Honeywell NetAXS, 800-04410 User Manual

5 (1)

NetAXS™

Access Control Unit

User’s Guide

If this panel is to be added to an existing loop, then all panels need to be upgraded. Please see www.honeywellaccess.com.

April 2009

© 2009 Honeywell. All rights reserved.

800-04410, Revision A

Copyright© 2009 Honeywell. All rights reserved.

All product and brand names are the service marks, trademarks, registered trademarks, or registered service marks of their respective owners. Printed in the United States of America. Honeywell reserves the right to change any information in this document at any time without prior notice.

Microsoft and Windows are registered trademarks of Microsoft Corporation. Windows Server is a trademark of Microsoft Corporation.

Ordering Information

Please contact your local Honeywell representative or visit us on the web at www.honeywellaccess.com for information about ordering.

Feedback

Honeywell appreciates your comments about this manual. Please visit us on the web at www.honeywellaccess.com to post your comments.

CONTENTS

What’s New in Release 3.1.8

Dynamic Screens and Performance Enhancements .....................................................................

ix

Multi-language Support....................................................................................................................

ix

CSV Reports and Card Upgrade ......................................................................................................

x

Reverse IP............................................................................................................................................

x

Chapter 1 Connecting to the Web Server

1.1

Overview ........................................................................................................................................

1

1.2

Connecting to the Web Server ....................................................................................................

2

1.3

Reading the Select Panel..............................................................................................................

7

Chapter 2 Configuring via the Web Server

2.1

Overview ......................................................................................................................................

10

2.2

Configuring the System .............................................................................................................

11

 

2.2.1 Host/Loop Communications Tab ..........................................................................

11

 

2.2.2

General Tab ...........................................................................................................

14

 

2.2.3 File Management Tab............................................................................................

17

 

2.2.4 Network Tab..........................................................................................................

20

 

2.2.5

Site Codes Tab.......................................................................................................

21

 

2.2.6 Downstream Devices Tab......................................................................................

23

2.3

Configuring Time Management ...............................................................................................

24

 

2.3.1 Current Time Tab ..................................................................................................

24

 

2.3.2 Time Zones Tab.....................................................................................................

26

 

2.3.3

Holidays Tab .........................................................................................................

29

2.4

Configuring the Doors................................................................................................................

31

 

2.4.1 Reader Tab.............................................................................................................

31

 

2.4.2

Outputs Tab ...........................................................................................................

38

 

2.4.3

Inputs Tab..............................................................................................................

42

2.5

Configuring Access Levels........................................................................................................

45

2.6

Maintaining Cards.......................................................................................................................

47

 

2.6.1 Adding New Cards ................................................................................................

47

 

2.6.2

Displaying and Modifying Cards ..........................................................................

49

 

2.6.3

Deleting Cards .......................................................................................................

50

 

2.6.4

Displaying Reports ................................................................................................

51

NetAXS™ Access Control Unit User’s Guide, Document 800-04410, Revision A

iii

2.7

Configuring Other I/O & Groups Tab .....................................................................................

52

 

2.7.1

Inputs Tab..............................................................................................................

52

 

2.7.2

Outputs Tab ...........................................................................................................

55

 

2.7.3 Groups Tab ............................................................................................................

57

2.8

Configuring Interlocks ...............................................................................................................

59

2.9

Configuring Users.......................................................................................................................

61

Chapter 3 Configuring via WIN-PAK

3.1

Overview ......................................................................................................................................

65

3.2

Adding a New NetAXS™ Panel ..............................................................................................

66

 

3.2.1

Creating the Panel with Quick Start Wizard .........................................................

66

 

3.2.2

Configuring the Panel Manually ...........................................................................

67

Chapter 4 Monitoring NetAXS™ Status

4.1

Overview ......................................................................................................................................

75

4.2

Monitoring Alarms .....................................................................................................................

76

4.3

Monitoring Events ......................................................................................................................

79

4.4

Monitoring Inputs .......................................................................................................................

82

4.5

Monitoring Outputs ....................................................................................................................

85

4.6

Monitoring System Status .........................................................................................................

87

Chapter 5 Upgrading NetAXS™ Firmware

A.1

Overview .....................................................................................................................................

89

A.2

NetAXS™ Release 3.1.8 Upgrade Procedure .......................................................................

89

 

A.2.1 Planning the Upgrade ...........................................................................................

89

 

A.2.2 Mixed Revision Loops..........................................................................................

