Honeywell S9200U1000 Installation Manual

0 (0)

S9200U1000 Universal Hot Surface

Ignition Integrated Furnace Control

INSTALLATION INSTRUCTIONS

APPLICATION

The S9200U1000 Universal Integrated Furnace Control is a combustion control used in single stage gas heating and cooling appliances. Keyed wire harnesses allow the S9200U1000 to replace most furnace controls and to be applied to most heating and cooling single stage appliances.

The S9200U1000 can be used with conventional thermostats as well as the EnviraCOM™ enabled VisionPRO IAQ and FocusPRO. The S9200U1000 Universal Integrated Furnace Control is intended for residential natural or liquid propane fueled furnaces only.

The S9200U1000 EnvriaCOM™ communications capability allows its use in twinning applications and enables communication with local and remote diagnostic devices such as the QuickLook hand held device (QuickLook™ 72), EnviraLNK® web-based application and the W8735D Telephone Access Module (TAM).

FEATURES

The S9200U1000 provides:

Main burner ignition using a 120V hot surface igniter.

Flame rectification circuit to monitor flame presence.

Monitoring of system pressure switch, high temperature limit, and rollout functions.

Appliance operation/safety requirements controlled via microprocessor.

Control of a standard induction-type circulating fan motor (based on appliance requirements), in response to a conventional low voltage or EnviraCOM™ thermostat.

LED system status, performance and diagnostic indication.

Wire harnesses provided for simple replacement of most IFCs and integration with most heating and cooling appliances.

Twinning capability.

EnviraCOM™ communication capability to enable local and/or remote system status, diagnostics, troubleshooting, and HVAC system control.

SPECIFICATIONS

Line Voltage: Line 120V (97-132 Vac), 60 Hz Low Voltage: Line 24V (19-30 Vac), 60 Hz

Current Draw: 0.5A Input Current @24 Vac, plus valve load @ 24 Vac plus cooling contactor

Igniter Current: 5.0A resistive @ 132 Vac output

Thermostat Anticipator Setting: (Stage 1 only) 100mA Prepurge: 30 seconds

HSI Warm-up: 17/27 or 30/30 seconds (1st/next trial) depending on DIP switch S2 setting

Trial for Ignition: 4, 6, or 8 seconds depending on DIP switch S2 setting

Postpurge: 15 seconds Inter-trial Purge: 60 seconds

Auto Restart Delay: 60 minutes (after Soft Lockout) Ignition Trials: Three; two retries if flame is not sensed

on the first trial

Flame Failure Response Time: 2 seconds maximum @ 1 A

LEDs: Three LEDs provide the following:

A red LED provides system status and faults

An amber LED provides flame status information

A green LED provides information about the EnviraCOM™ traffic

Wire harnesses:

12 pin, 3 x 4 connector, 7 inches; main harness

4-pin, 4 x 1 connector, 7 inches; igniter/inducer harness

Fan Delays:

Heat Fan ON Delay: 30 or 60 seconds depending on DIP switch S1 setting

Heat Fan OFF Delay: 60, 90, 120, or 180 seconds depending on Dip Switch S1 setting

Cool Fan ON Delay: 5 seconds

Cool Fan OFF Delay: 0 or 60 seconds (depending on DIP Switch S1 setting)

Gas Control: Any 24 Vac redundant, direct ignition gas control rated at 1.5A or less; Honeywell VR88345M4320 recommended

Cooling Contactor:

Any 24 Vac contactor rated at 1.0A or less

Induced Draft Blower:

2.2FLA/3.5LRA maximum @ 120 Vac

Circulator Load: 14.5FLA/25LRA maximum @ 120 Vac

Line Voltage Humidifier:

1A resistive load maximum @ 120 Vac

Electronic Air Cleaner:

1A resistive load maximum @ 120 Vac Replaceable Fuse: 3.0 Amp, Automotive type

Operating Temperature: -40°F to 175°F (-40°C to 79°C) Relative humidity: 0% to 95% non-condensing Dimensions: See Fig. 1 on page 7

69-2075-05

S9200U1000 UNIVERSAL HOT SURFACE IGNITION INTEGRATED FURNACE CONTROL

INSTALLATION AND CONFIGURATION OVERVIEW

The following is an overview of the steps required to install and configure the S9200U1000 Integrated Furnace Control:

1.Identify cross reference target using Table 1.

