Honeywell L7224 User Manual

5 (3)
Honeywell L7224 User Manual

L7224 Series

Oil Electronic

Aquastat® Controller

TECHNICIAN’S QUICK REFERENCE GUIDE

The following service procedure provides a quick overview for L7224 Series Controllers. For more information, refer to form 69-1384.

On the L7224U the High Limit, High Limit Differential, Low Limit, and Low Limit Differential can be adjusted to the settings recommended by the boiler OEM.

Adjusting Settings

To discourage unauthorized changing of Aquastat® settings, a procedure to enter the adjustment mode is required. To enter the adjustment mode, press the UP, DOWN, and I buttons simultaneously for three seconds. Press the I button until the feature requiring adjustment is displayed:

HL—High Limit.

LL—Low Limit.

Ldf—Low Limit differential.

F - C—°F or °C.

Then press the UP and/or DOWN buttons to move the set point to the desired value. After 60 seconds without any button inputs, the control will automatically return to the READ mode.

To use the L7224U in a cold start boiler application, disable the Low Limit function by pressing the UP arrow button, DOWN arrow button and I buttons simultaneously for three seconds. Then push the I button until LL is displayed. Then press the down arrow button until OFF is displayed.

Display

In the RUN mode, the Aquastat® will flash “bt” (boiler temp) followed by the temperature (i.e., 220), followed by °F or °C.

To read boiler settings, press the I key to read the parameter of interest. For example, press I (HL) High Limit is displayed, followed by a three-digit number, i.e., 220, followed by °F or °C.

69-1957—1

L7224 SERIES

Pressing the I button again will display the LL (Low Limit) followed by a three-digit number and the corresponding degree designator. See the table below for an explanation of display readout.

After approximately 60 seconds without any key presses, the display will enter a dim display mode. To return to the bright display mode, simply press and release any key.

 

 

Display

Text

Description

Shows

bt

Boiler Temperature

 

HL

High Limit

 

LL

Low Limit

 

Hdf

High Limit Differential

 

Ldf

Low Limit Differential

 

tt

Local Thermostat Status

 

tte

Enviracom Thermostat Status

 

brn

Burner Status

 

cir

Circulator Status

 

Zc

Zone Control

 

Zr

Zone Request

 

err

Error Code

 

f

Degrees Fahrenheit

 

c

Degrees Celsius

 

 

 

M22149

 

Table 1. LED Error Codes

Error Code

Cause/Action

Err1

Sensor fault; check sensor.

Err2

ECOM fault; check EnviraCOM. wiring.

Err3

Hardware fault; replace control.

Err4

B1 fault; check B1 wiring/voltage.

Err5

Low Line; Check L1-L2, 110 Vac.

Err6

Fuse; Check ECOM wires, Replace fuse.

Err7

EEPROM, HL, LL, Hdf, Ldf, Reset to default values.

Err8

Repeated B1 fault (voltage present at B1 when

 

output is turned off); check B1 wiring/voltage.

69-1957—1

2