89

 

A.2.3 Uploading Data from the Panel ............................................................................

90

 

A.2.4 Upgrades to Gateway vs. Multi-drop Panels ........................................................

90

 

A.2.5 Upgrade Notes ......................................................................................................

92

 

A.2.6 Clearing the Cache in the Internet Browsers Used by the

 

 

NetAXS™ Web Server ..........................................................................................

93

Index

iv www.honeywell.com

LIST OF FIGURES

Figure 1-1: NetAXS™ Web Server Hub Connection ................................................................

2

Figure 1-2: NetAXS™ Web Server Direct Connection .............................................................

3

Figure 2-1: NetAXS™ System Configuration Flow Chart ......................................................

10

Figure 2-2: Configuration > System >Host/Loop Communications Tab .................................

11

Figure 2-3: Configuration > System > General Tab .................................................................

14

Figure 2-4: Configuration > System > File Management Tab .................................................

17

Figure 2-5: Configuration > System > Network Tab ...............................................................

20

Figure 2-6: Configuration > System > Site Codes Tab ............................................................

21

Figure 2-7: Configuration > System > Downstream Devices Tab ...........................................

23

Figure 2-8: Configuration > Time Management > Current Time Tab .....................................

24

Figure 2-9: Configuration > Time Management > Time Zones Tab .......................................

26

Figure 2-10: Configuration > Time Management > Holidays Tab ..........................................

29

Figure 2-11: Configuration > Doors > Reader > General Tab .................................................

31

Figure 2-12: Configuration > Doors > Reader > Card Formats Tab ........................................

35

Figure 2-13: Discrete Lock Output Configuration ...................................................................

38

Figure 2-14: Configuration > Doors > Outputs > Group Tab >Lock .......................................

39

Figure 2-15: Configuration > Doors > Inputs Tab ...................................................................

42

Figure 2-16: Configuration > Access Levels ...........................................................................

45

Figure 2-17: Cards > Add Cards ..............................................................................................

47

Figure 2-18: Cards > Card Data ...............................................................................................

49

Figure 2-19: Cards > Delete Cards ...........................................................................................

50

Figure 2-20: Configuration > Other I/O & Groups > Inputs Tab .............................................

53

Figure 2-21: Configuration > Other I/O & Groups > Outputs Tab ..........................................

55

Figure 2-22: Configuration > Other I/O & Groups > Groups Tab ...........................................

57

Figure 2-23: Configuration > Interlocks ..................................................................................

59

Figure 2-24: Configuration > Users .........................................................................................

62

Figure 3-1: Quick Start Wizard - Panel Screen ........................................................................

66

Figure 3-2: WIN-PAK Panel Configuration Screen - Basic Tab .............................................

67

Figure 3-3: WIN-PAK Panel Configuration Screen - Card Format Tab ..................................

68

Figure 3-4: WIN-PAK Panel Configuration Screen - Time Zones Tab ...................................

69

Figure 3-5: WIN-PAK Panel Configuration Screen - Options Tab .........................................

70

Figure 4-1: Status > Alarms > Unacknowledged Tab ..............................................................

76

Figure 4-2: Status > Alarms > Acknowledged Tab ..................................................................

77

Figure 4-3: Status > Events > Panel Tab ..................................................................................

79

Figure 4-4: Status > Events > Web Tab ...................................................................................

81

Figure 4-5: Status > Inputs .......................................................................................................

82

NetAXS™ Access Control Unit User’s Guide, Document 800-04410, Revision A

v

Figure 4-6: Status > Outputs > Doors/Aux/Other/DnStr Tab ..................................................

85

Figure 4-7:

Status > Outputs > Groups Tab .............................................................................

86

Figure 4-8:

Status > System .....................................................................................................

87

vi www.honeywell.com

LIST OF TABLES

Table 1-1: Reading the Select Panel ............................................................................................

7

Table 2-1: Configuration > System > Host/Loop Communications Tab Field Descriptions.....

12

Table 2-2: Configuration > System > General Tab Fields ........................................................

14

Table 2-3: Configuration > Time Management Tab Field Descriptions ...................................

25

Table 2-4: Configuration > Doors > Reader Tab Descriptions .................................................

33

Table 2-5: Configuration > Doors > Reader > Card Format Fields ..........................................

35

Table 2-6: Configuration > Doors > Output Tab Field Descriptions ........................................