2.Remove old device and carefully identify and mark any wiring. See “Replacement” on page 6.

3.Mount the S9200U1000 Integrated Furnace Control. See “Replacement” on page 6.

4.Connect the wiring harnesses and make the wiring connections. See “Wiring” on page 7.

5.Configure the field settings and safety timings. See “Safety Timings, Field Settings, and Fixed Parameters” beginning on page 11.

CROSS REFERENCE

IMPORTANT

Only use the S9200U1000 on 120 Vac applications.

See Table 1 for the replacement details for other manufacturers’ controls. See Table 2 for replacement details for Trane controls.

69-2075—05

2

S9200U1000 UNIVERSAL HOT SURFACE IGNITION INTEGRATED FURNACE CONTROL

Table 1. S9200U1000 Replaces These Integrated

Furnace Controls.

[Only use the S9200U1000 on 120 Vac applications.]

 

 

 

Safety

 

 

Field Settings

Timing

 

 

Settings -

SKU

Harness

Recommendation-

DIP Switch

DIP Switch S1

S2

United

 

 

 

Technologies

 

 

 

1012-925A

 

 

 

1012-925B

50024568

SW1: ON

 

 

Main Connector

 

1012-925C

 

 

 

SW2: OFF

SW1: ON

Rheem/ Robert

 

50024566

SW3 & SW4: 60/90/

SW2: ON

Shaw

Inducer & HSI

120/180

 

62-24268-01

Connector

 

 

62-24268-02

 

 

 

62-24268-03

 

 

 

695-200

 

 

 

 

 

 

 

Nordyne

 

 

 

624557

 

 

 

6245570

 

 

 

624557-0

 

 

 

624564

 

 

 

6245640

 

 

 

624591

 

 

 

624591A

 

 

 

624591-A

 

 

 

624591-B

50024568

 

 

624591-C

SW1: ON

 

Main Connector

 

624591-D

 

SW2: OFF

SW1: ON

624628

50024565

SW3 & SW4: 60/90/

SW2: OFF

 

Inducer & HSI

120/180

 

624628-0

 

Connector

 

 

6246310

 

 

 

 

 

624631-0

 

 

 

624631A

 

 

 

624631-A

 

 

 

624631-B

 

 

 

710128A

 

 

 

902378

 

 

 

902696

 

 

 

903106

 

 

 

CAR903106

 

 

 

United

50024568

SW1: ON

 

Technologies

Main Connector

 

 

 

SW2: OFF

SW1: ON

1012-955A

 

 

50024565

SW3 & SW4: 60/90/

SW2: OFF

1012955A

Inducer & HSI

120/180

 

 

Connector

 

 

Table 1. S9200U1000 Replaces These Integrated

Furnace Controls.

[Only use the S9200U1000 on 120 Vac applications.]

 

 

 

Safety

 

 

Field Settings

Timing

 

 

Settings -

SKU

Harness

Recommendation-

DIP Switch

DIP Switch S1

S2

 

 

 

 

Texas Instruments

 

 

 

6DT-1

 

 

 

6DT-2

 

 

 

61F3

 

 

 

York

 

 

 

03100662000

 

 

 

031-00662-000

 

 

 

031-00662-700

 

 

 

031-01140-000

 

 

 

031-01140-001

 

 

 

031011140002

 

 

 

031-01140-002

 

 

 

031-01140-701

 

 

 

031-01140-702

Main Connector

SW1: ON

 

 

not required.

 

031.01234.000

 

 

 

SW2: OFF

SW1: OFF

031-01234-700

 

50024561

SW3 & SW4: 60/90/

SW2: ON

031-01235-000

Inducer & HSI

120/180

 

031-01235-700

Connector

 

 

031-01250-000

 

 

 

031-01266-000

 

 

 

031-01267-00

 

 

 

031-01267-000

 

 

 

031-01267-001

 

 

 

031-01267-001A

 

 

 

031-01284-000

 

 

 

031-01933-000

 

 

 

031-01972-000

 

 

 

031-01973-000

 

 

 

031-02166-000

 

 

 

031-09166-000

 

 

 

031-09167-000

 

 

 

331-01933-000

 

 

 

331-01972-200

 

 

 

331-09167-000

 

 

 

43101972100

 

 

 

431-01972-100

 

 

 

CAR33101972200

 

 

 

CAR03101973000

Main Connector

 

 

CAR50A55843

SW1: ON

 

not required.

