M6063
ACTUATORS
PRODUCT DATA
APPLICATION
The Honeywell M6063 actuators are designed to provide floating control in heating and air-conditioning systems. High control performance, robust and rigid design are standard for these actuators.
In combination with the valves V5433A / V5442A it is possible to control very exact heating and cooling water temperatures. The mechanical interface between actuator and valve is designed for reliable operation. For a wide range of applications rotary valves up to DN50 are available.
|
|
FEATURES |
|
||
|
|
∙ Protected against overload and blocking |
|||
|
|
∙ Maintenance-free electrical actuator for rotary valves |
|||
|
|
∙ |
Clear position indicator |
|
|
|
|
∙ Direct mounting on rotary valves |
|||
|
|
∙ |
Manual operation |
|
|
|
|
∙ |
High torque |
|
|
|
|
∙ |
Prewired |
|
|
|
|
∙ |
Long lifetime |
|
|
SPECIFICATIONS M6063L AND M6063A |
|
|
|
||
Type |
M6063L 1009 |
M6063L 4003 |
|
M6063A 1003 |
M6063A 4007 |
Auxiliary switch |
— |
250 Vac, 3 (1) A |
|
— |
250 Vac, 3 (1) A |
Power supply |
230/240 Vac |
230/240 Vac |
|
24 Vac |
24 Vac |
Power consumption |
3 VA |
3 VA |
|
3 VA |
3 VA |
Control signal |
230/240 Vac floating |
230/240 Vac floating |
24 Vac floating |
24 Vac floating |
|
Angle of rotation |
90° |
90° |
|
90° |
90° |
Run time |
100s / 90° |
100s / 90° |
|
100s / 90° |
100s / 90° |
Nominal torque |
7 Nm |
7 Nm |
|
7 Nm |
7 Nm |
Protection standard |
IP 44 |
IP 44 |
|
IP 44 |
IP 44 |
according to EN 60529 |
|
|
|
|
|
Insulation class |
II |
II |
|
II |
II |
according to EN 60730 |
|
|
|
|
|
Ambient temperature |
0 – 60°C |
0 – 60°C |
|
0 – 60°C |
0 – 60°C |
for operation |
|
|
|
|
|
Water temperature range |
2 – 110°C |
2 – 110°C |
|
2 – 110°C |
2 – 110°C |
in the valve |
|
|
|
|
|
Relative humidity |
non condensing |
non condensing |
non condensing |
non condensing |
|
Weight |
0,5 kg |
0,6 kg |
|
0,5 kg |
0,6 kg |
EN0B-078 GE51R0997
PRODUCT DATA
SUITABLE VALVES
Three-way rotary valve V5433A, four-way rotary valve V5442A.
OPERATION
The actuators are powered by a synchronous motor. The spindel rotates through a range of 90°. The motor is switched off in the end position by end switches. The manual operation declutches the valve from the gear.
No adjustment necessary. The actuators are maintenance-free.
ELECTRICAL INSTALLATION |
brown |
M |
24 Vac |
R black |
|
230 Vac |
|
|
The actuators are prewired. |
blue |
|
N |
|
|
COM |
|
|
Power supply:
Blue: N (COM in case of 24 Vac)
Brown: Clockwise action
Black: Counterclockwise action
Fuse and switch are to be realized according to country specific instructions!
Actuator alternative with auxiliary switches:
Technical specifications of auxiliary switches: 250 Vac, 3 (1) A |
230 Vac |
Auxiliary switches enable the actuator to switch off external |
N |
devices like circulation pumps, blowers and indicator lights at its |
|
mechanical end positions. |
|
Connection:
Black and grey: Switch S1 (contact opened by end stop left) Brown and pink: Switch S2 (contact opened by end stop right)
Whether to select switch S1 or S2 depends on the mounting position of the rotary valve and the actuator (additional mixing from left or right side).
ORDER NUMBER, DIMENSIONS
max. 3 (1) A
S1 |
S2 |
9 |
9 |
7 |
7 |
5 |
5 |
3 |
3 |
1 |
1 |
OS Number |
Power supply |
Auxiliary switch |
a [mm] |
|
b [mm] |
c [mm] |
d [mm] |
e [mm] |
|
|
|
|
|
|
|
|
|
|
|
M6063L 1009 |
230/240 Vac floating |
— |
81 |
97 |
|
300 |
101 |
69 |
|
|
|
|
|
|
|
|
|
|
|
M6063L 4003 |
230/240 Vac floating |
X |
81 |
97 |
|
300 |
101 |
69 |
|
|
|
|
|
|
|
|
|
|
|
M6063A 1003 |
24 Vac floating |
— |
81 |
97 |
|
300 |
101 |
69 |
|
|
|
|
|
|
|
|
|
|
|
M6063A 4007 |
24 Vac floating |
X |
81 |
97 |
|
300 |
101 |
69 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
c
b |
Power supply: |
Auxiliary switch: |
|
|
|
Cable colour Black |
Cable colour Grey |
|
|
|
|
a
e d
EN0B-078