41

Table 2-7: Configuration > Doors > Inputs Tab Field Descriptions .........................................

44

Table 2-8: Cards > Add Cards Field Descriptions ....................................................................

48

Table 2-9: Cards > Reports Field Descriptions .........................................................................

51

Table 2-10: Configuration > Other I/O & Groups > Inputs Tab Field Descriptions .................

54

Table 2-11: Configuration > Other I/O & Groups > Outputs Tab > Fields ..............................

56

Table 2-12: Configuration > Other I/O & Groups > Groups Tab Field Descriptions ...............

58

Table 2-13: Configuration > Interlocks > Field Descriptions ...................................................

60

Table 3-1: Interlock Reassignments for NetAXS™ ..................................................................

72

Table 4-1: Status > Alarms Field Descriptions .........................................................................

77

Table 4-2: Status > Events > Panel Tab Field Descriptions ......................................................

80

NetAXS™ Access Control Unit User’s Guide, Document 800-04410, Revision A

vii

viii www.honeywell.com

What’s New in Release 3.1.8

Dynamic Screens and Performance Enhancements

Dynamic screens are screens that can refresh data without re-submitting. In the Honeywell NetAXS™ panel, there is now a persistent connection between the web screens and the panel. This allows status updates from the panel to be pushed out to the screens automatically to display the data seamlessly on the screen.

In addition to the dynamic screens, other panel-side enhancements have been made that improve screen performance. Now the web server detects when panels of a loop come online faster. In the past, there was a 30to 45-second delay during which a panel could be online before the web would detect it. Data transfer between the panel and web browsers has been optimized to reduce bandwidth requirements and improve screen response times overall.

Multi-language Support

Multi-language support consists of “language files” installed with the firmware or imported to a panel. A language selection is available on a per-user basis. The language files are available by upload from the panel or from the Honeywell website. You can customize the upload.

There are options to import, export, or delete the language files from a panel. During upgrades, the language files with default names are replaced by those included with the firmware, so we recommend that customizations be saved and imported with a different filename than any present after upgrade. After toggling firmware sets, some phrases may change or appear in English until the language file(s) matching the active firmware version are imported, or the next upgrade is completed.

NetAXS™ Access Control Unit User’s Guide, Document 800-04410, Revision A

ix

CSV Reports and Card Upgrade

CSV Reports and Card Upgrade

A requested feature was added to the NetAXS™ panel to support card holder updates and additions to the database via a CSV (comma separated variable) file. In order to support this, a CSV report is first created via a request from the web page. This report can be edited directly or loaded into a spreadsheet to be edited. If loaded into a spreadsheet, the file can be saved in CSV format. The modified CSV file can then be downloaded to the gateway and loop panels.

Also, an option is provided to either replace or append the card database. Replacing the database deletes the existing card database, and appending the existing database adds new cards and updates to existing cards, if needed. This file is downloaded first to the gateway panel, and then automatically to each downstream panel. The file is sent to the downstream panel as a background process that allows other web screens to continue to operate. Note that the panels will not need to reboot after the file is downloaded.

Reverse IP

Reverse IP is implemented in the NetAXS™ panel to function with the WIN-PAK CS Reverse IP communication setting. This allows the panel to exist behind a firewall while communication to WIN-PAK CS is conducted on a pre-set port. This allows the NetAXS™ panel to be on a DHCP network. Reverse IP connections are currently limited to one NetAXS™ panel per WIN-PAK CS port. The NetAXS™ panel does not currently support encrypted reverse IP communication.

x www.honeywell.com

Connecting to the Web Server 1

In this chapter...

Overview

1

Connecting to the Web Server

2

1.1 Overview

A NetAXS™ access control site is configured with a host system and NetAXS™ access control units that exceed existing N-1000-III/IV, Pro Series specifications and approvals, and that communicate with each other and with a variety of input and output devices. Each access control unit, or panel, has four reader ports. See the

NetAXS™ NX4L1 Installation Guide, NetAXS™ NX4S1 Installation Guide, or

NetAXS™ NX4S2 Installation Guide to view illustrations of the supported NetAXS™ system configurations.

You can communicate with the NetAXS™ access control unit either through a host software system or by connecting to the NetAXS™ web server by an Ethernet connection. This chapter describes how to connect to the NetAXS™ web server. Chapter 2 describes how to use the NetAXS™ web interface after you are connected to the NetAXS™ panel through the NetAXS™ web server. Chapter 3 describes how to use the web server interface.