 

G951ADB1401

 

SW2: OFF

SW1: OFF

G951ADB1401C

50024561

SW3 & SW4: 60/90/

SW2: ON

 

Inducer & HSI

120/180

 

G951ADB-1401C

 

Connector

 

 

G951ADB1402

 

 

 

 

 

G951ADB-1402

 

 

 

G951AEB-1403

 

 

 

P03101267001

 

 

 

P031-01267-001

 

 

 

PTH031011400-00

 

 

 

031-00662

 

 

 

 

 

 

 

United

Main Connector

SW1: ON

 

Technologies

not required.

 

 

 

SW2: OFF

SW1: OFF

1012-83-9651B

50024561

SW3 & SW4: 60/90/

SW2: ON

 

Inducer & HSI

120/180

 

 

Connector

 

 

3

69-2075—05

S9200U1000 UNIVERSAL HOT SURFACE IGNITION INTEGRATED FURNACE CONTROL

Table 1. S9200U1000 Replaces These Integrated

Furnace Controls.

[Only use the S9200U1000 on 120 Vac applications.]

 

 

 

 

 

 

 

Safety

 

 

Field Settings

Timing

 

 

Settings -

SKU

Harness

Recommendation-

DIP Switch

DIP Switch S1

S2

 

 

 

 

Goodman1

50026393

SW1: ON

 

 

Main Connector

 

1809913

SW1: OFF

 

SW2: OFF

B1809913

50026446

SW3 & SW4: 60/90/

SW2: ON

 

Inducer & HSI

120/180

 

B18099-13

 

 

Connector

 

 

United

 

 

 

Technologies

 

 

 

1012933D

 

 

 

1012-933D

 

 

 

1012-83-

 

 

 

9336AHSC1

 

SW1: ON

 

1012-83-9337A

 

 

 

SW2: OFF

SW1: OFF

Texas Instruments

50026393

SW3 & SW4: 60/90/

SW2: ON

41F-5

120/180

 

 

Main Connector

 

 

White Rodgers

 

 

50026446

 

 

50T35730

 

 

 

Inducer & HSI

 

 

50T35-730

 

 

Connector

 

 

50T35743

 

 

 

 

 

50T35-743

 

 

 

ICM280

 

 

SW1-SW2:

 

 

SW1-SW4:

Check

 

 

control

 

 

Check control Field

 

 

Safety

 

 

Settings

Timings

 

 

before setting.

 

 

before

 

 

 

setting.

Table 1. S9200U1000 Replaces These Integrated

Furnace Controls.

[Only use the S9200U1000 on 120 Vac applications.]

 

 

 

 

 

 

 

Safety

 

 

Field Settings

Timing

 

 

Settings -

SKU

Harness

Recommendation-

DIP Switch

DIP Switch S1

S2

 

 

 

 

White Rodgers1

 

 

 

50A55-843 -

 

SW1: Check

 

Universal

 

Settings

SW1: OFF

 

 

SW2: Check

 

 

Settings

SW2: OFF

 

 

SW3 & SW4: 60/90/

 

 

 

120/180

 

50A55-286

 

SW1: ON

SW1: OFF

 

 

SW2: OFF

 

 

SW3 & SW4: 60/90/

SW2: ON

 

 

120/180

 

50A50-143

 

SW1: ON

 

 

 

SW2: Check

SW1: OFF

 

 

Settings

 

 

SW2: ON

 

 

SW3 & SW4: 60/90/

 

 

120/180

 

50A55-241

 

SW1: ON

SW1: OFF

 

 

SW2: OFF

 

 

SW3: ON

SW2: ON

 

 

SW4: ON

 

50A50-286

 

SW1: ON

SW1: OFF

 

