Honeywell PFU 780 Technical Information

Page 1
Industrial & Commercial Thermal
AGA

Burner control unit PFU 780

Technical Information · GB
6 Edition 02.12l
• For pilot and main burners of unlimited capacity in thermoprocessing equipment pursuant to EN 7462
• Display of the program status, unit parameters and flame signal; Manual mode for burner adjustment and for diagnostic purposes
Page 2

Table of contents

Burner control unit PFU 780.........................1
Table of contents ....................................2
1 Application ........................................4
1.1 Examples of application ...........................6
1.1.1 Stage-controlled main burner with alternating
pilot burner ..................................................6
1.1.2 Stage-controlled main burner with permanent
pilot burner ..................................................7
1.1.3 Modulating-controlled burner ........................8
1.1.4 PFU 780..D: High temperature equipment............9
2 Certification ..................................... 10
3 Function ..........................................11
3.1 Connection diagram ..............................11
3.1.1 PFU 780 ..............................................11
3.1.2 PFU 780..K2 .........................................12
3.2 PFU 780 program sequence......................13
3.3 Program status and fault messages..............16
4 Parameters .......................................18
4.1 Scanning the parameters .........................19
4.2 Flame control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
4.2.1 Flame signal, pilot burner ...........................20
4.2.2 Flame signal, main burner...........................20
4.2.3 Program status when the most recent fault
occurred . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
4.2.4 Switch-off threshold of the flame amplifier.........20
4.2.5 High temperature operation with PFU..D . . . . . . . . . . . .21
4.2.6 UVS check ........................................... 24
4.3 Pilot and main burner monitoring ................25
4.3.1 Permanent pilot burner...............................27
4.3.2 Interrupted pilot burner .............................28
4.4 Behaviour in start-up position/standby ..........29
4.4.1 Flame simulation check in start-up position/
standby ....................................................29
4.4.2 Minimum burner pause time t
4.5 Behaviour during start-up ........................31
....................30
BP
4.5.1 Safety time on start-up tSA ..........................31
4.5.2 Flame proving period t
4.5.3 Minimum combustion time t
4.5.4 Burner start-up at tempts ...........................33
...........................32
FS
......................32
B
4.6 Behaviour during operation.......................35
4.6.1 Safety time during operation tSB for pilot and main
burners ....................................................35
4.6.2 Fault lock-out or restart , pilot burner ...............35
4.6.3 Fault lock-out or restart, main burner ................37
4.7 Air valve control PFU..L ...........................39
4.7.1 Purge.................................................39
4.7.2 Cooling in start-up position/standby ...............39
4.7.3 Burner start ..........................................39
4.7.4 Air valve opens in the case of external activation
(not during start-up).......................................40
4.7.5 Air valve opens in the case of external activation
(even during start-up) ......................................41
4.7.6 Air valve opens with valve V2 ........................ 42
4.7.7 Air valve opens with operating signal ................43
4.7.8 Low fire over run time t
4.7.9 Behaviour of the air valve in the event of a fault
lock-out.................................................... 45
after a normal shut-down 44
KN
4.8 Manual operation ................................ 46
4.8.1 Manual mode limited to 5 minutes..................46
4.9 Password .........................................47
5 Selection ........................................ 48
5.1 Calculating the safety time t
.................. 48
SA
5.2 Selection table ....................................49
5.2.1 Type code............................................49
6 Project planning information .................... 50
6.1 Cable selection .................................. 50
6.1.1 Ignition cable........................................50
6.1.2 Ionisation cable .....................................50
6.1.3 UVLeitung ..........................................50
6.2 Ignition electrode ................................ 50
6.2.1 Electrode gap .......................................50
PFU 780 · Edition 02.12l 2
= To be continued
Page 3
6.2.2 Star electrodes ......................................50
6.3 Minimum combustion time.......................51
6.4 Safety interlocks (Limits) .........................51
6.5 Emergency stop ..................................52
6.5.1 In the event of fire or electric shock . . . . . . . . . . . . . . . . . 52
6.5.2 Via the safety interlocks (limits)..................... 52
6.6 Reset ..............................................52
6.6.1 Parallel reset......................................... 52
6.6.2 Permanent remote reset ............................ 52
6.6.3 Automatic remote reset (PLC) ...................... 52
6.6.4 Burner start ......................................... 52
6.6.5 Restart and start-up attempts ......................52
6.7 Fault message ....................................53
6.8 Protecting the pilot burner from overload ........53
6.9 Installation........................................53
6.10 Wiring............................................53
6.10.1 UVS sensor wiring..................................53
6.11 PFU switched off ................................53
6.12 Furnace control .................................54
6.13 Note on EC type-examination...................54
6.14 Mains switch ....................................54
6.15 Changing parameters ...........................54
7 Flame control .....................................55
7.1 With ionisation sensor ............................55
7.2 With UV sensor ....................................55
7.3 Via the temperature in high temperature
equipment ............................................55
8 Accessories...................................... 56
8.1 High-voltage cable ...............................56
8.2 BCSoft ............................................56
8.3 Stickers for labelling ..............................56
8.4 “Changed parameters” stickers ..................56
8.5 Radio interference suppressed electrode
adapters ..............................................57
8.6 Socket connectors ................................57
8.7 Module subrack ...................................57
8.8 Power supply PFP 700............................58
8.9 Relay module PFR 704 ...........................59
8.10 Field bus interface PFA 700.................... 60
8.11 Impulse system MPT 700 .......................61
9 Technical data ....................................62
9.1 Safety-specific characteristic values .............64
9.2 Operating controls................................65
10 Maintenance cycles ............................ 66
11 Legend ..........................................67
12 Glossary........................................ 68
12.1 Waiting time
tW ..............................68
12.2 Safety time on start-up tSA ..................... 68
12.3 Ignition time t
................................. 68
Z
12.4 Flame simulation/Flame simulation delay time t
12.5 Safety time during operation t
..........................................68
LV
.............69
SB
12.6 Flame signal .....................................69
12.7 Fault lock-out ....................................69
12.8 Safety interlocks (Limits) ........................69
12.9 Pilot gas valve V1 ................................69
12.10 Main gas valve V2 ..............................69
12.11 Continuous operation..........................70
12.12 Air valve.........................................70
12.13 Diagnostic coverage DC .......................70
12.14 Mode of operation..............................70
12.15 Safe failure fraction SFF .......................70
12.16 Probability of dangerous failure PFH
12.17 Mean time to dangerous failure MT TF
........70
D
.......70
d
Feedback ...........................................71
Contact.............................................71
PFU 780 · Edition 02.12l 3
= To be continued
Page 4
Application
Module subrack BGT for instance serves to accom­modate several function units. It is provided with a backplane with screw terminals for simple, reliable wiring.

1 Application

The burner control units PFU 780 control, ignite and
monitor gas burners for intermittent or continuous op­eration. As a result of their fully electronic design they react quickly to various process requirements and are therefore also suitable for frequent cycling operation.
The PFU 780 can be used for industrial burners of un-
limited capacity which are ignited by pilot burners. Pilot and main burners are controlled and monitored inde­pendently. This reduces the main burner start-up time.
The pilot burner can burn permanently or be switched
off. The main burners may be modulating or stage­controlled.
the burner always ignites in a safe condition after it has been restarted.
The burner control unit is used for burners with me-
chanical combustion air supply where the fan is con­trolled by a separate logic and for atmospheric burners.
The air valve control on the PFU 780L assists the fur-
nace control for cooling, purging and capacity control tasks.
The program status, the unit parameters and the level
of the flame signal can be read directly from the unit.
Pilot and main burners can be controlled manually for
commissioning and diagnostic purposes.
On industrial furnaces, the PFU 780 reduces the load on the central furnace control by taking over tasks that only relate to the burner, for example it ensures that
PFU 780 · Edition 02.12l 4
Page 5
Application
If the local requirements on the burner control units change, the PC software BCSoft can be adjusted to the unit parameters of the application by using the optical interface.
To support service personnel, BCSoft offers a conveni-
ent visualisation system of the input and output signals and the error history.
Intermittent shuttle kiln in the ceramics industry
Bogie hearth forging furnace in the metallurgical industry
Walking beam furnace with overhead firing
PFU 780 · Edition 02.12l 5
Page 6
Application
PFU 780
22e

1.1 Examples of application

1.1.1
Stage-controlled main burner
with alternating pilot burner
L1, N, PE
DI
P
SPS PLC CPE
DI
26e 10c
22a
A
P
ϑ1
ϑ2
14a 30e 10a
10e
µC
28c 16c 18e
18a
2e 4e
2c 4c
6a 6e
1
2
TZI
VBY
1
2
UV
VAG
Control: Main burner ON/OFF.
The main burner can be started with
reduced capacity after the operat­ing signal from the pilot burner has been detected. The pilot burner is switched off automatically after the main burner has started up. When the main burner is switched off, the pilot burner automatically switches on again.
A UV sensor monitors the flame sig­nal from pilot and main burners. UV sensor UVD 1 is used for continu­ous operation, UV sensor UVS for intermittent operation.
02–04 02–04 06–08 06–08
VR..L
ϑ1
1
ϑ2
2
t
PFU 780 · Edition 02.12l 6
Page 7
Application
PFU 780
22e

1.1.2 Stage-controlled main burner with permanent pilot burner

Control: Main burner ON/OFF.
L1, N, PE
DI
P
SPS PLC CPE
DI
26e 10c
22a
A
P
VBY
ϑ1
ϑ2
14a 30e 10a
10e
µC
26a
28c 16c 18e
18a
TZI
1
2
2e 4e
2c 4c
6a 6e
1
2
VAG
The main burner can be started with
reduced capacity after the operat­ing signal from the pilot burner has been detected. Pilot and main burn­ers can be operated simultaneously. Both are ionisation-controlled inde­pendently.
04 02–04 06–08 06–08
VR..R
04
ϑ1
1
ϑ2
2
t
PFU 780 · Edition 02.12l 7
Page 8
Application
PFU 780
1.1.3

Modulating-c ontrolled burner

Control: Main burner continuous
The butterfly valve for air BV is
moved to ignition position in order
L1, N, PE
DI
P
SPS PLC
mA
CPE
DI
26e 10c
22a
16c 18e
VBY
28c
TZI
1
26a
ϑ1
µC
2
10e
18a
ϑ2
14a
2e 4e
2c 4c
6a 6e
1
2
VAG
to start the main burner. The main burner can be started at low-fire rate after the operating signal from the pilot burner has been detected.
The control system controls the
burner capacity via the butterfly valve for air BV after the operating state has been signalled. Pilot and main burners can be operated si­multaneously.
M
BV+IC
PFU 780 · Edition 02.12l 8
Page 9
Application
PFU 780..D
STWL1>750 °C
PFU 780..D