NetAXS™ Access Control Unit User’s Guide, Document 800-04410, Revision A

1

Connecting to the Web Server

Connecting to the Web Server

1.2 Connecting to the Web Server

This section describes how to connect a computer to the NetAXS™ web server via Ethernet and Internet Explorer.

Notes:

• The NetAXS™ panel that you are connecting to the computer is the Gateway panel. DIP switch 6 on a Gateway panel must be set to ON for a successful connection.

The Microsoft Windows™ screen captures used in this section reflect the Windows 2000™ platform. If you are using another Windows™ platform, the screens will be somewhat different.

Perform the following steps:

1.Connect your computer's Ethernet port and the NetAXS™ panel's Ethernet Port by using either of two methods:

a.Connect both the computer’s Ethernet port and the NetAXS™ panels Ethernet port to an Ethernet hub with standard Ethernet patch cables.

Figure 1-1: NetAXS™ Web Server Hub Connection

Terminal

Ethernet Port

Ethernet Port

Ethernet

Cable

NetAXS Panel

b.Connect the computer’s Ethernet port directly to the NetAXS™ panel’s Ethernet port with an Ethernet cable.

2 www.honeywell.com

Connecting to the Web Server

Connecting to the Web Server

Figure 1-2: NetAXS™ Web Server Direct Connection

Terminal

Ethernet Port

Ethernet

Cable

NetAXS Panel

2.Configure the computer’s network connection:

a.Select Start > Settings > Control Panel.

b.Click Network and Dial-up Connections.

NetAXS™ Access Control Unit User’s Guide, Document 800-04410, Revision A

3

Connecting to the Web Server

Connecting to the Web Server

c.Identify your local Ethernet connection (commonly labeled Local Area Connection), and right click the icon to display the Local Area Connection Properties screen.

d.Highlight the Internet Protocol (TCP/IP) connection.

e.Click Properties to display your system’s current Internet Protocol properties.

f.Important: Keep a record of your computer’s current network configuration as it appears in this screen. You will need to re-instate this configuration later.

g.Select “Use the following IP address."

h.Enter "192.168.1.10" in the IP address field.

i.Enter "255.255.255.0" in the Subnet mask field.

4 www.honeywell.com

Honeywell NetAXS, 800-04410 User Manual

Connecting to the Web Server

Connecting to the Web Server

j.Click OK to accept the entries.

3.Open your browser (Internet Explorer shown below), and enter https://192.168.1.150 as the target address.

NetAXS™ Access Control Unit User’s Guide, Document 800-04410, Revision A

5

Connecting to the Web Server

Connecting to the Web Server

4. Press the Enter key to display the Honeywell NetAXS™ login screen.

Note: If you are using Microsoft Internet Explorer 7, and you receive a certificate error message, follow these steps to clear it:

a.Enter the IP Address of the panel into the URL box.

b.Click Continue to the website (not recommended) to display the login screen.

c.Click Certificate Error at the top-right of the IP Address. The “Untrusted Certificate” screen appears.

d.Click the View Certificates bar. The “Certificate Information” screen appears.

e.Click Install Certificate. The “Certificate Import Wizard” screen appears.

f.Click Next and follow the prompts; leave all settings at their default values. A Security Warning asks if you want to install the certificate.

g.Click Yes. A Certificate Import Wizard message states “The import was successful.”

h.Click OK. The Certification Information message appears again.

i.Click OK.

j.Close the web browser and re-open it.

k.Enter the IP Address again into the URL box. The login screen appears without the certificate error

5.Enter “admin” in the User Name field, and enter “admin” in the Password field. Both the user name and password are case-sensitive.

6.Click Login to display the NetAXS™ main window. Note that the Select Panel column on the right edge of the screen displays all panels available to the computer. This list will include the gateway panel that you are connected to over Ethernet and any downstream panels connected via RS-485 to the Gateway panel.

Note: It is recommended that you change your default user name (admin) and password (admin) to a new user name and password at this time. To do this, proceed to the instructions in Chapter 2, Configuring the NetAXSSystem, Steps to modify a user:, page 63.

