300mA |
|
|
|
|
|
|
|
|
* |
|
|
|
|
(Current available from Aux. terminals = 600 mA max.)† |
TOTAL = |
|
*If using hardwire devices such as PIRs, refer to the specifications for that particular unit's current draw. ** Values are for standby/alarm; alarm for keypads means armed with backlighting on and sounder on
†In UL installations, maximum current draw from the Auxiliary Output and the Alarm Output combined must not exceed 600 mA (500 mA max from Aux. Output). ‡Values are for relays OFF/relays ON.
CALIFORNIA STATE FIRE MARSHALL (CSFM) AND UL RESIDENTIAL FIRE
24-HOUR BATTERY BACKUP REQUIREMENTS
The California State Fire Marshal and UL have regulations which require that all residential fire alarm control panels must be provided with a backup battery which has sufficient capacity to operate the panel and its attached peripheral devices for 24 hours in the intended standby condition, followed by at least 4 minutes in the intended fire alarm signaling condition. This control panel can meet these requirements without using a supplementary power supply, provided that the panel’s auxiliary power and bell output currents are limited as indicated below.
OUTPUT LIMITATIONS AND CORRESPONDING REQUIRED BATTERIES
OUTPUT CURRENT LIMITATIONS |
BATTERY INFORMATION |
||
Output Current Total |
Maximum Auxiliary Current |
Battery Capacity |
Recommended Battery |
|
|
To Use (Amp/Hrs) |
(Yuasa Model No.) |
600mA maximum total of |
45mA |
4AH |
NP4-12 (or ADEMCO 467) |
auxiliary power plus bell |
160mA |
7AH |
NP7-12 |
output currents |
200mA |
8AH |
NP4-12 (two) ‡ |
|
425mA |
14AH |
NP7-12 (two) ‡ |
|
500mA |
17.2AH |
NPG18-12 |
‡ NOTE: Use two batteries, connected in parallel. Obtain an Ademco Battery Harness Kit SA5140-1. (Both batteries will fit inside the cabinet.)
2-2
Mounting and Wiring the Control
AC Power, Battery, and Ground Connections
1321 Transformer
|
1 |
|
2 |
TO |
-001-V0 |
1 AND 2 |
1321X10 |
TERMINALS |
|
Connect the 1321 Transformer (1321CN in Canada) to terminals 1 and 2 on the control board. See Wire Run Chart for wire size to use.
•Use caution when wiring the transformer to the control to guard against blowing the transformer fuse (the fuse is non-replaceable).
Wire Run Chart
Distance from control |
Wire Size |
Up to 50 feet |
# 20 |
50–100 feet |
# 18 |
100-250 feet |
# 16 |
1361X10 Transformer
(required if using Powerline Carrier devices)
AC |
AC |
|
Sync |
S |
Ou |
|
tput |
igna |
Com l |
|
|
mon |
X10
Data
TO
8-PIN
CONNECTOR
1 |
2 |
|
|
||
TO |
-001-V0 |
|
1361X10 |
||
1 AND 2 |
||
TERMINALS |
|
Battery Connections
BLACK
RED |
|
|
CONNECT |
001-V0 |
|
FLYING LEADS |
- |
|
conn |
||
AFTER AC POWER |
||
IS APPLIED |
batt |
•Wiring to the AC transformer must not exceed 250 feet using 16 gauge wire. The voltage reading between terminals 1 and 2 of the control must not fall below 16.5VAC or an “AC LOSS” message will be displayed.
•Do not plug the transformer into the AC outlet until all wiring connections to the control are complete. As a safety precaution, always power down the control when making such connections.
1. Splice one end of a 3-conductor cable
to the wire ends of the SA4120XM-1 |
|
|
|
|
|
|
|
1 |
KEY |
3 |
4 |
5 |
6 |
7 |
8 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
Cable. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
2. Connect the SA4120XM-1 cable plug |
|
1361X10 TRANSFORMER |
|
17 (RED) |
|
(ORANGE) |
(YELLOW) |
18 (GREEN) |
(BLUE) |
(PURPLE) |
(BLACK) |
||||||
to the 8-pin connector on the control |
|
|
|
|
|
|
|
|
|
||||||||
(see the Summary of Connections |
AC |
AC |
SYNC COM |
DATA |
|
|
|||||||||||
1 |
2 |
3 |
4 |
5 |
|
|
|||||||||||
diagram for location of the 8-pin |
|
OUTPUT |
|
+12 AUX. |
GND (-) |
OUTPUT |
|
|
|
|
|||||||
|
|
|
|
|
|
|
|
|
DATA |
COM |
SYNC |
||||||
connector). |
|
|
|
|
|
|
|
|
|
||||||||
|
|
|
|
|
|
|
|
||||||||||
3. Connect the other end of the |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
SA412OX |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
CABLE |
|
3-conductor cable to the 1361X10 |
1 |
2 |
|
|
|
|
|
|
|
|
|
|
|
|
|
||
Transformer, as shown in Figure 4. |
CONTROL |
|
|
|
|
|
|
|
|
|
|
|
|
|
|||
|
BOARD |
|
|
|
|
|
|
|
|
|
|
|
|
|
TERMS.
Canadian Installations: See Powerline Carrier Device section for connections to the PSC04 X-10 Interface and trigger pins.
1.Place the 12-volt backup battery in the cabinet.
2.After all connections to the control are completed and AC power has been applied, connect the red and black flying leads on the control board to the battery. Do not attach these leads to the battery terminals until all connections are completed.
UL For UL installations and Residential fire installations, refer to the chart on page 2-2 at left for the correct battery size required to meet the mandatory standby time.
Battery Saver Feature
Earth Ground
BOARD CONTROL
25
CONNECT
PROPER
EARTH
GROUND
IF
DESIRED
earth_gnd-001-V0
The battery will disconnect from the system after its voltage decreases below 9VDC. This assists the control panel in recharging the battery when AC is restored. IMPORTANT: The panel will not power up initially on battery power only. You must plug the transformer in first, and then connect the battery.
•This product has been designed and laboratory-tested to ensure its resistance to damage from generally expected levels of lightning and electrical discharge, and does not normally require an earth ground.
•If an earth ground is desired for additional protection in areas of severe electrical activity, terminal 25 on the control board, or the cabinet, may be used as the ground connection point. The following are examples of good earth grounds available at most installations.
Metal Cold Water Pipe: Use a non-corrosive metal strap (copper is recommended) firmly secured to the pipe to which the ground lead is electrically connected and secured.
AC Power Outlet Ground: Available from 3-prong, 120VAC power outlets only. To test the integrity of the ground terminal, use a 3-wire circuit tester with neon lamp indicators, such as the UL Listed Ideal Model 61-035, or equivalent, available at most electrical supply stores.
2-3
Installation and Setup Guide
Sounder (Bell) Connections
Basic Connections
3 4
ALARM OUTPUT |
|
10.5 - 13.5 VDC |
|
2A MAX. |
V0 |
|
spkr conn-001- |
Make sounder connections to alarm output terminals 3 (+) and 4 (–).
•The 12VDC sounder output activates when an alarm occurs.
•Total current drawn from this output cannot exceed 2 amps (going beyond 2 amps will overload the power supply, or may cause the electronic circuit protecting the sounder output to trip).
•You must install a battery, since the battery supplies this current.
Supervised output
1.Cut the red Bell Supervision Jumper located above terminals 2 and 3 on the PC board.
2.Connect a 2k ohm resistor across the terminals of the last sounder. See Figure 5.
This control complies with NFPA requirements for temporal pulse sounding of fire notification appliances. Temporal pulse sounding for a fire alarm consists of: 3 pulses – pause – 3 pulses – pause – 3 pulses–etc..
UL
•Use only UL Listed sounding devices for UL installations.
•Bell supervision is required for fire alarm installations.
•The total current drawn from the alarm output and the auxiliary power output, combined, cannot exceed 600 mA. In addition, the sounding device must be a UL Listed audible signal appliance rated to operate in a 10.2-13.8 VDC voltage range, and must be mounted indoors.
TERMINALS ON |
EXTERNAL ALARM |
|
|
CONTROL BOARD |
SOUNDER |
|
|
4 |
|
|
|
ALARM |
|
2000 |
|
OBSERVE |
OHM |
|
|
OUTPUT |
|
||
POLARITY |
EOL |
|
|
TERMINALS |
|
||
+ |
RESISTOR |
||
+ |
|
||
|
|
|
|
3 |
|
|
|
2 |
IF BELL SUPERVISION IS ENABLED |
|
|
|
|
|
|
|
(RED JUMPER ON CONTROL BOARD IS CUT) |
|
|
|
CONNECT A 2000 OHM RESISTOR ACROSS |
-V0 |
|
|
THE EXTERNAL SOUNDER AS SHOWN BY |
||
CUT RED JUMPER ON CONTROL |
THE DOTTED LINE. |
|
001- |
|
|
sounder |
|
BOARD TO ENABLE BELL |
DO NOT CONNECT THE RESISTOR AT THE |
||
(SOUNDER) SUPERVISION. |
ALARM OUTPUT TERMINALS THEMSELVES! |
Figure 5. Sounder Wiring (Supervised)
Connecting the Keypads and Other Addressable Devices
Connections
|
|
4 _ |
|
|
|
|
5 + |
|
|
|
6 IN |
|
|
|
7 OUT |
BLACK |
RED |
GREEN |
YELLOW |
AR |
|
|
|
MED |
|
|
|
READY |
|
|
|
|
|
|
conn-001-V0 |
Supplementary Power (optional)
UL Use a UL Listed, battery-backed supply for UL installations. The battery supplies power to these keypads in case of AC power loss.
