Honeywell H8908D, H8908C, H8908B, H8908A User Manual

0 (0)

H8908A/B Humidistat;

H8908C/D Dehumidistat

APPLICATION

The H8908 family of low-voltage humidistats/ dehumidistats provide accurate control of whole house humidifiers, dehumidifiers, and ventilators. They have a snap-acting, dust-proof SPST switch and can be mounted to a duct or wall.

Before Installing this Product...

1.Read these instructions carefully. Failure to follow them could damage the product or cause a hazardous condition.

2.Check the ratings given in the instructions and on the product to make sure the product is suitable for your application.

3.Installer must be a trained, experienced service technician.

CAUTION

Personal Injury Hazard.

Power supply can cause electrical shock.

Disconnect power supply before beginning installation.

NOTE: The H8908 electrical connections are not shared with the thermostat.

INSTALLATION INSTRUCTIONS

M24726

Fig. 1. H8908A,D control.

 

 

 

OUTDOOR

HUMIDITY

 

 

 

TEMPERATURE

SETTING

 

 

 

-20 F

-30 C

15%

Humidity

 

 

-10 F

-25 C

Control

0 F

-20 C

25%

 

+10 F

-10 C

Régulateur

d'humidité

+20 F

-5 C

35%

 

 

Over 20 F

Over 0 C

 

 

 

 

40%

HOLE FOR WIRING

CASE REMOVAL

THE DUCT MOUNTING

SLOT

INSTALLATIONS

M13371

Fig. 2. H8908B,C control.

Place Bar Code Here

69-1341EF-07

H8908A/B HUMIDISTAT; H8908C/D DEHUMIDISTAT

DUCT INSTALLATION

1.Choose a location on the duct.

 

ALTERNATE LOCATION

RETURN

RETURN

AIR

AIR

6 in. (152 mm)

15 in. (381 mm)

MINIMUM

 

MINIMUM

BEST

 

LOCATION

 

RETURN AIR DUCT

M13369

 

Fig. 3. Duct installation locations.

2.Apply sticker template to duct and drill holes for mounting screws. Cut along the dotted line of the template with metal shears or tin snips.

M24800

Fig. 4. Drill and cut holes in duct.

3.Run two-fan, low-voltage wire to the mounting location on the duct. See Fig. 5.

IMPORTANT

Use rated 18-22 gauge wire. Leave approximately 6 in. of wire to properly connect the humidistat.

RETURN

SUPPLY

REMOTE MOUNT

INSTALLATION

1. Choose a location in the living area.

NOTE: Select a location clear of drafts or excessive humidity. Avoid mounting near doors or windows, or in bathrooms or kitchens. See Fig. 6.

M24718

Fig. 6. Choose a location in the living area.

2.Cut 1 in. diameter wire hole in wall.

3.Run two-fan, low-voltage wire to the mounting location in the living area.

IMPORTANT

Use rated 18-22 gauge wire. Leave approximately 6 in. of wire to properly connect the humidistat.

M24721

Fig. 7. Run wire to the mounting location.

TWO-FAN 18-22 GAUGE WIRE

M24720

Fig. 5. Run wire to the mounting location.

69-1341EF—07

2

4.Remove the base bracket from the humidistat. For duct mount, slide the black gasket onto the base bracket. See Fig. 8.

NOTE: Use gasket only when mounting the control to ductwork. Leave off when mounting to a wall.

H8908A/B HUMIDISTAT; H8908C/D DEHUMIDISTAT

5.Secure the base bracket to the duct or remote location. Secure to the duct with four 1-in. (25 mm) screws (provided) or to the wall with two 1-in. (25 mm) screws (provided).

M24722

Fig. 9. Mount base bracket to duct or remote location.

M24733

Fig. 8. Seal base bracket.

3

69-1341EF—07

H8908A/B HUMIDISTAT; H8908C/D DEHUMIDISTAT

WIRING

CAUTION

Personal Injury Hazard.