6 www.honeywell.com

Connecting to the Web Server

Reading the Select Panel

1.3 Reading the Select Panel

The Select Panel is located at the right margin of the NetAXS™ web server main screen, shown in the preceding section. The presence of a number in one of the Select Panel cells indicates that its associated panel is online. For example, if you see a number 1 in a cell, this indicates that panel 1 is online. The combinations of size and color of the number and the color of the cell background indicate the panel’s status, as shown in the following table:

Notes:

• Holding the cursor over a cell also displays a popup message, which conveys the panel in that cell is online or selected.

• The Select Panel refreshes automatically when the panel’s status changes.

Table 1-1: Reading the Select Panel

Cell Display

Status

 

 

Large red number on a blue background, such as

Panel 1 is selected, and it has unacknowledged

“1” in the example below:

alarms.

Small black number on white background, such as “2” in the example below:

Panel 2 is not selected and it has no unacknowledged alarms.

 

 

 

 

NetAXS™ Access Control Unit User’s Guide, Document 800-04410, Revision A

7

Connecting to the Web Server

Reading the Select Panel

Table 1-1: Reading the Select Panel (continued)

Cell Display

Status

 

 

 

 

Large white number on blue background, such as

Panel 2 is selected, and it has no unacknowledged

“2” in the example below:

alarms.

 

 

 

 

Small white number on a red background, such as “1” in the example below:

Panel 1 is not selected, but it does have unacknowledged alarms.

8 www.honeywell.com

Configuring via the Web Server 2

In this chapter...

 

Overview

10

Configuring the System

11

Configuring the Doors

31

Configuring Other I/O & Groups Tab

52

Configuring Interlocks

59

Configuring Time Management

24

Configuring Access Levels

45

Configuring Users

61

NetAXS™ Access Control Unit User’s Guide, Document 800-04410, Revision A

9

Configuring via the Web Server

Configuring the System

2.1 Overview

This chapter explains the NetAXS™ configuration functions as accessed via the NetAXS™ web server. These functions should be performed only by the NetAXS™ system administrator or service personnel.

Caution: The sequence of NetAXS™ configuration tasks is critical. If the sequence given below is not followed, the NetAXS™ system cannot be successfully configured.

The flow chart in Figure 2-1 shows the order in which to perform the administrative functions.

Figure 2-1: NetAXS™ System Configuration Flow Chart

Configure the Panel

Configuration > System > Host/Loop Communications (Host/Loop

Communications Tab, page 11)

Configuration > System > Network (Network Tab, page 20)

Configuration > System > General (General Tab, page 14)

Configuration > System > Site Codes (Site Codes Tab, page 21)

Configure the Time Zones

Configuration > Time Management > Time Zones (Time Zones Tab, page 26)

Configure the Doors

Configuration > Doors > Reader (Reader Tab, page 31)

Configuration > Doors > Output (Outputs Tab, page 38)

Configuration > Doors > Inputs (Inputs Tab, page 42)

Configure the Access Levels

Configuration > Access Levels (Configuring Access Levels, page 45)

Create the Cards

Cards > Add Cards (Adding New Cards, page 47)

Assign Access Levels to Cards

Cards > Add Cards (Adding New Cards, page 47)

10 www.honeywell.com

Configuring via the Web Server

Configuring the System

2.2 Configuring the System

2.2.1 Host/Loop Communications Tab

In order to maintain your NetAXS™ system configuration or to monitor its status, you must connect to the NetAXS™ panel by using one of two modes:

Host mode (monitor only) – a host software system, such as WIN-PAK™, connects to the panel (through the NetAXS™ gateway panel, which has an on-board PCI communications adapter), and it enables you to monitor the status of the NetAXS™ system. The on-board PCI adapter functions as an interface between a host computer’s RS-232 port and one or more panels connected on the Multidrop line.

Web mode (configure and monitor) – the NetAXS™ web server connects to the panel and enables you to configure the panel and monitor system status.

This tab enables you to select and configure the communication mode you will use to connect to the panel.

Note: A Gateway panel installed with release 3.1.8 or newer of NetAXS™ firmware cannot communicate fully with previous versions of NetAXS™ that may be installed on existing panels. If your panels are running release 2 (v2.2.21 or older), they must be upgraded to release 3.

Click the Host/Loop Communications tab:

Figure 2-2: Configuration > System >Host/Loop Communications Tab

NetAXS™ Access Control Unit User’s Guide, Document 800-04410, Revision A

11

Configuring via the Web Server

Configuring the System

The Host/Loop Communications tab enables you to:

Configure the following host settings:

Connection type (host or web server)

Communications type

Baud rate

Port number

Time sync

Configure the loop baud rate for communication among downstream panels.

