Honeywell T7984 C, T7984 B, T7984 A User Manual

0 (0)

T7984 A,B,C Electronic Modulating Control

Thermostats

PRODUCT DATA

FEATURES

APPLICATION

These microprocessor-based thermostats provide proportional - integral (PI) individual room temperature control in zoned commercial Heating, Ventilating, and Air Conditioning systems such as hydronic heating and/ or cooling, pressure dependent VAV or by-pass box with or without terminal reheat.

The T7984 family provides modulating analog 2 to 10 Vdc control. Optional features include automatic heat/ cool changeover, reheat control, remote night setback with local timed override, and remote sensor on VAV models.

PI (proportional and integral) control action provides accurate, stable room temperature control.

T7984 models are used with Series 70 direct-coupled damper actuators such as ML7161 or ML7984, or with valve actuators such as ML7285, ML7421, VC7930 or M7410.

All models feature user-friendly set point knob.

All models feature output status LEDs for installer check-out.

Locking cover and range stops are standard.

Night setback models feature selection of two different offset temperatures and use central time switch control.

Night setback models feature 2 1/2 hour local timed override.

Heat/cool models feature automatic changeover with 3° or 5°F (1.5°C or 3°C) selectable Zero Energy Band (Z.E.B.) to meet requirements of ASHRAE 90.1

Heat/cool models have installer-definable setpoint at midpoint of Z.E.B, at heating setpoint, or at cooling setpoint.

Reheat models feature fast/slow response selection to match heating system dynamics.

DIP switch selectable 75°F (24°C) high limit heating setpoint and low limit cooling setpoint.

Horizontal and vertical covers included.

 

Contents

Application.........................................................................

1

Features ............................................................................

1

Specifications ....................................................................

2

Ordering Information .........................................................

2

Installation .........................................................................

3

T7984A..............................................................................

4

T7984B..............................................................................

5

T7984C..............................................................................

6

Checkout ...........................................................................

8

95C-10815-2

T7984 A,B,C ELECTRONIC MODULATING CONTROL THERMOSTATS

SPECIFICATIONS

IMPORTANT

The specifications given in this publication do not include normal manufacturing tolerances. Therefore, this unit may not exactly match the listed specifications. Also, this product is tested and calibrated under closely controlled conditions, and some minor differences in performance can be expected if those conditions are changed.

MODELS: T7984A,B,C, 2 to 10 Vdc analog output

Table 1. Model Specifications

 

 

Cool/Heat

 

 

 

Main

 

 

 

 

 

Changeover

 

 

 

Temperature

 

Mode Selection

 

Model

Output 1

For Output 1

Output 2

Night Setback

Sensor *

 

Input

 

 

 

 

 

 

 

 

 

 

 

T7984A

Modulating 2 to

Dry Contact or

On/off

 

-

Internal or

 

-

 

 

10 Vdc

Sensor

 

 

 

remote

 

 

 

 

 

 

 

 

 

 

 

 

 

T7984B

Modulating 2 to

-

-

 

Dry Contact

Internal or

 

Jumper

 

 

10 Vdc

 

 

 

 

remote

 

 

 

 

 

 

 

 

 

 

 

 

T7984C

Modulating 2 to

Dry Contact or

Modulating 2 to

Dry Contact

Internal or

 

-

 

 

10 Vdc

Sensor

10 Vdc

 

 

remote

 

 

 

 

 

 

 

 

 

 

 

 

 

* Remote sensor

models are:

 

 

 

 

 

 

 

 

272845 Remote wall mount sensor

 

 

 

 

 

 

 

 

272847 Remote duct mount sensor

 

 

 

 

 

 

 

 

DIMENSIONS

 

 

 

* The maximum heating setpoint and minimum cooling

See Figure 1.

 

 

 

setpoint is electronically limited to 75°F [24°C].