 

SW2: OFF

 

 

SW3 & SW4: 60/90/

SW2: ON

 

 

120/180

 

50A50-438

50024561

SW1: Check

 

 

Settings

SW1: OFF

 

Inducer & HSI

SW2: ON

 

SW2: ON

 

Connector

SW3 & SW4: 60/90/

 

 

120/180

 

50A50-209

 

SW1: ON

SW1: OFF

 

 

SW2: OFF

 

 

SW3: ON

SW2: ON

 

 

SW4: ON

 

50A50-230

 

SW1: ON

SW1: OFF

 

 

SW2: OFF

 

 

SW3: ON

SW2: ON

 

 

SW4: ON

 

50A50-205

 

SW1: ON

 

50A50-206

 

SW2: OFF

SW1: OFF

50A50-207

 

SW3: ON

SW2: ON

 

 

SW4: OFF

 

50A50-288

 

 

 

 

 

50A50-142

 

SW1: ON

SW1: OFF

 

 

SW2: OFF

 

 

SW2: OFF

 

50A50-110

 

 

 

 

SW3 & SW4: 60/90/

SW1: OFF

50A50-111

 

 

120/180

SW2: ON

50A50-112

 

 

 

 

50A55-120

 

SW1: OFF

SW1: OFF

 

 

SW2: OFF

 

 

SW3: ON

SW2: OFF

 

 

SW4: OFF

 

69-2075—05

4

S9200U1000 UNIVERSAL HOT SURFACE IGNITION INTEGRATED FURNACE CONTROL

Table 1. S9200U1000 Replaces These Integrated

Furnace Controls.

[Only use the S9200U1000 on 120 Vac applications.]

 

 

 

 

 

 

 

Safety

 

 

Field Settings

Timing

 

 

Settings -

SKU

Harness

Recommendation-

DIP Switch

DIP Switch S1

S2

50A50-113

 

SW1: ON

 

 

 

SW2: OFF

 

 

 

SW3 & SW4: 60/90/

 

 

 

120/180

 

50A50-295

 

SW1: ON

 

 

 

SW2: OFF

 

 

 

SW3: ON

 

 

 

SW4: OFF

SW1: OFF

50A50-296

 

SW1: ON

SW2: ON

 

 

SW2: OFF

 

 

 

SW3 & SW4: 60/90/

 

 

 

120/180

 

50A50-408

 

SW1: OFF

 

 

 

SW2: OFF

 

 

 

SW3 & SW4: 60/90/

 

 

 

120/180

 

50A50-241

50024561

SW1: ON

 

 

SW2: OFF

SW1: OFF

 

Inducer & HSI

 

SW3 & SW4: 60/90/

SW2: ON

 

Connector

120/180

 

 

 

 

50A55-143

 

SW1: ON

 

 

50031795

SW2: 30/60

 

 

SW3 & SW4: 60/90/

 

 

 

 

 

 

120/180

 

50A55-288

 

SW1: ON

 

 

 

SW2: OFF

 

 

50024561

SW3 & SW4: 60/90/

SW1: OFF

 

120/180

 

Inducer & HSI

 

SW2: OFF

50A50-285

Connector

SW1: OFF

 

 

SW2: OFF

 

 

 

SW3: ON

 

 

 

SW4: OFF

 

50A55-285

 

SW1: ON

 

 

50031795

SW2: OFF

 

 

SW3 & SW4: 60/90/

 

 

 

 

 

 

120/180

 

 

 

 

 

Amana1

 

 

 

10207701

50024561

SW1: ON

 

10207702

SW2: OFF

SW1: OFF

Inducer & HSI

10207703

Connector

SW3: ON

SW2: ON

 

 

SW4: OFF

 

10207710

 

 

 

 

 

 

 

 

 

ICP

 

 

 

1010806

 

 

SW1: OFF

 

50024561

SW1: ON

SW2: OFF

1380-686

SW2: OFF

SW1: OFF

Inducer & HSI

 

SW3 & SW4: 60/90/

SW2: ON

 

Connector

120/180

 

1380-699

SW1: OFF

 

 

 

SW2: ON

 

 

 

 

Lennox

 

 

 

1214201

50024561

SW1: ON

 

 

SW2: OFF

SW1: OFF

 

Inducer & HSI

 

Connector

SW3: ON

SW2: OFF

 

SW4: OFF

 

 

 

 

1Wiring harness # 50031795 should be used if the control being replaced has a 2-pin inducer/igniter connector instead of a 4-pin inducer/igniter connector.