Steps: Use the descriptions in the following table to configure the settings:

Table 2-1: Configuration > System > Host/Loop Communications Tab Field Descriptions

Host/Loop

Setting

Description

 

 

 

Host

Connection type

Specifies the type of physical connection

 

 

between the host and the Gateway panel.

 

 

If you are connecting from a host software

 

 

system such as WIN-PAK, select one of the

 

 

following three connection options:

 

 

Direct via TCP/IP – Host connects directly to

 

 

the panel using the TCP/IP protocol.

 

 

Reverse TCP/IP – Panel connects directly to

 

 

the host system using the TCP/IP protocol.

 

 

You must enter the host IP address in the Host

 

 

IP Address field. The communication is not

 

 

encrypted.

 

 

Direct via RS-232 – Host connects directly to

 

 

the panel via the RS-232 protocol.

 

 

Hub Mode (modem) – Host and the panel

 

 

both connect to a modem.

 

 

If you will be connecting to the panel through

 

 

the NetAXS™ web server, click None.

 

 

(Currently not supported)

 

 

 

 

Comms Type

Specifies the type of communications.

 

 

Ack/NAK – Provides a response (either an

 

 

acknowledgement or a

 

 

non-acknowledgement) in a transmission

 

 

between the host and panel(s). This is the

 

 

recommended communications type.

 

 

Non Ack/NAK – Does not provide a response

 

 

(either an acknowledgement or a

 

 

non-acknowledgement) in a transmission

 

 

between the host and panel(s).

 

 

 

12 www.honeywell.com

Configuring via the Web Server

Configuring the System

Table 2-1: Configuration > System > Host/Loop Communications Tab Field Descriptions (continued)

Host/Loop

Setting

Description

 

 

 

 

Baud Rate

Specifies the transmission rate (bits per

 

 

second) between the host and the panel. Select

 

 

the highest rate that your modem will support

 

 

(19,200 bps is recommended).

 

 

 

 

Port Number

Specifies the port number for the Ethernet port

 

 

(default is 3001).

 

 

 

 

Host IP Address

Enter the host system (or WIN-PAK server) IP

 

 

address here if you selected Reverse TCP/IP

 

 

in the Connection Type field on this screen.

 

 

 

 

Time Sync

Synchronizes the panel’s time with the host’s

 

 

time.

 

 

Enabled – Causes the panel(s) to be

 

 

automatically time-synchronized with the

 

 

host.

 

 

 

Loop

Baud Rate

Specifies the transmission rate (bits per

 

 

second) among the downstream NetAXS™

 

 

panels on the loop. For NetAXS™

 

 

downstream panels, it is recommended that

 

 

you select 115,200.

 

 

 

 

Force Baud Reset

Tells all downstream NetAXS™ panels to

 

 

change to the selected Downstream baud rate.

 

 

This saves the user from having to go to each

 

 

panel one by one

 

 

 

NetAXS™ Access Control Unit User’s Guide, Document 800-04410, Revision A

13

Configuring via the Web Server

Configuring the System

2.2.2 General Tab

Click Configuration > System in the NetAXS™ menu to display the System Configuration (General) screen:

Figure 2-3: Configuration > System > General Tab

The General Tab enables you to:

Set the general configuration settings.

Reset the panel.

Steps: Use the descriptions in the following table to configure the general settings, and click Submit Changes:

Table 2-2: Configuration > System > General Tab Fields

Parameter

Description

 

 

Name

Unique name that identifies the panel.

 

 

Address

Displays the address set by the panel’s DIP switches.

 

 

Type

Displays “NetAXS” as the panel type.

 

 

14 www.honeywell.com

 

 

Configuring via the Web Server

 

 

Configuring the System

 

 

 

 

 

Table 2-2: Configuration > System > General Tab Fields

 

 

 

 

 

Parameter

Description

 

 

 

 

 

 

Boot Time

Displays the time that power was applied to the NetAXS™ panel.

 

 

 

 

 

 

Reset

Reboots the panel. A reset does not change the current configuration

 

 

 

in the database.

 

 

 

 

 

 

Anti-Passback

Enabled – Enables anti-passback, which prevents an entrant to an

 

 

 

area from passing his card back to another potential entrant.

 

 

 

Local – Enforces anti-passback only at doors configured locally to

 

 

 

the panel controlling the original card read.

