Honeywell N10230-2POS, N0524, N05230-2POS, N1024 PRODUCT DATA

0 (0)

N0524/N1024, N05230-2POS/N10230-2POS

NON-SPRING RETURN DIRECT-COUPLED DAMPER ACTUATORS FOR FLOATING AND 2-POSITION CONTROL

GENERAL

This non-spring return direct-coupled damper actuator provides floating and two-position control for:

air dampers,

VAV units,

air handlers,

ventilation flaps,

louvers, and

reliable control for air damper applications with up to 1 m2 / (5 Nm) and 2 m2 (10 Nm) (seal-less damper blades; air friction-dependent).

 

PRODUCT DATA

SPECIFICATIONS

 

Supply voltage

 

N0524/N1024

24 Vac/dc -15%/+20%,

 

50/60 Hz

N05230-2POS/N10230-2POS 230 Vac -15%/+20%, 50/60 Hz

Nominal voltage

 

N0524/N1024

24 Vac/dc, 50/60 Hz

N05230-2POS/N10230-2POS

230 Vac, 50/60 Hz

All values stated hereinafter apply to operation under nominal voltage conditions.

Power consumption

 

N0524/N1024

5 VA / 2 W

N05230-2POS

22 VA / 2 W at 50 Hz

 

25 VA / 2 W at 60 Hz

N10230-2POS

22 VA / 2 W at 50 Hz

 

25 VA / 2 W at 60 Hz

Ambient limits

-20...+60 °C (-5...+140 °F)

Ambient operating limits

Ambient storage limits

-30...+80 °C (-22...+176 °F)

Relative humidity

5...95%, non-condensing

Safety

 

Protection standard

IP54

Protection class

II as per EN 60730-1

Overvoltage category

II

Lifetime

 

Full strokes

60000

Repositions

1.5 million

Mounting

 

Round damper shaft

8...16 mm

Square damper shaft

6...13 mm; 45° steps

Shaft length

min. 41 mm

FEATURES

Declutch for manual adjustment

Adjustable mechanical end limits

Removable access cover for direct wiring

Mountable in any orientation

Rotation direction and service/OFF switch

End switches (when included)

Rating

5 A (resistive), 3 A (inductive)

Triggering points

5° / 85°

Torque rating

5 Nm / 10 Nm

Runtime for 90°

 

N0524 / N1024

90 sec (dc / 60 Hz ac)

N0524 / N1024

110 sec (50 Hz ac)

N05230-2POS

65...110 s (60/50 Hz)

N10230-2POS

65...140 s (60/50 Hz)

Rotation stroke

95° ± 3°

Dimensions

see "Dimensions" on page 6

Weight (without cables)

450 g

Noise rating

35 dB(A) max. at 1 m;

 

40 dB(A) for 230 Vac at

 

65 sec runtime

® U.S. Registered Trademark

EN0B-0477GE51 R0408

Copyright © 2008 Honeywell Inc. • All rights reserved

 

Honeywell N10230-2POS, N0524, N05230-2POS, N1024 PRODUCT DATA

N0524/N1024 AND N05230-2POS/N10230-2POS DAMPER ACTUATORS FOR FLOATING/2-POSITION CONTROL

PRODUCT IDENTIFICATION SYSTEM

N = non-spring return

S = spring return

05

=

5 Nm

 

equipped with two

10

=

10 Nm

 

end switches

 

 

 

 

 

 

SmartAct N 0 5 2 4 - S W 2

010 = modulating + floating + ON/OFF

24 = 24 V floating + ON/OFF

230 = 230 V ON/OFF

Fig. 1. Product Identification System

MODELS

order no.

supply voltage

end switches

torque

N05024

 

--

5 Nm

N05024-SW2

24 Vac/dc

2

 

N1024

--

10 Nm

 

N1024-SW2

 

2

 

 

N05230-2POS

230 Vac

--

5 Nm

N10230-2POS

10 Nm

 

 

BASIC FEATURES

1

2

N0524

3

4

Dir

Service/Off

Rev

5

 

6

 

Fig. 2. Setting units and control elements

Legend for Fig. 2:

1)Universal shaft adapter

2)Mechanical end limits (manually adjustable)

3)Declutch button

4)Function selection switch

5)Removable access cover

6)Anti-rotation bracket

Contents of Package

The delivery package includes the actuator and parts 1 through 6 (see Fig. 2), plus two cable grommets and a spare cable grommet.

RUN MODES

The function selection switch (see Fig. 3) can be used to place the actuator into either of two different modes:

Service/Off; or

the floating/2-position run mode ("Dir" for CCW-closing dampers or "Rev" for CW-closing dampers).

floating/2-position

Service / Off

Dir

Dir

Service/Off Service/Off

Rev

Rev

Fig. 3. Function selection switch

Power-Off Behavior

If power is removed, the shaft adapter remains in position.

Service/Off

If the function selection switch is set to the "Service/Off" position, then all rotary movement is cancelled, and all control signals are ignored, thus allowing the actuator to be manually operated safely.

Floating/2-Position Run Mode

If the function selection switch has been set to one of the two floating/2-position control settings – and if the actuator is wired correspondingly (see Fig. 8, Fig. 9, and Fig. 10) – then as soon as operating power is applied, the shaft adapter will run according to the control signals applied.

Table 1 describes the behavior ("stops," rotates "CCW," or rotates "CW") of the N0524 / N1024 in dependence upon the control signals (switch "open" or "24 Vac/dc") applied to terminals 3 and 4, the function selection switch setting, and the manner in which the actuator is wired (either for floating mode: see Fig. 8; or for 2-position mode: see Fig. 9).

Table 1. Behavior of N0524/N1024

 

wiring

control signal at

 

switch setting

 

 

term. 3

term. 4

Dir

Service/Off

 

Rev

 

 

 

 

float.

open

open

stops

stops

 

stops

 

open

24Vac/dc

CCW

stops

 

CW

 

 

24Vac/dc

open

CW

stops

 

CCW

 

2-pos.

24Vac/dc

open

CW

stops

 

CCW

 

24Vac/dc

24Vac/dc

CCW

stops

 

CW

 

 

 

Table 2 describes the behavior ("stops," rotates "CCW," or rotates "CW") of the N05230-2POS / N10230-2POS in dependence upon the control signals (switch "open" or "230 Vac") applied to terminals 1 and 3 and the function