NOTE: To replace controls in Table 2, a jumper (not provided) may be required to short out the rollout switch on the main 12-pin connector plug from the furnace. The rollout switch is located between pins 5 and 11 on the 12-pin connector. Refer to Table 3 and Fig. 2 on page 7.

Table 2. Replacing Additional Controls. [Only use the S9200U1000 on 120 Vac applications.]

SKU Harness

D330927P01

D330930P01

D330934P01

D340035P01

D340354P01

D340774P01

D341235P01

50A50-571

50024561

50A55-571 Inducer & HSI Connector

50A50-473

50A50-474

50A50-405

50A50-406

50A50-471

50A55-474

50A55-438

Field Settings

Safety

Timing

Recommendatio

Settings -

n - DIP Switch

DIP Switch

S1

S2

SW1: ON

SW1: OFF

SW2: OFF

SW3 & SW4: 60/

SW2: OFF

90/120/180

 

SW1: OFF

SW1: OFF

SW2: OFF

SW3 & SW4: 60/

SW2: ON

90/120/180

 

 

 

SW1: ON

 

SW2: OFF

 

SW3: ON

 

SW4: OFF

 

SW1: ON

SW1: OFF

SW2: OFF

SW3 & SW4: 60/

SW2: OFF

90/120/180

 

SW1: OFF

 

SW2: OFF

 

SW3: ON

 

SW4: OFF

 

SW1: OFF

SW1: OFF

SW2: OFF

SW3 & SW4: 60/

SW2: ON

90/120/180

 

 

 

SW1: OFF

SW1: OFF

SW2: OFF

SW3: ON

SW2: OFF

SW4: OFF

 

SW1: Check

 

Settings

SW1: OFF

SW2: OFF

SW2: OFF

SW3 & SW4: 60/

90/120/180

 

INSTALLATION

When Installing This Product…

1.Read these instructions carefully. Failure to follow them could damage the product or cause a hazardous condition.

2.Check the ratings given in these instructions to make sure the integrated furnace control is suitable for your application.

3.Installer must be a trained, experienced service technician.

4.After installation is complete, check out operation as provided in these instructions.

5

69-2075—05

S9200U1000 UNIVERSAL HOT SURFACE IGNITION INTEGRATED FURNACE CONTROL

WARNING

Fire or Explosion Hazard.

Can cause severe injury, property damage, or death.

1.The integrated furnace control can malfunction if it gets wet, leading to accumulation of explosive gas.

Never install where water can flood, drip or condense on the control.

Never try to use an integrated furnace control that has been wet—replace it.

2.Liquefied petroleum (LP) gas is heavier than air and will not naturally vent upward.

Do not operate electric switches, lights, or appliances until you are sure the appliance area is free of gas.

WARNING

Electrical Shock Hazard.

Can cause severe injury, property damage, or death.

1.Make sure to turn power off to the furnace. Failure to do this may result in electrical shock or equipment damage

2.Disconnect power supply before beginning wiring or making wiring connections to prevent electrical shock or equipment damage.

CAUTION

Equipment Damage Hazard.

Water can cause equipment damage or malfunction.

If furnace control must be mounted near water or moisture, provide suitable waterproof enclosure.

Replacing An Existing Furnace Control

Location

In most cases the integrated furnace control is mounted on a panel within the circulator compartment of the furnace. The location must provide:

Access to the field wiring terminals.

Operating ambient temperatures between -40°F and 175°F (-40°C and 79°C).

Relative humidity below 95% non-condensing.

Protection from water, steam or corrosive chemicals that are used to clean the appliance.

Protection from dripping water, such as from an overfilled humidifier or from condensation.

Protection from dust or grease accumulation.

IMPORTANT

Be sure to identify the safety timings on the existing furnace control before any wires are disconnected. If this information is unavailable, check with the furnace manufacturer for recommended settings.

