Honeywell K5305-1V5, VISTA 20P, VISTA-20PSIA, VISTA-15P, VISTA-15PSIA User Manual

0 (0)

ADEMCO VISTA SERIES

VISTA-20P / VISTA-20PSIA

VISTA-15P / VISTA-15PSIA

Security Systems

Installation and Setup Guide

K5305-1V5 10/04 Rev. A

RECOMMENDATIONS FOR PROPER PROTECTION

The Following Recommendations for the Location of Fire and Burglary Detection Devices Help Provide Proper Coverage for the Protected Premises.

Recommendations For Smoke And Heat Detectors

With regard to the number and placement of smoke/heat detectors, we subscribe to the recommendations contained in the National Fire Protection Association's (NFPA) Standard #72 noted below.

Early warning fire detection is best achieved by the installation of fire detection equipment in all rooms and areas of the household as follows: For minimum protection a smoke detector should be installed outside of each separate sleeping area, and on each additional floor of a multi-floor family living unit, including basements. The installation of smoke detectors in kitchens, attics (finished or unfinished), or in garages is not normally recommended.

For additional protection the NFPA recommends that you install heat or smoke detectors in the living room, dining room, bedroom(s), kitchen, hallway(s), attic, furnace room, utility and storage rooms, basements and attached garages.

In addition, we recommend the following:

Install a smoke detector inside every bedroom where a smoker sleeps.

Install a smoke detector inside every bedroom where someone sleeps with the door partly or completely closed. Smoke could be blocked by the closed door. Also, an alarm in the hallway outside may not wake up the sleeper if the door is closed.

Install a smoke detector inside bedrooms where electrical appliances (such as

 

KITCHEN

TV ROOM

KITCHEN

DINING

BDRM

DINING

BEDROOM BEDROOM

 

 

 

 

 

 

 

 

LIVING ROOM

BDRM

 

 

 

 

LIVING ROOM

 

 

 

BEDROOM

BEDROOM

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Smoke Detectors for Minimum Protection

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Smoke Detectors for Additional Protection

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BEDROOM

 

 

Heat-Activated Detectors

BEDROOM

TO

BEDROOM

 

 

BR

 

 

 

 

 

 

 

 

KTCHN

 

GARAGE

LVNG RM

 

.

CLOSED

 

 

 

 

 

DOOR

 

BASEMENT

 

 

 

 

 

 

 

 

floor_plan-001-V0

portable heaters, air conditioners or humidifiers) are used.

Install a smoke detector at both ends of a hallway if the hallway is more than 40 feet (12 meters) long.

Install smoke detectors in any room where an alarm control is located, or in any room where alarm control connections to an AC source or phone lines are made. If detectors are not so located, a fire within the room could prevent the control from reporting a fire or an intrusion.

THIS CONTROL COMPLIES WITH NFPA

REQUIREMENTS FOR TEMPORAL PULSE

SOUNDING OF FIRE NOTIFICATION

APPLIANCES.

Recommendations For Proper Intrusion Protection

For proper intrusion coverage, sensors should be located at every possible point of entry to a home or commercial premises. This would include any skylights that may be present, and the upper windows in a multi-level building.

In addition, we recommend that radio backup be used in a security system so that alarm signals can still be sent to the alarm monitoring station in the event that the telephone lines are out of order (alarm signals are normally sent over the phone lines, if connected to an alarm monitoring station).

ii

Table Of Contents

Features and Installation Highlights............................................................................................................

1-1

Capabilities and Functions................................................................................................................................................

1-1

Compatible Devices ...........................................................................................................................................................

1-2

Important Installation Highlights (Installer Please Read) .............................................................................................

1-2

Mounting and Wiring the Control .................................................................................................................

2-1

Installing the Control Cabinet and PC Board ..................................................................................................................

2-1

Cabinet and Lock .........................................................................................................................................................

2-1

Mounting the PC Board Alone (no RF Receiver) ........................................................................................................

2-1

Mounting Board with RF Receiver..............................................................................................................................

2-1

AUXILIARY DEVICE CURRENT DRAW WORKSHEET ..............................................................................

2-2

AC Power, Battery, and Ground Connections ..................................................................................................................

2-3

1321 Transformer.........................................................................................................................................................

2-3

1361X10 Transformer ..................................................................................................................................................

2-3

Battery Connections.....................................................................................................................................................

2-3

Battery Saver Feature .................................................................................................................................................

2-3

Earth Ground ...............................................................................................................................................................

2-3

Sounder (Bell) Connections ...............................................................................................................................................

2-4

Basic Connections ........................................................................................................................................................

2-4

Supervised output ........................................................................................................................................................

2-4

Connecting the Keypads and Other Addressable Devices ...............................................................................................

2-4

Connections ..................................................................................................................................................................

2-4

Supplementary Power (optional).................................................................................................................................

2-4

Keypad Notes ...............................................................................................................................................................

2-5

Long Range Radio Connections...................................................................................................................................

2-5

Table of Device Addresses .................................................................................................................................................

2-5

Hardwire Zones and Zone Expansion ...............................................................................................................................

2-6

Hardwire Zones ............................................................................................................................................................

2-6

Double-Balanced Zones................................................................................................................................................

2-6

Zone Doubling ..............................................................................................................................................................

2-6

Smoke Detectors...........................................................................................................................................................

2-6

Smoke Detector Notes..................................................................................................................................................

2-7

4219/4229 Expansion Zones ........................................................................................................................................

2-7

Installing the RF Receiver and Wireless Transmitter Zones ..........................................................................................

2-8

Compatible Receivers...................................................................................................................................................

2-8

Receiver Connections ...................................................................................................................................................

2-8

RF Receiver Notes........................................................................................................................................................

2-8

Installing a 5800TM Module .......................................................................................................................................

2-9

Installing the Transmitters .........................................................................................................................................

2-9

Transmitter Battery Life .............................................................................................................................................

2-9

Installing a Keyswitch.....................................................................................................................................................

2-10

Keyswitch Connections ..............................................................................................................................................

2-10

Keyswitch Notes.........................................................................................................................................................

2-10

Connecting Relay Modules, Powerline Carrier Devices and Output Triggers..............................................................

2-11

4204/4229 Relay Modules ..........................................................................................................................................

2-11

Powerline Carrier Devices .........................................................................................................................................

2-11

On-Board Triggers .....................................................................................................................................................

2-12

Phone Line/Phone Module, and Audio Alarm Verification (AAV) Connections............................................................

2-13

Phone Line..................................................................................................................................................................

2-13

4285/4286 Phone Module...........................................................................................................................................

2-13

Phone Module Problems ............................................................................................................................................

2-13

Audio Alarm Verification Connections......................................................................................................................

2-14

Programming Overview ...................................................................................................................................

3-1

About Programming ..........................................................................................................................................................

3-1

Mechanics of Programming...............................................................................................................................................

3-1

Data Field Programming Procedures..........................................................................................................................

3-1

Interactive Mode Programming ( 56, *57, 58, 79, 80, 81, 82)...........................................................................

3-2

Loading Factory Defaults/Initializing for Download..................................................................................................

3-2

Exiting the Programming Mode ..................................................................................................................................

3-2

Zone Type Definitions........................................................................................................................................................

3-2

iii

Table Of Contents (continued)

Data Field Programming .................................................................................................................................

4-1

About Data Field Programming........................................................................................................................................

4-1

System Setup Fields ( 20 – 29) .......................................................................................................................................

4-1

Zone Sounds & Timing ( 31– 39) .....................................................................................................................................

4-1

Dialer Programming ( 40 – 50) .......................................................................................................................................

4-2

System Status Report Codes .............................................................................................................................................

4-4

Miscellaneous System Fields ............................................................................................................................................

4-5

Pager Programming Fields................................................................................................................................................

4-7

Miscellaneous System Fields ............................................................................................................................................

4-8

Configurable Zone Type Fields .........................................................................................................................................

4-9

Touch Screen Device (AUI) Enable.................................................................................................................................

4-11

Keypad Programming Fields...........................................................................................................................................

4-11

Menu Mode Programming ...............................................................................................................................

5-1

Zones and Partitions..........................................................................................................................................................

5-1

About Zone Programming ( 56 and 58 Menu Modes) ....................................................................................................

5-1

56 Zone Programming Procedure ...................................................................................................................................

5-1

Completing Zone Programming ........................................................................................................................................

5-4

58 Expert Programming Mode Procedures.....................................................................................................................

5-4

Wireless Key Programming Templates ............................................................................................................................

5-6

About Output Device Programming (*79/*80 Menu Mode) .............................................................................................

5-8

Programming Output Devices...........................................................................................................................................

5-8

*79 Menu Mode: Output Device Mapping ........................................................................................................................

5-8

*80 Menu Mode: Defining Output Functions .................................................................................................................

5-10

About Zone Lists (*81 Menu Mode) ................................................................................................................................

5-12

Zone List Programming...................................................................................................................................................

5-12

About Function Keys (*57 Menu Mode)..........................................................................................................................

5-13

Programming Function Keys ..........................................................................................................................................

5-13

About Descriptor Programming (*82 Menu Mode) ........................................................................................................

5-14

Programming Zone Descriptors (Menu Mode 82).........................................................................................................

5-14

Adding Custom Words (will not be annunciated by 4285/4286 Phone Module) ...........................................................

5-15

Programming Installer and User Schedules ..................................................................................................................

5-17

System Communication and Operation .......................................................................................................

6-1

Panel Communication with Central Station ....................................................................................................................

6-1

Report Code Formats.........................................................................................................................................................

6-1

Ademco Contact ID® .........................................................................................................................................................

6-3

System Security Codes ......................................................................................................................................................

6-4

Panic Keys......................................................................................................................................................................

6-6

Setting the Real-Time Clock .............................................................................................................................................

6-6

Various System Trouble Displays.....................................................................................................................................

6-7

Testing the System.............................................................................................................................................

7-1

About Test Procedures.......................................................................................................................................................

7-1

System Test........................................................................................................................................................................

7-1

Checking Transmitter Enrollment (Sniffer Mode)...........................................................................................................

7-1

Go/No Go Test Mode ..........................................................................................................................................................

7-2

Dialer Communication Test and Periodic Test Reports...................................................................................................

7-2

Automatic Standby Battery Tests.....................................................................................................................................

7-2

Specifications & Accessories...........................................................................................................................

8-1

Security Control.................................................................................................................................................................

8-1

Compatible Devices ...........................................................................................................................................................

8-1

5800 Series Transmitter Input Loop Identification .........................................................................................................

8-3

Regulatory Agency Statements ......................................................................................................................

9-1

Limitations and Warranty .............................................................................................................................

10-7

iv

S E C T I O N 1

Features and Installation Highlights

This manual applies to the following Honeywell security systems:

ADEMCO VISTA-20P/ADEMCO VISTA-20PSIA/ADEMCO VISTA-20PCN (collectively referred to as VISTA-20P series), ADEMCO VISTA-15P/ADEMCO VISTA-15PSIA/ADEMCO VISTA-15PCN (collectively referred to as VISTA-15P series)

Features and procedures apply to all, except where differences are noted.