The battery-backed power supply should have enough power to supply the keypads with the UL required minimum standby power time.
Connect keypads and other addressable devices (4204, 4219, 4229, 4286, 5881, LRR, etc.) to the control’s keypad terminals as shown on the Summary of Connections diagram. The system supports up to 8 keypads, which can be assigned to partitions in any combination (see program fields *190-*196).
Determine wire size using the Wire Run Chart on the following page. For single 4-wire runs, determine the current drawn by all units, then refer to the Wiring Run chart to determine the maximum length that can be safely used for each wire size.
Use supplementary power if the control’s aux. power load for all devices exceeds 600mA (suggested power supply: AD12612). Connect as shown in Figure 6. Be sure to connect the negative (–) terminal on the power supply unit to terminal 4 (AUX –) on the control.
IMPORTANT: Keypads powered from supplies that do not have a backup battery will not function if AC power is lost. Make sure to power at least one keypad in each partition from the control’s auxiliary power output.
SUPPLEMENTARY |
CONTROL TERMINAL STRIP |
|||||
POWER SUPPLY |
||||||
|
|
|
|
|||
+ |
– |
AUX. AUX. DATA DATA |
||||
|
|
– |
+ |
IN |
OUT |
|
|
|
4 |
5 |
6 |
7 |
WIRERED |
|
WIREGRN |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
WIREBLK |
WIREYEL |
|
|
|
|
|
WIRERED |
|
WIREGRN |
|
|
||||
DIRECTLY TO |
WIREBLK |
|
|
WIREYEL |
|
||||||||||
|
|
|
|
IMPORTANT: |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
MAKE THESE |
|
|
|
|
|
|
|
|
|
|
|
KEYPADTO |
KEYPADTO |
KEYPADTO |
KEYPADTO |
CONNECTIONS |
KEYPADTO |
|
KEYPADTO |
|
KEYPADTO |
KEYPADTO |
V0-supplypwrsupp |
||||
SCREW |
|
|
|||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
|
|
|
|
TERMINALS AS |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
SHOWN. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Figure 6. Using a Supplementary Power Supply
2-4
Mounting and Wiring the Control
Keypad Notes
ARMED
READY
1 |
OFF |
|
|
|
|
|
4 |
|
|
2 |
AWAY |
|
|
MAX |
|
3 |
|
|||
|
5 |
|
STAY |
|||
7INST |
|
TEST |
|
|||
ANT |
8 |
6 |
|
|||
|
|
|
CODE |
|
BYPASS |
|
|
READY |
0 |
|
9 |
CHIME |
|
|
|
|
|
|
||
|
|
|
|
|
# |
|
Long Range Radio
Connections
Set device addresses. Refer to the instructions included with the devices and set each address according to the Table of Devices Addresses.
See Keypad Programming Fields (fields *190-*196) in Section 4. Data Field Programming for details on enabling keypad addresses, assigning keypad partitions and selecting keypad sounding options.
IMPORTANT: Each keypad must be assigned a unique, predefined address, from 16 to 23. The first keypad is address 16 (default = partition 1, all sounds enabled).
TOUCH SCREEN KEYPAD (AUI) NOTES:
•Use of up to 2 AUI devices (e.g., 6270, Symphony) is independent from standard keypads and does not affect the number of standard keypads the system can support.
•AUI devices must be set for either address 1 or address 2, depending on which unit is enabled in field *189.
•To ensure proper AUI device operation, connect only to controls having microprocessor version 3.0 or higher, and use AUI devices with the following rev levels: 6270 series use version 1.0.9 or higher; 8132/8142 (Symphony) series use version 1.1.175 or higher.
Connect the data in/data out terminals and voltage input terminals of the Long Range Radio to the control's keypad connection points.
Set the radio’s address to “03” following the instructions provided with the radio.
• Use compatible Long Range Radios (e.g., 7720PLUS, 7820, 7835C, or 7845C).
Wire Run Chart For Devices* Drawing Aux Power From The Control (12V+ & 12V–)
Wire |
TOTAL CURRENT DRAWN BY ALL DEVICES CONNECTED TO A SINGLE WIRE RUN |
||||
Size |
50 mA or less |
100 mA |
300 mA |
500 mA |
600 mA |
#22 |
900 ft (274m) |
450 ft (137m) |
150 ft (46m) |
90 ft (27m) |
75 ft (23m) |
#20 |
1400 ft (427m) |
700 ft (213m) |
240 ft (73m) |
140 ft (43m) |
120 ft (37m) |
#18 |
1500 ft (457m) |
1100 ft (335m) |
350 ft (107m) |
220 ft (67m) |
170 ft (52m) |
#16 |
1500 ft (457m) |
1500 ft (457m) |
550 ft (168m) |
350 ft (107m) |
270 ft (82m) |
*Includes Keypads, RF Receivers, Zone Expander/Relay Units, 4285/4286 Phone Module, and Long Range Radio.
Maximum wire lengths for any device that is homerun to the control can also be determined from the Wiring Run Chart, based on the current draw of that device alone.
The length of all wire runs for both partitions combined must not exceed 1500 feet (457m) when unshielded quad conductor cable is used (750 feet if shielded cable is used). This restriction is due to the capacitive effect on the data lines when quad cable is used.
Table of Device Addresses
This Device |
Uses Address |
Reports as†† |
Enabled By… |
RF Receiver |
00 |
100 |
*56 zone programming: input device type entry |
AUI 1 |
01 |
101 |
automatic if AUI enable field *189 enabled for AUI 1 |
AUI 2 |
02 |
102 |
automatic if AUI enable field *189 enabled for AUI 2 |
Long Range Radio |
03 |
103 |
automatic if output to long range radio field *29 enabled |
4286 Voice Module |
04 |
104 |
automatic if phone module access code field *28 enabled |
Zone Expanders (4219/4229): |
|
|
*56 zone programming: input device type, entry 2, then: |
module 1 (for zones 09 - 16) |
07** |
107 |
automatic if zone no. 9-16 set as AW type or relay assigned |
module 2 (for zones 17 - 24) |
08 |
108 |
automatic if zone no. 17-24 set as AW type or relay assigned |
module 3 (for zones 25 - 32) |
09† |
109 |
automatic if zone no. 25-32 set as AW type or relay assigned |
module 4 zones 33 - 40 |
10† |
110 |
automatic if zone no. 33-40 set as AW type or relay assigned |
module 5 zones 41 - 48 |
11† |
111 |
automatic if zone no. 41-48 set as AW type or relay assigned |
Relay Modules (4204): |
|
|
*79 output device programming: device address prompt: |
module 1 |
12 |
112 |
entered at device address prompt |
module 2 |
13 |
113 |
entered at device address prompt |
module 3 |
14† |
114 |
entered at device address prompt |
module 4 |
† |
115 |
entered at device address prompt |
|
15 |
|
|
Keypads: |
|
|
data field programming as listed below: |
keypad 1 |
16 |
n/a |
always enabled for partition 1, all sounds enabled. |
keypad 2 |
17 |
n/a |
data field *190 |
keypad 3 |
18 |
n/a |
data field *191 |
keypad 4 |
19 |
n/a |
data field *192 |
keypad 5 |
20 |
n/a |
data field *193 |
keypad 6 |
21 |
n/a |
data field *194 |
keypad 7 |
22 |
n/a |
data field *195 |
keypad 8 |
23 |
n/a |
data field *196 |
5800TM Module |
28 |
n/a |
automatic |
** address 07 not available if zone-doubling enabled
† 4219/4229 addresses 9-11 and 4204 addresses 14-15 apply to the VISTA-20P.
†† Addressable devices are identified by “1” plus the device address when reporting. Enter a report code for zone 91 to enable addressable device reporting (default = reports enabled). See field *199 for addressable device (ECP) 3-digit/2-digit identification keypad display options.
2-5
Installation and Setup Guide
Hardwire Zones and Zone Expansion
Hardwire Zones
HI LO
-zones V0-001
Double-Balanced Zones
(V20P only)
Zone Doubling
(V20P only)
Smoke Detectors
TO ZONE 1 |
||
TERMINALS |
||
2-WIRE |
8 |
|
9 |
||
SMOKE |
||
DETECTOR |
-V0 |
|
HI |
||
-001 |
||
LO |
||
ZONE 1 |
5806 |
Normally Open Zones/ N.O. EOLR Zones
1.Connect open circuit devices in parallel across the loop; for EOLR zones, connect the EOLR across the loop wires at the last device.
2.Enable normally open/EOLR zones using Zone Programming mode, “Hardwire Type” prompt.