Replacement

To replace the existing furnace control:

1.Remove the access panel to gain access to the furnace control.

2.Unclip the wiring harness from the furnace control and identify/mark all wires not connected to a wiring plug.

3.Once the furnace control is free from all wiring, either unclip or unscrew the furnace control from the base plate.

4.Select the location within the appliance most suitable so that all existing cables or required harnesses will reach without straining either the cables or the plugs. We recommend mounting the S9200U1000 in the same location as the old furnace control, if possible. Ambient temperature at the S9200U1000 must be within the control specifications.

5.The S9200U1000 can be mounted vertically in any orientation. See Fig. 4 on page 9 for typical mounting orientation.

6.Secure the board to the mounting panel base plate with the two sheet metal screws inserted through the eyelets located on the edges of the board. See Fig. 1 on page 7.

7.From Table 1 on page 3, identify the wiring harness(es) required for the quick installation of the S9200U1000. The provided wiring harness adapters are intended to connect to the existing wiring harness. See Table 3 on page 7 and Table 4 on page 8 for pin-out information for the provided wiring harnesses.

8.Connect the appropriate end of the wiring harness to the 12-pin plug on the S9200U1000 (if required) and the other end to the existing wiring plug (previously removed from the existing furnace control). Connect the appropriate igniter/inducer harness (if required) to the 4 pin plug and the other end to either the existing plug or spade connectors (previously removed from the existing furnace control).

IMPORTANT

The provided wiring harnesses are keyed. Do not force the connection if the plug on the harness and receptacle on the S9200U1000 do not easily snap closed.

9.Connect the quick-connect cables to the appropriate contacts on the S9200U1000

10.Set the Safety timings as required using switch S2. Refer to Table 10 on page 12 for switch setting information.

11.Set the field selectable timings as required using switch S1. Refer to Table 9 on page 11 for setting information.

12.Review the connections to insure no wiring is loose and there is a proper earth ground to the appliance chassis.

13.Turn power ON to the appliance. See “Checkout” on page 13 and the control sequence diagrams, Fig. 9- Fig. 11 beginning on page 17.

69-2075—05

6

Honeywell S9200U1000 Installation Manual

S9200U1000 UNIVERSAL HOT SURFACE IGNITION INTEGRATED FURNACE CONTROL

1 1/2

(38)

4 1/8

(105)

6 1/8

(156)

M24905

Fig. 1. S9200U1000 dimensions in inches and (mm).

Wiring

WARNING

Fire or Explosion Hazard.

Can cause severe injury, property damage, or death.

Make sure the proper wiring harness is used. Check the cross reference tables (Table 1 on page 3) and review the appliance wiring schematic.

The S9200U1000 is intended to connect to the appliance with the aid of wiring harnesses. Carefully review the wiring harness selection table for the correct wiring harnesses. See Table 1 on page 3.

Check the wiring diagram (Fig. 4 on page 9) and the diagram furnished by the appliance manufacturer for all terminal designations. Table 5 and Table 6 beginning on page 8 describe the wiring connections for Class 2 and Class 1 installations.

Typical wiring connections are shown in Fig. 5 on page 10.

Check the wiring diagrams furnished by the appliance manufacturer, if available, for circuits that differ from the general hookup shown. Carefully follow any special instructions affecting the general procedures outlined below.

All wiring must comply with local codes and ordinances.

See “Wiring Harnesses” for the main and igniter/inducer harness plug connections and details.

See “Wiring Connections” on page 8 for wiring connections, but also refer to furnace manufacturer instructions, if available.

NOTE: The Safety Timing jumper is described in Table 7 on page 11.

IMPORTANT

The common ground required for the S9200U1000 and the main burner must be supplied through the plug connected to the Main Harness (12-pin connector) receptacle on the board.

Wiring Harnesses

The following describes the main and igniter/inducer harness connections.

MAIN HARNESS PLUG CONNECTIONS

The following describes the harness plug connectors for the main harness. See Table 3 and Fig. 2.

IMPORTANT

The common ground required for the S9200U1000 and the main burner must be supplied through the plug connected to the Main Harness (12-pin connector) receptacle on the board.