 

 

 

Global – Enforces anti-passback at panels throughout the NetAXS™

 

 

 

system after a successful card read at any one of the system’s readers.

 

 

 

Forgiveness – Causes all system codes to be reset at midnight every

 

 

 

day. This enables a cardholder who exited the building in the evening

 

 

 

without using his card to use his card for entry the following

 

 

 

morning.

 

 

 

 

 

 

Gateway Panel Addr

Sets the panel address of the Gateway panel, or the panel directly

 

 

 

connected to the host system.

 

 

 

 

 

 

Web Session Timeout

Activates a web session timeout after the specified time period has

 

 

 

elapsed. Define the time period either in minutes or in hours. Enter

 

 

 

the number in the box, then select either minutes or hours.

 

 

 

 

 

 

Hybrid Mode

Enabled – Implements a superior method of communication that

 

 

 

provides dynamic database synchronization between the NetAXS™

 

 

 

database and WIN-PAK SE Release 2 or WIN-PAK PE Release 2. It

 

 

 

allows full web functionality while using a WIN-PAK SE Release 2

 

 

 

or WIN-PAK PE Release 2 as the host. When connected to

 

 

 

WIN-PAK SE Release 2 or WIN-PAK PE Release 2 or later,

 

 

 

WIN-PAK enables you to:

 

 

 

approve changes made via the web interface.

 

 

 

• import those changes into the WIN-PAK database.

 

 

 

• disapprove those changes and revert the panel's

 

 

 

configuration to the configuration stored in the WIN-PAK

 

 

 

database.

 

 

 

Note: Consult your Honeywell Access Control representative for the

 

 

 

latest list of Host software packages that support this feature.

 

 

 

 

 

 

Free Egress

Enabled – Configures the panel for free egress. Reader 1 activates

 

 

 

output 1, reader 2 activates output 2, reader 3 activates output 3, and

 

 

 

reader 4 activates output 4. Inputs 1, 3, 5, and 7 are egress defaults

 

 

 

that activate outputs 1, 2, 3, and 4, respectively. Inputs 2, 4, 6, and 8

 

 

 

are status defaults for outputs 1, 2, 3, and 4, respectively.

 

 

 

 

 

NetAXS™ Access Control Unit User’s Guide, Document 800-04410, Revision A

15

Configuring via the Web Server

Configuring the System

Table 2-2: Configuration > System > General Tab Fields

Parameter

Description

 

 

Duress Detect

Enabled – Enables the user to trigger an alarm or output device in

 

times of duress, such as when the operator is forced to grant access

 

against his will to an unauthorized person. This feature is available

 

only when the reader is configured with a “Card and Pin” access

 

mode (see Reader Tab, page 31).

 

When this feature is enabled, you can configure an auxiliary output

 

with a pulse time and connect it to a device with an interlock (see

 

Outputs Tab“ on page 55 for the output configuration).

 

During normal operation, the duress output does nothing. To energize

 

the output, the cardholder presents his card to a reader that is

 

configured for Card and PIN access (see “Reader Tab“ on page 31).

 

The cardholder then enters a PIN that is either one number higher or

 

one number lower than his correct PIN. For example, if his PIN is

 

2222, the cardholder would enter either 2221 or 2223. Even though

 

the PIN is incorrect, the door will still open normally, but the duress

 

output pulses and an alarm is generated. In this way, the cardholder

 

notifies others without detection by the unauthorized person.

 

 

Continuous Card Reads

Enabled – Enables continuous card reading while the output is being

 

energized. When this option is not enabled, a reader will not be able

 

to read a second card during the pulsing of the output caused by the

 

previous card read.

 

 

Reader LEDs

Identifies the color of a reader LED when a grant is authorized.

 

 

Cardholder Note 1

Specifies any information field you might want to put on a card. For

 

example, if you enter “Department” here, a field labeled

 

“Department” appears on the card. The user who creates the card

 

would then enter the cardholder’s department name. See Adding

 

New Cards, page 47.

 

 

Cardholder Note 2

Specifies any information field you might want to put on a card. For

 

example, if you enter “Phone Number” here, a field labeled “Phone

 

Number” appears on the card. The user who creates the card would

 

then enter the cardholder’s telephone number. See Adding New

 

Cards, page 47.

 

 

16 www.honeywell.com

Configuring via the Web Server

Configuring the System

2.2.3 File Management Tab

Firmware is software that is embedded in the NetAXS™ board. The firmware provides this web interface and all access control functionality. Periodically, the firmware is updated. This tab enables you to download new versions of the firmware, revert to a previous version of the firmware, upload and/or download card and configuration databases.