SIA Installations: The VISTA-20PSIA and VISTA-15PSIA are certified SIA-compliant controls that meet SIA specifications for False Alarm Reduction. The other controls described in this manual are not certified as SIA compliant, but can be programmed for False Alarm Reduction. To program for False Alarm Reduction, follow the SIA Guidelines noted in the applicable programming fields.

NOTE: Throughout this manual, device model numbers are ADEMCO model numbers unless otherwise noted.

Capabilities and Functions

Feature/Function

ADEMCO VISTA-20P Series

ADEMCO VISTA-15P Series

Partitions

2 partitions, can protect two independent

VISTA-15P is not a partitioned system.

 

areas

 

 

Common zone option allows either

 

 

partition to arm, while leaving a common

 

 

area (ex. lobby or foyer) disarmed for

 

 

access into the other partition.

 

Zones

Up to 48 protection zones plus 16 keyfob

Up to 32 zones plus 8 keyfob zones (zones

 

zones (zones 49-64) for total of 64 zones:

49-56) for total of 40 zones:

 

8 basic hardwired zones (zones 1-8) with

6 basic hardwired zones (zone 1-6)

 

optional zone-doubling feature

Up to 16 additional wired zones (zones 9-

 

Up to 40 additional wired zones (zones 9-

24) using up to 2 4219/4229 modules

 

48) using up to 5 4219/4229 modules

Up to 26 wireless transmitter zones

 

Up to 40 wireless transmitter zones (5800

(5800 series; zones 9-34)

 

series; zones 9-48)

Up to 2 configurable zone types

 

Up to 4 configurable zone types

 

Security Codes

Up to 48 Security Codes, with separate

Up to 32 Security Codes, with separate

 

authority levels and partition access

authority levels

One-button arming

Dedicated keys can arm the system.

Dedicated keys can arm the system.

Schedules

Up to 32; can control devices and/or auto-

Up to 8; can control devices and/or auto-

 

arm/disarm

arm/disarm

Keypad macros

Up to 4; activated by wired keypads

Up to 2; activated by wired keypads

Paging

Up to 4 pagers; certain system conditions

Up to 2 pagers; certain system conditions

 

can report to pagers; can use a dedicated

can report to pagers; can use a dedicated

 

key on keypads to send a signal to a pager

key on keypads to send a signal to a pager

Event Logging

100 events; log display is done via Ademco

50 events; log display is done via Ademco

 

Compass Downloader software or

Compass Downloader software or

 

installer/master code at Keypad

installer/master code at Keypad

Zone descriptors

Can assign for all zones (for alpha display keypads and/or 4285/4286 Phone Module).

Bell supervision

Optional, detects external sounder wiring short or open; causes a trouble condition,

 

keypad display, and sends a report to the central monitoring station, if enabled.

RF jam detection

Optional, for wireless systems detects a condition that may impede proper RF reception

 

(i.e., jamming or other RF interference); causes keypad display, and sends a report to the

 

central monitoring station (if trouble reporting is enabled).

Telephone Line

Built-in option can monitor the telephone line voltage and can cause a local display, or a

Monitoring

display and trouble/alarm sound

 

Downloading

Via an IBM compatible computer, Compass downloading software, and a compatible

 

HAYES or CIA modem specified by Ademco.

 

1-1

Installation and Setup Guide

Compatible Devices

Device

VISTA-20P

VISTA-15P

Notes

Addressable Keypads

8

8

6150 Fixed-Word Keypad, 6160 Alpha Keypad, 6150V

 

 

 

Fixed-Word Display Voice Keypad, 6160V Alpha

 

 

 

Display Voice Keypad, 6150RF Keypad/Transceiver

Touch Screen (AUI)

2

2

Touch Screen (AUI) devices are in addition to the 8

Devices

 

 

addressable keypads. E.g., Symphony, 6270

4219, 4229 Zone

Up to 5 for

Up to 2 for

Zone numbers are predefined according to the device

Expander Modules

up to 40

up to 16

addresses used. See Expander Module Addresses table

 

exp. zones

exp. zones

in Wiring section and set addresses accordingly.

5800 Series Wireless

Up to 40 RF

Up to 26 RF

Uses 5881/5883 Series Receivers/Transceivers.

 

zones

zones

 

Output relays and/or

Up to 16

Up to 8

Use any combination of 4204, 4229 and or Powerline

Powerline Carrier

 

 

Carrier Devices.

Devices (X-10 type)

 

 

Map output devices via *79 Menu mode.

On-Board Triggers

2

2

Can be used to reset 4-smoke detectors.

Output functions

Up to 48

Up to 24

Program output functions via *80 Menu mode.

4285/4286 Phone

Partition 1

yes

Provides access to the system via on premises or off-

Module

only

 

premises phones for arming, disarming, etc., plus

 

 

 

control of relay outputs and Powerline Carrier devices.

Audio Alarm

Using AAV

Using AAV

Use ADEMCO UVS or Eagle Model 1250; can be used

Verification

module

module

in conjunction with an output trigger to permit voice

 

 

 

dialog between an operator at the central station and

 

 

 

a person at the premises.

Alarm output

12VDC, 2

12VDC, 2

Can drive the compatible sounders; steady output for

 

AMP output

AMP output

burglary/panic, or temporal pulse (3 pulses – pause –

 

 

 

3 pulses – pause – 3 pulses. . .) for fire. Uses current

 

 

 

limiting circuitry for protection.

Auxiliary Power Output

See note.

See note

12VDC, 600 mA maximum; uses fuse for protection.

Backup Battery

See note.

See note.

Rechargeable (sealed lead-acid type) 12VDC, 4AH

 

 

 

minimum.

Long Range Radio

See note.

See note.

Primary telephone number messages can be reported

 

 

 

via ECP connection to various Long Range Radios

 

 

 

(check compatibility/availability of specific models)

AC Power Supply

See note.

See note.

Plug-in 120VAC transformer, ADEMCO 1321

 

 

 

(1321CN in Canada) or, if using Powerline Carrier

 

 

 

devices, ADEMCO 1361X10 Transformer Module

NOTE: All devices and accessories used in a Canadian installation must be Listed for use in Canada.

Important Installation Highlights (Installer Please Read)

This system uses addressable keypads and Zone Expander Modules (see Table of Addresses in

Section 2. Mounting and Wiring – Wiring the Keypads and Other Addressable Devices).

Keypads must be set for addresses 16-23 (first keypad is address 16, which is different from previous controls) and programmed in data fields *190-*196.

Zone Expander Modules must be set for specific addresses (07-11), based on the zone numbers used.

4204 Relay Modules must be set for specific addresses (12-15).

This control will not power-up unless AC power is connected (will not power-up on battery alone). However, once the system is powered up, it will operate on battery power in the event of AC loss.

Relays have two programming menu modes: Use *79 Menu mode to map module addresses and device (output) numbers. Use *80 Menu mode to define the output functions.

This system supports programmable function keys. Use *57 Menu mode to define the function keys.

This system provides various paging features. Refer to the Programming Overview section for a summary on pager programming.

1-2

S E C T I O N 2

Mounting and Wiring the Control

Installing the Control Cabinet and PC Board

Cabinet and Lock

1.

Mount the control cabinet to a

 

 

sturdy wall in a clean, dry area,

 

 

which is not readily accessible to

 

 

the general public, using fasteners

 

 

or anchors (not supplied) with the

 

 

four cabinet mounting holes.

 

2.

Remove cabinet door, then remove

 

 

the lock knockout from the door.

 

 

Insert the key into the lock.

CHECK

SNAP

POSITION

TAB

LOCKED

PUSH

 

 

ADEMCO

 

SNAP

UNLOCKED

TAB

CABINET DOOR

STEP 1

BOTTOM

 

PUSH

 

ON LOCK

 

UNTIL IT

IS SEATED

SECURELY

ADEMCO

 

STEP 2

lock snap-001-V0

 

cab

Figure 1. Installing the Cabinet Lock

3.Position the lock in the hole, making certain that the latch will make contact with the latch bracket when the door is closed. When correctly positioned, push the lock until the snap tabs hold it securely.

The cabinet can be secured without a lock by using 2 screws in the cover's edge.

Mounting the PC Board

Before installing the cabinet's contents, remove the metal cabinet knockouts required for

Alone (no RF Receiver)

wiring entry. Do not remove the knockouts after the circuit board has been installed.

1.Hang two short mounting clips (provided) on the raised cabinet tabs (see Detail B).

2.a. Insert the top of the circuit board into the slots at the top of the cabinet. Make sure that the board rests on the correct row (see Detail A).

b.Swing the base of the board into the mounting clips and secure the board to the cabinet with the accompanying screws (see Detail B).

CIRCUIT

CABINET

BOARD

 

CIRCUIT

 

BOARD

 

+

+

CABINET

DETAIL B

 

SIDE VIEW

DETAIL A

OF MOUNTING

SIDE VIEW

CLIPS

OF BOARD

 

SUPPORTING

 

SLOTS

 

 

MOUNTING-001-V0

 

Figure 2. Mounting the PC Board

Mounting Board with RF

Do not mount the cabinet on or near metal objects. This will decrease RF range and/or

Receiver

block RF transmissions from wireless transmitters.

Do not locate the cabinet in an area of high RF interference (revealed by frequent or prolonged lighting of the LED in the receiver (random flicker is OK)

1.a. Remove the receiver board from its case, then insert the top of the board into the slots at the top of the cabinet, as shown in Detail A in Figure 3 on the next page. Make sure that the board rests on the correct row of tabs.

b.Swing the base of the board into the mounting clips and secure it to the cabinet with the accompanying screws.

c.Insert the top of the control's board into the slot in the clips and position two clips at the lower edge of the board.

d.Swing this board into place and secure it with two additional screws.

2.Insert grounding lugs (supplied with the receiver) through the top of the cabinet into the left-hand terminals of the antenna blocks (at the upper edge of the receiver board) and secure them to the cabinet top with the screws provided (see Detail B).

3.Insert the receiver's antennas through the top of the cabinet, into the blocks' righthand terminals, and tighten the screws.

2-1

Installation and Setup Guide

CABINET

A

B

CABINET

BOARD

RECEIVER CIRCUIT BOARD SUPPORTING

SLOTS

+

+

 

CIRCUIT

 

BOARD

 

MOUNTING

 

CLIP

CONTROL

CIRCUIT

BOARD

 

DETAIL A

MOUNTING

SIDE VIEW

CLIP

OF BOARD -

SUPPORTING SLOTS

INSTALLATION WITH RECEIVER CIRCUIT BOARD

WHITE

BLACK

RED

MOUNTING

MOUNTING

MOUNTING

CLIP

CLIP

CLIP

NOTE

A COMBINATION OF THESE MOUNTING CLIPS HAS BEEN INCLUDED IN YOUR INSTALLATION KIT.

USE THE APPROPRIATE CLIPS FOR MOUNTING.

IF NO RF RECEIVER IS USED, MOUNT THE PC BOARD USING EITHER THE WHITE OR BLACK CLIPS, WHICHEVER ARE INCLUDED IN THE CONTROL PANEL'S HARDWARE KIT.