Normally Closed Zones/ N.C. EOLR Zones
1.Connect closed circuit devices in series in the high (+) side of the loop; for EOLR zones, connect the EOLR in series following the last device.
2.Enable normally closed/EOLR zones using Zone Programming mode, “Hardwire Type” prompt.
End of Line Resistor (EOLR) Notes
•If the EOLR is not at the end of the loop, the zone is not properly supervised and the system may not respond to an “open” on the zone.
•Zone 1 is intended for EOLR only.
UL For UL commercial burglar alarm installations, use EOLR zones.
Connect as shown below (resistor provided for one device).
IMPORTANT: Double-balanced zones provide zone tamper protection, and should be used as burglary zones only.
Do not use double-balanced zones as fire zones.
12 |
13 |
14 |
|
2k |
TAMPER |
2k |
|
CONTACTS |
|||
2k |
TAMPER |
2k |
|
CONTACTS |
|||
|
|
||
2k |
|
2k |
|
ZONE 3 |
ZONE 4 |
zone-002-V0
Fig. 7. Typical Double Balanced Zones
This feature provides two hardwired |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
normally closed zones for each standard |
|
|
10 |
|
|
|
|
|
|
|
11 |
|
|
|||
hardwired zone connected to the control’s |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
terminals (but does not increase the total |
|
|
|
ZONE 2 |
|
|
|
|
|
|||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
number of zones supported by the control). If |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
3k |
|
|
|
|
|
|||
enabled (Zone Programming mode, |
|
|
|
ZONE 10 |
|
|
|
|
|
|||||||
“Hardwire Type” prompt, option “3”), |
|
|
|
|
|
|
V0 |
|||||||||
|
|
|
|
|
|
|
|
|
|
|
|
004- |
|
|||
|
|
|
|
|
|
|
|
|
|
|
|
|
||||
hardwire zones are automatically paired as |
|
|
|
|
|
|
|
|
6.2k |
|
|
|
zone- |
|||
shown in the table. Connect as shown below |
Fig. 8. Typical Zone Doubling Wiring |
|||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
(resistors provided). |
|
|
|
|
|
|
|
|||||||||
Zone Doubling Table |
|
|
|
|
|
|||||||||||
• Do not use zone doubling for fire |
|
|
|
|
|
|
|
|||||||||
Zone |
Paired with zone |
|
|
|
|
|
||||||||||
zones. |
2 |
10 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
3 |
11 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
NOTE: A short across the EOL (i.e., at |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
4 |
12 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
terminal) on either zone of a zone-doubled |
5 |
13 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
pair or on a double-balanced zone causes a |
6 |
14 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
7 |
15 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
tamper condition (displayed as CHECK plus |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
8 |
16 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
zone numbers). |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
1.Connect up to 16 (10, if “clean me” option used) 2-wire smoke detectors across zone 1 terminals 8 (+) and 9 (-) as shown in the Summary of Connections diagram at the back this manual. Observe proper polarity when connecting the detectors.
2.Connect an EOL resistor across the loop wires at the last detector.
3.Connect 4-wire smoke detectors (up to 16, depending on detector current draw) to any zone from 2-8 as shown in Figure 7 (on next page).
Power Reset: This control does not automatically reset power to 4-wire smoke detector zones, so you must use a relay (e.g., 4204, 4229), or on-board trigger to reset power (also required for fire verification). Do this by programming the designated relay/trigger as zone type 54 (fire zone reset); see On-Board Trigger section for other information.
NOTE: Maximum current on trigger 17 is 100mA.
2-6
|
|
Mounting and Wiring the Control |
|
|
|
|
|
|
Smoke Detector Notes |
• Fire Verification (zone type 16): The control panel will “verify” a fire alarm by |
|
|
|
resetting the smoke detectors after the first alarm trigger, and then waiting 90 seconds |
|
|
|
for a second alarm trigger. If the smoke detector or thermostat does not trigger again, |
|
|
|
the control will disregard the first trigger, and no alarm signal will occur. This feature |
|
|
|
eliminates false alarms due to electrical or physical transients. |
|
|
|
SIA Installations: If using fire verification on zones other than zone 1, UL Fire Alarm |
|
|
|
Listed relay accessories must be used to reset power as described in the Power Reset |
|
|
|
paragraph above. |
•The zone 1 alarm current supports only one smoke detector in the alarmed state.
•Clean Me Option: If enabled (field *174 = 1; *56 zone programming, response time prompt = 3), certain ESL smoke detectors send “clean me” reports as appropriate. If used, the maximum number of detectors is reduced to 10 (not standard 16). Refer to the ESL documentation included with the smoke detector for information regarding compatibility with the clean-me option.
•Do not use 4-wire smoke detectors on zone 1.
+ |
5 |
|
|
|
|
|
|
RELAY |
|
|
|
AUX PWR |
PROGRAM |
|
BLK |
+ |
RED |
RELAY |
|
|
|
|
|
OUTPUT |
AS ZONE |
|
|
|
EOL |
TERMINALS |
TYPE 54 |
|
|
|
|
|
|
|
POWER |
||
|
(FIRE ZONE |
|
|
N.O. |
SUPERVISION |
|
RESET) |
|
|
||
|
|
|
|
RELAY MODULE |
|
|
4 |
|
|
|
|
|
N.C. |
|
|
A77-716B. |
|
|
|
|
|
||
CONTACT OPENS |
|
|
|
USE N.O. |
|
|
|
|
CONTACT, |
||
MOMENTARILY UPON |
+ |
|
|
||
|
VIOLET |
WHICH CLOSES |
|||
FIRE ALARM RESET |
|
||||
|
|
||||
|
|
4-WIRE SMOKE |
|
|
WHEN POWER |
|
|
|
|
IS APPLIED. |
|
|
|
OR COMBUSTION |
|
|
|
|
|
DETECTOR |
2000 |
|
|
|
|
|
|
|
|
|
|
|
OHMS |
|
|
|
|
|
EOLR |
|
|
TO ZONE TERM. (+) |
|
|
|
-V0 |
|
|
|
|
-007 |
||
|
|
HEAT |
|
|
|
TO ZONE TERM. ( ) |
|
|
wiresmk |
||
|
|
|
|||
|
DETECTOR |
|
|
|
|
|
|
|
|
|
4 |
Figure 9a. 4-Wire Smoke Detector Using Relay for Power Reset
AUX PWR (+) |
5 |
|
|
|
TO OUTPUT 17 ( ) |
|
BLK |
+ |
RED |
|
|
|
|
|
PROGRAM OUTPUT 17 |
|
|
|
EOL |
FOR "OUT NORM |
|
|
|
POWER |
LOW" = YES IN 79 MENU |
+ |
|
N.O. |
SUPERVISION |
MODE AND AS ZONE |
|
RELAY MODULE |
||
|
|
VIOLET |
||
TYPE 54 IN |
4-WIRE SMOKE |
|
A77-716B. |
|
80 MENU MODE |
OR COMBUSTION |
|
|
USE N.O. |
|
DETECTOR |
2000 |
|
CONTACT, |
|
|
|
||
|
|
OHMS |
|
WHICH CLOSES |
|
|
EOLR |
|
WHEN POWER |
TO ZONE TERM. (+) |
|
|
|
IS APPLIED. |
|
|
|
|
|
|
HEAT |
|
|
|
|
DETECTOR |
|
|
|
TO ZONE TERM. ( ) |
|
|
|
|
4_wiresmk-008-V0
|
|
Figure 9b. 4-Wire Smoke Detector Using Output 17 for Power Reset |
4219/4229 Expansion |
1. |
Connect each module to the control’s keypad terminals and set the device addresses. |
Zones |
|
• VISTA-20P: Up to 40 expansion zones using up to 5 Zone Exp. Modules. |
|
|
• VISTA-15P: Up to 16 expansion zones using up to 2 Zone Exp. Modules. |
|
2. |
Connect sensors to the module’s loops. See Figure 8 on the following page. |
|
|
• Use 1000 ohm end-of-line resistors at the end of loops connected to the 4219/4229 |
|
|
modules. (EOLRs used on the control terminals are 2000 ohms.) |
|
|
• Expansion zones have normal response time (300–500 msec), except zone connected |
|
|
to each module’s loop “A,” which can be set for fast response (10–15 msec). |
|
3. |
If using relays with the 4229, connect the desired field wiring to the unit's relay contact |
|
|
terminals. |
2-7
Installation and Setup Guide
|
RELAY |
RELAY |
|
|
|
|
|
|
|
|
|
|
4229 |
|
|
|
|
||
|
CONNECTOR |
2 |
|
|
DIP SWITCH |
|
|
|
|
|
|
|
|
|
|
|
|
||
|
|
|
|
|
FOR SETTING ADDRESS |
|
|
EITHER OR BOTH CAN BE USED |
|
|
TERMINALS ON |
||||||||
|
|
|
|
|
AND ZONE "A" RESPONSE |
|
|
|
|||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
CONTROL PANEL |
|
|
|
|
RELAY |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
1 |
|
|
|
|
|
|
|
|
|
|
TB2 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
NO C |
NC |
|
|
|
|
|
|
|
4-PIN CONSOLE PLUG |
4 |
GRN |
DATA OUT (>) |
(TERM 6) |
||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||
|
|
|
TAMPER JUMPER POSITION |
|
|
|
|
|
|
|
TO CONTROL |
||||||||
|
|
|
|
|
|
|
|
|
|
|
|
||||||||
|
|
|
|
|
|
|
|
|
|
BLK |
|
|
|
||||||
|
|
|
4229 IN CABINET |
|
|
|
|
|
|
|
4 |
3 |
(–) GROUND |
|
(TERM 4) |
