MS4120F; MS4620F,S; MS8120F,S; S2024-F; S20230-F
Fast-Acting, Two-Position Actuators
PRODUCT DATA
• 175 lb-in. (20 N•m) minimum driving torque at 350°F (176°C).
• Reversible mounting facilitates use in either clockwise (cw) or counterclockwise (ccw) spring rotation.
• Integral spring return ensures level of return torque.
• Stainless steel internal spring.
• Fifteen-second spring return timing.
• No special cycling required during long-term holding. (See Operation section.)
• No audible noise during holding.
• Patent pending design eliminates need for limit switches to reduce power consumption.
• Models available for 24, 120, and 230 Vac applications.
• Ninety-five degree angle of rotation.
• Actuator holds rated torque at reduced power level.
• Die-cast aluminum housing.
The MS4120F, MS4620F, MS8120F, S2024-F, and S20230-F Fast-Acting, Two-Position Actuators are spring return direct coupled actuators (DCA) for on/off damper control. The actuator accepts an on/off signal from a single-pole, singlethrow (spst) controller. Reversible mounting allows actuator to be used for either clockwise (cw) or counterclockwise (ccw) spring rotation.
Designed to operate reliably in smoke control systems requiring Underwriter’s Laboratories Inc. UL555S ratings up to 350°F.
•Housing design allows flush mounting to damper.
•Self-centering shaft adapter (SCSA), patent pending.
•Designed to operate reliably in smoke control systems requiring Underwriter’s Laboratories Inc. UL555S ratings up to 350°F.
MS4120F, MS4620F, MS8120F
•High temperature Teflon® lead wires.
•Models available with integral high temperature (350°F) SPST position-indicating switches (7°, 85° stroke).
— Specification Data Sheet |
63-2592 |
— Motor/Actuator Selection Guide |
|
for Damper Applications |
63-8419 |
— Engineering Manual of Automatic Control |
|
(also called The Gray Manual) |
77-1100 |
— Direct Coupled Actuator |
|
Quick Selection Guide |
63-8553 |
— Damper Torque Calculator |
63-8437 |
S2024-F, S20230-F, MS4620S, MS8120S
•Double-insulation rating.
•High-temperature, halogen-free, silicone-free leadwires.
•Models available with integral high temperature (350°F) SPDT position-indicating switches (7°, 85° stroke).
63-2584—7
MS4120F; MS4620F,S; MS8120F,S; S2024-F; S20230-F FAST-ACTING, TWO-POSITION ACTUATORS
Models: See Tables 1, 2, and 3.
Table 1. Models.
|
Voltage |
Internal Auxiliary |
Model |
in Vac |
Switches |
MS4120F1006 |
120 |
None |
|
|
|
MS4120F1204 |
120 |
2 SPSTa |
MS4620F1005 |
230 |
None |
|
|
|
MS4620F1203 |
230 |
2 SPSTa |
MS8120F1002 |
24 |
None |
|
|
|
MS8120F1200 |
24 |
2 SPSTa |
S2024-F (MS8120S1006) |
24 |
None |
|
|
|
S20230-F (MS4620S1009) |
230 |
|
|
|
|
S2024-F-SW2 (MS8120S1204) |
24 |
2 SPDTa |
S20230-F-SW2 (MS4620S1207) |
230 |
|
|
|
|
aInternal switches are designed to pass UL555S requirements (at 350°F).
Dimensions: See Fig. 1.
Device Weight: 7 lb (3.2 kg).
Stroke: 95° ± 3°, mechanically limited.
Electrical Ratings:
Power Input:
MS4120F: 120 Vac ±10%, 60 Hz.
MS4620F,S; S20230-F: 230 Vac ±10%, 50/60 Hz.
MS8120F,S; S2024-F: 24 Vac +20%, -10%, 50/60 Hz
(Class 2).
Power Consumption:
MS4120F: Driving: 0.35A, 35W. Holding: 0.15A, 10W.
MS4620F,S; S20230-F:
Driving: 0.20A, 35W. Holding: 0.14A, 10W.
MS8120F,S; S2024-F: Driving: 45 VA. Holding: 10 VA.
Electrical Connections:
Lead Wires:
MS4120F, MS4620F, MS8120F: 1m Teflon wire. MS4620S, MS8120S, S2024-F, S20230-F: 1m halogen-
free, silicone-free wire.
Two integral 3/8 in. flexible conduit connections.
Timing (At Rated Torque and Voltage):
Drive Open: 15 seconds typical.
Spring Close: 15 seconds typical.