1.1.4 PFU 780..D: High temperature equipment

The flame is controlled indirectly on
the basis of the temperature. During the start-up process, as long as the wall temperature is below auto igni­tion temperature the flame must be controlled by conventional meth­ods. When the working temperature has exceeded 750°C, the safety temperature monitor (STW) takes over the indirect flame control.
µC
26a
18a
22a
DI
PFU 780 · Edition 02.12l 9
µC
26a
18a
22a
DI
Page 10
Certification
2 Certification
Certified pursuant to SIL
For systems up to SIL 3 pursuant to EN 61508
Pursuant to EN ISO 138491:2006, Table 4, the PFU can be used up to PL e.
EC type-tested and certified
pursuant to
– Gas Appliances Directive (2009/142/EC) in conjunc-
tion with EN 298:200401,
Meets the requirements of the
– Low Voltage Directive (2006/95/EC),
– EMC Directive (2004/108/EC).
AGA approved
AGA
Australian Gas Association, Approval No.: 5597
www.aga.asn.au/product _directory
PFU..T is FM approved
Factory Mutual Research Class: 1997.
Suitable for applications pursuant to NFPA 86. www.approvalguide.com
PFU 780 · Edition 02.12l 10
Page 11
Function
L1 (L1)
N (L2)
24 V
0 V
P
30e
26e
DI
22a
30a
20c 230 V
28c
N
26a
18a
ϑ1
10e
12e
ϑ2
14a
14e
A
10a
12a
10c
12c
32c 24c
c2
c1
PFU 780
F1
1
2
µC
sk1
l
22e
v1
16c
v2
18e
N

3.1 Connection diagram

V1
V2
For cable selection and wiring, see page 50 (Project
planning information).

3.1.1 PFU 780

For the explanation of symbols, see page 67 (Legend).
2a
a
4a
2e
s
4e
2c
m
n
A
S
SK
M
N
L
V2
V1
C
1
4c
6a 6e
max. 1 A, 24 V
2

3 Function

Z
I
26a
28c N
18a
26a
28c
N
UVS
18a
1 2
20c
3
24c
PFU 780 · Edition 02.12l 11
Page 12
Function
L1 (L1)

3.1.2 PFU 780..K2

P
30e
26e
DI
22a
PFU 780..K2
F1
sk1
l
v1
v2
22e
16c
18e
N
V1
V2
As a replacement unit for burner control unit PFU 798.
For the explanation of symbols, see page 67 (Legend).
N (L2)
24 V
0 V
Z
I
26a
ϑ2
30a
32c 24c
20c 230 V
c2
28c
N
c1
26a
18a
ϑ1
10e
12e
14a
14e
A
10a
12a
10c
12c
28c N
1
2
µC
28c
N
26a
18a
UVS
2a
a
4a
2e
s
4e
2c
m
n
A
S
SK
M
N
L
V2
V1
C
1
4c
6a 6e
18a
1 2
20c
3
24c
max. 1 A, 24 V
2
PFU 780 · Edition 02.12l 12
Page 13
Function
A
00
01
02
Switch on PFU 780
In the event of fault signal:
Safety interlocks (Limits)
Start-up position/standby
flame simulation check
Flame simulation check
next start-up attempt (P10)
Reset
If parameter P15 = 1:
Pilot burner start-up
with ϑ1 signal
Wait until
waiting time t
has elapsed
If parameter P15 = 0:
Safety time t
running (P22),
ignition in process,
V1 opens and min.
combustion time tB
starts to elapse (P20)
If no flame detected:
or fault lock-out
W
SA1
PFU 780
If the air valve control is used, the unit offers the following additional functions:
In start-up position, the air valve can be opened for cool-
(display A0).
ing
Using parameter 31, it can be determined whether the air valve can be activated exter­nally during start-up (display A1).
The air valve can be set to open
together with V1 (display via parameter 30.
A2
)
3.2

PFU 780 program sequence

Normal start-up
If an “old” fault is still being sig­nalled after switching on, it will be necessary to reset this first.
The safety interlocks (terminal 26e)
must be closed and the burner con­trol unit must be switched on.
The PFU 780 conducts a self-test
when in the start-up position (the burner is switched off). If it does not determine a malfunction of the internal electronic circuitry or of the flame sensors, the burner can be started. The pilot burner start-up is activated via the signal input “Start­up signal ϑ1” (terminal 10e). Once the start-up signal ϑ1 has been applied, the PFU 780 opens valve V1 and ignites the burner. The igni­tion time t
is constant. If a flame
Z
is detected during the safety time t
, the flame proving period t
SA1
starts after the safety time t
SA1
FS1
has
elapsed.
If the pilot burner has been started successfully and its flame has stabilised, the burner control unit issues the Enable signal for main burner operation. The operation sig­nalling contact for the pilot burner (terminals 2c/4c) closes.
PFU 780 · Edition 02.12l 13
Page 14
If no flame detected:
next start-up attempt (P10)
or fault lock-out
Function
03
04
05
Flame proving period t
running (P23)
In the event of flame failure:
restart or fault lock-out
Operating signal
Pilot burner closes
In the event of flame failure:
restart or fault lock-out
Main burner start-up
with ϑ2 signal
Wait until
min. burner pause time t
has elapsed (P21)
FS1
BP
The PFU coordinates the correct
The air valve can be set to open
together with V1 (display via parameter 30.
A3
)
program run for the pilot and main burners. The main burner can be started via the signal input “Start­up signal ϑ2” (terminals 14a/14c) if required.
Once the start-up signal ϑ2 has been applied (terminals 14a and
The air valve can be set to open
together with V1 (display A4) via parameter 30.
14e), the PFU 780 opens valve V2. The main burner is ignited by the
pilot burner.
If a flame is detected during the safety time t
The air valve can be set to open
A5
together with V1 (display via parameter 30.
)
time t burner has been started success­fully and its flame has stabilised, the operation signalling contact
period t
FS2
has elapsed. If the main
SA2
, the flame proving
SA2
starts after the safety
(terminals 6a/6e) closes.
If parameter P15 = 0:
Flame simulation check
Start-up of the pilot burner without flame signal
If no flame is detected during the
06
Safety time t
min. combustion time tB
starts to elapse (P20)
running (P24),
SA2
V2 opens and
The air valve can be set to open
with V2 or to be activated ex­ternally (display eter 30.
A6
) via param-
safety time t out occurs or up to three further start-up attempts occur. (Param­eter 10, “Pilot burner start-up at-
, either a fault lock-
SA1
tempts”).
If no flame detected:
next start-up attempt (P11)
or fault lock-out
PFU 780 · Edition 02.12l 14
Page 15
If no flame detected:
next start-up attempt (P11)
or fault lock-out
Function
07
08
08
00
Flame proving period
t
running (P25)
FS2
In the event of flame failure:
restart or fault lock-out
Operating signal
Main burner closes
In the event of flame failure:
restart or fault lock-out
Normal shut-down
via ϑ signal for
pilot and main burners
If min. combustion time t
has elapsed:
Operation signalling contact
V1 and V2 close,
min. burner pause time tBP
starts to elapse (P21)
opens,
Behaviour of the pilot burner in the event of flame failure during
The air valve can be set to open
with V2 or to be activated ex­ternally (display A7) via param­eter 30.
operation
If the flame fails during operation, either an immediate fault lock-out occurs or a restart occurs. This pro­cedure can be set via the optical in-
The air valve can be set to open
with the operating signal or to be activated externally (display
A8
) via parameter 30.
terface (parameter 12, “Pilot burner restart”).
Behaviour of the main burner in the event of flame failure during start-up
If no flame is detected during the safety time t
, either a fault lock-
SA2
out occurs or up to three further start-up attempts occur. (Param­eter 11, “Main burner start-up at­tempts”).
B
Behaviour of the main burner in the event of flame failure during operation
If the flame fails during operation, either an immediate fault lock-out occurs or a restart occurs. This pro­cedure can be set via the optical in­terface (parameter 13, “Main burner restart”).
PFU 780 · Edition 02.12l 15
Page 16
Function

3.3 Program status and fault messages

During operation, the 7-segment display shows the pro­gram status. In the event of a fault, the PFU halts the program run, the display blinks and it then displays the cause of the fault.
Program status
Start-up position/standby
Cooling
Waiting time/Pause time
Safety time on star t-up, pilot burner
Flame proving period, pilot burner
Operation, pilot burner
Waiting time, main burner
Safety time on star t-up, main burner
Flame proving period, main burner
Operation, main burner
Purge
Air valve
High temperature operation**
DISPLAY
The burner control unit can be reset using the Reset
button or the remote reset.
Fault message (blinking*)
00
A0
1
2
3
4
5
6
7
8
P0
Flame failure during flame proving period, pilot burner
Flame failure during flame proving period, main burner
Flame simulation, pilot burner
Start-up without fl ame signal, pilot burner
Flame failure during operation, pilot burner
Flame simulation, main burner
Start-up without fl ame signal, main burner
Flame failure during operation, main burner
A
. .
10
32
33
35
36
51
Short-circuit on ignition or valve output
Faulty remote reset
Supply voltage too low
Faulty parameterisation
Short-circuit on a valve output
Safety interlock failure
PFU 780 · Edition 02.12l 16
Page 17
Function
Program status
DISPLAY
52
53
In Manual mode, two dots will blink on the display in program status 01–08. ** Optionally available.
Fault message (blinking*)
Permanent reset
Time bet ween two start-ups is too short
PFU 780 · Edition 02.12l 17
Page 18
Parameters

4 Parameters

Description Parameter Value range
Flame signal, pilot burner 01
Flame signal, main burner 02
0–30 µA
0–30 µA
Factory default
setting
Program status when the most recent fault occurred 03 x0–x8 Switch-off threshold, pilot burner 04 Switch-off threshold, main burner 05
1–20 µA 1 µA 1–20 µA 1 µA
Start-up attempts, pilot burner 10 1–4 1 Start-up attempts, main burner 11 1–4 1 Restart, pilot burner 12 0; 1 0 Restart, main burner 13 0; 1 0 Safety time during operation for V1 and V2 t
SB
14 1; 2 s 1 s Flame simulation check in start-up position/standby 15 0; 1 1 Permanent pilot burner 16 0; 1 1 Minimum combustion time t Minimum burner pause time t
B
BP
Pilot burner safety time on start-up t Pilot burner flame proving period t
FS1
Main burner safety time on start-up t Main burner flame proving period t
SA1
24 3; 5 s
SA2
FS2
20 25 s t
21 0–250 s 0 s
22 3; 5; 10 s
23 0–25 s 0 s
25 0–25 s 0 s Air valve control 30 0; 2; 3 0 Air valve c an be activated ex ternally on star t-up 31 0; 1 0 Air valve closed/can be activated in the event of malfunction 32 0; 1 1 High temperature operation** 33 2; 3
Adjustable*
 
    
SA
        
PFU 780 · Edition 02.12l 18
Page 19
Parameters
Description Parameter Value range
Manual mode limited to 5 minutes 34 0; 1 1 UVS check (1 x in 24 hours) 35 0; 1 0
Low fire over run time 36 0; 5; 15; 25 s 0 s
Purge 42 0; 1 1
Multi-flame control 45 0; 1 0
Password 50 0000–9999 1234
* Adjustable using BCSoft sof tware and a PC opto-adapter ** Please quote in your order. 0 = Function inactive 1 = Function active
Factory default
setting
On parameterisation, ensure that the program se­quence started matches the application. Select the parameters so that the burner can restart as intended in all operating phases.