MOUNTING: Mounts to single-gang NEMA-standard 2"x 4"

REMOTE SENSOR: 47 kΩ NTC thermistor [part nos. 272845

electrical box, or directly to wall requires 1 1/8“ [35„mm]

and 272847].

 

 

 

 

access hole for wiring.

 

 

 

 

 

 

 

 

ANALOG OUTPUT: 2 to 10 Vdc, 2 mA max.

WIRING: Four to eight 1/8“ screw terminals suitable for 2 no.

 

 

 

 

 

 

18 AWG [1 mm 2] wires each depending on model.

 

SWITCHED OUTPUT RATING: 0.5A running, 1.1A inrush,

POWER SUPPLY: 19-30 Vac, 50-60 Hz, 2 VA, Class 2. (Does

24Vac, protected with selfresetting fuse.

 

 

 

 

 

 

 

 

not include actuator or reheat stage power requirements.)

OPERATING PARAMETERS: See Table 2 for installer selections.

OPERATING AMBIENT:

 

 

APPROVALS:

 

 

 

 

32-104°F [0-40°C] at 5-95% Relative Humidity (non-

 

Designed for Class II low voltage installation only.

condensing).

 

 

 

Case and cover meets UL„94-5V flammability requirements,

ACCURACY: 1°F (0.6°C) PRECISION: ±1°F (0.5°C) tempera-

and North American codes for line voltage thermostat

enclosures.

 

 

 

 

ture after stabilization.

 

 

 

 

 

 

 

 

Meets requirements of F.C.C. Part 15 Class B, IEC 801-3 for

 

 

 

 

PRECISION: ±1°F (0.5°C) temperature after stabilization.

radio frequency interference.

 

 

SETPOINT RANGE: 55-90°F [13-32°C], T7984A.

 

ACCESSORIES:

 

 

 

 

Heating: 55-75°F [13-24°C], T7984B, C*.

 

272845 - Remote sensor (wall mounted).

 

 

 

272846 - Adaptor plate for 2-gang NEMA, or British 75 mm

 

 

 

 

Cooling: 75-90°F [24-32°C], T7984B, C*.

 

electrical box.

 

 

 

 

 

 

 

 

272847 - Remote sensor (duct mounted).

 

 

ORDERING INFORMATION

When purchasing replacement and modernization products from your TRADELINE® wholesaler or distributor, refer to the TRADELINE® Catalog or price sheets for complete ordering number.

If you have additional questions, need further information, or would like to comment on our products or services, please write or phone:

1.Your local Honeywell Automation and Control Products Sales Office (check white pages of your phone directory).

2.Honeywell Customer Care 1885 Douglas Drive North

Minneapolis, Minnesota 55422-4386

In Canada–Honeywell Limited/Honeywell Limitée, 35 Dynamic Drive, Scarborough, Ontario M1V 4Z9.

International Sales and Service Offices in all principal cities of the world. Manufacturing in Australia, Canada, Finland, France, Germany, Japan, Mexico, Netherlands, Spain, Taiwan, United Kingdom, U.S.A.

95C-10815–2

2

Honeywell T7984 C, T7984 B, T7984 A User Manual

T7984 A,B,C ELECTRONIC MODULATING CONTROL THERMOSTATS

Table 2. Option Settings

 

 

T7984 Model

Parameter

Selection

A

B

C

 

 

 

 

 

Reheat Time

Fast (7.5 min.); or Normal

 

 

Constant

(15 min.)

 

 

 

 

 

 

 

 

Zero Energy

3°F (1.5°C); or 5°F (3°C)

 

Band

 

 

 

 

 

 

 

 

 

Setpoint

Heating; Cooling or H/C

 

Definition

midpoint

 

 

 

 

 

 

 

 

Night

5°F (3°C) heat/cool offset, or

 

Setback

10°F (5°C) setback / cooling

 

 

 

 

shutdown

 

 

 

 

 

 

 

 

Main Sensor

Remote or internal

 

 

 

 

 

Fig. 1. Dimensions in inches (mm)

INSTALLATION

Location

Install the thermostat about 5 ft. (1.5 m) above the floor in an area with good air circulation at average temperature conditions.