Click File Management to display the File Management tab:

Figure 2-4: Configuration > System > File Management Tab

The File Management tab enables you to:

View and re-set the current firmware configuration.

Revert to another firmware version.

Restore (or download) firmware.

Back up (or upload) panel, card, and configuration data from the panel to the host system.

Restore (or download) card database files.

Restore (or download) backup files from the host to the panel.

Delete a file.

NetAXS™ Access Control Unit User’s Guide, Document 800-04410, Revision A

17

Configuring via the Web Server

Configuring the System

Steps to reset the firmware version:

1.In the Active Image column, click to select the firmware version to which you want to revert. The prompt “Switching to an alternate firmware set requires a panel reboot” appears.

2.Click OK to reboot the panel.

Steps to restore (or download) firmware:

1.Click Browse to locate the firmware file.

2.Click Download to download the selected firmware file.

Note: Every panel has its own database, and each panel’s database must be backed up individually.

Steps to back up (or upload) data from the panel to the host system:

1.From the Upload dropdown list, select one of the following types of upload from the panel to the host system:

Card and common configuration data—uploads cards, time zones, card formats, holidays, access levels, and site codes in a .CSV file.

Panel configuration data—uploads inputs, outputs, groups, interlocks, readers, and panel configuration in a .CSV file.

Card, common, and panel configuration data—uploads both the card and panel configuration items in a .CSV file.

Card report (short)—uploads the Card Number, Last Name, First Name, Trace, VIP, Limited Use, Card Expiration, Temporary, Supervisor, and Access Level card values in a

.CSV file.

Card report (long)—uploads the Card Number, Last Name, First Name, Trace, VIP, Limited Use, Card Expiration, Temporary, Supervisor, Access Levels, Site Codes, Number of Bits, Pin, Info 1, Info 2, Time Zones, Activation Date, Issue Level, APB State, and Control Device card values in a .CSV file.

Alarms and events report—uploads the Date, Time, Event Type, Acknowledged Date, Acknowledged Time, and Message of Alarms/Events for alarms and events in a .CSV file.

Language: English default, Spanish, French, Italian, Dutch, Czech, and simplified Chinese. This is a text file that uploads a language package that translates the text on all of the web screens for a user who has specified a language preference.

2.Click Upload to upload the data to the host PC or laptop. Follow the instructions to save a backup file on your PC. Be sure to give the backup file a useful name for easy identification and restoring.

Note: Card report (short and long) data is stored in a 64-bit format. Microsoft Excel displays up to 32 characters. Therefore, you should save the report and then open the it in Notepad, instead of opening the report immediately in the default .CSV format in Excel.

18 www.honeywell.com

Configuring via the Web Server

Configuring the System

Steps to download a card database report (.CSV file) from the host system to the panel:

1.Click Browse to locate the .CSV file.

2.Click Download to download the file. If the file is in the correct report format, this message appears: “Would you like to append or replace the database? Access Control does not function while replacing a database, and updating may take several minutes.” If the file is not in the correct report format, a message states the error condition.

If the database update is successful, this message appears: “Update Successful. Restarting Access Control.” If the database update is not successful, a message states the error condition.

Steps to restore (or download) backup files from the host system to the panel:

1.Click Browse to locate the backup file.

2.Click Download to download the selected backup file.

Steps to delete language files:

1.From the Delete dropdown list, select the language file you want to delete.

2.Click Delete to delete the file.

NetAXS™ Access Control Unit User’s Guide, Document 800-04410, Revision A

19

Configuring via the Web Server

Configuring the System

2.2.4 Network Tab

Your NetAXS™ panel is physically configured in one of a number of possible network configurations. See the “System Configuration” section in the NetAXS™ NX4L1 Installation Guide, NetAXS™ NX4S1 Installation Guide, and NetAXS™ NX4S2 Installation Guide for illustrations of the supported network configurations. For the panel to function in any of these configurations, the other panels and devices in the network must know the panel’s network addresses.

Click Network to display the Network tab:

Figure 2-5: Configuration > System > Network Tab

The Network tab enables you to:

View the panel’s MAC address.

View and edit the panel’s IP address.

View and edit the panel’s subnet mask.

View and edit the panel’s default gateway.

20 www.honeywell.com