4.1 Scanning the parameters

During operation, the 7-segment display shows the pro­gram status.
The flame signal and all following parameters of the
PFU can be scanned one after the other by repeatedly pressing the Reset/Information button (for 2 s).
In the event of a fault, the PFU halts the program run, the display blinks and it then displays the cause of the fault in coded form.
Adjustable*
     
PFU 780 · Edition 02.12l 19
Page 20
Parameters

4.2 Flame control

4.2.1 Flame signal, pilot burner

Parameter 01 Flame signal of the pilot burner, display in μA, measur­ing range: 0–30 μ A.

4.2.2 Flame signal, main burner

Parameter 02 Flame signal of the main burner, display in ing range: 0–30 μ A.

Program st atus when the m ost rece nt fault occurr ed

4.2.3
Parameter 03 Program status when the most recent fault occurred
This indicates the program status in which the last
burner fault occurred (e.g. the unit indicates that a flame simulation has been detected with a blinking
01
).
In parameter 03, it is now shown which program posi­tion the unit was in when the fault was detected (wait­ing time
01
or standby
00
).
Result: A flame simulation was detected during the waiting time or standby.
μA, measur-
4.2.4 Switch-off threshold of the flame amplifier
Parameter 04, pilot burner switch-off threshold Parameter 05, main burner switch-off threshold
The sensitivity at which the burner control unit still de-
tects a flame can be set between 1 and 20
μA.
Example: In the case of UV control with the UV sensor
UVS, the signal of the burner to be monitored is influ­enced by other burners.
The set value can be incremented in parameter 04 so
that only the flame of the system’s “own” burner is de­tected.
The measured flame signal of the system’s “own” burner
should be at least 3
μA (empirical value) higher than the
set switch-off threshold.
PFU 780 · Edition 02.12l 20
Page 21
Parameters

4.2.5 High temperature operation with PFU..D

Parameter 33 Operation of firing systems at temperatures above
750°C. The PFU features a safety-relevant DI input
(Digital Input). This input supports the “High tempera­ture operation” function. If firing systems are operated above 750°C, the system is considered to be a high temperature equipment (see EN 7462). Flame control must be in operation until the furnace wall temperature has exceeded 750°C. Note the requirements of the Standards!
Flame control can be dispensed with during high tem­perature operation to improve the system availability.
This means that no incorrect flame signals, e.g. signals
from a UV sensor which are interpreted as extraneous signals due to reflection of UV radiation, may lead to faults.
When the DI input is activated, the burner control unit reverts to High temperature mode. This means: the PFU operates without evaluation of the flame signal. The safety function of the device-internal flame control sys­tem is placed out of operation.
In High temperature mode, the gas valves are opened without flame control.
The precondition for high temperature operation is that
an external flame safeguard ensures the presence of the flame in fail-safe manner indirectly via the tempera­ture. For this purpose, we recommend a safety tem-
perature monitor with twin thermocouple (DIN 3440). Sensor discontinuity, sensor short-circuit, failure of a component or mains failure must set the installation to a safe state.
The voltage may be applied to the DI input (terminal 22a) so as to activate High temperature mode only
when the temperature at the furnace wall has exceeded
750°C. The PFU starts the burner as usual, without
monitoring the presence of the flame.
0402 03
06 07 0800
t
t
Z
t
SA1
FS1
t
SA2tFS2
88
30a 26e 10e 28c 22a 16c 26a 2c–4c 14a 18e 18a 6a–6e 2e–4e
ϑ1
DI
V1
1
1
ϑ2
V2
2
2
t
If the temperature in the furnace chamber drops below
750°C, the DI input must be disconnected from the
electrical power supply and the furnace must be oper­ated with the internal flame control system.
PFU 780 · Edition 02.12l 21
Page 22
Parameters
The PFU then responds, depending on setting:
Parameter 33 = 1
0402 0301
06 07 0808
FA
t
W
t
t
t
SA1
FS1
Z
t
SA2tFS2
88
30a 26e 10e 28c 22a
16c 26a
2c–4c 14a
18e
18a 6a–6e 2e–4e 2a–4a
ϑ1
DI
V1
1
1
ϑ2
V2
2
2
t
If the flame fails during high temperature operation, the ready contact opens for the duration of the flame fail­ure (FA).
When High temperature mode is ended, the PFU switches off the burner and restarts with flame simu­lation check (recommended in the case of UV control with UVS).
Parameter 33 = 2
0402 0301
06 07 0808
t
t
t
t
W
Z
SA1
FS1
t
SA2tFS2
88
30a 26e 10e 28c 22a
16c 26a
2c–4c 14a
18e
18a 6a–6e 2e–4e 2a–4a
ϑ1
DI
V1
1
1
ϑ2
V2
2
2
t
When High temperature mode is ended, the PFU switches off the burner and restarts with flame simu­lation check (recommended in the case of UV control with UVS).
PFU 780 · Edition 02.12l 22
Page 23
Parameters
Parameter 33 = 3
08
08
88
30a 26e 10e 28c 22a 16c 26a 2c–4c 14a 18e 18a 6a–6e 2e–4e
ϑ1
DI
V1
1
1
ϑ2
V2
2
2
t
When High temperature mode is ended, the burner re­mains in operation and the PFU performs flame control again (recommended in the case of ionisation control or UV control with UVD).
If no flame signal is present when High temperature mode is ended, the burner control unit performs a fault lock-out, regardless of parameter 33.
Fault, pilot burner
04 04
88
30a 26e 10e 28c 22a 16c 26a 2c–4c 14a 18e 18a 6a–6e 2e–4e
ϑ1
DI
V1
1
1
ϑ2
V2 2
2
t
Fault, main burner
08
08
88
30a 26e 10e 28c 22a 16c 26a 2c–4c 14a 18e 18a 6a–6e 2e–4e
ϑ1
DI
V1
1
1
ϑ2
V2
2
2
t
Parameter 33 = 4
08
08
88
30a 26e 10e 28c 22a 16c 26a 2c–4c 14a 18e 18a 6a–6e 2e–4e 2a–4a
ϑ1
DI
V1 1
1
ϑ2
V2
2
2
t
If the flame fails during high temperature operation, the ready contact is opened for the duration of the flame
failure.
When High temperature mode is ended, the burner re­mains in operation and the PFU performs flame control again (recommended in the case of ionisation control or UV control with UVD).
PFU 780 · Edition 02.12l 23
Page 24
Parameters

4.2.6 UVS check

Parameter 35
An automatic restart of the burner control unit can be
activated every 24 hours via this parameter. The time starts each time the start-up signal (ϑ) is applied.
Parameter 35 = 0: Unlimited burner operation.
Parameter 35 = 1: An automatic restart is activated once every 24 hours.
It must be ensured in this case that the program se­quence started matches the application. This param­eter may be set in this way only if the burner can restart as intended in all operating phases.
PFU 780 · Edition 02.12l 24
Page 25
Parameters
t

4.3 Pilot and main burner monitoring

Burner control unit PFU 780 for pilot and main burner combination of unlimited capacity.
Pilot burner: single-stage-controlled.
Main burner: modulating or stage-controlled.
The burner control unit PFU 780 has separate start-up
signal inputs for the pilot burner (terminal 10e) and the main burner (terminal 14a). The burner control unit co­ordinates the program run (the interplay) of both burn­ers. If required, the main burner can be started once the pilot burner has reached its operating position. Benefit:
The time for starting up the main burner can be reduced
as low as its safety time. By using two flame amplifiers, the pilot and main burners can be monitored separately.
The PFU 780 can also be used on indirectly ignited sur-
face burners with end point monitoring.
Three different operating modes are possible:
Permanent pilot burner
88 02–04 06–08 04 06–08 04
ϑ1
1
ϑ2
2
For applications which require a high system availabil-
ity or where a continuously burning flame is necessary.
The pilot burner is ignited once and remains constantly
in operation. The main burner is controlled separately.
Intermittent pilot burner
88 02–04 06–08 00 02–04 06–08 00
ϑ
1
2
t
Pilot and main burners are controlled with one start-
up signal (terminals 10e and 14a in parallel). The main burner starts automatically after the operating signal
from the pilot burner has been detected. Operation is
terminated simultaneously for both burners.
PFU 780 · Edition 02.12l 25
Page 26
Parameters
Interrupted pilot burner
88 02–04 06–08 02–04 06–08
ϑ1
1
ϑ2 2
t
The pilot burner is switched off during the main burner
safety time t no distinction can be made between the flame signals of the pilot and main burners (e.g. if both burners can be monitored with a single UV sensor). If the start-up signal for the pilot burner is applied continually, the pilot burner restarts immediately after the main burner has been switched off.
. This type of flame control is required if
SA2
PFU 780 · Edition 02.12l 26
Page 27
Parameters

4.3.1 Permanent pilot burner Parameter 16 = 1

04 06 07 08 02 03 00
t
Z
t
SA1
t
FS1
ϑ
L1
PFU 780
A
P
t
SA2
TZI
VBY
VAG
1
t
1
SPS
2
PLC CPE
2
FS2
88
30a 26e 10e 28c 16c 26a 2c–4c 14a 18e 18a 6a–6e 2e–4e
ϑ1
V1
1
1
ϑ2
V2
2
2
t
Operating mode: Permanent pilot burner
In the “Permanent pilot burner” operating mode, the pi­lot burner remains in operation until its start-up signal drops.
If this parameter is activated (P16 = 1), both flames are controlled independently in the case of pilot and main burner monitoring.
Operating mode: Intermittent pilot burner
Start-up as in the illustration “Permanent pilot burner” with the difference being that the start-up signal for pi­lot and main burners is applied synchronously and that immediately after the flame proving period t main burner is started.
FS1
, the
VR..R
PFU 780 · Edition 02.12l 27
Page 28
Parameters