Auxiliary Switches:
Ratings (maximum load): 250 Vac, 5A resistive, 3A inductive. Settings (fixed): 7° nominal stroke, 85° nominal stroke.
Torque Rating (at Rated Voltage):
Typical Holding (minimum at 350°F): 175 lb-in. (20 N•m). Spring Return (minimum at 350°F): 175 lb-in. (20 N•m). Stall Maximum (fully open at 75°F): 425 lb-in. (48.0 N•m). 350°F Minimum Driving: 175 lb-in. (20 N•m).
Design Life (at Rated Voltage): 30,000 full stroke cycles.
Minimum Damper Shaft Length:
1 in. (25 mm); 3-1/4 (83 mm) recommended.
Cycling Requirements:
Prolonged holding-period (1 year) testing of these actuators has been performed with no spring return failures. The actuator and the internal spring are designed to require no special cycling during long-term holding.
Honeywell recommends following all local, state and national codes for periodic testing of the entire smoke control system. Refer to National Fire Protection Association (NFPA) National Fire Codes®: NFPA90A, NFPA92A and NFPA92B for your application.
NFPA recommends periodic examination of each fire/smoke damper (semi-annually or annually) to ensure proper performance.
Mounting: Self-centering shaft adapter. Round Damper Shafts: 0.5 to 1.06 in. Square Damper Shafts: 1/2 to 3/4 in.
Actuator can be mounted with shaft in any position.
IMPORTANT
•Honeywell does not recommend using linkages with these actuators because side-loading of the output hub reduces actuator life.
•3/4 in. or greater shaft diameter recommended.
Noise Rating at 1m (Maximum):
Driving or Spring Return: 70 dBA.
Holding: 20 dBA (no audible noise).
ORDERING INFORMATION
When purchasing replacement and modernization products from your TRADELINE® wholesaler or distributor, refer to the TRADELINE® Catalog or price sheets for complete ordering number.
If you have additional questions, need further information, or would like to comment on our products or services, please write or phone:
1.Your local Honeywell Automation and Control Products Sales Office (check white pages of your phone directory).
2.Honeywell Customer Care 1885 Douglas Drive North
Minneapolis, Minnesota 55422-4386
In Canada—Honeywell Limited/Honeywell Limitée, 35 Dynamic Drive, Scarborough, Ontario M1V 4Z9.
International Sales and Service Offices in all principal cities of the world. Manufacturing in Australia, Canada, Finland, France, Germany, Japan, Mexico, Netherlands, Spain, Taiwan, United Kingdom, U.S.A.
63-2584—7 |
2 |
MS4120F; MS4620F,S; MS8120F,S; S2024-F; S20230-F FAST-ACTING, TWO-POSITION ACTUATORS
Temperature Ratings:
Ambient: -40°F to 130°F (-40°C to 55°C).
Shipping and Storage: -40°F to 140°F (-40°C to 60°C).
IMPORTANT
The actuator is designed to meet UL555S standards at 350°F (176°C). The actuator must be tested with the damper to achieve this rating.
NOTE: The actuator is designed to operate for 30 minutes during a one-time excursion to 350°F (176°C).
Humidity Ratings: 5% to 95% RH noncondensing.
Environmental Protection Ratings:
NEMA2 and IP54 when mounted on a horizontal shaft.
Accessories:
205649 Mounting Bracket (not supplied with actuator).
Approvals: See Table 4.
Controller Type:
MS4120F: Line voltage (120 Vac), 2-position, spst (Series 40). MS4620F,S; S20230-F: Line voltage (230 Vac), 2-position, spst
(Series 40).
MS8120F,S; S2024-F: Low voltage (24 Vac), 2-position, spst (Series 80).
Table 2. Actuator Selection (MS Series).
M Electrical Motor
S Fail Safe Function (Spring Return)
|
|
41 |
120 Vac 2-position Control; Reversible Mount Spring Return |
||||||||||||
|
|
46 |
230 Vac 2-position Control; Reversible Mount Spring Return |
||||||||||||
|
|
81 |
24 Vac 2-position Control; Reversible Mount Spring Return |
||||||||||||
|
|
|
|
|
20 |
175 lb-in. (20 N•m) |
|||||||||
|
|
|
|
|
|
|
F |
Fire and Smoke (US) |
|||||||
|
|
|
|
|
|
|
S |
Fire and Smoke (EU) |
|||||||
|
|
|
|
|
|
|
|
|
1 |
No Feedback |
|||||
|
|
|
|
|
|
|
|
|
|
|
0 |
No Auxiliary Switches |
|||
|
|
|
|
|
|
|
|
|
|
|
2 |
Two Auxiliary Switches |
|||
|
|
|
|
|
|
|
|
|
|
|
|
|
XX |
System Controlled Numbers |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
M |
S |
41 |
20 |
F |
1 |
2 |
XX |
|
Table 3. Actuator Selection (S20 Series).
