Honeywell t8624d User Manual

0 (0)

T8624D Chronotherm® IV

Deluxe Programmable

Multistage Thermostats

INSTALLATION INSTRUCTIONS

APPLICATION

The T8624D Chronotherm® IV Deluxe Programmable Multistage Thermostats provides electronic control of 24 Vac single-zone multistage systems.

Refer to Table 1 for a general description of the thermostats. All T8624 thermostats require a common wire to supply power.

 

 

Table 1.

Description of T8624 Thermostats.

 

 

 

 

Fan

 

T8624

Changeover

System Selection

Selection

Comments

D

Automatic

Heat-Off-Cool-Auto

 

On-Auto

System and fan selections are done by keyboard.

 

 

 

 

 

 

MERCURY NOTICE

If this control is replacing a control that contains mercury in a sealed tube, do not place your old control in the trash. Dispose of properly.

Contact your local waste management authority for instructions regarding recycling and the proper disposal of the old control.

INSTALLATION

When Installing this Product...

1.Read these instructions carefully. Failure to follow the instructions can damage the product or cause a hazardous condition.

2.Check the ratings given in the instructions and on the product to make sure the product is suitable for your application.

3.Installer must be a trained, experienced service technician.

4.After completing installation, use these instructions to check out the product operation.

Location

Install the thermostat about 1.5m (5 ft) above the floor in an area with good air circulation at average temperature. See Fig. 1.

Do not install the thermostat where it can be affected by:

drafts, or dead spots behind doors and in corners.

hot or cold air from ducts.

radiant heat from sun or appliances.

concealed pipes and chimneys.

unheated (uncooled) areas such as an outside wall behind the thermostat.

® U.S. Registered Trademark

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Copyright © 2002 Honeywell •

• All Rights Reserved

69-1412-1

 

 

Honeywell t8624d User Manual

T8624D CHRONOTHERM® IV DELUXE PROGRAMMABLE MULTISTAGE THERMOSTATS

Wallplate Installation

Position wallplate horizontally on the wall or on a

The thermostat can be mounted horizontally on the wall

2 in. x 4 in. (50.8 mm x 101.6) mm wiring box.

or on a 2 in. x 4 in. (50.8 mm x 101.6 mm) wiring box.

 

YES NO

NO

1.5 METERS

(5 FEET)

NO

M10856

Fig. 1. Typical location of thermostat.

1.Position and level the wallplate (for appearance only). The thermostat will function correctly even when not level.

2.Use a pencil to mark the mounting holes. See Fig. 2.

3.Remove the wallplate from the wall and drill two 3/16 inch (76 mm) holes in the wall (if drywall) as marked. For firmer material such as plaster, drill two 7/32 inch (5.56 mm) holes. Gently tap anchors (provided) into the drilled holes until flush with the wall.

4.Position the wallplate over the holes, pulling wires through the wiring opening.

5.Loosely insert the mounting screws into the holes.

6.Tighten mounting screws.

WALL

WIRES

THROUGH WALL

WALL

ANCHORS (2)

WIRING

All wiring must comply with local electrical codes and ordinances. Refer to Fig. 3 for typical hookup. A letter code is located near each terminal for identification.

CAUTION

Electrical Shock Hazard.

Can cause electrical shock or equipment damage.

Disconnect power before beginning wiring.

1.Loosen the terminal screws on the wallplate and connect the system wires. See Fig. 4.

IMPORTANT

Use 18 gauge, color-coded thermostat cable for proper wiring.

2.Securely tighten each terminal screw.

3.Push excess wire back into the hole.

4.Plug the hole with nonflammable insulation to prevent drafts from affecting the thermostat.

MOUNTING

HOLES

MOUNTING

SCREWS

M15044

Fig. 2. Mounting the wallplate.

69-1412—1

2

T8624D CHRONOTHERM® IV DELUXE PROGRAMMABLE MULTISTAGE THERMOSTATS

 

 

 

 

 

 

 

 

 

 

 

 

 

Mounting Thermostat

 

 

 

 

 

THERMOSTAT

 

 

 

 

 

1.

Engage tabs at the top of the thermostat and wall-

RC

Y1

G

O

 

Y2

C

B

W2

W1

R

OT OT

2.

plate. See Fig. 5.

2

 

 

 

 

 

 

 

 

 

 

 

 

Press lower edge of case to close and latch.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FAN

C

O

MPRESS

O

R

 

HEAT

 

 

NOTE: To remove the thermostat from the wall, first pull

 

 

 

 

OUTDOOR

 

out at the bottom of the thermostat; remove top

 

 

RELAY

CONTACTOR 2

 

RELAY

 

SENSOR

 

 

 

 

 

 

 

 

 

 

2

 

 

 

 

last.

COMPRESSOR

COOL

 

 

 

 

 

 

HEAT

 

 

 

 

CONTACTOR 1

DAMPER

 

HEAT

 

 

 

 

 

 

 

 

 

DAMPER

RELAY

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3

 

 

 

 

 

 

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

 

 

L1

 

 

 

 

 

 

 

 

 

 

 

L1

 

 

(HOT)

 

 

 

 

 

 

 

 

 

 

 

(HOT)

 

 

L2

 

 

 

 

 

 

 

 

 

 

 

L2

 

 

1

 

COOLING

 

 

 

 

 

 

 

 

HEATING

 

A. ENGAGE TABS

 

 

 

 

 

 

 

 

 

 

 

 

 

TRANSFORMER

 

 

 

 

 

 

 

TRANSFORMER

 

AT TOP OF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

THERMOSTAT

1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD

 

AND WALLPLATE.