4.3.2 Interrupted pilot burner Parameter 16 = 0

04 06 07 08 02 03 00
t
Z
t
SA1
t
FS1
ϑ
L1
PFU 780
A
P
VAS
t
TZI
SA2
t
FS2
1
SPS
2
PLC CPE
88
30a 26e 10e 28c 16c 26a 2c–4c 14a 18e 18a 6a–6e 2e–4e
ϑ1
V1 1
1
ϑ2
V2
2
2
t
Operating mode: Interrupted pilot burner
If parameter 16 = 0, the pilot burner is switched off once the safety time t
flame signal can be connected to terminals 18a or 26a.
The pilot burner is switched off after the main burner
safety time t
SA2
has elapsed. In this setting, the
SA2
has elapsed.
VAG
VR..R
UV
1
2
PFU 780 · Edition 02.12l 28
Page 29
Parameters

4.4 Behaviour in start-up position/standby

4.4.1 Flame simulation check in start-up position/ standby

Parameter 15
This defines the instant for the flame simulation check.
88
00
t
LV
If the PFU notices an extraneous signal during the flame simulation check, it starts the flame simulation delay time tLV (25 s). If the extraneous signal is discon­tinued during this period, the burner can start up. Oth­erwise, a fault lock-out occurs. 1 blinks on the display if an extraneous signal is detected by the pilot burner and 5 blinks if an extraneous signal is detected by the main burner.
Parameter 15 = 0: The flame simulation check is con­ducted after applying the start-up signal (ϑ) during the waiting time t
.
W
Parameter 15 = 1: The flame simulation check is con­ducted provided no start-up signal (ϑ) is applied (during the so-called start-up position/standby). This allows fast start-up of the burner since there is no waiting time t
01
30a 26e 10e 28c 26a 16c 18e 2c–4c 2e–4e
ϑ1
V1 V2
1
t
.
W
The burner must have been switched off for at least 4 s before start-up in order for the flame simulation check to be conducted correctly.
Flame simulation check depending on parameter 16 (Pilot burner operating mode):
Parameter 15 = 1, Parameter 16 = 1
88 00 02 06
ϑ1
V1
ϑ2
V2
t
Parameter 15 = 0, Parameter 16 = 1
02
t
W1
06
t
W2
88 00 01 05
ϑ1
ϑ2
V1
V2
t
Parameter 15 = 1, Parameter 16 = 0
88 00 02 06
ϑ1
V1
ϑ2
V2
t
Parameter 15 = 0, Parameter 16 = 0
02
t
W1
06
t
W2
88 00 01 05
ϑ1
ϑ2
V1
V2
t
PFU 780 · Edition 02.12l 29
Page 30
Parameters

4.4.2 Minimum burner pause time tBP

Parameter 21 Programmable time between 0 and 250 s.
05 04
t
BP
t
SA2
t
FS2
88 08 06 07 08
1 5
ϑ
1
4 7
1
9
V1
12 16-17
ϑ
2
21
2
9 14 V2
28-29 18-19
1
2
t
An immediate restart of the main burner after a nor­mal shut-down, a start-up attempt, restart, cooling or purging is prevented by the pause time. The pause time starts when the air valve is switched off. If a start­up signal (ϑ2) is applied before expiry of this time, the start-up is delayed until the end of the pause time.
After the pause time, the burner is started if the start­up signal (ϑ) is applied.
The minimum burner pause time t
serves to adapt the
BP
program sequence to the requirements of the applica­tion.
The time should be set such that the system can be moved to ignition position, i.e. butterfly valves can be closed and, possibly, gas can be flared off, before a re­start occurs.
See examples of application Stage-controlled main burner with alternating pilot burner and Stage-con­trolled main burner with permanent pilot burner.
The pause time has an effect on the behaviour of the main burner only. Background: The pilot burner is only used in single-stage operation.
PFU 780 · Edition 02.12l 30
Page 31
Parameters

4.5 Behaviour during start-up

4.5.1 Safety time on start-up tSA

Pilot burner
Parameter 22
04 02 03 00
t
Z
t
SA1
Safety time on start-up t
t
FS
for the pilot burner.
SA1
88
30a 26e 10e 28c 26a 16c 18e 2c–4c 2e–4e
Main burner
Parameter 24
04 06 07 08 02 03 00
ϑ1
1 V1 V2
1
t
Safety time on start-up t
t
Z
t
SA1
t
FS1
t
SA2
for the main burner.
SA2
t
FS2
88
30a 26e 10e 28c 16c 26a 2c–4c 14a 18e 18a 6a–6e 2e–4e
ϑ1
V1
1
1
ϑ2
V2
2
2
t
PFU 780 · Edition 02.12l 31
Page 32
Parameters

4.5.2 Flame proving period tFS

Pilot burner
Parameter 23
t
Z
t
SA1
t
FS
Main burner
Parameter 25
04 06 07 08 02 03 00
t
Z
t
SA1
t
FS1
t
SA2
4.5.3 Minimum combustion time t
B
Parameter 20
04 06 07
88
04 02 03 00
30a 26e
ϑ1
10e 28c
1
26a 16c
V1
18e
V2
1
2c–4c 2e–4e
t
t
B
88
30a 26e 10e 16c 26a 2c–4c 14a 18e 18a 6a–6e 2e–4e
ϑ1
V1
1
1
ϑ2
V2
2
2
t
Programmable time to maximum 25 s during which the main burner remains in operation. In the case of brief activation of the start-up signal input (ϑ2) (e.g. with a pulse), the combustion time tB is started, and the main
t
FS2
88
30a 26e 10e 28c 16c 26a 2c–4c 14a 18e 18a 6a–6e 2e–4e
ϑ1
V1 1
ϑ2
V2
2
t
burner remains in operation for at least this period.
1
2
Programmable time between 0 and 25 s.
This time elapses before the PFU starts the next pro-
gram step so as to give the flame time to stabilise.
PFU 780 · Edition 02.12l 32
Page 33
Parameters

4.5.4 Burner start-up attempts

Pilot burner
Parameter 10
This indicates the number of possible start-up attempts
of the burner.
In accordance with EN 7462, three start-ups are per­mitted in specific cases in the event of flame failure during start-up, if the safety of the installation is not impaired. Note the requirements of the Standards!
If no flame is detected during start-up, either a fault lock-out is performed or further start-up attempts in accordance with EN 7462 occur.
Pursuant to NFPA 86, only one start-up attempt is per­mitted in the event of flame failure during start-up. For units approved by FM Approval (see type label), it is only possible to select one start-up attempt.
1 start-up attempt
Parameter 10 = 1
02 00
t
Z
02
t
SA
88
30a 26e 10e 28c 26a 16c 18e 2c–4c 2e–4e
ϑ1
V1 V2
t
If no flame forms during start-up, a fault lock-out is performed after expiry of time tSA. The display blinks and shows the cause of the fault.
2 or 3 start-up attempts
Parameter 10 = 2, 3
02 00
t
Z
t
SA1
t
Z
88
30a 26e
ϑ1
10e 28c 26a
V1
16c
V2
18e
1
2c–4c 2e–4e
t
t
SA1
If several start-up attempts are set and if the PFU de­tects a flame failure during start-up, it closes valve V1 after the safety time t
has expired and attempts to
SA1
start up again. After the last programmed start-up at­tempt has been completed, the burner control unit con­ducts a fault lock-out. The display blinks and shows the cause of the fault.
PFU 780 · Edition 02.12l 33
Page 34
Parameters
Main burner
Parameter 11
This indicates the number of possible start-up attempts
of the main burner.
In accordance with EN 7462, three start-ups are per­mitted in specific cases in the event of flame failure during start-up, if the safety of the installation is not impaired. Note the requirements of the Standards! If no flame is detected during start-up, either a fault lock-out is performed or further start-up attempts in accord­ance with EN 7462 occur.
Pursuant to NFPA 86, only one start-up attempt is per­mitted in the event of flame failure during start-up. For units approved by FM Approval (see type label), it is only possible to select one start-up attempt.
1 start-up attempt
Parameter 11 = 1
04 06 02 03 00
t
Z
t
SA1
t
FS1
t
SA2
06
88
30a 26e 10e 28c 16c 26a 2c–4c 14a 18e 18a 6a–6e 2e–4e
ϑ1
V1
1
1
ϑ2
V2
2
2
t
If no flame forms during the start-up of the main burner, a fault lock-out is performed after expiry of time t
SA2
.
The display blinks and shows the cause of the fault.
2 or 3 start-up attempts
Parameter 11 = 2, 3
04 06 02 03 00
t
Z
t
SA1
t
FS1
t
SA2
05
t
06
t
W
SA2
05
t
06
06
t
W
SA2
88
30a 26e 10e 28c 16c 26a 2c–4c 14a 18e 18a 6a–6e 2e–4e
ϑ1
V1
1
1
ϑ2
V2
2
2
t
If several start-up attempts are set and if the PFU does not detect a flame signal during start-up, it closes valve
V2 after the safety time t
has expired and attempts
SA2
to start up again. After the last programmed start-up attempt has been completed, the burner control unit conducts a fault lock-out. The display blinks and shows the cause of the fault.
PFU 780 · Edition 02.12l 34
Page 35
Parameters

4.6 Behaviour during operation

4.6.1
Safety time during operation tSB for pilot and main
burners
Parameter 14
This indicates the safety time during operation tSB
for valves V1 and V2. The default in accordance with EN 298 is 1 s. The PFU has also the available option of a safety time during operation tSB of 2 s. Prolonging the time increases the installation availability in the case of brief-duration signal fades (e.g. fades of the flame signal). In accordance with EN 7462, the safety time of the installation during operation (including closing time of the valves) may not exceed 3 seconds (note the requirements of the Standards).

