AQUATROL Zoning System
AQ1000TN2 Non-Programmable Communicating Thermostat
The AQ1000TN2 thermostat is used to control the ambient air
temperature or floor temperature in hydronic heating applications.
It communicates with and is powered by an AQ2000 series zoning
module to provide zoning control.
• 2-wire polarity-insensitive non-programmable network
communicating thermostat.
• Liquid crystal display with user buttons.
• Outdoor, indoor and floor temperature displays.
• Floor temperature sensing with minimum and maximum limits (when
used with optional AQ12C20 Slab/Floor Sensor - sold separately)
• Selectable temporary and permanent backlight.
Application: Hydronic single-stage zoning heat
Network Zoning: Ye s
Zones: Single or Multi-zone
Dimensions, Approximate: 2.8 in wide x 4.6 in high x 1.0 in deep (7
cm wide x 12 cm in high x 2.5 cm deep)
Electrical Connections: Wire-clamp screw terminals
Network Bus: Low voltage, Class II, 2-wire polarity-insensitive, digital
communicating link to AQ2000 series zoning modules.
User Interface (Programming): LCD Display
User Interface (System Configuration): DIP Switches
Thermostat Type: 2-wire Communicating Thermostat
Sensor Element: Thermistor
Sensors (Floor): AQ12C20 slab/floor sensor, lead length 10 feet (3 m)
(sold separately).
Setting Temperature
Range
Product Number
AQ1000TN2/U 40 F to 100 F 5 C to 38 C ± 1 F ±0.5 C TH, TH, Sensor,
Differential
Temperature
Ter mina l
Designations
Sensor
Mounting: Vertical Mount
Color: Premier White®
Temperature Control Mode Selections: “A” for Ambient Air, “F” for
Floor, “AF” for Ambient & Floor.
Temperatures Displayed: Indoor, Set Point, Outdoor
Temperature Display Interval: +/- 1.0 F (+/- 0.5 C)
Floor Sensor Temperature Rating: -58F to 230F (-50C to 110C)
Floor Temperature Limit Range (AF Model): 40 F to 100 F
(5 C to 38 C)
Outdoor Temperature Display Range: -58 F to 149 F (-50C to 65 C)
Ambient Temperature Range: 32 F to 158 F (0 C to 70 C)
Temperature Range, Storage: -20 F to 130 F (-30 C to 55 C)
Operating Humidity Range (% RH): 5 to 90% RH, non-condensing
Weight: 0.2 lb (0.1 kg)
Type o f
Control
Provided LCD Icons Displayed (Mode) Power Method(F) (C) (F) (C)
Proportional
Integral (PI)
Vacation Mode; Set point; Keypad
Lock; Comfort/Unoccupied; Heat On
Powered (24 Vdc) by
AQ zoning module
Controls
Hydronic
AQ1000TP2 Programmable Heat/Cool Thermostat
The AQ1000TP2 thermostat is used to control the ambient air
temperature or floor temperature in hydronic heating applications.
It communicates with and is powered by an AQ2000 series zoning
module to provide zoning control.
• 2-wire polarity-insensitive programmable network communicating
thermostat
• Liquid crystal display, with 7 user buttons for programming
• Floor temperature sensing with minimum and maximum limits (when
used with optional AQ12C20 Slab/Floor Sensor - sold separately)
• 7-day programmable
• Single-stage Heating and Cooling
• Outdoor, indoor, and floor temperature display
• Selectable temporary and permanent backlit
Application: Hydronic single-stage zoning, heating and cooling
Programmability: 7-day programmable
Network Zoning: Ye s
Zones: Single or Multi-zone
Dimensions, Approximate: 3.0 in. wide x 4.9 in. high x 1.0 in. deep
(7.8 cm wide x 12.5 cm high 2.5 cm deep)
Electrical Connections: Wire-clamp screw terminals
Network Bus: Low voltage, Class II, 2-wire polarity-insensitive, digital
communicating link to AQ2000 series zoning modules.
User Interface (Programming): LCD Display and 7 user programming
buttons
User Interface (System Configuration): DIP Switches
Thermostat Type: 2-wire Communicating Thermostat
Sensor Element: Thermistor
Sensors (Floor): AQ12C20 slab/floor sensor, lead length 10 feet (3 m)
(sold separately).
Mounting: Vertical Mount
Color: Premier White®
Temperature Control Mode Selections: “Air” for Ambient Air, “Floor”
for Floor, “Air/Floor” for Ambient & Floor limits
Temperatures Displayed: Indoor, Set Point, Outdoor
Temperature Display Interval: (+/- 0.5 C)
Floor Sensor Temperature Rating: -58F to 230F (-50C to 110C)
Floor Temperature Limit Range (AF Model): 40 F to 100 F
(5 C to 38 C)
Outdoor Temperature Display Range: -58 F to 149 F (-50C to 65 C)
Ambient Temperature Range: 32 F to 158 F (0 C to 70 C)
Temperature Range, Storage: -20 F to 130 F (-30 C to 55 C)
Operating Humidity Range (% RH): 5 to 90% RH, non-condensing
Weight: 0.3 lb (0.5 kg)
Product Number
AQ1000TP2/U 40 F to 100 F 5 C to 38 C ± 1 F ±0.5 C TH, TH, Sensor,
Setting Temperature
Range
Differential
Temperature
Termi nal
Designations
Sensor
70-6910 193
Type of Control
Provided
Proportional
Integral (PI)
LCD Icons Displayed
(Mode) Power Method
Fan On; Vacation Mode; Cool
On; Set point; Keypad Lock;
Comfort/Unoccupied; Heat On
Powered (24 Vdc) by
AQ zoning module