||||
WHT |
GRY VIO BLK YEL ORG |
BRN |
(NOT TAMPER) |
|
|
|
|
|
|
|
|
|
|
|
|
|
|||
4229 REMOTE |
|
|
|
|
|
|
|
|
3 |
2 |
RED |
(+) 12VDC |
|
(TERM 5) |
|||||
|
|
|
(TAMPER PROTECTED) |
|
|
|
|
TB1 |
2 |
|
|
DATA IN (<) |
|
|
|||||
|
NO NC C GND NO NC C |
|
|
|
|
|
|
|
|
|
|
|
YEL |
|
|
||||
|
|
|
|
|
|
|
|
|
|
|
|
1 |
1 |
FROM |
|
(TERM 7) |
|||
|
1 |
2 |
3 |
4 |
5 |
6 |
7 |
8 |
9 |
10 |
11 |
|
|
||||||
|
|
|
12 |
|
|
CONTROL |
|
|
RLY |
RLY |
|
|
|
|
TERMINATE EACH |
|
|
|
|
PROGRAMMED ZONE |
||
2 |
1 |
REED |
|
|
|
|
|
|
|
WITH 1000 OHM (1K) |
|||
RELAYS OFF |
(TAMPER) |
|
|
|
END-OF-LINE RESISTOR |
|
SWITCH |
|
|
|
(EACH ZONE'S MAX. |
||
|
|
|
|
|
LOOP RESISTANCE |
|
|
|
|
|
|
|
|
|
|
ZONES A B |
C D |
E F |
G H |
300 OHMS + EOL) |
|
|
4229-002-V0 |
Figure 10. Wiring Connections, 4219 & 4229 (4229 shown)
Installing the RF Receiver and Wireless Transmitter Zones
Compatible Receivers |
Use any ADEMCO 5800 Series Wireless Receivers, such as: |
||||
|
|
RF Receiver |
No. of Zones |
||
|
|
5881L/5882L |
up to 8 |
|
|
|
|
5881M/5882M |
up to 16 |
|
|
|
|
5881H/5882H, |
VISTA-20P |
= up to 40 plus 16 buttons |
|
|
|
5883, 6150RF |
VISTA-15P |
= up to 26 plus 8 buttons |
|
Receiver Connections |
1. Set Device Address to “00” (set all switches to the right, “off” position). |
2.Mount the receiver, noting that the RF receiver can detect signals from transmitters within a nominal range of 200 feet.
3.Connect the receiver's wire harness to the control's keypad terminals. Plug the connector at the other end of the harness into the receiver. Refer to the installation instructions provided with the receiver for further installation procedures regarding antenna mounting, etc.
WIRELESS ZONE NUMBERS
VISTA-20P: transmitter zones 9-48 button zones 49-64
VISTA-15P: transmitter zones 9-34 button zones 49-56
NOTE
CIRCUIT BOARD IS MOUNTED IN CONTROL'S CABINET. GROUNDING LUGS (2) PROVIDED MUST BE INSERTED IN LEFT-HAND TERMINALS OF ANTENNA BLOCKS AND SECURED TO CABINET. (SEE RECEIVER'S AND CONTROL'S INSTRUCTIONS)
MOUNTING
HOLES
|
ANTENNAS |
|
|
|
|
(INSERT IN |
|
|
|
|
RIGHT-HAND |
|
|
|
|
TERMINALS) |
|
|
|
|
INSERT IN |
|
|
|
|
RIGHTHAND |
|
|
|
|
TERMINALS |
|
|
|
|
|
YELLOW |
||
|
|
RED |
TO CONTROL'S |
|
|
|
REMOTE KEYPAD |
||
MODEL NO. IS INDICATED ON CIRCUIT BOARD |
BLACK |
|||
|
|
CONNECTION |
||
|
|
GREEN |
||
5882 |
DIP |
POINTS. |
||
|
||||
LOCATION |
SWITCH |
|
|
|
INTERFERENCE |
|
WIRING OPENING |
||
INDICATOR |
|
|
||
|
LED |
|
KNOCKOUT AREA |
|
|
|
|
||
CIRCUIT BOARD |
|
FOR SURFACE WIRING |
||
|
|
SOCKET |
PLUG |
TO RELEASE CIRCUIT BOARD, |
|
REMOVE SCREWS AND |
|
BEND BACK TABS |
5881-003-V0 |
|
|
Figure 11. 5881/5882 RF Receiver (cover removed) |
|
RF Receiver Notes |
Set the following options: |
||
|
*22 |
RF Jam Option† |
|
† These fields must be |
*24 |
RF House ID Code (if using wireless keypads) for each partition |
|
enabled for Residential Fire, |
*67 |
Transmitter Low Battery Report Code† |
|
UL Residential Burglar |
*75 |
Transmitter Low battery restore report code† |
|
Alarm, and UL Commercial |
|||
• The receiver is supervised and a trouble report is sent (“CHECK 100” displayed) if |
|||
Burglar Alarm installations. |
|||
|
communication between the panel and receiver is interrupted, or if no valid RF signals |
||
|
|||
|
from at least one supervised transmitter are received within 12 hours. |
||
|
If the receiver is mounted remotely: |
||
|
• Place the RF receiver in a high, centrally located area for best reception. |
||
|
• Do not locate the receiver or transmitters on or near metal objects. This will decrease |
||
|
range and/or block transmissions. |
||
|
• Do not locate the RF receiver in an area of high RF interference (indicated by frequent |
||
|
or prolonged lighting of the LED in the receiver; random flicker is OK). |
||
|
• Do not locate RF receiver closer than 10 feet from any keypads to avoid interference |
||
|
from the microprocessors in those units. |
2-8
|
|
|
Mounting and Wiring the Control |
|
|
|
|
|
|
|
Installing a 5800TM |
• Use this module only if you are using one or more wireless bi-directional keypads or |
||
|
Module |
keyfobs with a wireless Receiver; 5800TM is not necessary if using a Transceiver (e.g., |
||
|
|
|
5883). |
|
|
|
|
• The 5800TM must be set to address 28 (cut red-W1 jumper). |
|
|
|
|
• The 5800TM can be used in partition 1 only. |
|
|
|
|
• For additional information regarding the 5800TM, refer to the 5800TM’s instructions. |
|
|
|
|
1. Mount the 5800TM next to the RF receiver (between one and two feet from the |
|
|
|
|
receiver’s antennas) using its accompanying mounting bracket. Do not install within |
|
|
|
|
the control cabinet. |
|
|
|
|
2. Connect the 5800TM to the control panel’s keypad connection terminals as shown on |
|
|
|
|
the Summary of Connections diagram and set to address 28. |
|
|
Installing the |
• Refer to the table of compatible devices at the back of this manual. |
||
|
Transmitters |
• Supervised transmitters† send check-in signals to the receiver at 70-90 minute |
||
|
|
|
intervals. If at least one check-in message is not received from each transmitter within |
|
|
|
|
a 12-hour period, the “missing” transmitter number(s) and “CHECK” is displayed. († |
|
|
|
|
Hand-held transmitters, e.g., 5802, 5802CP, 5804, 5804BD, 5827, 5827BD, do not send |
|
|
|
|
||
|
|
|
check-in signals.) |
|
|
|
|
||
|
|
|
• To be sure reception of the transmitter's signal at the proposed mounting location is |
|
|
|
|
adequate, perform a Go/No Go Test, described in the Testing the System section. |
|
|
|
|
• Install transmitters in accordance with the instructions provided with each. |
|
|
|
|
• Set 5827, 5827BD, 5804BD wireless keypads to the programmed House ID (field *24), |
|
|
|
|
using its DIP switches (5827) or follow the instructions provided with the device. |
|
|
|
|
• Use *56 or *58 Zone Programming Menu modes to program zone information and enroll |
|
|
|
|
transmitters (VISTA-20P: zones 9-48, buttons 49-64; VISTA-15P: zones 9-34, buttons |
|
|
|
|
49-56). |
|
|
|
|
• Wireless Keys: Use Wireless Key Programming Templates section of the *58 Zone |
|
|
|
|
Programming Menu mode to program zone information and enroll each button of the |
|
|
|
|
wireless keys used. Once a wireless key is enrolled, it must be assigned to a user before |
|
|
|
|
it becomes active. See Adding/Deleting Security Codes section for procedure. |
|
|
|
|
|
|
|
|
|
ULC NOTE: In accordance with ULC standards, the RF supervision period for the VISTA-20PCN |
|
|
|
|
and VISTA-15PCN is three hours for Fire zones (Zone Type 9 and 16) and 12 hours for all other zone |
|
|
|
|
types. |
|
|
|
|
|
|
|
|
|
UL The following transmitters are not intended for use in UL installations: 5802MN, 5802MN2, 5804, |
|
|
|
|
5804BD, 5814, 5816TEMP, 5819, 5819WHS & BRS, and 5850. |
|
|
|
|
The 5827BD and 5800TM can be used in UL Listed Residential Burglar installations. |
|
|
|
|
||
|
Transmitter Battery Life |
• See Wireless Transmitter paragraph in the Limitations of This Alarm System |
||
|
|
|
statement located at the end of this manual for information on transmitter battery |
|
|
|
|
life. |
|
|
|
|
• Some transmitters (e.g., 5802 and 5802CP) contain long-life but non-replaceable |
|
|
|
|
batteries, and no battery installation is required. At the end of their life, the complete |
|
|
|
|
unit must be replaced (and a new serial number enrolled by the control). |
|
|
|
|
• Button-type transmitters (such as 5801, 5802, and 5802CP) should be periodically |
|
|
|
|
tested for battery life. |
|
|
|
|
• The 5802MN and 5804 Button Transmitters have replaceable batteries. |
|
|
|
|
Do not install batteries in wireless transmitters until you are ready to enroll during |
|
|
|
|
system programming. After enrolling, batteries need not be removed. |
2-9
Installation and Setup Guide
Installing a Keyswitch
Keyswitch Connections
GREEN |
RED |
1.Connect the 4146 keyswitch's normally open momentary switch to a zone’s (2-8) terminals. Remove the 2000 ohm EOL resistor if connected across the selected zone.