4.6.2 Fault lock-out or restart, pilot burner

Parameter 12
This parameter determines whether the PFU starts a
one-off restart or performs an immediate fault lock-out for the burner after an installation fault such as a flame failure or failure of air flow (see also Project planning information).
Immediate fault lock-out following flame failure
Parameter 12 = 0: Pilot burner fault lock-out.
04
04
t
SB
88
30a 26e 10e 28c 26a 16c 18e
2c–4c 2e–4e
ϑ1
1 V1 V2
1
t
After a fault lock-out, the burner control unit can be
reset, either with the button on the front panel or using an external button. Several burner control units can be reset in parallel using the external button.
The PFU cannot be reset by mains failure. The fault
signalling contact does, however, open as soon as the mains voltage fails.
See also parameter 32, Behaviour of the air valve in the event of a fault lock-out.
PFU 780 · Edition 02.12l 35
Page 36
Parameters
Restart following flame failure
Parameter 12 = 1: Restart following flame failure.
1x
88
04 04 03 01
30a 26e
ϑ1
10e 28c
1
26a 16c
>2 s
t
t
SB
t
Z
t
t
W
SA1
FS1
If the PFU detects a flame failure after a minimum op­erating time of 2 s, the valves are closed and the opera­tion signalling contact is opened within time tSB.
The burner control unit now attempts to restart the
burner once. If the burner does not function, a fault lock-out occurs. The display blinks and shows the cause of the fault.
In accordance with EN 7462, a restart may be con­ducted only if the safety of the installation is not im­paired. Restart is recommended for burners which oc­casionally display unstable behaviour during operation.
The precondition for a restart is that activation of the
restart allows the burner to restart as intended (in all operating phases). In this case, it must be ensured that the program sequence started by the PFU matches the application.
2c–4c 2e–4e
V1
1
t
PFU 780 · Edition 02.12l 36
Page 37
Parameters
S

4.6.3 Fault lock-out or restart, main burner

This parameter determines whether the PFU starts a
one-off restart or performs an immediate fault lock-out for the main burner after a flame failure (see also Pro­ject planning information).
Immediate fault lock-out following flame failure
Parameter 13 = 0: Main burner fault lock-out
08
08
t
B
88
30a 26e 10e 28c 16c 26a 2c–4c 14a 18e 18a 6a–6e 2e–4e
ϑ1
V1 1
1
ϑ2
V2
2
2
t
After a flame failure, the burner control unit performs a fault lock-out within the safety time during operation tSB. This involves disconnecting the power from the gas valves and the ignition transformer. The fault signalling contact closes, the display blinks and shows the current program status (see table “Program status and fault messages”).
After a fault lock-out, the burner control unit can be
reset, either with the button on the front panel or using an external button. Several burner control units can be reset in parallel using the external button.
The PFU cannot be reset by mains failure. The fault
signalling contact does, however, open as soon as the mains voltage fails.
See also “Behaviour of the air valve in the event of a
fault lock-out”.
PFU 780 · Edition 02.12l 37
Page 38
Parameters
Restart following flame failure
Parameter 13 = 1: Restart following flame failure.
1x
08
>2 s
06
05
t
SB
t
t
W2
SA2
07
08
t
FS2
88
30a 26e 10e 28c 16c 26a 2c–4c 14a 18e 18a 6a–6e 2e–4e
ϑ1
V1
1
1
ϑ2
V2
2
2
t
If the PFU detects a flame failure after a minimum op­erating time of 2 s, valve V2 is closed and the operation signalling contact is opened within time tSB.
The burner control unit now attempts to restart the
main burner once. If the burner does not function, a fault lock-out occurs. The display blinks and shows the cause of the fault.
In accordance with EN 7462, a restart may be con­ducted only if the safety of the installation is not im­paired. Restart is recommended for burners which oc­casionally display unstable behaviour during operation.
The precondition for a restart is that activation of the
restart allows the burner to restart as intended (in all operating phases). In this case, it must be ensured that the program sequence started by the PFU matches the application.
PFU 780 · Edition 02.12l 38
Page 39
Parameters

4.7 Air valve control PFU..L

Parameter 30, Behaviour of the air valve during opera­tion
Parameter 31, Behaviour of the air valve during start-up
Parameter 32, Behaviour of the air valve in the event of a fault lock-out
The PFU..L features an adjustable air valve control. The
display shows that purging is currently being carried out with tivated for cooling or heating.
The PFU..L supports the following functions:
– Purge
– Cooling in start-up position/standby
– Switching of the burner between low and high burner
output during operation via the air valve
– To start up the burner as intended, external activation
of the air valve can be blocked during start-up (pre­vents synchronisation problems between the PFU and the central control system)
– Controlling the air valve so that it
– opens with valve V2,
– opens once the main burner has reached its operat-
ing position
– Low fire over run time t
P 0
. A indicates that the air valve is being ac-
after a normal shut-down
KN

4.7. 1 Purge

Parameter 42 = 0: The air valve is closed when voltage is
applied to terminal 30e.
Parameter 42 = 1: The air valve is opened when voltage
is applied to terminal 30e.
In the case of multiple burner applications, burners with mechanical combustion air supply are used. The air for combustion and pre-purge is supplied by a central fan controlled by a separate logic. This logic determines the purging time.
The PFU..L supports centrally-controlled pre-purge or
post-purge. The PFU..L is informed that purging is cur­rently being performed by input 30e. It then opens the air valve, regardless of the status of the other inputs (purging has priority). The display indicates
PFU 780..K2: For purging, the safety interlock (limits)
must activate input 26e and input 30e of the PFU.

4.7. 2 Cooling in start-up position/standby

The air valve can be activated externally via input 10a for cooling in the start-up position. During activation of
the air valve the display shows ing is currently being carried out.

4.7.3 Burner start

Parameters 30 and 31 determine the behaviour of the
air valve during burner start.
A 0
, indicating that cool-
P 0
.
PFU 780 · Edition 02.12l 39
Page 40
Parameters
PFU 780
A
P
L1
1
2
SPS PLC CPE
ϑ
VR..R
VAG
TZI
2
1
UV
VAS
4.7. 4
Air valve opens in the c ase of exter nal activation ( not
during start-up)
00 A0 00
A0
03
02
t
t
Z
t
SA1
06
04
t
t
FS1
SA2
FS2
88
A807
30a 26e 10e 28c 16c 26a 2c–4c
14a 18e 18a 6a–6e 10a 22e
2e–4e
Parameter 30 = 0: The air valve opens if it is activated externally by input 30e.
Parameter 31 = 0: The air valve remains closed during start-up
ϑ1
V1
1
1
ϑ2
V2
2
2
A
t
even if it is activated externally.
These settings are required on burners on which the
gas/air ratio is controlled via a pneumatic link and which also need to be started at low fire, e.g. on two­stage-controlled burners. In this case, activation of the air valve during burner start via input 10a must be pre­vented.
External control allows switchover between low fire and
high fire during operation.
The air valve can be activated externally via input 10a for cooling the burner in the start-up position/standby.
PFU 780 · Edition 02.12l 40
Page 41
Parameters
SA1

4.7. 5 Air valve opens in the case of external activation (even during start-up)

00 A0 00
A0
A2
L1
A4
FS1
PFU 780..L
VAS 1
VAG
A6
t
SA2
TZI
t
FS2
1
2
1
2
A3
t
t
Z
t
ϑ
A
P
88
A8 A7
30a 26e
ϑ1
10e 28c
V1
16c
1
26a
1
2c–4c
ϑ2
14a
V2
18e
2
18a
2
6a–6e
A
10a 22e 2e–4e
t
UV
Parameter 30 = 0: The air valve opens if it is activated externally via input 10a.
Parameter 31 = 1: The air valve can be activated even during start-up.
These settings may be selected only if the burner can
start with full air capacity.
The air valve can be activated externally via input 10a for cooling the burner in the start-up position/standby.
VAS
PFU 780 · Edition 02.12l 41
Page 42
Parameters
SA1

4.7. 6 Air valve opens with valve V2

00 A0
00
02
L1
03
t
t
Z
t
ϑ
A
P
A6
04
t
FS1
PFU 780..L
SA2
TZI
VBY
VAG
1
t
FS2
1
2
2
SPS PLC CPE
Parameter 30 = 2:
88
A8 A7
30a 26e
ϑ1
10e 28c
V1
16c
1
26a
1
2c–4c
ϑ2
14a
V2
18e
2
18a
2
6a–6e
A
10a 22e 2e–4e
t
The air valve opens simultaneously with valve V2. Application:
Single-stage-controlled main burner is switched ON/
OFF via the ϑ input.
The air valve can be activated externally via input 10a for cooling the burner in the start-up position/standby.
VR..R
PFU 780 · Edition 02.12l 42
Page 43
Parameters

4.7.7 Air valve opens with operating signal

04
06
t
SA
ϑ
L1
A
P
t
FS
PFU 780..L
TZI
VBY
VAG
1
88
A8 07
30a 26e
ϑ1
10e 28c
V1
16c
1
26a
1
2c–4c
ϑ2
14a
V2
18e
2
18a
2
6a–6e
A
10a 22e 2e–4e
t
1
SPS
2
PLC CPE
2
Parameter 30 = 3: The air valve opens simultaneously with the operating
signal. Application: Two-stage-controlled main burner is switched ON/OFF
via the ϑ input.
The air valve can be activated externally via input 10a for cooling the burner in the start-up position/standby.
VR..R
PFU 780 · Edition 02.12l 43
Page 44
Parameters
KN
PFU 780..L
A
L1
1
SPS
ϑ
4.7. 8
Low fire over run time tKN after a nor mal shut-down
A8
t
P
VG..N
VAS 1
GIK..B
VR..R
88
00
30a 26e
ϑ1
10e 28c 16c 26a 2c–4c
ϑ2
14a 18e 18a 6a–6e
22e
2e–4e
2
PLC CPE
TZI
1
2
Parameter 36
Settings: 0; 3; 5; 10; 15; 25 or 60 (low fire over run time
in seconds)
This parameter is applicable to systems with a pneu-
V1
1
1
V2
2
2
matic link between gas and air and On/Off control.
Parameter 36 = 0 (low fire over run time t
KN
= 0 s): Without low fire over run, the gas side is closed imme­diately owing to the quick-closing gas valve in the case of On/Off control. The air side closes more slowly. The
t
air flowing in during the closing time increases the O2 content in the combustion chamber.
Parameter 36 = 3; 5; 10; 15; 25 or 60 (low fire over run
time t
= 3, 5, 10, 15, 25 or 60 s):
KN
The air valve closes slowly after the activation signal
has been switched off. The gas valve remains open for tKN. This means that the burner, after deactivation of the main burner start-up signal (ϑ2), is initially adjusted down to low fire and then switched off completely.
Using the low fire over run function reduces the O
con-
2
tent in the furnace atmosphere.
Flame control is still operational. Can be used only in
the case of pneumatic link and On/Off control. It must be ensured that no excess gas occurs.
The low fire over run time has an effect on the behaviour
of the main burner only.
Background: The pilot burner is only used in single-
stage operation.
PFU 780 · Edition 02.12l 44
Page 45
Parameters
4.7. 9
Behaviour of the air valve in the event of a fault lock-
out
Parameter 32:
This determines whether the air valve can be activated
in the case of a fault lock-out.
Parameter 32 = 0:
The air valve is closed in the event of a fault. It cannot be
activated externally via terminal 10a.
Parameter 32 = 1:
The air valve can be activated externally via input 10a
even during a fault, e.g. for cooling.
PFU 780 · Edition 02.12l 45
Page 46
Parameters

4.8 Manual operation

For convenient setting of the burner or analysing faults.
The parameter display is not available in Manual mode.
Manual mode can be accessed only if the unit was not in Fault state before switching off. The following times/ functions are not active in Manual mode: start-up at­tempts, restart, minimum combustion time and cycle lock.
If the Reset /Information button is pressed for 2 s dur­ing switch-on, the PFU reverts to Manual mode. Two dots blink on the display.
In this operating mode, the burner control unit operates independently of the status of the inputs (apart from the pre-purge input and the safety interlocks. These are of higher priority and will be processed first).
Each time after the button is pressed again, the PFU moves to the next section of the program sequence and stops there. After approx. 3 s, the flame signal will be displayed instead of the program parameter. Briefly pressing the Reset/Information button (< 1 s) displays the relevant Manual mode step. If there is flame simula­tion during the start-up, the flame signal is displayed immediately.
On units with air valve control, the air valve can be opened and closed repeatedly by pressing the button during operation.
Manual mode can be terminated by switching off the PFU (On/Off button).