ANTENNA

(2)

SCREW

(2)

GROUNDING

LUG

(2)

ANTENNA

MOUNT

(2 PLACES)

DETAIL B

ANTENNA AND GROUNDING

LUG INSTALLATION

pc_mount-001-V1

Figure 3. Mounting the PC Board and RF Receiver

AUXILIARY DEVICE CURRENT DRAW WORKSHEET

 

DEVICE

CURRENT

No. UNITS

TOTAL CURRENT

6150

Fixed-Word Keypad

40mA/70mA**

 

 

6160

Alpha Keypad

40mA/150mA**

 

 

6150V Fixed-Word Display Voice Keypad

60mA/160mA**

 

 

6160V Alpha Display Voice Keypad

60mA/190mA**

 

 

8132/8142 Series AUI (Symphony)

150mA/400mA**

 

 

6270

Touch Screen Keypad

180mA/280mA**

 

 

5881/5882 RF Receiver

60mA

 

 

5883

Transceiver

80mA

 

 

4219 Zone Expander

30mA

 

 

4204

Relay Unit

15/180mA

 

 

4229

Zone Expander/Relay Unit

30/100mA

 

 

4285 Phone Module

160mA

 

 

4286 Phone Module

300mA

 

 

 

 

 

 

 

*

 

 

 

 

(Current available from Aux. terminals = 600 mA max.)

TOTAL =

 

*If using hardwire devices such as PIRs, refer to the specifications for that particular unit's current draw. ** Values are for standby/alarm; alarm for keypads means armed with backlighting on and sounder on

†In UL installations, maximum current draw from the Auxiliary Output and the Alarm Output combined must not exceed 600 mA (500 mA max from Aux. Output). ‡Values are for relays OFF/relays ON.

CALIFORNIA STATE FIRE MARSHALL (CSFM) AND UL RESIDENTIAL FIRE

24-HOUR BATTERY BACKUP REQUIREMENTS

The California State Fire Marshal and UL have regulations which require that all residential fire alarm control panels must be provided with a backup battery which has sufficient capacity to operate the panel and its attached peripheral devices for 24 hours in the intended standby condition, followed by at least 4 minutes in the intended fire alarm signaling condition. This control panel can meet these requirements without using a supplementary power supply, provided that the panel’s auxiliary power and bell output currents are limited as indicated below.

OUTPUT LIMITATIONS AND CORRESPONDING REQUIRED BATTERIES

OUTPUT CURRENT LIMITATIONS

BATTERY INFORMATION

Output Current Total

Maximum Auxiliary Current

Battery Capacity

Recommended Battery

 

 

To Use (Amp/Hrs)

(Yuasa Model No.)

600mA maximum total of

45mA

4AH

NP4-12 (or ADEMCO 467)

auxiliary power plus bell

160mA

7AH

NP7-12

output currents

200mA

8AH

NP4-12 (two) ‡

 

425mA

14AH

NP7-12 (two) ‡

 

500mA

17.2AH

NPG18-12

NOTE: Use two batteries, connected in parallel. Obtain an Ademco Battery Harness Kit SA5140-1. (Both batteries will fit inside the cabinet.)

2-2

Figure 4. 1361X10 Transformer Connections
8-PIN TRIGGER CONNECTOR

Mounting and Wiring the Control

AC Power, Battery, and Ground Connections

1321 Transformer

 

1

 

2

TO

-001-V0

1 AND 2

1321X10

TERMINALS

 

Connect the 1321 Transformer (1321CN in Canada) to terminals 1 and 2 on the control board. See Wire Run Chart for wire size to use.

Use caution when wiring the transformer to the control to guard against blowing the transformer fuse (the fuse is non-replaceable).

Wire Run Chart

Distance from control

Wire Size

Up to 50 feet

# 20

50–100 feet

# 18

100-250 feet

# 16

1361X10 Transformer

(required if using Powerline Carrier devices)

AC

AC

 

Sync

S

Ou

tput

igna

Com l

 

mon

X10

Data

TO

8-PIN

CONNECTOR

1

2

 

TO

-001-V0

1361X10

1 AND 2

TERMINALS

 

Battery Connections

BLACK

RED

 

CONNECT

001-V0

FLYING LEADS

-

conn

AFTER AC POWER

IS APPLIED

batt

Wiring to the AC transformer must not exceed 250 feet using 16 gauge wire. The voltage reading between terminals 1 and 2 of the control must not fall below 16.5VAC or an “AC LOSS” message will be displayed.

Do not plug the transformer into the AC outlet until all wiring connections to the control are complete. As a safety precaution, always power down the control when making such connections.

1. Splice one end of a 3-conductor cable

to the wire ends of the SA4120XM-1

 

 

 

 

 

 

 

1

KEY

3

4

5

6

7

8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Cable.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2. Connect the SA4120XM-1 cable plug

 

1361X10 TRANSFORMER

 

17 (RED)

 

(ORANGE)

(YELLOW)

18 (GREEN)

(BLUE)

(PURPLE)

(BLACK)

to the 8-pin connector on the control

 

 

 

 

 

 

 

 

 

(see the Summary of Connections

AC

AC

SYNC COM

DATA

 

 

1

2

3

4

5

 

 

diagram for location of the 8-pin

 

OUTPUT

 

+12 AUX.

GND (-)

OUTPUT

 

 

 

 

 

 

 

 

 

 

 

 

 

DATA

COM

SYNC

connector).

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3. Connect the other end of the

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SA412OX

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CABLE

3-conductor cable to the 1361X10

1

2

 

 

 

 

 

 

 

 

 

 

 

 

 

Transformer, as shown in Figure 4.

CONTROL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BOARD

 

 

 

 

 

 

 

 

 

 

 

 

 

TERMS.

Canadian Installations: See Powerline Carrier Device section for connections to the PSC04 X-10 Interface and trigger pins.

1.Place the 12-volt backup battery in the cabinet.

2.After all connections to the control are completed and AC power has been applied, connect the red and black flying leads on the control board to the battery. Do not attach these leads to the battery terminals until all connections are completed.

UL For UL installations and Residential fire installations, refer to the chart on page 2-2 at left for the correct battery size required to meet the mandatory standby time.

Battery Saver Feature

Earth Ground

BOARD CONTROL

25

CONNECT

PROPER

EARTH

GROUND

IF

DESIRED

earth_gnd-001-V0

The battery will disconnect from the system after its voltage decreases below 9VDC. This assists the control panel in recharging the battery when AC is restored. IMPORTANT: The panel will not power up initially on battery power only. You must plug the transformer in first, and then connect the battery.

This product has been designed and laboratory-tested to ensure its resistance to damage from generally expected levels of lightning and electrical discharge, and does not normally require an earth ground.

If an earth ground is desired for additional protection in areas of severe electrical activity, terminal 25 on the control board, or the cabinet, may be used as the ground connection point. The following are examples of good earth grounds available at most installations.

Metal Cold Water Pipe: Use a non-corrosive metal strap (copper is recommended) firmly secured to the pipe to which the ground lead is electrically connected and secured.

AC Power Outlet Ground: Available from 3-prong, 120VAC power outlets only. To test the integrity of the ground terminal, use a 3-wire circuit tester with neon lamp indicators, such as the UL Listed Ideal Model 61-035, or equivalent, available at most electrical supply stores.

2-3

Installation and Setup Guide

Sounder (Bell) Connections

Basic Connections

3 4

ALARM OUTPUT

 

10.5 - 13.5 VDC

 

2A MAX.

V0

 

spkr conn-001-

Make sounder connections to alarm output terminals 3 (+) and 4 (–).

The 12VDC sounder output activates when an alarm occurs.

Total current drawn from this output cannot exceed 2 amps (going beyond 2 amps will overload the power supply, or may cause the electronic circuit protecting the sounder output to trip).

You must install a battery, since the battery supplies this current.

Supervised output

1.Cut the red Bell Supervision Jumper located above terminals 2 and 3 on the PC board.

2.Connect a 2k ohm resistor across the terminals of the last sounder. See Figure 5.

This control complies with NFPA requirements for temporal pulse sounding of fire notification appliances. Temporal pulse sounding for a fire alarm consists of: 3 pulses – pause – 3 pulses – pause – 3 pulses–etc..

UL

Use only UL Listed sounding devices for UL installations.

Bell supervision is required for fire alarm installations.

The total current drawn from the alarm output and the auxiliary power output, combined, cannot exceed 600 mA. In addition, the sounding device must be a UL Listed audible signal appliance rated to operate in a 10.2-13.8 VDC voltage range, and must be mounted indoors.

TERMINALS ON

EXTERNAL ALARM

 

 

CONTROL BOARD

SOUNDER

 

 

4

 

 

 

ALARM

 

2000

 

OBSERVE

OHM

 

OUTPUT

 

POLARITY

EOL

 

TERMINALS

 

+

RESISTOR

+

 

 

 

 

3

 

 

 

2

IF BELL SUPERVISION IS ENABLED

 

 

 

 

 

 

(RED JUMPER ON CONTROL BOARD IS CUT)

 

 

CONNECT A 2000 OHM RESISTOR ACROSS

-V0

 

THE EXTERNAL SOUNDER AS SHOWN BY

CUT RED JUMPER ON CONTROL

THE DOTTED LINE.

 

001-

 

 

sounder

BOARD TO ENABLE BELL

DO NOT CONNECT THE RESISTOR AT THE

(SOUNDER) SUPERVISION.

ALARM OUTPUT TERMINALS THEMSELVES!

Figure 5. Sounder Wiring (Supervised)

Connecting the Keypads and Other Addressable Devices

Connections

 

 

4 _

 

 

 

5 +

 

 

 

6 IN

 

 

 

7 OUT

BLACK

RED

GREEN

YELLOW

AR

 

 

 

MED

 

 

 

READY

 

 

 

 

 

 

conn-001-V0

Supplementary Power (optional)

UL Use a UL Listed, battery-backed supply for UL installations. The battery supplies power to these keypads in case of AC power loss.

The battery-backed power supply should have enough power to supply the keypads with the UL required minimum standby power time.

Connect keypads and other addressable devices (4204, 4219, 4229, 4286, 5881, LRR, etc.) to the control’s keypad terminals as shown on the Summary of Connections diagram. The system supports up to 8 keypads, which can be assigned to partitions in any combination (see program fields *190-*196).

Determine wire size using the Wire Run Chart on the following page. For single 4-wire runs, determine the current drawn by all units, then refer to the Wiring Run chart to determine the maximum length that can be safely used for each wire size.

Use supplementary power if the control’s aux. power load for all devices exceeds 600mA (suggested power supply: AD12612). Connect as shown in Figure 6. Be sure to connect the negative (–) terminal on the power supply unit to terminal 4 (AUX –) on the control.

IMPORTANT: Keypads powered from supplies that do not have a backup battery will not function if AC power is lost. Make sure to power at least one keypad in each partition from the control’s auxiliary power output.

