Read the instructions before use. This control shall be installed in accordance with the rules in force. Additional versions of this manual are available online at https://customer.honeywell.com/enUS/Pages/default.aspx in Canadian French, Portuguese, and German. Please enter 32-00015 in the search box and choose Technical Literature from the drop-down box.

AVERTISSEMENTNT

Lire les instructions avant l'utilisation. Cette commande doit être installée conformément aux lois en vigueur. Des versions supplémentaires de ce manuel sont disponibles enligne à https://customer.honeywell.com/enUS/Pages/default.aspx en français du Canada, en portugais et en allemand. Veuillez inscrire 32-00015 dans le casier de recherche et choisissez Documentation technique à partir du menu déroulant.

GENERAL INFORMATION

The Honeywell U2-101xS series model is a viewing head and signal processor in a single enclosure intended for use with a burner control system in Industrial Flame Monitoring applications. There are several options available (see Table 1 on page 2). Each model includes one, two, or all three sensors, and can be ordered with quick disconnect (non-PF Models DIV2,ZN2) or pigtail external connection method (PF Models DIV1,ZN1).

Each sensor operates independently from another, allowing adjustment of each sensor.

IMPORTANT

Flame monitoring systems are safety systems.

Please read this manual carefully and completely before installation and before attempting adjustments.

Only qualified personnel familiar with Flame Safety System should carry out installation and configuration.

U2 is certified to be used in prescribed manner.

Any modification or inappropriate installation or operation may result in unsafe operation and will void implied or expressed warranty.

Sensors

WARNUNG

Lesen Sie vor der Verwendung die Anweisung. Diese Konsole muss entsprechend den geltenden Vorschriften installiert werden. Zusätzliche Versionen dieses Handbuchs sind online unter https://customer.honeywell.com/enUS/Pages/default.aspx in Frankokanadisch, Portugiesisch und Deutsch verfügbar. Bitte geben Sie im Suchfeld 32-00015 ein und wählen Sie Fachliteratur im Drop-Down Menü aus

ATENÇÃO

Leia as instruções antes de usar. Esse controle tem que ser instalado de acordo com as normas vigentes. Outras versões desse manual estão disponíveis online em https://customer.honeywell.com/enUS/Pages/default.aspx em francês do Canadá, português e alemão. Insira 32-00015 em cada caixa e selecione Literatura Técnica na caixa suspensa.

Disposal and Recycling

Waste electrical products should not be disposed of with general waste. Please recycle where these facilities exist. Check with your local authority for recycling advice.

The UV tube detector has a peak response at 210 nm.

The IR solid state sensor has a peak response at 1400 nm.

The UV solid state sensor has a peak response at 310 nm.

Cabling Options (Sold Separately)

ASYU2S - Quick Disconnect (non-PF) models molded connector cable assembly with 50 foot of C22S cable.

 

Contents

GENERAL INFORMATION ...............................................

1

SPECIFICATIONS ............................................................

2

INSTALLATION .................................................................

3

OPERATION .....................................................................

6

U2 MENU PARAMETER SETTINGS ................................

7

TROUBLESHOOTING ......................................................

10

SAFETY MANUAL ............................................................

13

Safety Function of the U2-S Model ..............................

14

Proof Test Procedure ...................................................

14

Proof Test Interval ........................................................

14

Product Decommissioning ...........................................

15

32-00015-04

U2-S MODEL COMBINATION VIEWING HEAD AND SIGNAL PROCESSOR

ASYU2S-100 - Quick Disconnect (non-PF) models molded connector cable assembly with 100 foot of C22S cable.

ASYU2S-200 - Quick Disconnect (non-PF) models molded connector cable assembly with 200 foot of C22S cable.

ASYU2S-300 - Quick Disconnect (non-PF) models molded connector cable assembly with 300 foot of C22S cable.

C22S - Raw shielded 12 conductor, 22g, ITC, CIC approved. Order by the foot.

Table 1. Models and Associated Features.