Do not install thermostat where it may be affected by:

drafts, or dead air spots behind doors and in corners.

hot or cold air from ducts.

radiant heat from sun or appliances.

concealed pipes and chimneys.

unheated (cooled) areas such as an outside wall behind the thermostat.

Mounting

The thermostat can be mounted directly on the wall with or without a wallplate or a standard single gang electrical box, or double gang with adaptor plate (accessory part 272846).

CAUTION

Disconnect power supply to prevent electrical shock or equipment damage.

Wiring

Typical wiring connections are shown in Fig.2 to Fig.7. Wiring connections may be made to the screw terminal block with 2- 18AWG or 1-14AWG, solid or stranded copper wires. Connect the system wires to the thermostat terminals. Push excess wire back into hole. Plug hole to prevent drafts.

Auxiliary screw terminal strip may be used in a junction box when the application requires multiple wires to be brought down at the thermostat. This can make troubleshooting, startup and servicing easier.

DIP Switch Settings

T7984 thermostats must be configured for proper operation by setting DIP switches.

T7984B

Reheat output control action: 7.5 or 15 minutes.

T7984B,C

Zero energy band (ZEB): 3°F (2°C) or 5°F (3°C)

Setpoint adjustment: cooling,centred, heating centred with limit override for commissioning.

Night setback amount: see Table 2 for complete listing of option settings.

T7984A,B,C

Main sensor, internal or remote.

Table 3. T7984 DIP Switch Definition

OUTPUT 2 ON/OFF CPH

 

T7984B only

 

For more information, see on/off output cycle per hour application note.

CYCLES/HOUR

 

S1

It is possible to fix the number of times per hour the on/off

FAST

8 CPH

 

1

output will be energized.

SLOW 4 CPH

 

0

 

 

 

 

 

 

 

 

 

T7984B & C only

 

ZERO ENERGY BAND

 

 

 

 

 

On models which have 2 outputs, 1 for cooling and 1 for

 

ZEB

 

S2

5°F (3°C)

 

1

heating, it is possible to adjust the zero energy band value

3°F

(1.5°C)

 

0

(dead band between heating and cooling endpoints).

 

 

 

 

 

 

 

 

 

 

 

 

T7984B & C only

SETPOINT DIAL DEFINITION

 

 

For more information, see setpoint dial definition & setpoint limitation application note.

DEFINITION

S3

S4

 

Models with cooling and heating outputs

75°F OVERRIDE

1

1

 

» Setpoint dial centered, 75˚F limitation not active.

HEATING DIAL

0

1

 

» Setpoint dial defined as heating, 75˚F limitation active.

COOLING DIAL

1

0

 

» Setpoint dial defined as cooling, 75˚F limitation active.

CENTERED HC

0

0

 

» Setpoint dial centered, 75˚F limitation active.

 

 

 

 

 

 

 

 

DAY/NIGHT SETBACK

 

 

 

 

 

T7984B & C only

HEAT SETBACK

COOL SETUP

S5

Night mode setpoints can be adjusted

to different values depending on the

10°F (5°C)

20°F (10°C)

 

1

 

application.

5°F (3°C)

5°F (3°C)

 

0

 

 

 

 

 

 

 

REMOTE SENSOR

 

T7984A, B & C

 

On model T7984A, switch S7 & S8 are not used.

 

MAIN SENSOR

S6

 

 

 

For duct return air or remote room sensor control only.

LOCAL INTERNAL

1

 

 

 

Do not use remote sensor in supply or discharge air

REMOTE SENSOR

0

 

 

 

control applications.

ON = 1

OFF = 0 1 2 3 4 5 6

3

95C-10815–2