SUPPLEMENTARY

CONTROL TERMINAL STRIP

POWER SUPPLY

 

 

 

 

+

AUX. AUX. DATA DATA

 

 

+

IN

OUT

 

 

4

5

6

7

WIRERED

 

WIREGRN

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

WIREBLK

WIREYEL

 

 

 

 

 

WIRERED

 

WIREGRN

 

 

DIRECTLY TO

WIREBLK

 

 

WIREYEL

 

 

 

 

 

IMPORTANT:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MAKE THESE

 

 

 

 

 

 

 

 

 

 

KEYPADTO

KEYPADTO

KEYPADTO

KEYPADTO

CONNECTIONS

KEYPADTO

 

KEYPADTO

 

KEYPADTO

KEYPADTO

V0-supplypwrsupp

SCREW

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TERMINALS AS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SHOWN.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Figure 6. Using a Supplementary Power Supply

2-4

Mounting and Wiring the Control

Keypad Notes

ARMED

READY

1

OFF

 

 

 

 

4

 

 

2

AWAY

 

 

MAX

 

3

 

 

5

 

STAY

7INST

 

TEST

 

ANT

8

6

 

 

 

 

CODE

 

BYPASS

 

READY

0

 

9

CHIME

 

 

 

 

 

 

 

 

 

 

#

 

Long Range Radio

Connections

Set device addresses. Refer to the instructions included with the devices and set each address according to the Table of Devices Addresses.

See Keypad Programming Fields (fields *190-*196) in Section 4. Data Field Programming for details on enabling keypad addresses, assigning keypad partitions and selecting keypad sounding options.

IMPORTANT: Each keypad must be assigned a unique, predefined address, from 16 to 23. The first keypad is address 16 (default = partition 1, all sounds enabled).

TOUCH SCREEN KEYPAD (AUI) NOTES:

Use of up to 2 AUI devices (e.g., 6270, Symphony) is independent from standard keypads and does not affect the number of standard keypads the system can support.

AUI devices must be set for either address 1 or address 2, depending on which unit is enabled in field *189.

To ensure proper AUI device operation, connect only to controls having microprocessor version 3.0 or higher, and use AUI devices with the following rev levels: 6270 series use version 1.0.9 or higher; 8132/8142 (Symphony) series use version 1.1.175 or higher.

Connect the data in/data out terminals and voltage input terminals of the Long Range Radio to the control's keypad connection points.

Set the radio’s address to “03” following the instructions provided with the radio.

• Use compatible Long Range Radios (e.g., 7720PLUS, 7820, 7835C, or 7845C).

Wire Run Chart For Devices* Drawing Aux Power From The Control (12V+ & 12V–)

Wire

TOTAL CURRENT DRAWN BY ALL DEVICES CONNECTED TO A SINGLE WIRE RUN

Size

50 mA or less

100 mA

300 mA

500 mA

600 mA

#22

900 ft (274m)

450 ft (137m)

150 ft (46m)

90 ft (27m)

75 ft (23m)

#20

1400 ft (427m)

700 ft (213m)

240 ft (73m)

140 ft (43m)

120 ft (37m)

#18

1500 ft (457m)

1100 ft (335m)

350 ft (107m)

220 ft (67m)

170 ft (52m)

#16

1500 ft (457m)

1500 ft (457m)

550 ft (168m)

350 ft (107m)

270 ft (82m)

*Includes Keypads, RF Receivers, Zone Expander/Relay Units, 4285/4286 Phone Module, and Long Range Radio.

Maximum wire lengths for any device that is homerun to the control can also be determined from the Wiring Run Chart, based on the current draw of that device alone.

The length of all wire runs for both partitions combined must not exceed 1500 feet (457m) when unshielded quad conductor cable is used (750 feet if shielded cable is used). This restriction is due to the capacitive effect on the data lines when quad cable is used.

Table of Device Addresses

This Device

Uses Address

Reports as††

Enabled By…

RF Receiver

00

100

*56 zone programming: input device type entry

AUI 1

01

101

automatic if AUI enable field *189 enabled for AUI 1

AUI 2

02

102

automatic if AUI enable field *189 enabled for AUI 2

Long Range Radio

03

103

automatic if output to long range radio field *29 enabled

4286 Voice Module

04

104

automatic if phone module access code field *28 enabled

Zone Expanders (4219/4229):

 

 

*56 zone programming: input device type, entry 2, then:

module 1 (for zones 09 - 16)

07**

107

automatic if zone no. 9-16 set as AW type or relay assigned

module 2 (for zones 17 - 24)

08

108

automatic if zone no. 17-24 set as AW type or relay assigned

module 3 (for zones 25 - 32)

09

109

automatic if zone no. 25-32 set as AW type or relay assigned

module 4 zones 33 - 40

10

110

automatic if zone no. 33-40 set as AW type or relay assigned

module 5 zones 41 - 48

11

111

automatic if zone no. 41-48 set as AW type or relay assigned

Relay Modules (4204):

 

 

*79 output device programming: device address prompt:

module 1

12

112

entered at device address prompt

module 2

13

113

entered at device address prompt

module 3

14

114

entered at device address prompt

module 4

115

entered at device address prompt

 

15

 

 

Keypads:

 

 

data field programming as listed below:

keypad 1

16

n/a

always enabled for partition 1, all sounds enabled.

keypad 2

17

n/a

data field *190

keypad 3

18

n/a

data field *191

keypad 4

19

n/a

data field *192

keypad 5

20

n/a

data field *193

keypad 6

21

n/a

data field *194

keypad 7

22

n/a

data field *195

keypad 8

23

n/a

data field *196

5800TM Module

28

n/a

automatic

** address 07 not available if zone-doubling enabled

† 4219/4229 addresses 9-11 and 4204 addresses 14-15 apply to the VISTA-20P.

†† Addressable devices are identified by “1” plus the device address when reporting. Enter a report code for zone 91 to enable addressable device reporting (default = reports enabled). See field *199 for addressable device (ECP) 3-digit/2-digit identification keypad display options.

2-5

Installation and Setup Guide

Hardwire Zones and Zone Expansion

Hardwire Zones

HI LO

-zones V0-001

Double-Balanced Zones

(V20P only)

Zone Doubling

(V20P only)

Smoke Detectors

TO ZONE 1

TERMINALS

2-WIRE

8

9

SMOKE

DETECTOR

-V0

HI

-001

LO

ZONE 1

5806

Normally Open Zones/ N.O. EOLR Zones

1.Connect open circuit devices in parallel across the loop; for EOLR zones, connect the EOLR across the loop wires at the last device.

2.Enable normally open/EOLR zones using Zone Programming mode, “Hardwire Type” prompt.

Normally Closed Zones/ N.C. EOLR Zones

1.Connect closed circuit devices in series in the high (+) side of the loop; for EOLR zones, connect the EOLR in series following the last device.

2.Enable normally closed/EOLR zones using Zone Programming mode, “Hardwire Type” prompt.

End of Line Resistor (EOLR) Notes

If the EOLR is not at the end of the loop, the zone is not properly supervised and the system may not respond to an “open” on the zone.

Zone 1 is intended for EOLR only.

UL For UL commercial burglar alarm installations, use EOLR zones.

Connect as shown below (resistor provided for one device).

IMPORTANT: Double-balanced zones provide zone tamper protection, and should be used as burglary zones only.

Do not use double-balanced zones as fire zones.

12

13

14

2k

TAMPER

2k

CONTACTS

2k

TAMPER

2k

CONTACTS

 

 

2k

 

2k

ZONE 3

ZONE 4

zone-002-V0

Fig. 7. Typical Double Balanced Zones

This feature provides two hardwired

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

normally closed zones for each standard

 

 

10

 

 

 

 

 

 

 

11

 

 

hardwired zone connected to the control’s

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

terminals (but does not increase the total

 

 

 

ZONE 2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

number of zones supported by the control). If

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3k

 

 

 

 

 

enabled (Zone Programming mode,

 

 

 

ZONE 10

 

 

 

 

 

“Hardwire Type” prompt, option “3”),

 

 

 

 

 

 

V0

 

 

 

 

 

 

 

 

 

 

 

 

004-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

hardwire zones are automatically paired as

 

 

 

 

 

 

 

 

6.2k

 

 

 

zone-

shown in the table. Connect as shown below

Fig. 8. Typical Zone Doubling Wiring

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(resistors provided).

 

 

 

 

 

 

 

Zone Doubling Table

 

 

 

 

 

Do not use zone doubling for fire

 

 

 

 

 

 

 

Zone

Paired with zone

 

 

 

 

 

zones.

2

10

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3

11

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOTE: A short across the EOL (i.e., at

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4

12

 

 

 

 

 

 

 

 

 

 

 

 

 

 

terminal) on either zone of a zone-doubled

5

13

 

 

 

 

 

 

 

 

 

 

 

 

 

 

pair or on a double-balanced zone causes a

6

14

 

 

 

 

 

 

 

 

 

 

 

 

 

 

7

15

 

 

 

 

 

 

 

 

 

 

 

 

 

 

tamper condition (displayed as CHECK plus

 

 

 

 

 

 

 

 

 

 

 

 

 

 

8

16

 

 

 

 

 

 

 

 

 

 

 

 

 

 

zone numbers).

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.Connect up to 16 (10, if “clean me” option used) 2-wire smoke detectors across zone 1 terminals 8 (+) and 9 (-) as shown in the Summary of Connections diagram at the back this manual. Observe proper polarity when connecting the detectors.

2.Connect an EOL resistor across the loop wires at the last detector.

3.Connect 4-wire smoke detectors (up to 16, depending on detector current draw) to any zone from 2-8 as shown in Figure 7 (on next page).

Power Reset: This control does not automatically reset power to 4-wire smoke detector zones, so you must use a relay (e.g., 4204, 4229), or on-board trigger to reset power (also required for fire verification). Do this by programming the designated relay/trigger as zone type 54 (fire zone reset); see On-Board Trigger section for other information.

NOTE: Maximum current on trigger 17 is 100mA.

2-6

 

 

Mounting and Wiring the Control

 

 

 

 

 

Smoke Detector Notes

Fire Verification (zone type 16): The control panel will “verify” a fire alarm by

 

 

resetting the smoke detectors after the first alarm trigger, and then waiting 90 seconds

 

 

for a second alarm trigger. If the smoke detector or thermostat does not trigger again,

 

 

the control will disregard the first trigger, and no alarm signal will occur. This feature

 

 

eliminates false alarms due to electrical or physical transients.

 

 

SIA Installations: If using fire verification on zones other than zone 1, UL Fire Alarm

 

 

Listed relay accessories must be used to reset power as described in the Power Reset

 

 

paragraph above.

The zone 1 alarm current supports only one smoke detector in the alarmed state.

Clean Me Option: If enabled (field *174 = 1; *56 zone programming, response time prompt = 3), certain ESL smoke detectors send “clean me” reports as appropriate. If used, the maximum number of detectors is reduced to 10 (not standard 16). Refer to the ESL documentation included with the smoke detector for information regarding compatibility with the clean-me option.

Do not use 4-wire smoke detectors on zone 1.

+

5

 

 

 

 

 

 

RELAY

 

 

 

AUX PWR

PROGRAM

 

BLK

+

RED

RELAY

 

 

 

 

OUTPUT

AS ZONE

 

 

 

EOL

TERMINALS

TYPE 54

 

 

 

 

 

 

POWER

 

(FIRE ZONE

 

 

N.O.