 

 

 

 

 

 

 

 

 

Quick

Pipe Fit

Sensor Type

 

 

Model

Connector

Connection

UVTron

IR

 

UVSS

Typical Fuels

U2-1010S

X

 

X

X

 

X

All Fuels

U2-1010S-PF

 

X

X

X

 

X

All Fuels

 

 

 

 

 

 

 

 

U2-1010S-PF-050*

 

X

X

X

 

X

All Fuels

 

 

 

 

 

 

 

 

U2-1010S-PF-100

 

X

X

X

 

X

All Fuels

 

 

 

 

 

 

 

 

U2-1012S

X

 

 

X

 

 

Oil and Coal

 

 

 

 

 

 

 

 

U2-1012S-PF

 

X

 

X

 

 

Oil and Coal

 

 

 

 

 

 

 

 

U2-1016S

X

 

X

 

 

 

Gas and Light Oils

 

 

 

 

 

 

 

 

U2-1016S-PF

 

X

X

 

 

 

Gas and Light Oils

 

 

 

 

 

 

 

 

U2-1018S

X

 

X

X

 

 

All Fuels

 

 

 

 

 

 

 

 

U2-1018S-PF

 

X

X

X

 

 

All Fuels

 

 

 

 

 

 

 

 

* The U2-1010S-PF-050 has a 50-ft (15m) pigtail and the U2-1010S-PF-100 has a 100-ft (30m) pigtail.

SPECIFICATIONS

Input Power Supply: 22-26 VDC, 120 mA max (approximately 3.5 watts)

Remote Communication: 2 wire RS485 compatible with Modbus RTU protocol.

Flame And Fault Relay Contact Ratings:

1 A, 30 VDC (Resistive).

Maximum load current of 1A must be de-rated at temperatures higher than 50C ambient according to 1%/C, or 10mA/C. For example, the maximum current at 70C = 1A – (20C x 10mA) = 0.8A.

WARNINGI

Do not apply more than 30VDC to flame relay or self check relay.

WARNINGI

The U2 requires the use of an isolated 24VDC SELV (Safety Extra Low Voltage) power supply.

User Selectable Analog Output: 0-20 mA and 4-20 mA; 500 Ohm Load Max

File Select Input logic high: 21VDC min

File Select Input logic low: 16VDC max

User Interface: Capacitive TouchWheel with LED Display

Ambient temperature: -40 to 70 ºC (-40 to 158 ºF)

Enclosure: IP66

Weight: 2.8 kg (6.1 lbs)

Physical Dimensions: Diameter: 11.7 cm (4.6 inches)

Length: 15.5 cm (6.1 inches)

Finish: Silicone free powder coated

Mounting/Process Connection: 1” NPT female

Pipe Fit Models (PF version): 3/4” NPT

Fuses: Automatically resettable for power source and Flame Relay.

Maximum furnace back pressure: 35 Kg/Cm2 (500 PSI)

Selectable Flame Failure Response Time (FFRT):

1, 2, 3 seconds, Error= +0.0sec, -0.5sec.

Internal Temperature Indication: Degrees C or F in display menu of U2, or available at Modbus register 40019.

Self-Checking

Internal electronic self checking is performed once per second, to verify that system is operating properly. If self check detects an error, the flame relay, and self check relays will open, and the device will display "lockout". This lockout may only be cleared by manual entry reset at the U2 Touchwheel interface.