SFail Safe Function (Spring Return) 20 20 N•m (175 lb-in.)
24 24 Vac 2-position Control; Reversible Mount Spring Return
230 Vac 2-position Control; Reversible Mount Spring
230 Return
F Fire and Smoke Actuator
No Auxiliary Switches
-SW2 Two Auxiliary Switches
S 20 24 - F -SW2
Table 4. Approvals.
|
|
|
S20230-F, |
|
|
|
S2024-F, |
|
|
MS4620F, |
MS4620S, |
|
MS4120F |
MS8120F |
MS8120S |
UL/cUL |
X |
X |
|
|
|
|
|
UL873 Plenum Rating, |
X |
X |
|
File No. E4436; |
|
|
|
Guide No. XAPX.a |
|
|
|
CE |
|
X |
X |
|
|
|
|
C-TICK |
|
X |
X |
|
|
|
|
aPlenum applications require that conductors be enclosed in conduit (see Wiring section for conduit details).
3-15/16 (100) 2 (50)
1-9/16
(40)
10-11/16
(271)
8-5/8
(220)
M20051 |
1/4 (6) |
2-15/16 (75) |
Fig. 1. Dimensional drawing of actuator in inches (mm).
3 |
63-2584—7 |
MS4120F; MS4620F,S; MS8120F,S; S2024-F; S20230-F FAST-ACTING, TWO-POSITION ACTUATORS
1.Read these instructions carefully. Failure to follow them could damage the product or cause a hazardous condition.
2.Check the ratings given in the instructions and on the product to make sure the product is suitable for your application.
3.Installer must be a trained, experienced service technician.
4.After installation is complete, check out product operation as provided in these instructions.
WARNING
Electrical Power Hazard.
Line voltage can cause death or serious injury and short equipment circuitry.
Disconnect power supply before installation.
CAUTION
Electrical Shock or Equipment Damage Hazard. Low voltage can shock individuals or short equipment circuitry.
Disconnect power supply before installation.
IMPORTANT
All wiring must agree with applicable codes, ordinances and regulations.
The actuators are designed to open a damper by driving the damper shaft in either a clockwise or counterclockwise
direction. The actuator housing has two slots on the bottom, either of which, with a 205649 Mounting Bracket, secures it flush to a damper box (see Fig. 2).
NOTE: When mounted correctly, these slots allow the actuator to float without rotating relative to the damper shaft.
CAUTION
Equipment Damage Hazard.
Tightly securing actuator to damper housing can damage actuator.
Mount actuator to allow it to float along its vertical axis.
Before mounting the actuator onto the damper shaft, determine the:
—Damper/valve opening direction for correct spring return rotation. The actuator can be mounted to provide clockwise or counterclockwise spring return.
—Damper shaft size (see Specifications section).
Determine Appropriate Mounting Orientation
See Fig. 2 for mounting orientation.
NOTES:
—Actuators are shipped in the fully closed position.
—An arrow molded into the hub points to tick marks on the label to indicate the hub rotary position.
—See Fig. 3 for proper mounting to a square damper shaft.
CCW TO CLOSE |
CW TO CLOSE |
(FAIL-SAFE |
(FAIL-SAFE |
POSITION) |
POSITION) |
CW TO OPEN |
CCW TO OPEN |
M20052
Fig. 2. Spring Return DCA mounting orientation.
M21007 |
DAMPER SHAFT |
|
Fig. 3. Proper mounting to square damper shaft.
Measure Damper/Valve Shaft Length
If the shaft is less than three inches in length, the shaft coupling must be located between the damper/valve and actuator housing. If the shaft length is more than three inches, the shaft coupling may be located on either side of the actuator housing.
If the coupling must be moved from one side of the actuator to the reverse, follow these instructions (see Fig. 4):
1.Remove the retainer clip from the shaft coupling and set it aside for later use.
2.Remove shaft coupling from one side of the actuator.
3.Replace the shaft coupling on the opposite side of the actuator aligning it based on the stroke labelling.
4.Replace the retainer clip on the shaft coupling using the groove of the coupling.
63-2584—7 |
4 |