SUPERVISION

 

RESET)

 

 

 

 

 

 

RELAY MODULE

 

4

 

 

 

 

N.C.

 

 

A77-716B.

 

 

 

 

CONTACT OPENS

 

 

 

USE N.O.

 

 

 

CONTACT,

MOMENTARILY UPON

+

 

 

 

VIOLET

WHICH CLOSES

FIRE ALARM RESET

 

 

 

 

 

4-WIRE SMOKE

 

 

WHEN POWER

 

 

 

 

IS APPLIED.

 

 

OR COMBUSTION

 

 

 

 

DETECTOR

2000

 

 

 

 

 

 

 

 

 

 

OHMS

 

 

 

 

 

EOLR

 

 

TO ZONE TERM. (+)

 

 

 

-V0

 

 

 

-007

 

 

HEAT

 

 

TO ZONE TERM. ( )

 

 

wiresmk

 

 

 

 

DETECTOR

 

 

 

 

 

 

 

 

4

Figure 9a. 4-Wire Smoke Detector Using Relay for Power Reset

AUX PWR (+)

5

 

 

 

TO OUTPUT 17 ( )

 

BLK

+

RED

 

 

 

 

PROGRAM OUTPUT 17

 

 

 

EOL

FOR "OUT NORM

 

 

 

POWER

LOW" = YES IN 79 MENU

+

 

N.O.

SUPERVISION

MODE AND AS ZONE

 

RELAY MODULE

 

 

VIOLET

TYPE 54 IN

4-WIRE SMOKE

 

A77-716B.

80 MENU MODE

OR COMBUSTION

 

 

USE N.O.

 

DETECTOR

2000

 

CONTACT,

 

 

 

 

 

OHMS

 

WHICH CLOSES

 

 

EOLR

 

WHEN POWER

TO ZONE TERM. (+)

 

 

 

IS APPLIED.

 

 

 

 

 

HEAT

 

 

 

 

DETECTOR

 

 

 

TO ZONE TERM. ( )

 

 

 

 

4_wiresmk-008-V0

 

 

Figure 9b. 4-Wire Smoke Detector Using Output 17 for Power Reset

4219/4229 Expansion

1.

Connect each module to the control’s keypad terminals and set the device addresses.

Zones

 

• VISTA-20P: Up to 40 expansion zones using up to 5 Zone Exp. Modules.

 

 

• VISTA-15P: Up to 16 expansion zones using up to 2 Zone Exp. Modules.

 

2.

Connect sensors to the module’s loops. See Figure 8 on the following page.

 

 

• Use 1000 ohm end-of-line resistors at the end of loops connected to the 4219/4229

 

 

modules. (EOLRs used on the control terminals are 2000 ohms.)

 

 

Expansion zones have normal response time (300–500 msec), except zone connected

 

 

to each module’s loop “A,” which can be set for fast response (10–15 msec).

 

3.

If using relays with the 4229, connect the desired field wiring to the unit's relay contact

 

 

terminals.

2-7

Installation and Setup Guide

 

RELAY

RELAY

 

 

 

 

 

 

 

 

 

 

4229

 

 

 

 

 

CONNECTOR

2

 

 

DIP SWITCH

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FOR SETTING ADDRESS

 

 

EITHER OR BOTH CAN BE USED

 

 

TERMINALS ON

 

 

 

 

 

AND ZONE "A" RESPONSE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CONTROL PANEL

 

 

 

RELAY

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

 

 

 

 

 

 

 

 

 

 

TB2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NO C

NC

 

 

 

 

 

 

 

4-PIN CONSOLE PLUG

4

GRN

DATA OUT (>)

(TERM 6)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TAMPER JUMPER POSITION

 

 

 

 

 

 

 

TO CONTROL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BLK

 

 

 

 

 

 

4229 IN CABINET

 

 

 

 

 

 

 

4

3

(–) GROUND

 

(TERM 4)

WHT

GRY VIO BLK YEL ORG

BRN

(NOT TAMPER)

 

 

 

 

 

 

 

 

 

 

 

 

 

4229 REMOTE

 

 

 

 

 

 

 

 

3

2

RED

(+) 12VDC

 

(TERM 5)

 

 

 

(TAMPER PROTECTED)

 

 

 

 

TB1

2

 

 

DATA IN (<)

 

 

 

NO NC C GND NO NC C

 

 

 

 

 

 

 

 

 

 

 

YEL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

1

FROM

 

(TERM 7)

 

1

2

3

4

5

6

7

8

9

10

11

 

 

 

 

 

12

 

 

CONTROL

 

 

RLY

RLY

 

 

 

 

TERMINATE EACH

 

 

 

 

PROGRAMMED ZONE

2

1

REED

 

 

 

 

 

 

WITH 1000 OHM (1K)

RELAYS OFF

(TAMPER)

 

 

 

END-OF-LINE RESISTOR

SWITCH

 

 

 

(EACH ZONE'S MAX.

 

 

 

 

 

LOOP RESISTANCE

 

 

 

 

 

 

 

 

ZONES A B

C D

E F

G H

300 OHMS + EOL)

 

 

4229-002-V0

Figure 10. Wiring Connections, 4219 & 4229 (4229 shown)

Installing the RF Receiver and Wireless Transmitter Zones

Compatible Receivers

Use any ADEMCO 5800 Series Wireless Receivers, such as:

 

 

RF Receiver

No. of Zones

 

 

5881L/5882L

up to 8

 

 

 

 

5881M/5882M

up to 16

 

 

 

 

5881H/5882H,

VISTA-20P

= up to 40 plus 16 buttons

 

 

5883, 6150RF

VISTA-15P

= up to 26 plus 8 buttons

Receiver Connections

1. Set Device Address to “00” (set all switches to the right, “off” position).

2.Mount the receiver, noting that the RF receiver can detect signals from transmitters within a nominal range of 200 feet.

3.Connect the receiver's wire harness to the control's keypad terminals. Plug the connector at the other end of the harness into the receiver. Refer to the installation instructions provided with the receiver for further installation procedures regarding antenna mounting, etc.

WIRELESS ZONE NUMBERS

VISTA-20P: transmitter zones 9-48 button zones 49-64

VISTA-15P: transmitter zones 9-34 button zones 49-56

NOTE

CIRCUIT BOARD IS MOUNTED IN CONTROL'S CABINET. GROUNDING LUGS (2) PROVIDED MUST BE INSERTED IN LEFT-HAND TERMINALS OF ANTENNA BLOCKS AND SECURED TO CABINET. (SEE RECEIVER'S AND CONTROL'S INSTRUCTIONS)

MOUNTING

HOLES

 

ANTENNAS

 

 

 

(INSERT IN

 

 

 

RIGHT-HAND

 

 

 

TERMINALS)

 

 

 

INSERT IN

 

 

 

RIGHTHAND

 

 

 

TERMINALS

 

 

 

 

YELLOW

 

 

RED

TO CONTROL'S

 

 

REMOTE KEYPAD

MODEL NO. IS INDICATED ON CIRCUIT BOARD

BLACK

 

 

CONNECTION

 

 

GREEN

5882

DIP

POINTS.

 

LOCATION

SWITCH

 

 

INTERFERENCE

 

WIRING OPENING

INDICATOR

 

 

 

LED

 

KNOCKOUT AREA

 

 

 

CIRCUIT BOARD

 

FOR SURFACE WIRING

 

 

SOCKET

PLUG

TO RELEASE CIRCUIT BOARD,

 

REMOVE SCREWS AND

 

BEND BACK TABS

5881-003-V0

 

 

Figure 11. 5881/5882 RF Receiver (cover removed)

RF Receiver Notes

Set the following options:

 

*22

RF Jam Option†

These fields must be

*24

RF House ID Code (if using wireless keypads) for each partition

enabled for Residential Fire,

*67

Transmitter Low Battery Report Code†

UL Residential Burglar

*75

Transmitter Low battery restore report code†

Alarm, and UL Commercial

• The receiver is supervised and a trouble report is sent (“CHECK 100” displayed) if

Burglar Alarm installations.

 

communication between the panel and receiver is interrupted, or if no valid RF signals

 

 

from at least one supervised transmitter are received within 12 hours.

 

If the receiver is mounted remotely:

 

• Place the RF receiver in a high, centrally located area for best reception.

 

• Do not locate the receiver or transmitters on or near metal objects. This will decrease

 

range and/or block transmissions.

 

• Do not locate the RF receiver in an area of high RF interference (indicated by frequent

 

or prolonged lighting of the LED in the receiver; random flicker is OK).

 

• Do not locate RF receiver closer than 10 feet from any keypads to avoid interference

 

from the microprocessors in those units.

2-8

 

 

 

Mounting and Wiring the Control

 

 

 

 

 

 

Installing a 5800TM

• Use this module only if you are using one or more wireless bi-directional keypads or

 

Module

keyfobs with a wireless Receiver; 5800TM is not necessary if using a Transceiver (e.g.,

 

 

 

5883).

 

 

 

 

• The 5800TM must be set to address 28 (cut red-W1 jumper).

 

 

 

• The 5800TM can be used in partition 1 only.

 

 

 

• For additional information regarding the 5800TM, refer to the 5800TM’s instructions.

 

 

 

1. Mount the 5800TM next to the RF receiver (between one and two feet from the

 

 

 

receiver’s antennas) using its accompanying mounting bracket. Do not install within

 

 

 

the control cabinet.

 

 

 

2. Connect the 5800TM to the control panel’s keypad connection terminals as shown on

 

 

 

the Summary of Connections diagram and set to address 28.

 

Installing the

• Refer to the table of compatible devices at the back of this manual.

 

Transmitters

• Supervised transmitters† send check-in signals to the receiver at 70-90 minute

 

 

 

intervals. If at least one check-in message is not received from each transmitter within

 

 

 

a 12-hour period, the “missing” transmitter number(s) and “CHECK” is displayed. (†

 

 

 

Hand-held transmitters, e.g., 5802, 5802CP, 5804, 5804BD, 5827, 5827BD, do not send

 

 

 

 

 

 

check-in signals.)

 

 

 

 

 

 

• To be sure reception of the transmitter's signal at the proposed mounting location is

 

 

 

adequate, perform a Go/No Go Test, described in the Testing the System section.

 

 

 

• Install transmitters in accordance with the instructions provided with each.

 

 

 

• Set 5827, 5827BD, 5804BD wireless keypads to the programmed House ID (field *24),

 

 

 

using its DIP switches (5827) or follow the instructions provided with the device.

 

 

 

• Use *56 or *58 Zone Programming Menu modes to program zone information and enroll

 

 

 

transmitters (VISTA-20P: zones 9-48, buttons 49-64; VISTA-15P: zones 9-34, buttons

 

 

 

49-56).

 

 

 

 

Wireless Keys: Use Wireless Key Programming Templates section of the *58 Zone

 

 

 

Programming Menu mode to program zone information and enroll each button of the

 

 

 

wireless keys used. Once a wireless key is enrolled, it must be assigned to a user before

 

 

 

it becomes active. See Adding/Deleting Security Codes section for procedure.