4.8.1 Manual mode limited to 5 minutes

Parameter 34: Parameter 34 determines when Manual mode is termi-
nated.
Parameter 34 = 0: Manual mode is not limited in time. If this function has
been selected, operation of the furnace may be contin­ued manually in the event of failure of the central con­trol system.
Parameter 34 = 1: Manual mode ends automatically five minutes after the
last time the button was pressed. The PFU then moves abruptly back to start-up position/standby.
PFU 780 · Edition 02.12l 46
Page 47
Parameters

4.9 Password

Parameter 50: (Four-digit) password saved to protect parameter settings. To prevent unauthorised changes to param­eter settings, a password is stored in parameter 50. Changes to parameter settings can only be made once this number has been entered. The password can be changed using BCSoft.
Note the effect of parameter settings on the safe func­tioning of your system.
The password set at the factory can be found in the de-
livery note supplied.
PFU 780 · Edition 02.12l 47
Page 48
Selection

5 Selection

5.1 Calculating the safety time tSA

PFU 780 · Edition 02.12l 48
Page 49
Selection
PF U 780LT

5.2 Selection table

Type L T N D* U* K2*
PF U 780
* If “none”, this specifi cation is omitted.
= standard,  = available
Order example

5.2.1 Type code

Code Description
L Air valve control
T N
D* Digital input to interrupt fl ame control U* Preparation for UV sensor for continuous operation UVD 1 K2* Compatible with PFU 798
* If “none”, this specifi cation is omitted.
220–240 V~, 15/+10 %, 50/60 Hz 110–120 V~, 15/+10 %, 50/60 Hz
Mains voltage
PFU 780 · Edition 02.12l 49
Page 50
Project planning information

6 Project planning information

6.1 Cable selection

Use mains cable suitable for the type of operation and complying with local regulations. Do not route PFU cables in the same cable duct as frequency converter cables or cables emitting strong fields.

6.1.1 Ignition cable

Use unscreened high-voltage cable, see page 56 (Accessories). Cable length: max. 5 m, recommended
< 1 m. Screw the ignition cable securely into the ignition
transformer and run to the burner by the shortest pos­sible route.
The longer the ignition cable, the lower the ignition
capacity. Only use radio interference suppressed elec­trode adapters (with 1 kΩ resistor) for ignition elec­trodes, see see page 56 (Accessories) . Do not lay UV/ionisation cable and ignition cables together and lay them as far apart as possible.

6.1.2 Ionisation cable

Use unscreened high-voltage cable, see page 56 (Accessories) . Cable length: max. 100 m. Avoid ex­ternal electrical interference. Install as far as possible from mains and ignition cables and interference from electro-magnetic sources. If possible, do not lay in a metal conduit. Several ionisation cables can be routed together.
6.1.3 UVLeitung
Cable length: max. 100 m. Avoid external electrical
interference. Install as far as possible from mains and ignition cables and interference from electro-magnetic sources. If possible, do not lay in a metal conduit. Sev­eral UV cables can be routed together.

6.2 Ignition electrode

6.2.1 Electrode gap

Gap between electrode and burner earth: 2 mm ± 0.5 mm.

6.2.2 Star electrodes

We recommend using 7.5 kV ignition transformers on burners with star electrodes.
PFU 780 · Edition 02.12l 50
Page 51
Project planning information

6.3 Minimum combustion time

Even if the start-up signal (ϑ) is applied only briefly, the time set under parameter 20 elapses before the burner control unit shuts down the burner or signals a fault. To stabilise the burner operation, a minimum combustion time can be set independently of the central control system. If the start-up signal (ϑ) drops once the sec- ond safety time t remains in operation for at least time tB. The minimum combustion time tB starts to elapse following controller enable. If the start-up signal drops before the second safety time t
SA2
reverts directly to standby and the burner is not ignited.
The signal inputs for the pilot /main burner start-up sig-
nal cannot be used for a safety shut-down because the unit controls the valves until the minimum combustion time has elapsed.
04 06 07
has started to elapse, the burner
SA2
, e.g. during pre-purge, the control unit
88
30a 26e
ϑ1
10e
V1
16c
1
26a
1
2c–4c
ϑ2
14a 18e
V2 2
18a
2
6a–6e 2e–4e
t
B
t
haviour of the main burner. The minimum combustion time for the pilot burner is limited to the safety time on star t-up (t
SA1
).
Background: The pilot burner is only used in single-
stage operation.

6.4 Safety interlocks (Limits)

The limiters in the safety interlock (linking of all the rel-
evant safety control and switching equipment for the use of the application, e.g. safety temperature limiter, minimum and maximum gas pressure, tightness con­trol) must isolate terminal 26e from the voltage supply. If the safety interlock is interrupted, this is indicated by a blinking
If the safety interlocks fail, an immediate program abort with switch-off of all outputs occurs (even during the safety time). If the safety interlocks are operational again or the unit is switched back on, the program run is restarted in standby.
51
on the display.
In the case of pilot/main burner monitoring, the mini­mum combustion time only has an effect on the be-
PFU 780 · Edition 02.12l 51
Page 52
Project planning information

6.5 Emergency stop

6.5.1 In the event of fire or electric shock
If there is a risk of fire, electric shock or similar, inputs L1, N and 26e (safety interlocks) of the PFU should be disconnected from the electrical power supply–this should be reflected in the wiring on site.

6.5.2 Via the safety interlocks (limits)

The safety interlock turns off the power to input 26e,
such as in the event of air deficiency or similar.

6.6 Reset

6.6.1 Parallel reset

Several burner control units can be reset in parallel us­ing the external button. The PFU cannot be reset by mains failure.

6.6.2 Permanent remote reset

Permanent remote reset gives rise to a malfunction. If a remote reset signal is permanently applied to terminals
52
10c/12c,
Reset with a pulse < 1 s.

6.6.3 Automatic remote reset (PLC)

In the case of automatic remote reset (PLC), the reset pulse duration should not exceed 1 second. Check compliance with standards.
If a fault is acknowledged by remote reset too often, er-
10
ror
flashes on the display to indicate a fault.
(Too many remote resets) is displayed. The error
can only be acknowledged with the Reset /Information button on the unit.
The burner malfunction must be remedied. The mal­function can not be remedied by changing the method
of activation.

6.6.4 Burner start

A furnace start may only be initiated, if it has been en-
sured using an appropriate procedure that there is no combustible mixture in the combustion/processing chamber, in the connected areas or in the exhaust gas system (heat exchanger, dust collector). This can be achieved by pre-purge, which occurs immediately be-
fore ignition or within the period specified in the operat-
ing instructions.
In the case of multiple burner applications, pre-purge is not necessary after a normal burner shut-down.
Note the requirements of the Standards. For exceptions,
see Standards.

6.6.5 Restart and start-up attempts

The precondition for a restart/start-up attempt is that
activation of the restart allows the burner to restart as intended (in all operating phases). In this case, it must be ensured that the program sequence started by the
PFU matches the application.
Note the requirements of the Standards. For exceptions,
see Standards.
PFU 780 · Edition 02.12l 52
Page 53
Project planning information

6.7 Fault message

The fault signalling contact opens, as soon as the mains
voltage fails.

6.8 Protecting the pilot burner from overload

To protect the unit against overload by frequent cycling,
the maximum number of start-ups per minute is limited for the PFU. Excessive cycling triggers a fault message (blinking depends on the safety time tSA:
tSA [s] Ignition transformer TZI Max. start-ups/min .
3 51 5/100 6 5 51 5/100 5 10 51 5/1 00 4
53
). The max. number of start-ups per minute

6.9 Installation

Installation position: any.
Installation in 19” module subracks only, see page 57 (Socket connectors)
Install in clean environment ensuring enclosure IP 54 or higher, whereby no condensation is permitted.
Cable length between PFU and burner: max. 100 m.

6.10.1 UVS sensor wiring

Connect the UVS sensor directly to the PFU. Operating
the sensor with incorrect polarity or voltage can lead to destruction of the sensor.

6.11 PFU switched off

The PFU cannot be activated when no mains voltage is
applied or when it is switched off. The fault signalling contact is only closed when the unit is supplied with voltage and switched on.
If the unit is switched off, an immediate program abort with switch-off of all outputs occurs (even during the safety time). When the unit is switched on, the program run is restarted in standby.

6.10 Wiring

The PFU is suitable for hard wiring only. Do not reverse
phase and neutral conductor. Different phases of a three-phase current system must not be installed at the PFU. No voltage may be connected to the valve and ignition outputs.
PFU 780 · Edition 02.12l 53
Page 54
Project planning information

6.12 Furnace control

Switch on the system to start up the furnace, then release the burner start via the safety interlocks and afterwards start the burner control so that the burner control unit may monitor the burners as intended. To shut down the furnace, first disconnect the burner control unit from the temperature control (burner ON signal), then disconnect the safety interlocks and finally switch off the system.

6.13 Note on EC type-examination

Since EN 298 (1993) does not describe all functions of the PFU, the operator is responsible for ensuring that all parameters and functions are matched to the respec­tive application.

6.14 Mains switch

The mains switch in the unit isolates the PFU on two
poles from the mains. It does not meet the require­ments of EN 501561:2004 (5.2.2 Switch disconnec­tors) set out in chapter 5 for a device to disconnect the power supply. Although the mains switch cannot be used for disconnecting from the electrical power supply in accordance with EN 50156, it does allow the burner to be isolated functionally from the central control sys­tem. This function is required for manual operation and, in the case of PROFIBUS units, to switch off the unit without causing BUS errors. Disconnection for electri­cal maintenance work is to be implemented with an ex-
ternal switch per unit or group only, in accordance with Standard “EN 50156”.