2.Using a standard keypad cable as shown:
Connect the yellow and white keyswitch wires to trigger connector pin 3 (+12V). Connect the Red and Green LED wires to the appropriate output 17/output 18 trigger connector pins.
3.Connect a 2000 ohm EOL resistor across the momentary switch.
4.You can wire an optional closed-circuit tamper switch (model 112) in series with the zone. If the switchplate is then removed from the wall, the tamper will open, disabling keyswitch operation until the system is next disarmed from the keypad.
If the tamper is opened when the system is armed, an alarm will occur.
8-PIN TRIGGER CONNECTOR
1 |
KEY |
3 |
4 |
5 |
6 |
7 |
8 |
|
|
|
|
|
|
|
(YELLOW) |
(RED) |
(GREEN) |
OUTPUT 17 |
+12 AUX. |
OUTPUT 18 |
11
TYPICAL ZONE
ON CONTROL
BOARD
10
STANDARD
4146 KEYSWITCH
KEYPAD
CABLE (ARMED) RED
YELLOW
(READY) GREEN
WHITE |
|
820 |
820 |
ohms |
ohms |
BLACK |
|
RED |
|
TAMPER |
|
SWITCH (N. C.) |
|
BROWN |
BROWN |
LOCK |
|
SWITCH (N. O.) |
|
BLUE |
BLUE |
EOLR
(use appropriate value)
00-trigcon-004-V1
Figure 12. Keyswitch Wiring Connections
Keyswitch Notes
UL A UL Listed keyswitch is required for fire installations and UL commercial and residential burglar alarm installations. The Ademco 4146 keyswitch is UL Listed.
If a keyswitch is used on:
•an installation that transmits opening and closing signals, the keyswitch zone must be programmed to send opening and closing signals.
•a UL commercial burglar alarm installation, the keyswitch’s tamper switch must be connected in to the alarm system. This tamper switch zone must also be programmed for Zone Type 05 – Trouble by Day / Alarm by Night.
•a fire alarm installation, the keyswitch must be located next to an alphanumeric display keypad.
•Use 4146 keyswitch or any N.O. keyswitch.
•Use only one keyswitch per partition.
•When using a keyswitch, the zone it is connected to is no longer available for use as a protective zone.
•Use *56 Menu mode to program the keyswitch zone and assign it zone type 77.
•Use *80 Menu mode to program the LED functions: program outputs 17 and 18 for system operation zone type 78 (red LED) and 79 (green LED) as appropriate (see
Output Device Programming section).
2-10
Mounting and Wiring the Control
Connecting Relay Modules, Powerline Carrier Devices and Output Triggers
4204/4229 Relay Modules
UL For UL installation requirements, refer to the Installation Instructions for the 4204.
Powerline Carrier
Devices
UL Powerline Carrier devices and the 1361X10 Transformer are not UL Listed for fire or burglary functions and are intended for home automation.
1.Mount either remotely or in the control panel.
2.Connect each module to the control’s keypad terminals and set the device addresses as previously described in the Connecting Keypads and Other Addressable Device section. Use the connector harness supplied with the module. Use standard 4-conductor twisted cable for long wiring runs.
VISTA-20P: Up to 16 relays (if no powerline carrier devices are used) VISTA-15P: Up to 8 relays (if no powerline carrier devices are used)
3.Connect the desired field wiring to the unit's relay contact terminals.
4204 |
RELAY |
12 |
C |
|
DIP SWITCH |
4 |
11 |
NC |
|
TYPICAL |
10 |
|
||
FOR SETTING DEVICE ADDRESS |
NO |
|||
(SHOWN "OFF") |
||||
AND ENABLING/DISABLING TAMPER |
RELAY |
9 |
C |
|
|
|
|||
COVER TAMPER (REED) SWITCH |
3 |
8 |
NC |
|
7 |
NO |
|||
|
|
|||
|
|
|
||
4-PIN TOUCHPAD PLUG |
RELAY |
6 |
C |
|
|
||||
|
2 |
5 |
NC |
|
EITHER OR BOTH |
|
4 |
NO |
|
CAN BE USED |
RELAY |
3 |
C |
|
|
|
|||
TB1 |
1 |
2 |
NC |
|
|
|
|||
13 14 15 16 |
|
1 |
NO |
|
|
|
|||
YEL |
DATA IN |
|
TB2 |
|
|
FROM CONTROL |
|
|
|
BLK |
(–) GROUND |
|
|
|
|
|
|
||
GRN |
DATA OUT |
|
|
|
RED |
TO CONTROL |
|
|
|
(+) 12V |
4204_conn-1-V0 |
|||
|
Figure 13. 4204 Connections to Control
•Supervision: 4204 and 4229 modules are supervised against removal. The module’s device address is displayed as follows if a module is disconnected from the control’s terminals, or if the module cover is removed and the tamper jumper is installed:
Alpha: CHECK xx Wire Expansion FAULT xx Wire Expansion ALARM xx Wire Expansion
Fixed-Glass: lxx (or 91 if field *199 set for 2-digit display) where “xx is the module’s address.
•If communication/tamper failure occurs on a device with zones wired to it, all zones on the device will be displayed in their respective partitions.
1.Install the powerline carrier devices according to the instructions included with each. VISTA-20P: Up to 16 devices (if no relays are used)
VISTA-15P: Up to 8 devices (if no relays are used)
2.Use Programming Mode to enter the device house ID in data field*27, and enter the unit code using *79 Output Device menu Mode.
3.See connections diagram in the AC Wiring section for connecting the 1361X10 transformer to the triggers.
•You must use a 1361X10 Transformer instead of the 1321 Transformer.
•The 1361X10 Transformer provides AC power to the control panel, and also supplies signals from the control panel through the premises AC wiring to the Powerline Carrier devices (which are plugged into AC outlets). You can then make devices that are plugged into Powerline Carrier devices perform various functions in response to commands you enter at the security system keypads.
Canada: Use the PSC04 Powerline Interface as shown below.
8-PIN TRIGGER CONNECTOR |
|||||||
1 |
KEY |
3 |
4 |
5 |
6 |
7 |
8 |
|
|
|
|
|
|
|
|
(RED) |
|
(ORANGE) |
(YELLOW) |
(GREEN) |
(BLUE) |
(PURPLE) |
(BLACK) |
OUTPUT 17 |
|
+12 AUX. |
GND (-) |
OUTPUT 18 |
DATA |
COM |
SYNC |
|
|
|
|
|
|
|
SA4120XM-1 CABLE |
|
|
|
|
|
|
|
SYNC |
|
|
|
|
|
|
|
BLK |
|
|
|
|
|
|
|
GRN |
|
|
|
|
|
|
|
COM |
|
|
|
|
|
|
|
RED |
|
|
|
|
|
|
|
DATA |
|
|
|
|
|
|
|
YEL |
X-10 PSC04
POWERLINE INTERFACE
1 2 3 4
MODULAR PHONE CORD (not supplied)
1 - BLACK
2 - RED
3 - GREEN
4 - YELLOW
Figure 14. PSC04 Powerline Interface Connections
2-11
Installation and Setup Guide
On-Board Triggers |
Connect field wiring to the desired trigger pin on the 8-pin trigger connector centrally |
|
|
located above the terminal strip. |
|
|
• |
If using 1361X10 transformer and powerline carrier devices, use the SA4120XM-1 |
|
|
cable (part of 4120TR Trigger Cable). See Wiring the AC Transformer section for |
|
• |
transformer connections. |
|
If only using the on-board triggers, you can use a 4-wire cable (N4632-4, supplied |
with the control) as shown below.