 

 

 

 

 

 

 

 

ULC NOTE: In accordance with ULC standards, the RF supervision period for the VISTA-20PCN

 

 

 

 

and VISTA-15PCN is three hours for Fire zones (Zone Type 9 and 16) and 12 hours for all other zone

 

 

 

 

types.

 

 

 

 

 

 

 

 

UL The following transmitters are not intended for use in UL installations: 5802MN, 5802MN2, 5804,

 

 

 

 

5804BD, 5814, 5816TEMP, 5819, 5819WHS & BRS, and 5850.

 

 

 

 

The 5827BD and 5800TM can be used in UL Listed Residential Burglar installations.

 

 

 

 

 

Transmitter Battery Life

• See Wireless Transmitter paragraph in the Limitations of This Alarm System

 

 

 

statement located at the end of this manual for information on transmitter battery

 

 

 

life.

 

 

 

• Some transmitters (e.g., 5802 and 5802CP) contain long-life but non-replaceable

 

 

 

batteries, and no battery installation is required. At the end of their life, the complete

 

 

 

unit must be replaced (and a new serial number enrolled by the control).

 

 

 

• Button-type transmitters (such as 5801, 5802, and 5802CP) should be periodically

 

 

 

tested for battery life.

 

 

 

• The 5802MN and 5804 Button Transmitters have replaceable batteries.

 

 

 

Do not install batteries in wireless transmitters until you are ready to enroll during

 

 

 

system programming. After enrolling, batteries need not be removed.

2-9

Installation and Setup Guide

Installing a Keyswitch

Keyswitch Connections

GREEN

RED

1.Connect the 4146 keyswitch's normally open momentary switch to a zone’s (2-8) terminals. Remove the 2000 ohm EOL resistor if connected across the selected zone.

2.Using a standard keypad cable as shown:

Connect the yellow and white keyswitch wires to trigger connector pin 3 (+12V). Connect the Red and Green LED wires to the appropriate output 17/output 18 trigger connector pins.

3.Connect a 2000 ohm EOL resistor across the momentary switch.

4.You can wire an optional closed-circuit tamper switch (model 112) in series with the zone. If the switchplate is then removed from the wall, the tamper will open, disabling keyswitch operation until the system is next disarmed from the keypad.

If the tamper is opened when the system is armed, an alarm will occur.

8-PIN TRIGGER CONNECTOR

1

KEY

3

4

5

6

7

8

 

 

 

 

 

 

 

(YELLOW)

(RED)

(GREEN)

OUTPUT 17

+12 AUX.

OUTPUT 18

11

TYPICAL ZONE

ON CONTROL

BOARD

10

STANDARD

4146 KEYSWITCH

KEYPAD

CABLE (ARMED) RED

YELLOW

(READY) GREEN

WHITE

 

820

820

ohms

ohms

BLACK

 

RED

 

TAMPER

 

SWITCH (N. C.)

BROWN

BROWN

LOCK

 

SWITCH (N. O.)

BLUE

BLUE

EOLR

(use appropriate value)

00-trigcon-004-V1

Figure 12. Keyswitch Wiring Connections

Keyswitch Notes

UL A UL Listed keyswitch is required for fire installations and UL commercial and residential burglar alarm installations. The Ademco 4146 keyswitch is UL Listed.

If a keyswitch is used on:

an installation that transmits opening and closing signals, the keyswitch zone must be programmed to send opening and closing signals.

a UL commercial burglar alarm installation, the keyswitch’s tamper switch must be connected in to the alarm system. This tamper switch zone must also be programmed for Zone Type 05 – Trouble by Day / Alarm by Night.

a fire alarm installation, the keyswitch must be located next to an alphanumeric display keypad.

Use 4146 keyswitch or any N.O. keyswitch.

Use only one keyswitch per partition.

When using a keyswitch, the zone it is connected to is no longer available for use as a protective zone.

Use *56 Menu mode to program the keyswitch zone and assign it zone type 77.

Use *80 Menu mode to program the LED functions: program outputs 17 and 18 for system operation zone type 78 (red LED) and 79 (green LED) as appropriate (see

Output Device Programming section).

2-10

Mounting and Wiring the Control

Connecting Relay Modules, Powerline Carrier Devices and Output Triggers

4204/4229 Relay Modules

UL For UL installation requirements, refer to the Installation Instructions for the 4204.

Powerline Carrier

Devices

UL Powerline Carrier devices and the 1361X10 Transformer are not UL Listed for fire or burglary functions and are intended for home automation.

1.Mount either remotely or in the control panel.

2.Connect each module to the control’s keypad terminals and set the device addresses as previously described in the Connecting Keypads and Other Addressable Device section. Use the connector harness supplied with the module. Use standard 4-conductor twisted cable for long wiring runs.

VISTA-20P: Up to 16 relays (if no powerline carrier devices are used) VISTA-15P: Up to 8 relays (if no powerline carrier devices are used)

3.Connect the desired field wiring to the unit's relay contact terminals.

4204

RELAY

12

C

DIP SWITCH

4

11

NC

TYPICAL

10

 

FOR SETTING DEVICE ADDRESS

NO

(SHOWN "OFF")

AND ENABLING/DISABLING TAMPER

RELAY

9

C

 

 

COVER TAMPER (REED) SWITCH

3

8

NC

7

NO

 

 

 

 

 

4-PIN TOUCHPAD PLUG

RELAY

6

C

 

 

2

5

NC

EITHER OR BOTH

 

4

NO

CAN BE USED

RELAY

3

C

 

 

TB1

1

2

NC

 

 

13 14 15 16

 

1

NO

 

 

YEL

DATA IN

 

TB2

 

FROM CONTROL

 

 

BLK

(–) GROUND

 

 

 

 

 

GRN

DATA OUT

 

 

RED

TO CONTROL

 

 

(+) 12V

4204_conn-1-V0

 

Figure 13. 4204 Connections to Control

Supervision: 4204 and 4229 modules are supervised against removal. The module’s device address is displayed as follows if a module is disconnected from the control’s terminals, or if the module cover is removed and the tamper jumper is installed:

Alpha: CHECK xx Wire Expansion FAULT xx Wire Expansion ALARM xx Wire Expansion

Fixed-Glass: lxx (or 91 if field *199 set for 2-digit display) where “xx is the module’s address.

If communication/tamper failure occurs on a device with zones wired to it, all zones on the device will be displayed in their respective partitions.

1.Install the powerline carrier devices according to the instructions included with each. VISTA-20P: Up to 16 devices (if no relays are used)

VISTA-15P: Up to 8 devices (if no relays are used)

2.Use Programming Mode to enter the device house ID in data field*27, and enter the unit code using *79 Output Device menu Mode.

3.See connections diagram in the AC Wiring section for connecting the 1361X10 transformer to the triggers.

You must use a 1361X10 Transformer instead of the 1321 Transformer.

The 1361X10 Transformer provides AC power to the control panel, and also supplies signals from the control panel through the premises AC wiring to the Powerline Carrier devices (which are plugged into AC outlets). You can then make devices that are plugged into Powerline Carrier devices perform various functions in response to commands you enter at the security system keypads.

Canada: Use the PSC04 Powerline Interface as shown below.

8-PIN TRIGGER CONNECTOR

1

KEY

3

4

5

6

7

8

 

 

 

 

 

 

 

(RED)

 

(ORANGE)

(YELLOW)

(GREEN)

(BLUE)

(PURPLE)

(BLACK)

OUTPUT 17

 

+12 AUX.

GND (-)

OUTPUT 18

DATA

COM

SYNC

 

 

 

 

 

 

 

SA4120XM-1 CABLE

 

 

 

 

 

 

 

SYNC

 

 

 

 

 

 

 

BLK

 

 

 

 

 

 

 

GRN

 

 

 

 

 

 

 

COM

 

 

 

 

 

 

 

RED

 

 

 

 

 

 

 

DATA

 

 

 

 

 

 

 

YEL

X-10 PSC04

POWERLINE INTERFACE

1 2 3 4

MODULAR PHONE CORD (not supplied)

1 - BLACK

2 - RED

3 - GREEN

4 - YELLOW

Figure 14. PSC04 Powerline Interface Connections

2-11

Installation and Setup Guide

On-Board Triggers

Connect field wiring to the desired trigger pin on the 8-pin trigger connector centrally

 

located above the terminal strip.

 

If using 1361X10 transformer and powerline carrier devices, use the SA4120XM-1

 

 

cable (part of 4120TR Trigger Cable). See Wiring the AC Transformer section for

 

transformer connections.

 

If only using the on-board triggers, you can use a 4-wire cable (N4632-4, supplied

with the control) as shown below.

 

 

 

 

 

 

 

8-PIN TRIGGER CONNECTOR

8-PIN TRIGGER CONNECTOR

 

 

 

 

 

 

 

 

KEY

 

 

 

 

 

1

KEY

3

4

5

6

7

8

1

3

4

5

6

7

8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OUTPUT 17 (RED)

+12 AUX. (ORANGE)

GND (-) (YELLOW)

OUTPUT 18 (GREEN)

(BLUE)

(PURPLE)

SYNC (BLACK)

OUTPUT 17 (YELLOW)

(RED)

(BLACK)

(GREEN)

DATA

COM

+12 AUX.

GND (-)

OUTPUT 18

 

 

 

 

 

 

 

SA412OXM-1

 

 

 

 

 

 

 

 

 

 

CABLE

 

 

 

 

 

 

 

 

 

 

00-trigcon-003-V1

 

 

 

4-WIRE CABLE

00-trigcon-005-V2

Figure 15a. On-Board Trigger Connector with SA4120XM-1 Cable for Use With 1361X10 Transformer

Figure 15b. On-Board Trigger Connector with 4-Wire Cable for Trigger Use Only

Trigger outputs are normally high, and go low upon programmed condition.

The outputs can be programmed for inverted operation (normally low, go high) using *79 Menu mode.

Program these triggers using *80/*81 Menu modes as you would for any other relay output.

When using these outputs, note:

pin 1 = output number 17 (trigger 1):

15 ohms to ground when closed (output low), open when off (output high, normal default); can be used to reset smoke detector power (must set “output normal low = yes” in *79 Menu mode, and set for zone type 54, fire zone reset, in *80 Menu mode); or can support 12V relay module (e.g., Altronix AX-RBS) that draws less than 100mA

pin 5 = output number 18 (trigger 2):

100 ohms to ground when closed (output low); open when off (output high, normal default); or can support 12V relay module that draws less than 20mA

UL If on-board triggers are used, the wiring between the control unit and the UL Listed device must be run in conduit, be no more than 3 feet apart and have no intervening barriers or walls.

2-12

Mounting and Wiring the Control

Phone Line/Phone Module, and Audio Alarm Verification (AAV) Connections

Phone Line

4285/4286 Phone Module

Compatibility: 4286 Phone Modules must have software version WA428615.1 or higher (refer to the label on the square 4286 microprocessor chip).

UL The 4285 and 4286 modules are UL Listed only for use on residential fire and UL residential burglar alarm installations.

Connect incoming phone line and handset wiring to the main terminal block (via an RJ31X jack) as shown in the Summary of Connections diagram at the back of this manual.