 

PROTECTION AS REQUIRED.

 

 

 

 

 

 

 

 

 

2 JUMPER RC TERMINAL TO R TERMINAL WHEN INSTALLED ON A ONE TRANSFORMER SYSTEM.

3

CAN BE USED FOR CHANGEOVER VALVE ON HEAT

M11309

PUMP SYSTEMS.

Fig. 3. Typical hookup of T8624D in a heat pump system.

 

B. PRESS LOWER

 

 

EDGE OF CASE

 

FOR WRAPAROUND

TO LATCH.

M14628

FOR STRAIGHT INSERTION

 

INSERTION STRIP

STRIP 5/16 IN. (8 MM).

 

7/16 IN. (11 MM).

Fig. 5. Mounting thermostat on wallplate.

M4826

Fig. 4. Correct wiring technique.

3

69-1412—1

T8624D CHRONOTHERM® IV DELUXE PROGRAMMABLE MULTISTAGE THERMOSTATS

INCREASE TIME SETTING

SET WAKE TIMES

 

OR SCROLL FORWARD

AND SETPOINTS

 

THROUGH INSTALLER SETUP

 

 

AND SYSTEM TEST

 

 

 

SET CURRENT

 

 

 

DAY AND TIME

 

 

 

RETURN TO

 

 

 

NORMAL

 

 

 

OPERATIONS

 

 

 

ENTER

 

 

 

INDEFINITE

 

 

Time

OR TIMED

Run

Set Current

 

HOLD MODE

Program

Day/Time

 

 

Hold Temp

Day

 

SET CURRENT OR

 

 

 

PROGRAM DAY

 

Daylight

Copy

 

 

 

Time

CHANGE BETWEEN

 

DAYLIGHT SAVINGS

 

AND STANDARD TIME

COPY ONE PROGRAMMED

 

 

DAY TO ANOTHER DAY

SET LEAVE TIMES

SET RETURN TIMES

INCREASE TEMPERATURE

AND SETPOINTS

 

AND SETPOINTS

SETTING OR SCROLL

 

 

 

 

 

FORWARD THROUGH

 

 

 

 

 

INSTALLER SETUP OPTIONS

 

 

 

 

DECREASE TEMPERATURE

 

 

 

 

SETTING OR SCROLL

 

 

 

 

 

BACKWARD THROUGH

 

 

 

 

INSTALLER SETUP OPTIONS

 

 

 

 

DISPLAY INFORMATION

 

 

 

 

SUCH AS PRESENT

 

 

 

 

 

SETTINGS AND OUTDOOR

 

 

 

 

TEMPERATURE

 

 

Set Program

 

SET SLEEP TIMES

 

 

 

 

 

 

Wake

Leave

Return

Sleep

AND SETPOINTS

 

Heat/Cool

 

System

Fan

SELECT FAN

 

Settings

 

OPERATION

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SELECT SYSTEM

 

 

 

 

 

OPERATION

 

DECREASE TIME SETTING OR

 

CHANGE BETWEEN

 

 

HEATING AND COOLING

 

SCROLL BACKWARD THROUGH

 

SETPOINTS

 

INSTALLER SETUP AND SYSTEM TEST

M14624

 

Fig. 6. T8624D key locations and descriptions.

Using Thermostat Keys

The thermostat keys are used to:

set current day and time,

program times and setpoints for heating and cooling,

temporarily override program temperatures,

display present setting,

configure Installer Setup,

check System Test,

display outdoor temperature (select models),

set the system operation,

set the fan operation.

See Fig. 6 for the location of the keys.

SETTINGS

System and Fan Settings

The system default setting is Heat and the fan default setting is Auto. Use the System and Fan keys to change the settings. See Fig. 7. The fan settings can be set for each program period individually. The system selection is for all the program periods.

System settings control the thermostat operation as follows:

Heat: The thermostat controls the heating. Off: Both the heating and cooling are off. Cool: The thermostat controls the cooling.

Auto: The thermostat automatically changes between heating and cooling operation, depending on the indoor temperature.

Fan settings control the system fan as follows:

On: Fan operates continuously.

Auto: Fan operates with equipment.

 

 

Time

Set Program

 

Run

Set Current

Wake

Leave

Return

Sleep

Program

Day/Time

Hold Temp

Day

Heat/Cool

 

 

System

Settings

 

System

Fan

 

Daylight

Copy

 

 

 

 

Time

 

 

 

 

 

 

 

 

 

Fan

M14625

Fig. 7. T8624D System and Fan key locations.

NOTE: Always press the keys with your fingertip or similar blunt tool. Sharp instruments like a pen or pencil point can damage the keyboard.

Temperature Settings

Refer to Table 2 for the default program. If the daytime energy savings period is not used, press the period key (Leave or Return) until the time is blank. The fan setting feature is available on select thermostat models. See Owners Guide, form number 69-0940, for complete instructions on changing the program.

Table 2. Default Program Settings.

 

 

Heat

Cool

Fan

Period

Time

Setpoint

Setpoint

Setting

Wake

6:00 AM

70°F

78°F

Auto

 

 

(21°C)

(25.5°C)

 

Leave

8:00 AM

62°F

85°F

Auto

 

 

(16.5°C)

(29.5°C)

 

Return

6:00 PM

70°F

78°F

Auto

 

 

(21°C)

(25.5°C)

 

Sleep

10:00 PM

62°F

82°F

Auto

 

 

(16.5°C)

(28°C)

 

69-1412—1

4

Loading...
+ 8 hidden pages