|
|
|
|
|
|
|
8-PIN TRIGGER CONNECTOR |
|||||||
8-PIN TRIGGER CONNECTOR |
|
|
|
|
|
|
|
|||||||
|
KEY |
|
|
|
|
|
1 |
KEY |
3 |
4 |
5 |
6 |
7 |
8 |
1 |
3 |
4 |
5 |
6 |
7 |
8 |
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
OUTPUT 17 (RED) |
+12 AUX. (ORANGE) |
GND (-) (YELLOW) |
OUTPUT 18 (GREEN) |
(BLUE) |
(PURPLE) |
SYNC (BLACK) |
OUTPUT 17 (YELLOW) |
(RED) |
(BLACK) |
(GREEN) |
DATA |
COM |
+12 AUX. |
GND (-) |
OUTPUT 18 |
||||||
|
|
|
|
|
|
|
SA412OXM-1 |
|
|
|
|
|
|
|
|
|
|
CABLE |
|
|
|
|
|
|
|
|
|
|
00-trigcon-003-V1 |
|
|
|
4-WIRE CABLE
00-trigcon-005-V2
Figure 15a. On-Board Trigger Connector with SA4120XM-1 Cable for Use With 1361X10 Transformer
Figure 15b. On-Board Trigger Connector with 4-Wire Cable for Trigger Use Only
•Trigger outputs are normally high, and go low upon programmed condition.
•The outputs can be programmed for inverted operation (normally low, go high) using *79 Menu mode.
•Program these triggers using *80/*81 Menu modes as you would for any other relay output.
•When using these outputs, note:
pin 1 = output number 17 (trigger 1):
15 ohms to ground when closed (output low), open when off (output high, normal default); can be used to reset smoke detector power (must set “output normal low = yes” in *79 Menu mode, and set for zone type 54, fire zone reset, in *80 Menu mode); or can support 12V relay module (e.g., Altronix AX-RBS) that draws less than 100mA
pin 5 = output number 18 (trigger 2):
100 ohms to ground when closed (output low); open when off (output high, normal default); or can support 12V relay module that draws less than 20mA
UL If on-board triggers are used, the wiring between the control unit and the UL Listed device must be run in conduit, be no more than 3 feet apart and have no intervening barriers or walls.
2-12
Mounting and Wiring the Control
Phone Line/Phone Module, and Audio Alarm Verification (AAV) Connections
Phone Line
4285/4286 Phone Module
Compatibility: 4286 Phone Modules must have software version WA428615.1 or higher (refer to the label on the square 4286 microprocessor chip).
UL The 4285 and 4286 modules are UL Listed only for use on residential fire and UL residential burglar alarm installations.
Connect incoming phone line and handset wiring to the main terminal block (via an RJ31X jack) as shown in the Summary of Connections diagram at the back of this manual.
Wire colors represent the colors of the cable to the RJ31X jack.
1.Make 12V (+) and (–) and data in and data out connections from the phone module to the control, using the connector cable supplied with the phone module, then insert the keyed connector at the other end of the connector cable into the header on the phone module.
2.Connect Phone Module terminals as shown below. Use an RJ31X jack with a directconnect cord and make all connections exactly as shown.
3.Caller ID Units: If a Caller ID unit is being used, connect the unit directly to the “Handset” terminals (21 & 22) on the control, as shown.
INCOMING |
|
GROUND |
HANDSET TELCO LINE |
|
|
{ { |
|
|
TERMINALS
|
ON CONTROL |
|
21 |
22 |
||||
|
|
|||||||
|
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
|
|
CALLER ID |
|
|
|
|
|
|
|
|
UNIT |
|
|
|
|
|
|
|
|
|
|
|
|
|
(RING) |
||
IMPORTANT NOTE FOR |
|
(TIP) |
||||||
EXISTING INSTALLATIONS: |
|
|||||||
EXISTING WIRES |
|
|
|
|
|
|
||
CONNECTED TO THE |
|
|
|
|
|
|
||
"HANDSET" TERMINALS ON |
|
|
|
|
|
|
||
CONTROL MUST BE MOVED |
|
|
|
|
|
|
||
FROM THERE TO TERMINALS |
|
|
|
|
|
|
||
3 AND 4 ON THE 4285/4286. |
|
|
|
|
|
|
4285/4286 |
7 |
|
VIP MODULE |
5 6 |
|
LOUDER |
|
1 2 3 4 |
VOLUME |
|
|
(4286 |
KEYED |
|
ONLY) |
HEADER |
|
|
|
|
UNUSED |
|
|
|
YELLOW: TO DATA OUT (term. 7) |
|
|
NO CONNECTION |
|
CONNECTOR |
RED: |
TO AUX (+) (term. 5) |
WITH FLYING |
BLACK: |
TO AUX. GROUND (–) (term.4) |
LEADS |
GREEN: |
TO DATA IN (term. 6) |
23 |
24 |
25 |
TO EARTH GROUND (COLD WATER PIPE, ETC.) |
|
(TIP)GREEN |
(RING)RED |
|
RJ31XRING |
INCOMING TELCO LINE |
|
|
|||
|
|
DIRECT |
TIP |
|
|
|
|
|
|
|
|
CONNECT |
|
|
|
|
CORD |
|
TIP |
|
|
|
|
|
|
|
|
JACK |
RING |
|
|
|
|
|
|
|
|
CA38A |
PREMISES ANSWERING |
|
|
PLUG |
IN |
|
|
|
MACHINE AND PHONES |
||
|
|
CANADA |
||
|
|
|
|
|
(R)GREY |
BROWN(T) |
|
|
ANSWERING |
|
|
MACHINE |
||
|
|
|
|
|
|
|
|
|
* |
|
|
|
|
* |
* NOTE: IF THE TELEPHONE HAS BUILT-IN CALLER ID, THE CALLER ID FUNCTION MAY NOT WORK .
|
|
|
|
4285/4286 |
|
TO CONTROL |
|
|
|
TERMINAL ASSIGNMENTS |
|
PANEL |
1 - TIP |
||||
TERMINALS |
2 - RING } PHONE INPUT |
||||
USED FOR |
3 |
- TIP |
|||
4 |
- RING } PHONE OUTPUT |
||||
KEYPAD |
|||||
5 |
- NO CONNECTION |
||||
CONNECTIONS |
|||||
6 |
- |
AUDIO OUT |
|||
|
|||||
|
7 |
- |
} 4286 ONLY |
4286_cntrl-001-V0
Figure 16. 4285/4286 Phone Module Wiring Connections
•Only one phone module can be used and it can only be connected to partition 1.
•The phone lines must be in service for the phone module to function, even when accessing the system from an on-premises phone.
•If you are also using an Audio Alarm Verification (AAV) unit, refer to Audio Alarm Verification (AAV) section for special wiring connections.
CAUTION: To reduce the risk of fire, use only No. 26 AWG or larger telecommunication line cord for phone line connections.
Phone Module Problems If no touch tones are produced following access to the security system from on-premises (this problem may arise in rare cases), it may be necessary to reverse the wires connected to terminals 3 and 4 on the phone module and the wires connected to terminals (21) & (22) on the control. The wiring diagram shows the wiring connections that will provide proper operation in most cases.
Connection to the incoming telco line via a RJ31X jack and direct-connect cord, as shown, is essential, even if the system is not connected to a central station. The 4285 or 4286 will not function if this is not done and an error signal (fast busy signal) will occur when trying to access the system via the phone.
The house phone lines (gray and brown wires) must be wired to the phone module terminals; not to the control terminals. Otherwise, an error signal (fast busy signal) will occur when trying to access the system from an on-premises phone.
2-13
Installation and Setup Guide
Audio Alarm Verification Connections
(AAV, “listen-In”)
•Refer to the connection diagrams below. One diagram shows connections when a 4285/4286 Phone Module is used, the other shows connections when the 4285/4286 is not used.
•Connections use one of the on-board triggers.
•Set field *91 for AAV and program the appropriate output (output 17 or 18) using *80 Menu mode: select zone type 60 and output action 1 (close for 2 seconds) or action 2 (stay closed).
•For voice session monitoring, connect an EOLR zone to UVCM module terminals 6 & 7, and program the zone as zone type 81 (*56 Menu mode).