6.15 Changing parameters

In certain cases, it may be necessary to change the de-
fault settings. Using a separate software package and
a PC opto-adapter, it is possible to modify certain pa­rameters on the PFU, such as the switch-off threshold of the flame amplifier, the behaviour in the event of a
flame failure or if the pilot burner is to burn permanently
in the case of pilot and main burner monitoring.
The software package with PC opto-adapter, as well as
“Changed parameters” stickers, are available as acces-
sories – see section entitled page 56 (Accessories) .
The unit parameters set at the factory are specified in
the delivery note.
Document changed parameters in BCSoft using the
protocol function and enclose the protocol with the plant documentation.
If a replacement is ordered for a PFU with changed pa­rameters, refer to the protocol for details.
PFU 780 · Edition 02.12l 54
Page 55
Flame control

7 Flame control

7.1 With ionisation sensor

The PFU generates an alternating voltage (230 V AC)
between the sensing electrode and burner earth. The flame rectifies this voltage. Only the DC signal (depen­ding on the switch-off threshold for the pilot and main burners) is recognised by the burner control unit as a flame signal.
A flame cannot be simulated. Ignition and monitoring with a single electrode is possible.

7. 2 With UV sensor

A UV tube inside the UV sensor detects the ultraviolet light of a flame. It does not respond to sunlight, incan­descent bulb light or infrared radiation emitted by hot workpieces or red-hot furnace walls.
In the event of incident UV radiation the UV sensor rec­tifies the supplied alternating voltage. As with ionisati­on control, the burner control unit only detects this DC signal.
When using UV sensors of Type UVS, the burner control unit may be used for intermittent operation only. This means that operation must be interrupted at least once every 24 hours. This can be programmed using para­meter 35.
For further information, see brochure UVS.
The burner control unit PFU..U is prepared for UV sensor
UVD 1. This enables continuous operation. For further information, see Technical Information Bulletin UVD.

7.3 Via the temperature in high temperature equipment

High temperature equipment is defined as a thermo-
processing installation, in which the wall temperature of the combustion chamber and/or the processing cham­ber exceeds 750°C. Burner control unit PFU..D features a special “High temperature operation” function. During heating up, standard monitoring methods (ionisation or UV) must be used for flame control. When the working temperature has exceeded 750°C, indirect flame con­trol can be taken over by a central monitoring device. When the DI input (terminal 22a) is activated, the bur­ner control unit reverts to this operating mode.
Important: In “High temperature operation”, i.e. with the DI input being activated, burner control unit PFU..D does not evaluate the flame signal. The safety function of the burner control unit’s flame control is deactivated during this operating phase.
PFU 780 · Edition 02.12l 55
Page 56
Accessories
D-49018 Osnabrück, Germany
Achtung, geänderte Parameter!
Die Angaben auf dem Typenschild gelten nicht mehr in vollem Umfang. Aktuelle Parameter direkt auslesen.
Important, changed parameters!
The details on the type label are no longer completely accurate. Read the current parameters direct from the unit.
Attention, paramètres modifiés !
Les informations figurant sur la plaque signalétique ne sont plus valables dans leur intégralité. Veuillez vous référer directement aux paramètres actualisés.

8 Accessories

8.1 High-voltage cable

FZLSi 1/7 up to 180°C, Order No.: 04250410.
FZLK 1/7 up to 80°C, Order No.: 04250409.

8.2 BCSoft

Opto-adapter including BCSoft CDROM, Order No.: 74960437.
The current software can be downloaded from our In-
ternet site at http://www.docuthek.com. To do so, you need to register in the DOCUTHEK.

8.3 Stickers for labelling

8.4 “Changed parameters” stickers

Affix on the connection diagram of the PFU following
changes to unit parameters set at the factory.
100 pcs, Order No.: 74921492.
For printing with laser printers, plotters or engraving machines, 27 × 18 mm or 28 × 17.5 mm.
Colour: silver
PFU 780 · Edition 02.12l 56
Brenner 1 Zone 3
Page 57
Accessories

8.5 Radio interference suppressed electrode adapters

Plug cap, 4 mm, interference-suppressed, Order No. 04115308.
Straight adapter, 6 mm, interference-suppressed, Order No. 04115306.

8.6 Socket connectors

Type Order No.
Socket connector E, 48-pin solder tag connection 0 4120148 Socket connector E, 48-pin wire-wrap connection 04120158

8.7 Module subrack

Module subrack BGT S9U/1 for PFP 700, PFU 780
comprising: module subrack, printed-circuit board with rear terminal strip, function-tested, standard documentation, guide rails, without partial front plates, screw terminals at the rear.
Slots 1–9 for PFU 760/780, slot 10 for PFP 700, Order No. 84402281
Module subrack BGT SM8/1/1 for MPT 700, PFU 780
comprising:
module subrack, printed-circuit board with rear ter­minal strip, function-tested, standard documentation, guide rails, without partial front plates, screw terminals at the rear, single-zone operation for MPT 700 opera­ting modes 1–4, two-zone operation for MPT 700 ope­rating modes 1–4, but max. 4 burners per zone.
Slot 1 for MPT 700, slots 2–9 for PFU 760/780, slot
10 for PFP 700
Order No. 84402282 (no illustration provided)
Module subrack BGT SA for PFA 700/PFU 760 and PFA 710/PFU 780
consisting of: odule subrack, printed-circuit board with rear terminal strip,
function-tested, standard documentation, guide rails, wit-
hout partial front plates, screw terminals at the rear, relays and screw terminals for four free inputs and four free out­puts, connection to PROFIBUS DP with DSub socket.
BGT SA9: slot 1 for PFA 700, slots 210 for PFU 760, BGT SA8: slot 1 for PFA 710, slots 29 for PFU 780
Order no. BGT SA9U/1 DP700: 84402291 BGT SA8U/1 DP710: 84402292 (no illustration provided)
PFU 780 · Edition 02.12l 57
Page 58
Accessories

8.8 Power supply PFP 700

For supplying the control inputs of burner control unit PFU or for supplying the auxiliary voltage to relay module PFR 704. Operating status display on the front plate. PFP switches off in the event of an output over­load. Output voltage 24 V, output rating 14 VA. Order No. 84366510
L1
N
PFP 700
F1
30a
32c
S1
S0
O
I
UI
230 V
115 V
8ace
12ace
24 V= 600 mA
0 V
PFU 780 · Edition 02.12l 58
Page 59
Accessories
230 V~ 115 V~ 24 V=/~
0 V
230 V~ 115 V~ 24 V=/~
0 V
230 V~ 115 V~ 24 V=/~
0 V
230 V~ 115 V~ 24 V=/~
0 V
PFR 704
2e 2a 2c
1
4e
10e 10a 10c
2
12e
18e 18a 18c
3
20e
26e 26a 26c
4
28e
16a 16e
14a 14e
14c 16c
24a 24e
22a 22e
22c
24c
32a 32e
30a 30e
30c 32c

8.9 Relay module PFR 704

For contact multiplication, e.g. if several air valves are
activated via a single control signal for pre-purge, or
for heating/cooling switchover when using an MPT.
Switching status display on the front plate.
Input voltage: 110/120 V AC, 15/+10%, 50/60 Hz, 220/240 V AC, 15/+10%, 50/60 Hz, 24 V AC/DC, ± 10%.
Current per relay: 25 mA.
Contact rating of floating outputs: max. 2 A, 264 V (not fused internally).
6a 6e
8a 8e
8c
max. 2 A, 264 Vmax. 2 A, 264 Vmax. 2 A, 264 Vmax. 2 A, 264 V
6c
Order No. 84373510
PFU 780 · Edition 02.12l 59
Page 60
Accessories

8.10 Field bus interface PFA 700

For connection of up to nine automatic burner control
units PFU 760 to industrial communication networks
using PROFIBUSDP, in order to transfer measuring,
control and regulation signals as a bundle.
4 digital inputs: 24 V DC, ± 10%, < 10 mA , 4 digital outputs: relay contact, max. 1 A, 264 V (not fused internally).
Mains voltage: 110 – 240 V AC, 15/+10%, 50/60 Hz.
Further information can be found in Technical informa-
tion PFA.
L1
N
VP
RxD/TxD-P
RxD/TxD-N
DGND
24 V
24 V 0 V
24 V
24 V
PFA 700
32b 30a
8b 11b 12b
14b
18b
21b 22b
23b
26b
µC
PROFIBUS DP
1
4
I/O
1
4
15b
24 V=
16b
0 V
1c
1. PFU
10c
18c
10a
18a
19a
23a
20c
23c
19c
17b
24 V
30c
9c
9. PFU
1. PFU …
9. PFU
1a
1. PFU …
9a
9. PFU
1. PFU
9. PFU
1. PFU …
5. PFU
6. PFU …
9. PFU
PFU
30e
26e
PFU
ϑ
2
1
L1
PFU 780 · Edition 02.12l 60
Page 61
Accessories
L1
N
PE
1
mA
GND
2
mA
0
100%
GND 100% – 0
12–24 V
E2
E3
0 V

8.11 Impulse system MPT 700

With 11 outputs for activation of burner control units
PFU 780. The furnace atmosphere is circulated thanks
to intermittent operation, and thereby constant tem­perature distribution and shorter heating-up periods for all gas-fired heat treatment furnaces are ensured.
Mains voltage: 95240 V AC, ± 10%, 50/60 Hz.
Power consumption: 10 VA.
Additional auxiliary voltage: 1224 V DC, ± 10%, max. 1.1 A.
Controller inputs: 2 x 0(4)20 mA with common earth, floating, load impedance approx. 225 Ω.
MPT 700
30z
F1
30b 30d
28z 28b 28d
32z 32b 32d
20z 20b 20d
18z 18b 18d
E1
14z
14d
16z
14b 16b
8888
88
µC
2b 4b
10b
12b
2z
2d
4z
4d
6z
6d
8z
8d
10z
10d
12z
6b 8b
12–24 V
0 V
A1
A2
A3
A4
A5
A6
A7
A8
1
/
2
/
COM
Three-point step input: floating, 1224 V DC, load im-
pedance approx. 2.7 kΩ.
Digital inputs E1E3: with common earth, floating, 1224 V DC, load impedance approx. 2.7 kΩ.
Order No. 84395050
Further information can be found in brochure MPT.
PFU 780 · Edition 02.12l 61
Page 62
Technical data