Can cause electrical shock and injury.

Disconnect power before installation or servicing.

All wiring must comply with applicable local codes, ordinances and regulations. Make wiring connections according to humidifier (or dehumidifier/ventilator) instructions, if available; otherwise, see typical wiring diagrams in Fig. 12–19.

IMPORTANT

Select models of fan centers include humidifier taps so the current sensing relay, sail switch or air pressure switch is not needed. If not using a current sensing relay, sail switch, or air pressure switch, the humidifier must be energized during blower motor cycles for proper operation.

On multispeed blower applications, do not wire the high voltage side of the transformer to the same power source that services the furnace blower. Premature transformer burnout can occur. On HE365 fan powered humidifier models, only the two yellow wires are connected to the control. The remaining two red wires are only used with electronic humidity controls.

6.Using wire nuts, connect the low-voltage wire to the leads on the H8908 humidistat. See Fig. 6–19 for different wiring configurations.

M24734

Fig. 10. Wire the humidistat.

7.Mount the humidistat by hooking the two hinges at the top of the back cover to the raised edge at the top of the base bracket. Press the bottom of the humidistat in to engage the base hinge. You will hear a “click” when the humidistat is secured.

M24801

Fig. 11. Attach the humidistat to the base.

 

 

H8908

 

 

30

40

 

 

20

50

L1

POWER

10

60

(HOT)

OFF

ON

 

SUPPLY

FAN CONTROL

2

L2

 

 

 

1

 

TRANSFORMER

 

 

 

FURNACE

 

 

 

FAN

 

 

 

MOTOR

 

1 PROVIDE DISCONNECT MEANS AND

 

 

OVERLOAD PROTECTION AS REQUIRED.

 

2

 

HUMIDIFIER

24 VAC WIRING.

 

M24727

Fig. 12. Wiring H8908 with fan interlock.

H8908

L1

 

 

 

 

(HOT)

POWER

FAN CONTROL

 

SUPPLY

L2

 

 

 

 

1

 

 

 

DPST

 

 

 

SWITCHING

 

 

 

 

 

 

 

 

RELAY

 

H

 

L

2-SPEED

 

 

FAN

 

 

 

 

 

 

C

 

MOTOR

 

 

 

 

30

40

20

50

10

60

OFF

ON

2

 

TRANSFORMER

HUMIDIFIER

1POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

M24728

2 24 VAC WIRING.

Fig. 13. Wiring H8908 with 2-speed fan motor.

H8908

30

40

 

 

WATER

20

 

50

 

10

 

60

2

SOLENOID

OFF

ON

 

 

LEAD WIRE

TRANSFORMER

 

 

 

 

L2

L1

1

 

 

 

(HOT)

CURRENT

 

LO

 

 

SENSING

 

 

 

RELAY

C

HI

 

 

HUMIDIFIER

1POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

2 24V WIRING.

M24729

Fig. 14. Typical wiring diagram of current sensing relay with humidifier.

69-1341EF—07

4

Honeywell H8908D, H8908C, H8908B, H8908A User Manual

H8908A/B HUMIDISTAT; H8908C/D DEHUMIDISTAT

H8908

H8908

AIR

 

 

 

 

 

 

 

 

PRESSURE SWITCH/

30

40

 

30

40

FAN WIRING

 

 

SAIL SWITCH

20

50

 

20

50

TERMINALS

 

 

 

10

60

 

10

60

1

1

TO

2

OFF

ON

 

OFF

ON

 

 

 

 

 

 

 

SYSTEM

 

 

 

 

 

 

 

 

FAN

TRANSFORMER

 

 

 

 

HUMIDISTAT

 

 

 

 

 

 

TERMINALS

HUMIDIFIER

 

 

 

 

 

 

 

 

 

 

1

 

1

24V WIRING.