E.g., Using output 18 for the trigger, program an output function in *80 Menu mode as: ZT = 60, P = 0, Action = 1, Device = 18
•Suggested AAV Module: ADEMCO UVS (shown) or Eagle 1250
UL UL installations using the AAV feature must use the ADEMCO UVCM module (part of the ADEMCO UVS system).
|
|
|
|
|
|
|
|
5 |
TRIGGER |
|
|
|
|
|
|
|
|
|
|
|
|
|
CONNECTOR |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
18 |
|
ZONE |
|
|
|
|
EARTH |
|
|
|
|
|
|
CONTROL |
OUTPUT |
|
|
|
|
|
GROUND |
|
|
|
|
|
|
|
|
|
TERMINALS |
|
|
|
|
|
|
|
|
|
AUXILIARY |
4 |
5 |
|
21 |
22 |
23 |
24 |
25 |
|
||
|
|
|
AUDIO LEVEL |
|
|
|
|
|
|
|
|
|
||
|
|
|
ADJUSTMENT |
GND |
+12VDC |
|
|
|
|
|
|
|
||
|
|
|
|
TRIM POT |
|
|
|
|
|
|
|
|||
|
|
|
|
|
|
|
|
|
EOL |
|
|
|
|
|
|
|
UVCM |
|
|
|
34 |
|
|
RING |
|
|
|
|
|
|
|
MODULE |
|
|
|
TIP |
|
|
|
|
|
|||
|
|
|
33 |
|
|
|
|
|
|
|
||||
|
|
|
|
|
|
|
|
|
|
|
|
RED (R) |
|
|
|
|
|
|
|
|
32 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
31 |
|
|
|
|
|
|
GREEN (T) |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
RJ31X |
|
|
|
|
|
|
|
30 |
|
|
|
|
|
|
GREY (R) |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
NOTE: |
|
|
|
|
|
29 |
|
|
|
|
|
|
BROWN (T) |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
REFER TO UVCM MODULE |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
INSTRUCTIONS FOR |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
CONNECTIONS TO AUDIO |
|
|
|
|
11 |
|
|
OPTIONAL |
|
|
|
|
|
|
SPEAKERS AND MICROPHONE. |
|
|
|
|
|
|
|
|
|
|
|
|||
|
765 8 |
BANK2 |
|
|
|
|
MONITORING ZONE |
|
|
|
|
|||
|
|
|
|
910 |
|
|
|
|
|
|
||||
|
|
|
|
|
|
CONNECTION |
|
|
|
|
|
|||
|
|
|
|
|
|
|
|
|
(USE ZONE TYPE 81) |
|
|
|
|
|
2 = OFF |
2 = ON |
ON |
4321 |
SWITCH |
|
876 |
|
|
|
|
|
|
TO |
INCOMING |
SWITCH |
SWITCH |
|
|
|
|
|
|
|
|
|
|
|
PREMISES |
|
BANK 1 |
BANK 2 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
HANDSET |
|
||
1 = OFF |
1 = ON |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
3 = OFF |
3 = OFF |
|
|
|
FALLING VOICE TRIG |
5 |
|
|
|
|
|
|
|
PHONE LINE |
4 = OFF |
4 = ON |
|
8 |
1 |
|
|
|
|
|
|
|
|
||
5 = OFF |
5 = ON |
ON |
6543217 |
BANKSWITCH |
|
4321 |
|
|
|
|
|
|
|
003V0- |
6 = OFF |
6 = ON |
|
|
|
|
|
|
|
|
|
|
|
|
|
7 = OFF |
7 = ON |
|
|
|
|
|
|
|
|
|
|
|
|
|
8 = ON |
8 = ON |
|
|
|
GND |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
+12VDC IN |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
aav uvcm- |
Figure 17a. Connection of AAV Unit When Not Using a 4285/4286 Phone Module
NOTE:
REFER TO UVCM MODULE INSTRUCTIONS FOR CONNECTIONS TO AUDIO SPEAKERS AND MICROPHONE.
SWITCH |
SWITCH |
||
BANK 1 |
BANK 2 |
||
1 |
= OFF |
1 |
= ON |
2 |
= OFF |
2 |
= ON |
3 |
= OFF |
3 |
= OFF |
4 |
= OFF |
4 |
= ON |
5 |
= OFF |
5 |
= ON |
6 |
= OFF |
6 |
= ON |
7 |
= OFF |
7 |
= ON |
8 |
= ON |
8 |
= ON |
Figure 17b.
|
|
|
|
5 |
TRIGGER |
|
|
|
|
|
|
|
|
|
CONNECTOR |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
18 |
|
ZONE |
|
|
|
|
EARTH |
|
CONTROL |
|
OUTPUT |
|
|
|
|
|
GROUND |
|
|
|
|
|
TERMINALS |
|
|
|
|
|
|
AUXILIARY |
4 |
|
5 |
|
|
21 |
22 |
23 |
24 |
25 |
AUDIO LEVEL |
|
|
|
|
|
|
|
|
|
|
ADJUSTMENT |
GND |
+12VDC |
|
|
|
|
|
|
|
|
TRIM POT |
|
|
|
|
|
|
|
|
||
|
|
|
|
|
EOL |
|
|
|
|
|
UVCM MODULE
|
|
|
|
8 |
2 |
|
|
|
|
5 6 7 |
BANK |
|
|
|
|
||
|
|
|
|
||
|
|
||||
|
|
|
|
||
|
|
|
|
1 2 3 4 |
SWITCH |
|
|
|
|
||
|
|
|
|
||
|
|
|
|
||
ON |
|
|
|
||
|
|
|
|||
|
|
|
|||
|
|
|
|
|
|
|
|
|
|
|
|
|
8 |
1 |
|||
|
|
|
|
5 6 7 |
BANK |
|
|
|
|
||
|
|
|
|
||
|
|
||||
|
|
|
|
||
|
|
|
|
||
|
|
|
|
|
SWITCH |
|
|
|
|
1 2 34 |
|
|
|
|
|
||
|
|
|
|
||
|
|
|
|
||
ON |
|
|
|
||
|
|
|
RING |
34 |
TIP |
33 |
|
32 |
|
31 |
|
30 |
|
29 |
|
11 |
|
10 |
|
9 |
|
8 |
|
7 |
|
6 |
FALLING VOICE TRIG |
5 |
|
4 |
|
3 |
GND |
2 |
|
|
+12VDC IN |
1 |
RING
TIP
OPTIONAL MONITORING ZONE CONNECTION (USE ZONE TYPE 81)
4285/4286
4
3
2
1
RED (R) |
|
GREEN (T) |
|
GREY (R) |
RJ31X |
BROWN (T) |
|
TO
PREMISES
HANDSET
INCOMING
PHONE LINE
aav_uvcm-004-V0
Connection of AAV Unit When Using a 4285 or 4286 Phone Module
2-14
S E C T I O N 3
Programming Overview
About Programming
•You can program the system at any time, even at the installer's premises prior to the actual installation.
•Programming can also be performed remotely from the installer’s office/home, using an IBM personal computer, a modem, and Compass downloading software.
The following is a list of the various Programming modes used to program this system.
Programming Mode… |
Used to … |
Data Field Programming |
Program basic data fields used for setting the various system options. |
|
Most of the data fields in this system have been programmed for specific default |
|
values. However, some fields must be programmed for each particular installation to |
|
establish its specific alarm and reporting features. |
56 Zone Programming |
Assign zone characteristics, report codes, alpha descriptors, and serial numbers for |
|
5800 RF transmitters. See *56 Zone Programming in Section 5. Menu Mode |
|
Programming for procedures for programming zones. |
57 Function Key |
Program each of the four alphabet function keys to perform one of several system |
Programming |
operations. |
58 Zone Programming |
Similar to 56 mode, but provides a faster programming procedure and is intended for |
(Expert Mode) |
those more experienced in programming controls of this type. |
79 Output Device Mapping |
Assign device addresses used by 4229 or 4204 Relay modules and map specific relays |
|
and device outputs, and assign unit codes for Powerline Carrier devices. |
|
See About Output Device Programming in Section 5. Menu Mode |
|
Programming for details on setting devices for manual/automatic operation. |
80 Output Definitions |
Define up to 48 output definitions which can control the output relays mapped using |
|
*79 Output Device Mapping mode. |
81 Zone List Programming |
Create Zone Lists for relay/powerline carrier zones, chime, night-stay, cross zones, |
|
and pager zones. |
82 Alpha Programming |
Create alpha descriptors for easy zone identification. |
Scheduling Mode |
Create schedules to automate various system functions. |
(code + [#] +64) |
|
Mechanics of Programming
To program the system from a keypad:
•You must use a 2-line Alpha display keypad.
•Both partitions must be disarmed.
Data Field Programming Procedures
Task |
Procedure |
Entering Program Mode |
A) Press both [ ] and [#] at the same time within 50 seconds after power is applied, |
|
OR |
|
B) After power-up, enter [Installer code (4-1-1-2)] + 8 0 0 (long beep indicates one of the |
|
partitions is armed and system cannot enter program mode). |
|
(method “B” is disabled if you exit Program mode using 98) |
Go to a Data Field |
Press [ ] + [Field Number]. A display of “EE” or “Entry Error” means you have entered a |
|
nonexistent field. Simply re-enter [ ] plus a valid field number. |
Entering Data |
When the desired field number appears, simply enter the digits required. The keypad |
|
beeps three times after the last digit is entered and automatically displays the next data |
|
field in sequence. |
|
If entering less than the maximum digits available (e.g., phone number field), enter the |
|
desired digits, then press [ ] to end the entry. |
Review a Data Field |
Press [#] + [Field Number]. The field’s data is displayed, but no changes can be made. |
Deleting an Entry |
Press [ ] + [Field No.] + [ ] (applies only to phone number, account number, and pager |
|
character fields). |
3-1
Installation and Setup Guide
Interactive Mode Programming ( 56, *57, 58, 79, 80, 81, 82)
Entering Interactive Mode Press [ ] + [Interactive Mode No.] (for example, 56) while in Program Mode. The Alpha display keypad will display the first of a series of prompts.