Wire colors represent the colors of the cable to the RJ31X jack.

1.Make 12V (+) and (–) and data in and data out connections from the phone module to the control, using the connector cable supplied with the phone module, then insert the keyed connector at the other end of the connector cable into the header on the phone module.

2.Connect Phone Module terminals as shown below. Use an RJ31X jack with a directconnect cord and make all connections exactly as shown.

3.Caller ID Units: If a Caller ID unit is being used, connect the unit directly to the “Handset” terminals (21 & 22) on the control, as shown.

INCOMING

 

GROUND

HANDSET TELCO LINE

 

 

{ {

 

 

TERMINALS

 

ON CONTROL

 

21

22

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CALLER ID

 

 

 

 

 

 

 

 

UNIT

 

 

 

 

 

 

 

 

 

 

 

 

 

(RING)

IMPORTANT NOTE FOR

 

(TIP)

EXISTING INSTALLATIONS:

 

EXISTING WIRES

 

 

 

 

 

 

CONNECTED TO THE

 

 

 

 

 

 

"HANDSET" TERMINALS ON

 

 

 

 

 

 

CONTROL MUST BE MOVED

 

 

 

 

 

 

FROM THERE TO TERMINALS

 

 

 

 

 

 

3 AND 4 ON THE 4285/4286.

 

 

 

 

 

 

4285/4286

7

VIP MODULE

5 6

LOUDER

 

1 2 3 4

VOLUME

 

 

(4286

KEYED

 

ONLY)

HEADER

 

 

 

UNUSED

 

 

 

YELLOW: TO DATA OUT (term. 7)

 

NO CONNECTION

CONNECTOR

RED:

TO AUX (+) (term. 5)

WITH FLYING

BLACK:

TO AUX. GROUND (–) (term.4)

LEADS

GREEN:

TO DATA IN (term. 6)

23

24

25

TO EARTH GROUND (COLD WATER PIPE, ETC.)

(TIP)GREEN

(RING)RED

 

RJ31XRING

INCOMING TELCO LINE

 

 

 

 

DIRECT

TIP

 

 

 

 

 

 

 

CONNECT

 

 

 

 

CORD

 

TIP

 

 

 

 

 

 

 

JACK

RING

 

 

 

 

 

 

 

CA38A

PREMISES ANSWERING

 

 

PLUG

IN

 

 

MACHINE AND PHONES

 

 

CANADA

 

 

 

 

(R)GREY

BROWN(T)

 

 

ANSWERING

 

 

MACHINE

 

 

 

 

 

 

 

 

*

 

 

 

 

*

* NOTE: IF THE TELEPHONE HAS BUILT-IN CALLER ID, THE CALLER ID FUNCTION MAY NOT WORK .

 

 

 

 

4285/4286

TO CONTROL

 

 

 

TERMINAL ASSIGNMENTS

PANEL

1 - TIP

TERMINALS

2 - RING } PHONE INPUT

USED FOR

3

- TIP

4

- RING } PHONE OUTPUT

KEYPAD

5

- NO CONNECTION

CONNECTIONS

6

-

AUDIO OUT

 

 

7

-

} 4286 ONLY

4286_cntrl-001-V0

Figure 16. 4285/4286 Phone Module Wiring Connections

Only one phone module can be used and it can only be connected to partition 1.

The phone lines must be in service for the phone module to function, even when accessing the system from an on-premises phone.

If you are also using an Audio Alarm Verification (AAV) unit, refer to Audio Alarm Verification (AAV) section for special wiring connections.

CAUTION: To reduce the risk of fire, use only No. 26 AWG or larger telecommunication line cord for phone line connections.

Phone Module Problems If no touch tones are produced following access to the security system from on-premises (this problem may arise in rare cases), it may be necessary to reverse the wires connected to terminals 3 and 4 on the phone module and the wires connected to terminals (21) & (22) on the control. The wiring diagram shows the wiring connections that will provide proper operation in most cases.

Connection to the incoming telco line via a RJ31X jack and direct-connect cord, as shown, is essential, even if the system is not connected to a central station. The 4285 or 4286 will not function if this is not done and an error signal (fast busy signal) will occur when trying to access the system via the phone.

The house phone lines (gray and brown wires) must be wired to the phone module terminals; not to the control terminals. Otherwise, an error signal (fast busy signal) will occur when trying to access the system from an on-premises phone.

2-13

Honeywell K5305-1V5, VISTA 20P, VISTA-20PSIA, VISTA-15P, VISTA-15PSIA User Manual

Installation and Setup Guide

Audio Alarm Verification Connections

(AAV, “listen-In”)

Refer to the connection diagrams below. One diagram shows connections when a 4285/4286 Phone Module is used, the other shows connections when the 4285/4286 is not used.

Connections use one of the on-board triggers.

Set field *91 for AAV and program the appropriate output (output 17 or 18) using *80 Menu mode: select zone type 60 and output action 1 (close for 2 seconds) or action 2 (stay closed).

For voice session monitoring, connect an EOLR zone to UVCM module terminals 6 & 7, and program the zone as zone type 81 (*56 Menu mode).

E.g., Using output 18 for the trigger, program an output function in *80 Menu mode as: ZT = 60, P = 0, Action = 1, Device = 18

Suggested AAV Module: ADEMCO UVS (shown) or Eagle 1250

UL UL installations using the AAV feature must use the ADEMCO UVCM module (part of the ADEMCO UVS system).

 

 

 

 

 

 

 

 

5

TRIGGER

 

 

 

 

 

 

 

 

 

 

 

 

 

CONNECTOR

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

18

 

ZONE

 

 

 

 

EARTH

 

 

 

 

 

 

CONTROL

OUTPUT

 

 

 

 

 

GROUND

 

 

 

 

 

 

 

 

TERMINALS

 

 

 

 

 

 

 

 

AUXILIARY

4

5

 

21

22

23

24

25

 

 

 

 

AUDIO LEVEL

 

 

 

 

 

 

 

 

 

 

 

 

ADJUSTMENT

GND

+12VDC

 

 

 

 

 

 

 

 

 

 

 

TRIM POT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

EOL

 

 

 

 

 

 

 

UVCM

 

 

 

34

 

 

RING

 

 

 

 

 

 

 

MODULE

 

 

 

TIP

 

 

 

 

 

 

 

 

33

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RED (R)

 

 

 

 

 

 

 

32

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

31

 

 

 

 

 

 

GREEN (T)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RJ31X

 

 

 

 

 

 

30

 

 

 

 

 

 

GREY (R)

 

 

 

 

 

 

 

 

 

 

 

 

 

NOTE:

 

 

 

 

 

29

 

 

 

 

 

 

BROWN (T)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

REFER TO UVCM MODULE

 

 

 

 

 

 

 

 

 

 

 

 

 

INSTRUCTIONS FOR

 

 

 

 

 

 

 

 

 

 

 

 

 

CONNECTIONS TO AUDIO

 

 

 

 

11

 

 

OPTIONAL

 

 

 

 

 

SPEAKERS AND MICROPHONE.

 

 

 

 

 

 

 

 

 

 

 

 

765 8

BANK2

 

 

 

 

MONITORING ZONE

 

 

 

 

 

 

 

 

910

 

 

 

 

 

 

 

 

 

 

 

 

CONNECTION

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(USE ZONE TYPE 81)

 

 

 

 

2 = OFF

2 = ON

ON

4321

SWITCH

 

876

 

 

 

 

 

 

TO

INCOMING

SWITCH

SWITCH

 

 

 

 

 

 

 

 

 

 

 

PREMISES

 

BANK 1

BANK 2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HANDSET

 

1 = OFF

1 = ON

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3 = OFF

3 = OFF

 

 

 

FALLING VOICE TRIG

5

 

 

 

 

 

 

 

PHONE LINE

4 = OFF

4 = ON

 

8

1

 

 

 

 

 

 

 

 

5 = OFF

5 = ON

ON

6543217

BANKSWITCH

 

4321

 

 

 

 

 

 

 

003V0-

6 = OFF

6 = ON

 

 

 

 

 

 

 

 

 

 

 

 

 

7 = OFF

7 = ON

 

 

 

 

 

 

 

 

 

 

 

 

 

8 = ON

8 = ON

 

 

 

GND

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

+12VDC IN

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

aav uvcm-

Figure 17a. Connection of AAV Unit When Not Using a 4285/4286 Phone Module

NOTE:

REFER TO UVCM MODULE INSTRUCTIONS FOR CONNECTIONS TO AUDIO SPEAKERS AND MICROPHONE.

SWITCH

SWITCH

BANK 1

BANK 2

1

= OFF

1

= ON

2

= OFF

2

= ON

3

= OFF

3

= OFF

4

= OFF

4

= ON

5

= OFF

5

= ON

6

= OFF

6

= ON

7

= OFF

7

= ON

8

= ON

8

= ON

Figure 17b.

 

 

 

 

5

TRIGGER

 

 

 

 

 

 

 

 

 

CONNECTOR

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

18

 

ZONE

 

 

 

 

EARTH

 

CONTROL

 

OUTPUT

 

 

 

 

 

GROUND

 

 

 

 

TERMINALS

 

 

 

 

 

AUXILIARY

4

 

5

 

 

21

22

23

24

25

AUDIO LEVEL

 

 

 

 

 

 

 

 

 

 

ADJUSTMENT

GND

+12VDC

 

 

 

 

 

 

 

 

TRIM POT

 

 

 

 

 

 

 

 

 

 

 

 

 

EOL

 

 

 

 

 

UVCM MODULE

 

 

 

 

8

2

 

 

 

 

5 6 7

BANK

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1 2 3 4

SWITCH

 

 

 

 

 

 

 

 

 

 

 

 

ON

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

8

1

 

 

 

 

5 6 7

BANK

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SWITCH

 

 

 

 

1 2 34

 

 

 

 

 

 

 

 

 

 

 

 

ON

 

 

 

 

 

 

RING

34

TIP

33

 

32

 

31

 

30

 

29

 

11

 

10

 

9

 

8

 

7

 

6

FALLING VOICE TRIG

5

 

4

 

3

GND

2

 

+12VDC IN

1

RING

TIP

OPTIONAL MONITORING ZONE CONNECTION (USE ZONE TYPE 81)

4285/4286

4

3

2

1

RED (R)

 

GREEN (T)

 

GREY (R)

RJ31X

BROWN (T)

 

TO

PREMISES

HANDSET

INCOMING

PHONE LINE

aav_uvcm-004-V0

Connection of AAV Unit When Using a 4285 or 4286 Phone Module

2-14

S E C T I O N 3

Programming Overview

About Programming

You can program the system at any time, even at the installer's premises prior to the actual installation.

Programming can also be performed remotely from the installer’s office/home, using an IBM personal computer, a modem, and Compass downloading software.

The following is a list of the various Programming modes used to program this system.

Programming Mode…

Used to …

Data Field Programming

Program basic data fields used for setting the various system options.

 

Most of the data fields in this system have been programmed for specific default

 

values. However, some fields must be programmed for each particular installation to

 

establish its specific alarm and reporting features.