Table 3. Main Harness Plug Connector 12-pin

(Class 2, Low Voltage).

Pin #

 

 

Function

 

1

High Limit Out

 

 

 

2

Flame Sense - Flame Signal Input (90 Vac, current limited)

3

24 Vac Hot

 

 

 

4

Not Used

 

 

 

5

Rollout Switch Out

 

 

 

6

24 Vac Common

 

 

 

7

High Limit In + Pressure Switch Out

 

8

Chassis Ground

 

 

 

9

Main Valve Common

 

 

10

Pressure Switch In

 

 

 

11

Rollout Switch In

 

 

 

12

Main Valve

 

 

 

.

 

 

 

 

 

1

4

7

10

 

2

5

8

11

 

3

6

9

12

 

 

 

 

M24906

Fig. 2. S9200U1000 Main harness plug configuration.

7

69-2075—05

S9200U1000 UNIVERSAL HOT SURFACE IGNITION INTEGRATED FURNACE CONTROL

IGNITER/INDUCER HARNESS PLUG CONNECTIONS

The following describes the harness plug connectors for the igniter/inducer. See Table 4 and Fig. 3.

Table 4. Igniter/Inducer Harness Plug Connector 4-pin

(Class 1, Line Voltage).

Pin #

 

 

Reference Lettering

 

 

Function

1

IND-HOT

 

 

 

Inducer 120 Vac

2

IGN-HOT

 

 

 

Igniter 120 Vac

3

IND-NEUTRAL

 

 

 

Inducer Neutral

4

IGN-NEUTRAL

 

 

 

Igniter Neutral

.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4

 

3

2

 

1

 

M24907

Fig. 3. S9200U1000 Igniter/Inducer harness plug configuration.

Wiring Connections

Table 5 describes the wiring connections for Class 2 voltages.

Table 6 describes the wiring connections for Class 1 voltages.

See Fig. 5 on page 10 for wiring connection locations on the board.

Table 5. Wiring Connections (Class 2, Low Voltage).

 

Connection

 

Terminal Type

(see Fig. 4

Connects S9200U1000 to:

on page 9)

6-position

D/1 (optional)

EnviraCOM™ data connection (if

screw terminal

 

used)

(#5 screw)

 

 

C/3

24 volt ground

 

 

R/2

24 volt hot - Thermostat

 

W

Thermostat heat input

 

G

Thermostat continuous fan input

 

Y

Thermostat cool input / cooling

 

 

contactor output for EnviraCOM™

 

 

thermostats

Polarized 3-pin

E-COM

EnviraCOM™ diagnostic or

connector

 

communications device

12-pin

Main

See Table 3 on page 7

connector

Harness

 

 

Connector

 

Straight Spade

24 Vac

Transformer - 24 Vac

Quick-connect

 

 

COM

Transformer - Common

 

Fuse Block

Fuse

Fuse - Automotive Type - 3.0 Amps

. Table 6. Wiring Connections (Class 1, Line Voltage).

 

Connection

 

 

Terminal Type

(see Fig. 4

 

Connects S9200U1000 to:

on page 9)

 

4-pin

Igniter-

See Table 4

connector

Inducer

 

 

(male

Harness

 

 

terminals)

Connector

 

 

Straight Spade

COOL

Circulator cool speed output

Quick-connect

 

 

 

EAC

Electronic Air Cleaner 120 Vac output

 

 

HEAT

Circulator heat speed output

 

CONT

Continuous circulation

 

XFMR

Transformer 120 Vac output

 

L1

Line 120 Vac hot power supply

 

HUM

Humidifier 120 Vac output

 

PARK

Circulator Motor Park 120 Vac input

 

PARK

Circulator Motor Park 120 Vac input

Straight Spade

Neutrals

Any neutral connector can be used

Quick-connect

 

for:

 

 

 

120 Vac Input neutral

 

 

Transformer neutral

 

 

Electronic air cleaner neutral

 

 

Circulator neutral

 

 

Humidifier neutral

Straight Spade

Flame

Flame Sense - Signal input (90 Vac,

Quick-connect

 

current limited)

69-2075—05