 

 

 

L2

L1

 

 

NOTE: FOLLOW THE INSTALLATION INSTRUCTIONS

 

 

 

(HOT)

 

 

 

 

 

HUMIDIFIER

INCLUDED WITH THE STEAM HUMIDIFIER

 

 

 

 

 

1

 

 

TO WIRE THE SYSTEM FAN.

M24731

POWER SUPPLY. PROVIDE DISCONNECT MEANS

 

 

 

AND OVERLOAD PROTECTION AS REQUIRED.

Fig. 16. Wiring H8908 with steam humidifiers.

2

24V WIRING.

 

M24730B

 

 

 

 

Fig. 15. Wiring H8908 in line with

 

 

air pressure switch/sail switch and humidifier.

 

 

 

TH9421 VISION PRO

 

 

EQUIPMENT INTERFACE MODULE

 

 

THERMOSTAT

 

 

 

 

 

 

1

 

 

1

 

CONV.

HP

STAGE 1

 

 

 

 

 

 

W1

O/B

HEAT

 

 

 

2

 

 

2

 

 

 

 

 

 

 

W2

AUX

 

 

 

 

3

 

 

3

 

 

 

 

 

L2

C

 

W3

AUX2

 

 

 

 

 

C

 

STAGE 2

 

 

 

 

 

Y

Y

 

 

 

 

 

 

24 VAC

 

 

 

 

SYSTEM

 

R

HEAT

 

 

 

 

 

Y2

Y2

 

 

 

TRANSFORMER

 

 

 

 

 

 

 

RC

 

 

 

 

 

 

L1

R

 

G

G

 

 

 

 

 

 

 

RH

 

 

 

COMPRESSOR

 

 

 

 

 

 

 

 

 

 

H8908B

 

L2

C

 

H1

 

L

 

 

 

 

24 VOLT

 

 

U

 

NOT USED

 

 

TRANSFORMER

 

 

M2

 

OUT1

 

 

R

 

D1

 

FAN

 

 

 

L1

 

 

 

 

 

 

H

OR

OUT2

 

 

 

 

 

 

RELAY

 

 

 

 

 

 

M2

 

30

40

 

 

 

 

 

IN1

 

 

 

 

 

 

 

 

V1

 

 

 

20

50

 

 

 

 

N

 

IN2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

T2

 

 

 

10

60

 

 

 

 

 

 

 

 

OFF

ON

 

 

 

 

 

 

DATS1

 

 

 

 

 

 

 

 

 

C7089U1006

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DATS2

 

 

COM

N.O.

N.C.

 

 

 

 

 

 

 

S688 AIR

 

PRESSURE

HE225/HE265

SWITCH/

HUMIDIFIER

SAIL SWITCH

M24724B

Fig. 17. Wiring H8908 with VisionPRO® IAQ on typical 2-stage furnace.

VISIONPRO® THERMOSTAT

H8908D

Y2

RC

 

 

L

R

 

 

A

W

 

 

W2

Y

 

 

S1

G

 

 

S2

C

H8908D

 

 

HEATING

 

30

40

 

 

 

RELAY OR

 

20

50

 

 

 

VALVE COIL

 

10

60

 

 

OFF

ON

COOLING

FAN

 

 

CONTACTOR

RELAY

 

 

COIL

COIL

 

 

 

 

1

 

30

40

VENTILATOR/DEHUMIDIFIER

20

50

10

60

 

OFF

ON

 

 

 

TERMINALS

 

 

Fresh Air Ventilation System

 

 

Système de ventilation à air frais

M24732

Fig. 19. Typical wiring diagram for HR150, HR200, ER150 and ER200 Ventilator or DH90 Dehumidifier applications.

1 PROVIDE OVERLOAD PROTECTION

 

AND DISCONNECT MEANS AS REQUIRED.

M24725

Fig. 18. Wiring H8908 with VisionPRO® Thermostat for dehumidification.

5

69-1341EF—07

Loading...
+ 11 hidden pages