9 Technical data

Mains voltage:
220/240 V AC, 15/+10%, 50/60 Hz or
110/120 V AC, 15/+10%, 50/60 Hz,
for grounded and ungrounded mains.
Power consumption: < 8 VA.
Control inputs: Input voltage/current: Pilot burner, main burner, air valve, multi-flame control and remote reset:
24 V DC, ± 10%, < 7 mA per input.
Input voltage for safety interlocks, digital input DI and purge = mains voltage.
Input voltage of signal inputs:
Rated value 110/120 V AC 220/240 V AC
Signal “1” 80–132 V 160–264 V Signal “0” 0–20 V 0–40 V Frequenz 50/60 Hz 50/60 Hz
Rated value 24 V DC
Signal “1” 24 V, ±10 % Signal “0” < 1 V
Output voltage for voltage-related outputs = mains
voltage.
Contact rating
Gas valve V1, V2 Max. 1 A resistive
Air valve Max. 1 A resistive
Ignition Max. 1 A resistive Number of operating
cycles
Max. 1,000,000,
typically 400,000
Max. 1 A cos φ 0.3
Max. 1 A cos φ 0.3
Max. 1 A cos φ 0.3
Max. 250,000,
typically 100,000
Output current: max. 2 A per output, but total current for valves and ignition transformer max. 2.5 A.
Operation and fault signalling contacts:
dry contact (floating), max. 1 A, 24 V, not fused inter­nally.
Number of operating cycles: Mains switch: 1000, Reset/Information button: 1000.
Inherent current:
Signal “1” typ. 5 m A
PFU 780 · Edition 02.12l 62
Page 63
Technical data
Flame control: Sensor voltage: approx. 230 V AC. Sensor current: > 1 μA, Length of sensor cable: max. 100 m.
Fuse in unit: F1: 3.15 A, slow-acting, H pursuant to IEC 1272/5, F2: 3.15 A, slow-acting, H pursuant to IEC 1272/5.
Ambient temperature:
20 to +60 °C (4 to +60.00 °C),
Climate: no condensation permitted.
Enclosure: IP 00 pursuant to IEC 529, after installing in a 19” module subrack according to the instructions, e.g. type BGT, the front corresponds to IP 20.
Input/Output safety circuit: All the inputs and outputs marked “ diagrams) may be used for safety tasks.
Weight: approx. 650 g (23 oz.).
” (see connection
PFU 780 · Edition 02.12l 63
Page 64
Technical data
9.1 Safety-specific characteristic values
In the case of ionization control, suitable for Safet y Integrity Level
Diagnostic coverage DC 97. 9% Type of subsystem Type B to EN 615082, 7.4.3.1.4
Mode of operation
Mean probability of dangerous failure PFH
D
Mean time to dangerous failure MTTF Safe failure fraction SFF 99.2%
The specified values apply for the combination with
ionization electrode (sensor) and PFU 780 (logic).
Relationship between the Performance Level (PL) and the Safety Integrity Level (SIL)
PL SIL
a – b 1 c 1 d 2 e 3
SIL 3
High demand mode pursuant to EN 615084, 3.5.12
1.34 x 108 l/h
MTTFd = 1 / PFH
d
D
Pursuant to EN ISO 138491:2006, Table 4, the PFU can be used up to PL e.
Max. ser vice life under operating conditions:
20 years after date of production, plus max. 1/2 year in
storage prior to first use.
For a glossary of terms, see page 68 (Glossary).
PFU 780 · Edition 02.12l 64
Page 65
Technical data
3 HE =
133.4 (5.3“)
A
B
8 TE =
40.6 (1.6“)
D

9.2 Operating controls

A: 2-digit 7-segment display
B: Reset /Information button to reset the system after a
fault or to scan parameters on the display
C: Mains switch
C
F2
F1
D: Optical interface
E: Type label
E
PFU 780 · Edition 02.12l 65
Page 66
Maintenance cycles

10 Maintenance cycles

Burner control unit PFU requires little servicing.
PFU 780 · Edition 02.12l 66
Page 67
Legend
88
ϑ
1
ϑ
2
DI
A
1
2

11 Legend

Display
Blinking displ ay
88
Ready
Safety interlocks (Limits)
Start-up signal, pilot burner
Start-up signal, main burner Digital input
Ignition transformer
Gas valve
Air valve
P
Purge Ext. air valve control
Flame signal
Operating signal, pilot burner Operating signal, main burner Fault signal Reset Input signal
Output signal Flame simulation check
t
Waiting time 2 s
W
Safety time on star t-up 3 s, 5 s or 10 s
t
SA
Safety time during operation < 1 s or < 2 s
t
SB
Ignition time 2 s, 3 s or 6 s
t
Z
Flame simulation delay time 25 s
t
LV
Flame proving period 0–25 s
t
FS
Minimum combustion time tSA up to max. 25 s
t
B
Minimum burner pause time 0–250 s
t
BP
Low fire over run time 0 s, 5 s, 15 s or 25 s
t
KN
Input/Output safety circuit
PFU 780 · Edition 02.12l 67
Page 68
Glossary

12 Glossary

12.1 Waiting time t
02 02
01
t
t
W
Z
t
SA
Once the start-up signal ϑ has been applied, the wait­ing time tW starts to elapse. During this time, a self-test is conducted to detect errors in internal and external circuit components. If no malfunction is detected, the burner will start up.

12.2 Safety time on start-up tSA

This refers to the period of time between switching on
and switching off of the gas valve, when no flame signal is detected. The safety time on start-up tSA (3, 5 or 10 s) is the minimum operating time of the burner and burner control unit.
W
88
L1
30e
10e
ϑ
28c
16c
26a
18e
2c–4c
2e–4e
V1
V2
t

12.3 Ignition time tZ

If no malfunction is detected during the waiting time tW, the ignition time tZ then starts to elapse. Voltage is supplied to the pilot gas valve V1 and the ignition trans-
former and the burner is ignited. The duration of the
ignition time is either 2, 3 or 7 seconds (depending on safety time tSA selected).
12.4 Flame simulation/Flame simulation delay time t
An extraneous signal (flame simulation) is a flame sig-
nal that is detected, although there should be no flame according to the program sequence. If such an extrane­ous signal is detected, the flame simulation delay time tLV starts to elapse. If the flame simulation is discontin­ued during the flame simulation delay time tLV, star t-up can be initiated or operation continued. Otherwise, a
fault lock-out occurs.
LV
01 88
t
W
t
LV
01
30e
10e 28c
16c
26a
18e
2c–4c
2e–4e
L1
ϑ
V1
V2
t
PFU 780 · Edition 02.12l 68
Page 69
Glossary
12.5 Safety time during operation t
04 04
t
SB
30e
10e
28c
16c
26a
18e
2c–4c
2e–4e
88
L1
ϑ
SB
V1
V2
t
If the flame fails during operation, the valve outputs are disconnected within the safety time tSB.The default safety time during operation tSB in accordance with EN 298 is 1 second. In accordance with EN 7462, the safety time of the installation during operation (in­cluding closing time of the valves) may not exceed 3 seconds (see “Project planning information”). Note the requirements of the Standards!

12.6 Flame signal

If a flame is detected, the flame detector will supply a flame signal.

12.7 Fault lock-out

In the event of a fault lock-out, all valves and the igni­tion transformer are disconnected from the electrical power supply, and a fault is signalled. Resetting must take place manually following a fault lock-out.

12.8 Safety interlocks (Limits)

The limiters in the safety interlock (linking of all the rel-
evant safety control and switching equipment for the use of the application, e.g. safety temperature limiter, minimum/maximum gas pressure) must isolate input ( ) from the voltage supply.

12.9 Pilot gas valve V1

The start fuel flow rate for the pilot burner is released by
pilot gas valve V1. It opens when the safety time on start­up t
starts to elapse. It remains open until the burner is
SA1
switched off again by a normal shut-down or fault lock-out.

12.10 Main gas valve V2

The start fuel flow rate for the main burner is released
by main gas valve V2. It opens when the safety time on start-up t burner is switched off again by a normal shut-down or
fault lock-out.
L1 (L1)
N (L2)
starts to elapse. It remains open until the
SA2
P
30e
26e
DI
22a
30a
20c 230 V
32c 24c
PFU 780
F1
sk1
l
22e
v1
16c
v2
18e
2a
a
4a
N
V1
V2
PFU 780 · Edition 02.12l 69
Page 70
Glossary

12.11 Continuous operation

The gas burner runs continuously for more than 24
hours.

12.12 Air valve

The air valve can be used
– for cooling,
– for purging,
– to control the burner capacity in ON/OFF mode and
in High/Low mode when using a pneumatic air/gas ratio control system.

12.13 Diagnostic coverage DC

Measure of the effectiveness of diagnostics, which may be determined as the ratio between the failure rate of detected dangerous failures and the failure rate of total dangerous failures
NOTE: Diagnostic coverage can exist for the whole or parts of a safety-related system. For example, diagnos­tic coverage could exist for sensors and/or logic system and/or final elements. Unit: %.
from EN ISO 138491:2008

12.14 Mode of operation

High demand mode or continuous mode
Operating mode, where the frequency of demands for
operation made on a safety-related system is greater than one per year or greater than twice the proof-test
frequency
from EN 615084:2001

12.15 Safe failure fraction SFF

Fraction of safe failures related to all failures, which are
assumed to appear
from EN 13611/A2:2011

12.16 Probability of dangerous failure PFHD

Value describing the likelihood of dangerous failure per
hour of a component for high demand mode or con­tinuous mode. Unit: 1/h
from EN 13611/A2:2011
12.17 Mean time to dangerous failure
MTTF
Expectation of the mean time to dangerous failure
from EN ISO 138491:2008
d
PFU 780 · Edition 02.12l 70
Page 71

Feedback

Kromschröder AG
Michael Rehkamp
m.rehkamp@kromschroeder.com
Osnabrüc
k
Finally, we are offering you the opportunity to assess this “Technical Information (TI)” and to give us your opinion, so that we can improve our documents further and suit them to your needs.
Clarity
Found information quickly Searched for a long time Didn’t find information What is missing? No answer
Comprehension
Coherent Too complicated No answer
Scope
Too lit tle Sufficient Too wide No answer
Use
To get to know the product To choose a product Planning To look for information
Remarks

Contact

Contact
Elster GmbH Postfach 2809 · 49018 Osnabrück Strotheweg 1 · 49504 Lotte (Büren) Germany
Tel +49 541 12140
Fax +49 541 1214370 info@kromschroeder.com
ww w.kromschroeder.com
PFU 780 · Edition 02.12l
Navigation
I can find my way around I got “lost” No answer
The current addresses of our international agents
are available on the Internet: ww w.kromschroeder.de/Weltweit.20.0.html?&L=1
We reserve the right to make technical modifications in the interests of progress.
Copyright © 2016 Elster GmbH All rights reserved.
My scope of functions
Technical department Sales No answer
03250720
Loading...