After making the appropriate entry, press the [ ] key to accept the entry and continue to the next prompt.
Loading Factory Defaults/Initializing for Download
To Load Default Entries Press 97 while in Program Mode. This resets all data fields to the default values shown on the Program Form. Use 97 only if you wish to return to the original factoryprogrammed defaults.
Press 96 while in Program Mode. This initializes the system for downloading and resets all the subscriber account numbers and CSID.
Do not press 97 to load defaults if any programming has been done previously—data already programmed into the system will be changed!
Exiting the Programming Mode
Prevent installer code |
Press 98. Exits Programming Mode and prevents re-entry by: |
reentry |
Installer Code + [8] + [0] + [0]. To enter the programming mode if 98 was used to exit, |
|
you must first power the system down. Then power up again, and press [ ] and [#] at the |
|
same time, within 50 seconds of powering up. |
|
See field *88 for other Program mode lockout options. |
Allow installer code |
Press 99. Exits Programming Mode and allows re-entry by: |
reentry |
Installer Code + [ 8] + [0] + [0] or by: Pressing [ ] and [#] at the same time, within 50 |
|
seconds of power-up. |
Zone Type Definitions
Zone types define the way in which the system responds to faults in each zone.
Zone Type |
Description |
Type 00 |
Program a zone with this zone type if the zone is not used. |
Zone Not Used |
|
Type 01 |
• Assign to zones that are used for primary entry and exit. |
Entry/Exit |
• Provides entry delay when zone is faulted if control is armed in the Away, Stay, or Night-Stay |
Burglary #1 |
modes. |
|
• No entry delay provided when the panel is armed in the Instant/Maximum mode. |
|
• Entry delay #1 is programmable for each partition (field *35). |
|
• Exit delay begins whenever the control is armed, regardless of the arming mode selected, and |
|
is programmable (field 34). |
Type 02 |
• Assign to zones that are used for entry and exit and require more time than the primary |
Entry/Exit |
entry/exit point. |
Burglary #2 |
• Provides a secondary entry delay, in same manner as entry delay #1. |
|
• Entry delay #2 is programmable for each partition (field *36). |
|
• Exit delay is same as described for Type 01. |
Type 03 |
• Assign to all sensors or contacts on exterior doors and windows. |
Perimeter |
• Provides an instant alarm if the zone is faulted when the panel is armed in the Away, Stay, |
Burglary |
Night-Stay, Instant or Maximum modes. |
|
|
Type 04 |
• Assign to a zone covering an area such as a foyer, lobby, or hallway through which one must |
Interior Follower |
pass upon entry (to and from the keypad). |
|
• Provides a delayed alarm (using the programmed entry 1 time) if the entry/exit zone is faulted |
|
first. Otherwise this zone type gives an instant alarm. |
|
• Active when the panel is armed in the Away mode. |
|
• Bypassed automatically when the panel is armed in the Stay or Instant modes; |
|
if armed in Night-Stay mode, zones assigned to zone list 05 (night-stay zone list) are not |
|
bypassed when system armed in Night-Stay mode. |
3-2
|
|
Programming Overview |
|
|
|
|
Type 05 |
• Assign to a zone that contains a foil-protected door or window (such as in a store), or to a zone |
|
Trouble by Day/ |
covering a sensitive area such as a stock room, drug supply room, etc. |
|
Alarm by Night |
• Can also be used on a sensor or contact in an area where immediate notification of an entry is |
|
|
desired. |
|
|
• Provides an instant alarm if faulted when armed in the Away, Stay, Night-Stay, Instant or |
|
|
Maximum (night) modes. |
|
|
• During the disarmed state (day), the system will provide a latched trouble sounding from the |
|
|
keypad (and a central station report, if desired). |
|
Type 06 |
• Usually assigned to a zone containing an emergency button. |
|
24-hr Silent Alarm |
• Sends a report to the central station but provides no keypad display or sounding. |
|
|
|
|
Type 07 |
• Assign to a zone that has an emergency button. |
|
24-hour Audible |
• Sends a report to the central station, and provides an alarm sound at the keypad, and an |
|
Alarm |
audible external alarm. |
|
|
|
|
Type 08 |
• Assign to a zone containing an emergency button, or to a zone containing monitoring devices |
|
24-hour |
such as water or temperature sensors. |
|
Auxiliary Alarm |
• Sends a report to the central station and provides an alarm sound at the keypad. (No bell |
|
|
output is provided.) |
|
Type 09 |
• Provides a fire alarm on short circuit and a trouble condition on open circuit. A fire alarm |
|
Supervised Fire |
produces a pulsing bell output. |
|
|
• This zone type is always active and cannot be bypassed. |
|
|
|
|
Type 10 |
• Provides entry delay (using the programmed entry time), if tripped when the panel is armed in |
|
Interior w/Delay |
the Away mode. |
|
|
• Entry Delay 1 begins whenever sensors in this zone are violated, regardless of whether or not |
|
|
an entry/exit delay zone was tripped first. |
|
|
• Bypassed when the panel is armed in the Stay or Instant modes; if armed in Night-Stay mode, |
|
|
zones assigned to zone list 05 (night-stay zone list) are not bypassed when system armed in |
|
|
Night-Stay mode. |
|
Type 12 |
• Works as a dynamic monitor of a zone fault/trouble (not alarm). In the case of a short/open, the |
|
Monitor Zone |
message, "*ALARM*-24 Hr. Non-Burg. -#XXX " (where XXX is the zone number) will be sent |
|
|
to the Central Station. The system keypad will display a “check” message indicating the |
|
|
appropriate zone (but keypad beeping does not occur). Upon restoral of the zone, the message, |
|
|
"*RESTORE*-24 Hr. Non-Burg. -#XXX " will be sent to the Central Station. |
|
|
• The “check” message will automatically disappear from the keypad dynamically, when the |
|
|
zone restores; a user code + off sequence is not needed to reset the zone. |
|
|
• Faults of this zone type are independent of the system, and can exist at the time of arming |
|
|
without interference. |
|
|
• Since this is a “trouble” zone type, do not use this zone type with relays set to activate upon |
|
|
“alarm.” |
|
Type 14 |
• Assigned to any zone with a carbon monoxide detector. |
|
24 Hour Carbon |
• The bell output will pulse when this zone type is alarmed. |
|
Monoxide |
• Always active and cannot be bypassed. |
|
Monitor |
|
|
Type 16 |
• Provides a fire alarm when zone is shorted, but only after alarm verified. |
|
Fire |
• System verifies alarm by resetting zones for 12 seconds after short is detected. A subsequent |
|
w/Verification |
short circuit within 90 seconds triggers fire alarm. |
|
|
• Provides a trouble response when zone is open. |
|
Type 20 |
• Arms the system in Stay mode when the zone is activated. |
|
Arm-Stay (BR |
• Pushbutton units send the user number to the central station when arming or disarming. |
|
only) |
• User number for button must be assigned. |
|
|
|
|
Type 21 |
• Arms the system in Away mode when the zone is activated. |
|
Arm-Away (BR |
• Pushbutton units send the user number to the central station when arming or disarming. |
|
only) |
• User number for button must be assigned. |
|
|
|
|
Type 22 |
• Disarms the system when the zone is activated. |
|
Disarm (BR only) |
• User number for button must be assigned. |
|
|
|
3-3
Installation and Setup Guide
Type 23 * |
• Can be used on a zone when an output relay action is desired, but with no accompanying |
No Alarm |
alarm (e.g., lobby door access). |
Response |
|
|
|
Type 24 |
• Usually assigned to all sensors or contacts on exterior doors and windows where bells and/or |
Silent Burglary |
sirens are NOT desired. |
|
• Provides an instant alarm, with NO audible indication at any keypad or external sounder, if |
|
the zone is faulted when the system is armed in the Away, Stay, Instant, or Maximum modes. |
|
• A report is sent to the central station. |
Type 77 |
• Assign to zone wired to a keyswitch. |
Keyswitch |
• Do not use devices assigned as input type “BR” with this zone type. |
Type 81 |
• Assign to zone connected to AAV module. |
AAV Monitor |
• Monitors 2-way voice sessions as follows: |
Zone |
- When the zone is faulted, all alarm sounding and dialer reporting stops, except |
|
|
|
for fire alarms, which immediately terminate the voice session and cause |
|
a fire report to be sent. |
|
- When the zone is restored (session ended), sounding resumes (if bell timeout |
|
has not expired) and reports that were stopped are sent. |
Types 90-93 |
Allows for various custom responses. Options include response to entry/exit delays, response |
Configurable |
opens/shorts, types of alarm/trouble sounding, dial delay, and unique Contact ID report codes. |
|
Types 92 and 93 can only be programmed via downloader. UL installations: Zone Types 90 -93 |
|
may not be used as fire or burglar alarm zones on fire or UL burglar alarm installations. |
|
|
* The system can still be armed when these zone types are in a faulted condition.
NOTE: All of the zone types described are available for the wireless portion of the system, if used.
3-4