Approvals:

Quick disconnect type

General

FM, CSA, CE (EN298), and EAC

Hazardous Location

CSA

CLASS I, DIVISION 2, GROUPS A, B, C, D

CLASS II, DIVISION 1, GROUPS E, F, G

CLASS III DIVISION 1 T5

Ex nA nC IIC T5 Gc Ex tb IIIC T85°C Db

CLASS I, ZONE 2, AEx nA nC IIC T5 Gc

ZONE 21 AEx tb IIIC T85°C Db

IECEx SIR 15.0068X Ex nA nC IIC T5 Gc

Ex tb IIIC T85°C Db IP66

SIRA 15ATEX4193X Ex nA nC IIC T5 Gc

Ex tb IIIC T85°C Dc IP66

32-00015—04

2

U2-S MODEL COMBINATION VIEWING HEAD AND SIGNAL PROCESSOR

PF version

General

FM, CSA, CE (EN298), and EAC

Hazardous Location

CSA

CLASS I, DIVISION 1, GROUPS A, B, C, D

CLASS II, DIVISION 1, GROUPS E, F, G

CLASS III DIVISION 1 T6

Ex d IIC T6 Gb Ex tb IIIC T85°C Db

CLASS I, ZONE 1, AEx d IIC T5 Gb

ZONE 21 AEx tb IIIC T85°C Db

IECEx SIR 15.0068X Ex db IIC T6 Gb

Ex tb IIIC T85°C Db IP66

SIRA 15ATEX1192X Ex db IIC T6 Gb

Ex tb IIIC T85°C Db IP66

! CAUTION

Possible Equipment Damage

The aluminum surface of the U2 may store an electrostatic charge and become a source of ignition in applications with a low (<30%) relative humidity. Cleaning the surface should only be done with a damp cloth.

! CAUTION

Do not expose to acetone, gasoline, hexane, or ethyl acetate. label is not approved for these chemicals.

Non-PF/

 

 

Color

Function

Connection

9-Tan

File Select Output, 0 or +24V

To burner control

 

output. Feedback for system

system. 0V = File

 

controlling file input select.

Select Input is low, or

 

 

+24V if FileSelect

 

 

Input is high.

 

 

 

10-White

+RS485 Modbus

To Modbus +

 

 

 

11-Drain

Cable Overall Shield

To Earth Ground

 

 

 

12-Brown

-RS485 Modbus

To Modbus -

*Note - pink wire unused, leave unconnected.

! CAUTION

Check wiring before applying power to the system to make sure it is in accordance with the wiring chart. Incorrect wiring may result in unsafe operation or damage to U2.

NOTES:

1.For remote configuration and monitoring, refer to Honeywell manuals for FlameTool for PC (32-00001-01) and HMI S7999 Panel (32- 00003-01).

2.A total of eight parameter files are available. Files 2 through 7 may be accessed using Flametools, and configured using Modbus register 40093.

Wiring

See “Typical Installation Diagram.” on page 12.

 

 

 

Non-PF/

 

 

Color

Function

Connection

 

 

 

1-Red

Power Supply +24 VDC

To power supply

 

Connect to 22-26 VDC

positive terminal

 

 

 

2-Purple

File Select Input, 0 or 1

To control output.

 

 

>21V input = file 1,

 

 

<16V = active file

 

 

defined at Modbus

 

 

register

 

 

40093(default 0).

 

 

 

3-Orange

mA output (+)

To current meter

 

 

positive

 

 

 

4-Blue

mA output (-)

To current meter

 

 

negative

 

 

 

5-Black

Power Supply Return (-) or 0

To Power Supply

 

VDC

negative terminal.

 

 

 

6-Yellow

Flame Relay (NO)

To flame/fault relay

 

(power in)

power source

7-Green

Fault Relay (NO) (fault output)

To fault monitoring of

 

 

burner control system

8-Grey

Flame Relay (NO) (safety

To burner control

 

output)

system

 

 

 

INSTALLATION

See “Typical Installation Diagram.” on page 12.

Installation should be carried out by a qualified engineer and should meet all local standards and safety requirements.

Hazardous location installations require the use of ITC/CIC approved cable installed in cable tray for non-PF models, and in metal conduit for -PF models. The cable installation must conform to the latest revision of the National Electrical Code, or Canadian Electrical Code for Class I, Division 2 (non-PF models), or for Class I, Division 1 (-PF models).

WARNINGI

Approved CLI, DIV1 conduit seal must be installed at PF model enclosure fitting for CLI, DIV1 hazardous location use.