56 Zone Programming

Assign zone characteristics, report codes, alpha descriptors, and serial numbers for

 

5800 RF transmitters. See *56 Zone Programming in Section 5. Menu Mode

 

Programming for procedures for programming zones.

57 Function Key

Program each of the four alphabet function keys to perform one of several system

Programming

operations.

58 Zone Programming

Similar to 56 mode, but provides a faster programming procedure and is intended for

(Expert Mode)

those more experienced in programming controls of this type.

79 Output Device Mapping

Assign device addresses used by 4229 or 4204 Relay modules and map specific relays

 

and device outputs, and assign unit codes for Powerline Carrier devices.

 

See About Output Device Programming in Section 5. Menu Mode

 

Programming for details on setting devices for manual/automatic operation.

80 Output Definitions

Define up to 48 output definitions which can control the output relays mapped using

 

*79 Output Device Mapping mode.

81 Zone List Programming

Create Zone Lists for relay/powerline carrier zones, chime, night-stay, cross zones,

 

and pager zones.

82 Alpha Programming

Create alpha descriptors for easy zone identification.

Scheduling Mode

Create schedules to automate various system functions.

(code + [#] +64)

 

Mechanics of Programming

To program the system from a keypad:

You must use a 2-line Alpha display keypad.

Both partitions must be disarmed.

Data Field Programming Procedures

Task

Procedure

Entering Program Mode

A) Press both [ ] and [#] at the same time within 50 seconds after power is applied,

 

OR

 

B) After power-up, enter [Installer code (4-1-1-2)] + 8 0 0 (long beep indicates one of the

 

partitions is armed and system cannot enter program mode).

 

(method “B” is disabled if you exit Program mode using 98)

Go to a Data Field

Press [ ] + [Field Number]. A display of “EE” or “Entry Error” means you have entered a

 

nonexistent field. Simply re-enter [ ] plus a valid field number.

Entering Data

When the desired field number appears, simply enter the digits required. The keypad

 

beeps three times after the last digit is entered and automatically displays the next data

 

field in sequence.

 

If entering less than the maximum digits available (e.g., phone number field), enter the

 

desired digits, then press [ ] to end the entry.

Review a Data Field

Press [#] + [Field Number]. The field’s data is displayed, but no changes can be made.

Deleting an Entry

Press [ ] + [Field No.] + [ ] (applies only to phone number, account number, and pager

 

character fields).

3-1

To Initialize Download ID

Installation and Setup Guide

Interactive Mode Programming ( 56, *57, 58, 79, 80, 81, 82)

Entering Interactive Mode Press [ ] + [Interactive Mode No.] (for example, 56) while in Program Mode. The Alpha display keypad will display the first of a series of prompts.

After making the appropriate entry, press the [ ] key to accept the entry and continue to the next prompt.

Loading Factory Defaults/Initializing for Download

To Load Default Entries Press 97 while in Program Mode. This resets all data fields to the default values shown on the Program Form. Use 97 only if you wish to return to the original factoryprogrammed defaults.

Press 96 while in Program Mode. This initializes the system for downloading and resets all the subscriber account numbers and CSID.

Do not press 97 to load defaults if any programming has been done previously—data already programmed into the system will be changed!

Exiting the Programming Mode

Prevent installer code

Press 98. Exits Programming Mode and prevents re-entry by:

reentry

Installer Code + [8] + [0] + [0]. To enter the programming mode if 98 was used to exit,

 

you must first power the system down. Then power up again, and press [ ] and [#] at the

 

same time, within 50 seconds of powering up.

 

See field *88 for other Program mode lockout options.

Allow installer code

Press 99. Exits Programming Mode and allows re-entry by:

reentry

Installer Code + [ 8] + [0] + [0] or by: Pressing [ ] and [#] at the same time, within 50

 

seconds of power-up.

Zone Type Definitions

Zone types define the way in which the system responds to faults in each zone.

Zone Type

Description

Type 00

Program a zone with this zone type if the zone is not used.

Zone Not Used

 

Type 01

• Assign to zones that are used for primary entry and exit.

Entry/Exit

• Provides entry delay when zone is faulted if control is armed in the Away, Stay, or Night-Stay

Burglary #1

modes.

 

• No entry delay provided when the panel is armed in the Instant/Maximum mode.

 

• Entry delay #1 is programmable for each partition (field *35).

 

• Exit delay begins whenever the control is armed, regardless of the arming mode selected, and

 

is programmable (field 34).

Type 02

• Assign to zones that are used for entry and exit and require more time than the primary

Entry/Exit

entry/exit point.

Burglary #2

• Provides a secondary entry delay, in same manner as entry delay #1.

 

• Entry delay #2 is programmable for each partition (field *36).

 

• Exit delay is same as described for Type 01.

Type 03

• Assign to all sensors or contacts on exterior doors and windows.

Perimeter

• Provides an instant alarm if the zone is faulted when the panel is armed in the Away, Stay,

Burglary

Night-Stay, Instant or Maximum modes.

 

 

Type 04

• Assign to a zone covering an area such as a foyer, lobby, or hallway through which one must

Interior Follower

pass upon entry (to and from the keypad).

 

• Provides a delayed alarm (using the programmed entry 1 time) if the entry/exit zone is faulted

 

first. Otherwise this zone type gives an instant alarm.

 

• Active when the panel is armed in the Away mode.

 

• Bypassed automatically when the panel is armed in the Stay or Instant modes;

 

if armed in Night-Stay mode, zones assigned to zone list 05 (night-stay zone list) are not

 

bypassed when system armed in Night-Stay mode.

3-2

 

 

Programming Overview

 

 

 

 

Type 05

• Assign to a zone that contains a foil-protected door or window (such as in a store), or to a zone

 

Trouble by Day/

covering a sensitive area such as a stock room, drug supply room, etc.

 

Alarm by Night

• Can also be used on a sensor or contact in an area where immediate notification of an entry is

 

 

desired.

 

 

• Provides an instant alarm if faulted when armed in the Away, Stay, Night-Stay, Instant or

 

 

Maximum (night) modes.

 

 

• During the disarmed state (day), the system will provide a latched trouble sounding from the

 

 

keypad (and a central station report, if desired).

 

Type 06

• Usually assigned to a zone containing an emergency button.

 

24-hr Silent Alarm

• Sends a report to the central station but provides no keypad display or sounding.

 

 

 

 

Type 07

• Assign to a zone that has an emergency button.

 

24-hour Audible

• Sends a report to the central station, and provides an alarm sound at the keypad, and an

 

Alarm

audible external alarm.

 

 

 

 

Type 08

• Assign to a zone containing an emergency button, or to a zone containing monitoring devices

 

24-hour

such as water or temperature sensors.

 

Auxiliary Alarm

• Sends a report to the central station and provides an alarm sound at the keypad. (No bell

 

 

output is provided.)

 

Type 09

• Provides a fire alarm on short circuit and a trouble condition on open circuit. A fire alarm

 

Supervised Fire

produces a pulsing bell output.

 

 

• This zone type is always active and cannot be bypassed.

 

 

 

 

Type 10

• Provides entry delay (using the programmed entry time), if tripped when the panel is armed in

 

Interior w/Delay

the Away mode.

 

 

• Entry Delay 1 begins whenever sensors in this zone are violated, regardless of whether or not

 

 

an entry/exit delay zone was tripped first.

 

 

• Bypassed when the panel is armed in the Stay or Instant modes; if armed in Night-Stay mode,

 

 

zones assigned to zone list 05 (night-stay zone list) are not bypassed when system armed in

 

 

Night-Stay mode.

 

Type 12

• Works as a dynamic monitor of a zone fault/trouble (not alarm). In the case of a short/open, the

 

Monitor Zone

message, "*ALARM*-24 Hr. Non-Burg. -#XXX " (where XXX is the zone number) will be sent

 

 

to the Central Station. The system keypad will display a “check” message indicating the

 

 

appropriate zone (but keypad beeping does not occur). Upon restoral of the zone, the message,

 

 

"*RESTORE*-24 Hr. Non-Burg. -#XXX " will be sent to the Central Station.

 

 

• The “check” message will automatically disappear from the keypad dynamically, when the

 

 

zone restores; a user code + off sequence is not needed to reset the zone.

 

 

• Faults of this zone type are independent of the system, and can exist at the time of arming

 

 

without interference.

 

 

• Since this is a “trouble” zone type, do not use this zone type with relays set to activate upon

 

 

“alarm.”

 

Type 14

• Assigned to any zone with a carbon monoxide detector.

 

24 Hour Carbon

• The bell output will pulse when this zone type is alarmed.

 

Monoxide

• Always active and cannot be bypassed.

 

Monitor

 

 

Type 16

• Provides a fire alarm when zone is shorted, but only after alarm verified.

 

Fire

• System verifies alarm by resetting zones for 12 seconds after short is detected. A subsequent

 

w/Verification

short circuit within 90 seconds triggers fire alarm.

 

 

• Provides a trouble response when zone is open.

 

Type 20

• Arms the system in Stay mode when the zone is activated.

 

Arm-Stay (BR

• Pushbutton units send the user number to the central station when arming or disarming.

 

only)

• User number for button must be assigned.

 

 

 

 

Type 21

• Arms the system in Away mode when the zone is activated.

 

Arm-Away (BR

• Pushbutton units send the user number to the central station when arming or disarming.

 

only)

• User number for button must be assigned.

 

 

 

 

Type 22

• Disarms the system when the zone is activated.

 

Disarm (BR only)

• User number for button must be assigned.

 

 

 

3-3

Installation and Setup Guide

Type 23 *

• Can be used on a zone when an output relay action is desired, but with no accompanying

No Alarm

alarm (e.g., lobby door access).

Response

 

 

 

Type 24

• Usually assigned to all sensors or contacts on exterior doors and windows where bells and/or

Silent Burglary

sirens are NOT desired.

 

• Provides an instant alarm, with NO audible indication at any keypad or external sounder, if

 

the zone is faulted when the system is armed in the Away, Stay, Instant, or Maximum modes.

 

• A report is sent to the central station.

Type 77

• Assign to zone wired to a keyswitch.

Keyswitch

• Do not use devices assigned as input type “BR” with this zone type.

Type 81

• Assign to zone connected to AAV module.

AAV Monitor

• Monitors 2-way voice sessions as follows:

Zone

- When the zone is faulted, all alarm sounding and dialer reporting stops, except

 

 

for fire alarms, which immediately terminate the voice session and cause

 

a fire report to be sent.

 

- When the zone is restored (session ended), sounding resumes (if bell timeout

 

has not expired) and reports that were stopped are sent.

Types 90-93

Allows for various custom responses. Options include response to entry/exit delays, response

Configurable

opens/shorts, types of alarm/trouble sounding, dial delay, and unique Contact ID report codes.

 

Types 92 and 93 can only be programmed via downloader. UL installations: Zone Types 90 -93

 

may not be used as fire or burglar alarm zones on fire or UL burglar alarm installations.

 

 

* The system can still be armed when these zone types are in a faulted condition.

NOTE: All of the zone types described are available for the wireless portion of the system, if used.

3-4

Loading...
+ 56 hidden pages