Non-PF models must be secured as follows: hand-tighten the connector at viewing head until it can be turned no more. Continue tightening the connector an additional 180 degrees using pliers, or similar tool. Verify that connector cannot be loosened by hand.

WARNINGI

Over-tightening the connector can damage the connector or housing.

Damage will void warranty and hazardous location approvals. Do not exceed 180 degrees of further rotation after hand tightening!

3

32-00015—04

U2-S MODEL COMBINATION VIEWING HEAD AND SIGNAL PROCESSOR

WARNINGI

EXPLOSION HAZARD

DO NOT DISCONNECT WHILE CIRCUIT IS LIVE UNLESS AREA IS KNOWN TO BE NONHAZARDOUS.

Substitution of components may impair suitability for class i, division 2.

The U2-S model viewing port is designed for interface to a 1" NPT (M) fitting. The viewing head can be mounted in any orientation, any angle, upward or downwards.

It is recommended that earth ground is applied at the labeled earth ground screw connection on the housing. It is recommended the drain wire be connected to earth at power supply.

To reduce noise interference from ignition transformer or other high voltage sources, make sure all high voltage cables are in good condition and are at least 300 mm (12") away from U2 wiring.

Location/Mounting on Burner

Honeywell can provide mounting accessories such as a swivel mount, heat/electrical insulator, quick mechanical disconnect, high pressure isolation unit, etc. Check with your sales representative for your application.

1.Ensure location provides clear view of the flame under all operating conditions.

2.If the burner is provided with a pipe mount, use a bell type reducer to 1" NPT (M).

3.When using purge/cooling air, make sure hoses are electrically isolated from the Earth to prevent multiple ground loops.

4.Depending upon the application, purge/cooling air pressure and flow will be different. As it is easier to measure pressure than flow, ensure that the entrance to air connection is a minimum of 25 mm WC (1" wc) above back pressure at all the time, from minimum to maximum load.

5.IMPORTANT!

FLAME DISCRIMINATION

In multi-burner applications, it is important to sight for high frequency, high radiation intensity zone of the target flame, while sighting the low frequency, low radiation intensity zone of the background flame see Fig. 3 for IR, or Fig. 4 for UV for an example. This allows for filter, gain, and threshold settings to properly discriminate or recognize the target flame while rejecting background flame.

6.Where practical, use a swivel mount to allow for adjustments to optimize the flame viewing location.

1 (25) NPT

1(25)

 

 

5-3/32 (130)

CONNECTION

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4-19/32

(118)

 

 

 

 

 

 

 

3/4 (19) NPT

2-29/32 (73)

 

 

 

 

 

 

 

 

 

 

CONNECTION

 

 

 

 

 

M34431

Fig. 1. Dimensional drawings.

BURNER FRONT PLATE

 

OR WINDOWBOX

 

 

R-518-CL12-PG

1 (25)

PURGE AIR COUPLER

NPTF PIPE

AND R-518-PT12

 

INSULATING LOCKING

 

COUPLER ADAPTER

FLANGE

 

(OPTIONAL)

 

 

M33628

Fig. 2. Typical mounting example.

32-00015—04

4

Honeywell U2-1018S-PF, U2-1018S, U2-1016S, U2-1012S, U2-1010S-PF-100 User Manual

U2-S MODEL COMBINATION VIEWING HEAD AND SIGNAL PROCESSOR

HIGH FREQUENCY

FLICKER ZONE

DETECTOR IN GOOD SIGHTING POSITION (PARALLEL SIGHTING)

BURNER NOZZLE

CENTERLINE

DETECTOR IN POOR

SIGHTING POSITION

LOW FREQUENCY

FLICKER ZONE

M33285B

Fig. 3. IR viewing head location.

UV VIEWING

HEAD SIGHTED

ON UV ZONE

UV RADIATION

ZONE

BURNER NOZZLE

CENTERLINE

M33286B

Fig. 4. UV viewing head location.